FLORIDA FIRE & SOUND, INC.
637 TRIUMPH COURT — ORLANDO, FLORIDA 32805
407-298-8812 FAX 407 297-5882
www.FloridaFireandSound.com
EF 000 1162
DATE: 11/12/04
SUBMITTAL FOR:
Seminole Power Sports
1200 Rinehart Road
Sanford, Florida
FIRE ALARM SYSTEM
DESCRIPTION
MANUFACTUREE MODEL NO.
Fire Control Panel
FCI 7100-21D
Annunciator Panel
LCD -71 00
Suppl ' Notif. Appliance Circuit
SNAC-9
Manual Station
MS -7A
Smoke Detector
ASD-PL2
Base
ADB -FL
Duct Detectorr
ADP
Sampling Tube
ST -5
Remote Light
RA40OZ
Addressable Output Module
AOM -2R
Addressable Monitor Module
AMM -2
Wall Horn Strobe 11 Ocd
P1 224MC
Ceiling Horn Strobe 11 Ocd
P1 224MC
Sync Module
MDL
Fire Protective Cable
West Penn FPL -970
Fire Protective Cable
FPL -972
Fire Protective Cable
FPL -980
Fire Protective Cable
FPL -982
Battery
Elk ELK -1 280
Battery
.1 . ELK -1 2120
By: —7zr;�—
Sanford F
'Date: --,�
FIRE ALARM * CCTV * N
Fire Dept.
Final Insp.
Date�_
ACCESS* WTERCOM * BACKGROUND NIU!SIC
Date: 11/12/04
Time: 2:13 PM
1
110-90001
ASD -PL
Analog Photoelectronic Smoke Sensor
0.000
0.007
DUCT HOUSINGS,
12
121-90000
ACS -P200
Analog Duct Detector
0.004
0.004
ADDRIESSABLE M06ULES
3
190-00002
AMM -2
Addressable Monitor Mod, Cl "B"
0.001
0.021
6
190-90022
AOM -213
Addressable Output Relay Control Module
0.002
0.002
MANUAL STATi6rjis,
7
1100-0431
MS -7A
Addressable double action station (AMM -MS mini -module included)
0.002
0.002
PROJECT NAME:
Seminole Power Sports
1200 Rinehart Road
Sanford, Florida
Date: 11/12/04
Time: 2:13 PM
GTY ,Part#. Model,
Description 'StandbV.., Alarm
Current Current
a
C "�ICATIONAPP'iANCES-"-.-,"
L
F I NOTI
SPECTRALERT�' SERIES HORNSiSTROBL8
P1 224MC Horn, Electronic, w/1 10 cd Strobe, red 0.000 0.876
P11224 I IVIC Ceiling Horn, Electronic, w/1 10 cd Strobe, red 0.000 0.438
P1 224MC Ceiling Horn, Electronic, w/1 10 cd Strobe, red
0.000 0.292
ACCESSORIES:
POWER SUPPLIES
150-00012 SNAC-9 Supplementary Notification Appliance Ckt Panel 9 Amp W/ Sync 0.075 0.175
Total Supervisory Current, Amp
Enter number of standby hours per NFPA for the specific installation
Total Supervisory Capacity, A -H
Total Alarm Current, Amp
Enter Alarm period in minutes
Total Alarm Capacity, A -H
Total Alarm and Supervisory Capacity, A -H
0.075
'60
4.500
1.781
0.0833
0.148
4.648
. . ....... .
7, iZl
Provide 8 AH
FIRE CONTROL
INSTRUMENTS
UZI Building Intelligent Networks 7100SERIES
www.firecontrolinstruments.com
DESCRIPTION
The FCI 7100 series fire alarm control panel
is a multiprocessor-based,analcg addressable
system in a compact, yet expandable, plat-
form. Intended for commercial, industrial and
institutional installations, it is ideal for life safety
and property protection applications.
Th e basic 7 100 series control panel p ro-
vides two analog addressable signaling line
circuits (SLCs). Each SLC supports up to 99
analog addressable sensors, as well as up to
99 addressable monitor modules and/or con-
trol points.With 198 addresses available on
each SLC, total system capacity reaches 396
a did resses.The 7 100 uses an advanced Pre -
local that ensures an almost instant response
to events while at the same time suppressing
nuisance alarms.
