HomeMy WebLinkAbout1362 ORDINANCE NO. 1362
AN ORDINANCE OF THE CITY OF SANFORD, FLORIDA,
AMENDING CHAPTER 19-1 OF TIlE CODE OF THE CITY
OF SANFORD, FLORIDA° THE SAME BEING KNOWN AS
THE PLUMBING CODE. SAID AMENDMENT ADOPTING
THE 1976 REVISION TO THE 1975 EDITION OF THE
STANDARD PLUMBING CODE WITH THE FOLLOWING
AMENDMENTS: A1VLENDM ENT OF SECTION 1212.1 (b)
OF THE STANDARD PLUMBING CODE AS TO THE USE
OF MATERIALS FOR WATER DISTRIBUTION; AMENDMENT
OF TABLE 505 TO DELETE CERTAIN NON-METALLIC
]PIi~ING MATERIALS FOR PLUiViBING INSTALLATIONS;
AMENDMENT OF SECTION 1215.8 (a) OF THE STANDARD
PLUMBING CODE AS TO SAFETY PANS AND RELIEF
VALVE WASTE.
BE IT ENACTED BY THE FEOPLE OF THE CITY OF SANFORD, FLORIDA:
SECTION 1. That Sub-section (b) of Section 1212.1 of the 1976
Revision to the 1975 Edition of the Standard Plumbing Code is hereby amended
to read as follows:
"(b) Under Ground -- Inaccessible water distribution
piping under slabs shall be copper water tube minimum
type L 194 Standard water tube~ brass, lead, cast iron
pressure pipe or galvanized steel pipe, all to be installed
with appropriate approved fittings: Galvanized steel and
type L cooper tube and 194 Standard water tube shall be
protected when used under floor slabs in corrosive soils.
All ferrous pipe and fittings shall be coated with coal tar
enamel or other coating approved for such purpose. All
threaded joints shall be coated and wrapped after instal-
lation. Copper water tube under slab shall be a continuous
loop, or all approved fitting must be silver soldered."
SECTION 2. That Table 505 of the Standard Plumbing Code
entitled "MATERIALS FOR PLUMBING INSTALLATIONS" is amended by
deleting from the list of materials Bituminized Sewer Pipe & Fittings and
Concrele Sewer Pipe.
-1-
SECTION 3. That Sub-section (a) of Section 1215.8 of the 1976
Revision to the 1975 Edition of the Standard Plumbing Code is hereby amended
to read as follows:
"1215.8 -- SAFETY PANS AND RELIEF VALVE WASTE
(a) When water heaters or hot water storage tanks are
installed above the ceiling level, the tank or heater shall
rest in a galvanized steel or other metal pan of equal
corrosive resistance having a thickness at least equal to
24 gauge galvanized sheet steel.
SECTION 4. The 1976 Revision to the 1975 Edition of the Standard
PlUmbing Code, as prepared by the Southern Building Code Congress International,
Inc. as amended, is hereby adopted by the City, and a copy of said 1976 Revision to
the 1975 Edition of the Standard Plumbing Code~ as amended, is filed in the office
of the City Clerk as a matter of permanent record of the City~ and the matters and
contents therein are made a part of this Ordinance by reference as fully and
completely as if set forth herein, and such copy shall remain on file in said office
available for public inspection.
PASSED AND ADOPTED this llth day of October
A.D.~ 1976.
Mayo r
Atte st:
Sanford, Florida.
CERTIFICATE
I, H. N. Tamm, Jr., City Clerk of the City of Sanford,
Florida, do hereby certify that a true and correct copy of
the foregoing Ordinance No. 1362, PASSED and ADOPTED by the
City Commission of the City of Sanford, Florida, on the llth
day of October, 1976, was POSTED at the front door of the
City Hall in the City of Sanford, Florida, on the 12th day of
October, 1976.
City of Sanford, Florida