The system may be programmed with ei-
ther theWindowsil-based Field Configuration
Program (FCIP-71 00) or through a compre-
hensive set of intuitive, securely Password
protected front -panel programming options.
This important feature allows the system to
quickly adapt to any future requirements
brought on by changes in Occupancies, build-
ing remodels, or other contingencies.
The sophisticated circuitry and powerful
analog software enables the 7 100 series fire
alarm control panel to read the specific sen-
sitivity level of each sensor and compensate
for any changes due to age, dust accumula-
tion or other environmental factors.Th e
7 100 incorporates the FC] Listed Integrated
SensitivityTesting (LIST) which meets NFPA
72 sensitivity testing and maintenance re-
quirementsThe LIST testing allows subsmn-
tial savings in both maintenance and service
while virtually eliminating nuisance alarms.
The Model 7 100-21D features an integral
DigimlAlarnn CommunicatorTransmitter
(DACT) with all popular transmission formats
and a 16 -digit telephone number field, It is 8 -
digit Carrier Information Code (CIC) compli-
ant and also prevents"clialer-runaway" in the
event of intermittent system faultsThe 7100-
2D is UL Listed for Remote Station, Propri-
etary,and Central Station fire alarm systems.
The 7 100 is housed in an attractive, con-
temporary styled cabinet. It allows ample
space for wiring and room for batteries up to
7A/H capacity.
FEATURES
Integrof DIgftaIA form Communicator
(with the 7100-2D)
120 or 240YAC (optional) Input Line
Voltage
Intuitive Front Panel Programming
o 80-characterAlpho-numeric Display
Two Style 4 (Class"B") Signaling Line
Cimuits.Style 6 (Class"A") with
optional CACIM module
Two Style Y (Class "B") Regulated
Notification Appliance Circuits rated fo r
I.SA mp. each. Style Z (Class"A") with
optional CACIM module
Suitable for Pre -Action Deluge
applications with optional MCOM module
I Available with Plastic orMetal Door
PirriodicTrouble Reminder
-Individual Sensor Drift Compensation
Listed Integral SensitivityTesting (LIST)
Dual -stage Maintenance alerts ("Dirty"
and" Very Dirty")
Multilevel Sensor Sensitivity
Adjustments (Front Panel programmable)
Daylilifight SensitivityAdjustments
(Front Panel programmable)
Alarm Verification per Individual Sensor
PositiveAlarm Sequence for Sensors or
ManitorModules
Four Levels ofSystemAccess using Six
Digit Passwords with up to Five User
Passwords per Level
A Duplicate and ExtroA ddress Indications
ManchTime (60 or 120 BPM)/Temporol
Pattern/ Coded FoursiCallfornia Code/
User-Deftned Zone Coding
Cross Zoning
System Configuration Programming and
500 Event Log stored in Non -Volatile
Memory
Fan Restart with Sequential Restart Delay
Uploodi Download ol"Ponel Configuration
between Panel and FCP-7 100 program
(Password Protected feature)
Up to 64 7 100 panels In NetS0L0"
network with optional lNf-7100 module
COMPACTANALOG
ADDRESSABLE FIRE
CONTROL PANEL
(K) <,l
SiB69
MEA
307-99-E
3 0 M9 - EV. 1. 11
05211,
7165.0694:�l 9 (7 100)
7300-0694i231 (LCD -7100)
7300-0694:241 (LDM-7100)
An ISO 9001 Compan
1�1 1— 1.
All Rlg R--d
P- I
A H.n.y11 C.mpy
FIRE CONTROL
INSTRUMENTS
RiFloBuilding Intelligent Networia 7100 SERIES
www.firecontrt)linstruments.com
OPTIONAL ACCESSORIES
LCD -7 100
The LCD -71 00 remote serial display offers an 80-chal-
acter alphanumeric readout lbr remote display ofall sys-
tem events. It duplicates all the information on the 7 100
series panel displw/ and pmvides key switch protected func-
tions such as System ResefAlarmAcknowledge7rouble
Acknowledge, Signal Silence,and Dril;Test.
LEDs on the LCD -7100 indicateAlarm, Supervisory, Sys-
temTrouble, Pbwer Fault,Systems Silenced, NAC# I,and
N AC#2 Silenced conditions.
The LCD -7 100 can be surface or semi -flush mounted
on a standard four -gang electrical box and it can be in -
smiled up to 4.000 feet (1,219 m) from the main control
panel.The 7 100 series fire alarm control panel can sup-
port up to five (5) remote LCD -7 100 annunciators using
one pair of twisted, n on -shielded I BAWG min.wire for
serial communication and another pair of 16AWG min.
for operating voltage. (Refer to 9020-0486)
LDM-7100
The LED Driver module (LDM-71 00) is designed to
mount in a U.L. Listed remote annunciator and provides
outputs for remote panel switches and 33 remote LEDs.
Three LDM-7 100 modules may be installed in a single an-
nunciator for a total of 99 LEDs per annunciator This
combination may be repeated up to five times for a total
offifteen (15) LDM-7 100 at up to five different locations.
Maximum distances of up to 4,000 feet (1,219 in) can be
achieved using one pair of twisted, non -shielded wire for
serial communication and another pair ofstraight-lay wire.
for operating voltage. (Refer to 9020-05 19)
CAOM
The Class"A" Optional module (CAOM) allows StyleY
arid Z (Class"B" and"A") operation for, both Notification
Appliance Circuits and Style 4 and 6 (Class"B" and"A")
for both Signaling Line Circuit.. It also provides discon-
nect switches for each signaling line circuit and a com-
men disconnect Switch for both notification appliance cir
CLuts.
MCOM
The Municipal Connection Option Module (MCOM)
provides three choices of outputs. It can be configured as a
Municipal Circuit (City Box) output at:
- 24VDC nominal voltage
-0.0018 amp supervisory current
-0.5 10 amp maximum alarm current
-35 ohms maximum line resistance
- 14.5 ohms maximum trip coil resistance
It may also be setto serve as a Reverse Polarity output
with a nominal voltage output of 24VDC at 0.0 12 amp
maximum alarm and supervisory current.
The third option the MCOM provides is as a releasing
solenoid output rated at:
-24VDC nominal voltage
0.005 amp supervisory current
0.7 10 amp maximum alarm current
-2 ohms maximum line resistance
it is suitable to be used with:
-Skinner I2V2LBX25
A Asto T82 I OA 107
Asco 82 1 OG207
Skinner 73218BN4UNLVNOC I I I C2
-Skinner 73212BN4TNLVNOC322C2
-Skinner 71395SN2ENJ I NCH I I I C2
PTRM
The PrinterTransient module (PTRM) provides RS -232
Isolator/Transient protection for the 7 100's RS -232 port
(BSM connector J2). It is used in conjunction with a serial
printer applied to the RS -232 port for permanent record
keeping.
INI-71 00
The Intelligent Network Interface module allows the
7100 series fire alarm control panel to become the
platform ofa peer -to- peer, token ring,selfregenerative
network comprised of up to sixty-four (64) 71 00s.
Sp-11 1 -id -d b, m bA -d .,,d bl,li
FIRE CONTROL INSTRUMENTS
16 5—h— P,,kWd,MA02090 USA - T.1:781-471-3000 - Nx:781-471-3099
A H.neywerl C.mpy
EH38FIRE CONTROL
INSTRUMENTS
8wildingintelfigentNet—,k,
wwwfirecontrolinstruments.com
niH 11
, 0-t
T81 TBZ TB3 T"
r— — — — — — --
BSM
06 (7) 0
67
1 2 4 5 7 8
i —d . b� —d -- �1... -d — h. -.d . b�
- d e, -- �, e 2-11 Righ- R.I.— d
FIRE CONTROL INSTRIJ M ENTS
16 S—J-- NrkW,00d, MA 02050 USA - T,1.781-471-3000 - hx: 781-471-3099
A C.mp..y 1- —1— � 3 1 1— 1 �11
FIRE CONTROL
INSTRUMENTS
10[uilding Intelligent N,tw,&j 7100 SERIES
www.firecontmlinstruments.com
SPECIFICATIONS
Primary Input Power
Output Power
Non-resettable Power
Resettable Power
Two (2) Notification Appl i ance Circuits
Current
7100-2 (Two Loop)
7100-21D (Two Loop w/Dialer)
LCD-7�00
LDM-7 00
INI-7100-UTP,-FO
OperatingTemperature
Relative Humidity
Battery Charger Capacity
Alarm &Trouhle Relay Contacts
Dimensions
7100
LCD -7100
LDM-7100
Weight (7 100)
AGENCYAPPROVALS
U. L. File 5 1869
FM Approved
CSFM 307-99-E
307-99-EVol.11
MEA 7 165-0694:219 (7100)
7300-0694:231 (LCD -7100)
7300-0694:241 (LDM-7100)
120VAC,50/60 Hz @ 2.0 amps or 240VAC,SO/60 H� @ 1.0 amp
4 amps. @ 24VDC (tocal)
1.0 amp. max.
1.0 amp. max. 1 1.0 amp. max. from
both circuits
1. 5 am p- each @ 24VD C
Superviso,y
Alarm
0.065 amp.
0.085 amp.
0.085 amp.
0. 105 amp.
0.050 amp.
0.075 amp.
0.035 amp.
0.200 amp. (All LEDs lit)
0.040 amp.
0.040 amp.
32 - 120- F (0 - 49- C)
85 % (non -condensing)
3 1 A/H (Cabinet accommodates
7A/H Sim batteries)
Form"C",2 amps.@ 24VDC (resistive)
16.9" H . 14.5"W . 3" D (40 . 37 x 7.5 c,n)
4.25 " H x 8,25"W x 1.88" D (1 1.5 x 20.5 x 4.6 cm)
6"W x 4 1/2"W (15.24 x 1 1.5 cm)
24 lbs ( I I kg)
-o -d b� —d --N— p., - .,.d — b.1—d . b�
i,� --, —, —. —-1 �. --, -- t, 2-11 R K—, -d
FIRE CONTROL INSTRUMENTS
16 S,,Lt,w,,t P�rkVV,,t.,,d.MA 02090 USA - Tel!781-471-3000 - F,,: 781-471-3099 - —firecon—lins—m--c—,
A ll—y—d C—p-y 1.2-11110113 1
ffir"Mr�mv
FIRE'CONTROL
INSTRUMENTS
Building Intelligent Networkj 1100 SERIES
www.firecontr-oIinstruments.com
ORDERING INFORMATION
BASIC KITS
Part Number
Model
Description
00-�311
BK -7100-2
Basic System Kit,2 SLC (BSM,Keypad DisplayTransliormer)
00- 312
BK -7100-2D
Basic System Kit w/ DACT2 SLC
1100-1313
BK -7100-2-240V
Basic System Kit,2 SLC,240VAC
1 100-1314
BK -7100 -2D -240V
Basic System Kitw/ DACT 2 SLC,240VAC
CABINETS
1 100-1307
7100 -ENC -PLASTIC
Enclosure with Plastic Door, standard (16.9" H x 14.4" D x 3" D)
1 100-1308
7100 -ENC -META L
Enclosure with Metal Door, standard (16.9" H x 14.4" D x 3" D)
1 100-0480
NS -7100B
Enclosure, NetSOLO", Broadband, black (19" H x 19"W x 4" D)
1 100-0481
NS-710OR
Enctosure, NetSOLW Broadband,red (19" H x 19"W x 4" D)
OPTIONALMODULES
1 100-0399
LCD -7100
Remote SerialAnnunciator (80 -character)
1 100-0428
LDM-7100
Remote LED Driver Module
1 100-1233
CAOM
ClassA Option combination module with disconnect switches
for both Signaling Line Circuits and NotificationAppliance Circuits
1 100-1234
MCOM
Municipal Connection Option Module for Local Energy City Box,
Reverse Polarity Signaling, or Releasing Solenoid
1 100-1235
PTRM
PrinterTransient Module
1 100-0440
INI-7100-UTP
Intelligent Netvvork Interface module- UnshieldedTwisted Pair
1 100-0439
INI-7100-FO
Intelligent Network Interface module- Fiber Optic
REPLACEMENT PARTS
1420-0429
EN -71 00
Enclosure (replacement)
1 120-0779
CS -7100
Plastic Door (replacement)
1 120-0867
CS -7100M
Metal Door (replacement)
1 120-0778
T-71 00
Transiormer, 120VAC input (replacement)
1 120-0801
T-7100-240
Transbrmer,240VAC input (replacement)
1 120-0781
BSM -2
Basic System Module, 2 SLC (replacement)
1 120-0780
BSM -2D
Basic System Module,2 SLC vv/DACT (replacement)
1 120-0767
KeypadAssembly (replacement)
Sp-ir. p—d
------- I
FIRE CONTROL INSTRU MENTS
16 S ou th we s t Ph rk.We s two o d, M A 02090 USA - Te 1: 78 1-471- 3 000 - h : 781 -471.3 09 9 - www.fi re co n t ro I in s I r, me,, - c, m
A 11.neyw.11 Co.p.ny 9020 0466NER. 2�3 / Pq� 5 d S
IIIIIIIIIN E FIRE CONTROL
INSTRUMENTS
il FIRECONTROLINSTRUMENTS.COM
DESCRIPTION .
The LCD -7100 Remote Serial Display provides superior
flexibility to the 7100 Series installations. It features an.
80 -character display which duplicates all the information on
the 7100 Series panel display with the exception of menus,
The LCD -71 00 contains the following function keys:
Alarm Acknowledge
Trouble Acknowledge
Signal Silence
System Reset/Lamp Test
System Drill Test
A keylock must be placed in the "ON" position to enable
the function keys with the exception of the "Trouble Ac-
knowledge" key which is used to silence the trouble sounder
on the LCD -71 00.
LEDs on the LCD -7100 are:
Alarm
Supervisory
System Trouble
Power Fault
System Silenced
NAC #1 Silenced
NAC -1"12 Silenced
INSTALLATION
The LCD77 100 can be surface or flush mounted on a stan-
dard -four -gang electrical box and installed up to 4,000 feet
away from the main control. The 7100 Series control panel
can accommodate up to five (5) remote LCD -7 100 annuncia-
tors.
APPROVALS
UL S1949 FM 3006578
CSFM NYC -MEA
7100 SERIES
tL,CD-7100
REMOTE SERIAL LCD DISPLAY
FEATURES
80 -Character LCD Display
Full Complement of Function Keys
and LEDs
Remote Location up to 4,000 Feet
Away from Control Panel
7100 Series will Accommodate up to
Five (5) Annunciators
Surface or Flush Mount on Standard
Four -gang Electrical Box
Compact, Attractive Appearance
SPECIFICATIONS
Operating Voltage 24 VDC (nominal)
Supervisory current .050 amp.
Alarm current .075 amp,
Operating tempe rature (recommended) 60 to 80' F (15 to 27' C)
Absolute maximum
operating temperature range 32 to 120" F (0 to 490 Q
Relative humidity 85% max., non -condensing at 90' F (320 C)
Dimensions 8 '/4"L x 4 1/2" H x 1 7/8" D (20.5 x 11.5 x 4.6 cm)
ORDERING INFORMATION
Part No. Model Description
1100-0399 LCD -71 00 Remote Serial LCD Display
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed
by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice, (D 1999 All Rights Reserved
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
An ISO 9001 Cenified Company 9020-0486 /Ver. 1.4
��FIRE CONTROL
INSTRUMENTS
ASB=PL2
by:Honey"11
www.firecontrolinstruments.com ANALOG, ADDRESSABLE
PHOTOELECTRONIC
lei =1 i! I 4.11T-11 I
The FCI Series analog addressable plug-
in smoke sensors with integral communi-
cation provide features that surpass con-
ventional sensors. Sensitivity can be pro-
grammed in the control panel software, and
is continuously monitored and reported to
the panel. Point ID capability allows each
sensor's address to be set with decade
address switches, providing exact loca-
tions for selective maintenance when
chamber contamination reaches an unac-
ceptable level. The ASD-PL2 photo- elec-
tric sensor's unique optical sensing
chamber is engineered to sense smoke
produced by a wide range of combustion
sources. Dual electronic thermistors add
135'F (57'C) fixed -temperature thermal
sensing on the ASD-PLT2.
INSTALLATION
ASD-PL2 plug-in sensors use a sepa-
rate base to simplify installation, service,
and maintenance. A special tool allows
maintenance personnel to plug in and re-
move detectors without using a ladder.
Mount the base on a box which is at
least 1.5" (3.81 cm) deep. Suitable mount-
ing base boxes include:
* 4.0" (10. 16 cm) square box.
* 3.5" (8.89 cm) or 4.0" (10.16 cm) oc-
tagonal box.
* Single -gang box (except relay or isola-
tor base).
* With B501BH base, use a 4.0" (10. 16
cm) square box.
* With B224RB or B224BI base, use a
3.5" (8.89 cm) octagonal box, or a 4.0"
(10.16 cm) octagonal or square box.
NOTE: Because of the inherent supervi-
sion provided by the SLC, end -of -line
resistors are not required. Wiring 7 -taps"
or branches are permitted for Style 4
(Class "B) wiring.
FEATURES
• Sleek, low -profile design.
• Analog Addressable communica-
tion.
• Stable communication technique
with noise immunity.
• Low standby current.
• Rotary 01 to 99 address switches
• Optional remote, single -gang LED
Indicator (RA400Z).
• Dual LED design provides 360
viewing angle.
• Visible red LEDs flash every time the
detector is polled, and light steadily
on alarm.
• Built-in functional test switch
activated by external magnet.
• Optional relay, isolator, orsounder
bases.
- Listed to UL 268.
DETECTOR SPACING:
FCI recommends spacing sensors 'in
compliance with NFPA 72. In low airflow
applications with smooth ceilings, space
sensors 30 feet (9.144 m). For specific
information regarding sensor spacing,
placement, and special applications, refer
to NFPA 72. System Smoke Detector
Application Guide, document A05-1003,
is available at www.systemsensor.com.
SMOKE SENSOR
ASD-PL2
ASD-PTL2
LISTEO
a
<a>
APPROVED
An ISO 9001 ComDan
Specifications are provided for information only, and
are not intended to be used for installation purposes
and are believed to be accurate. However, no respon-
sibilityis assumed by Fire Control Instruments for their
use Specifications subject to change without
notice.
0 2003 All Rights Resenied
9020-0559tver. 1.2 Page 1 of 2
Fed
Asn=PI9
by Honeywell
REMOTE ANNUNCIATOR
+
+ — — — — — — — — — — — — -
Listed
Compatible
CONTROL 2 2
PANEL 03 3
--------------------------------------------
OPTIONAL RETURN LOOP
-------------------------------------------------------
SPECIFICATIONS
Size: 2. 1 " (5.1 cm) high x 4.1 " (110.4 cm) diameter installed in B501 base, 6.1 " (15.5 cm) diameter installed in ADB -FL
base.
Shipping weight: 5.2 oz. (147 g).
Operating temperature: ASD-PL2- O*C to 49'C (32'F to 120*F); ASD-PTL2- O'C to 38*C (32*F to 1 00'F).
Low-temperature signal forASD-PTL2 at 45'F/7.22'C (+/— 1 O'F/5.54'C).
UL -Listed velocity range: 0 — 4000 ft./min. (1219.2 m/min.), suitable for installation in ducts.
Relative humidity: 10% — 93% noncondensing.
Thermal ratings: fixed -temperature setpoint 135'F (57'C).
ELECTRICAL SPECIFICATIONS
Voltage range: 15 - 32 volts DC peak.
Standby current (max. avg.): 250 pA @ 24 VDC (without communication); 360 pA @ 24 VDC (one communication
every 5 seconds with LED enabled).
LED current (max.): 6.5 mA @ 24 VDC ("ON").
BASES AVAILABLE
B21OLP: 6.1" (15.5 cm) diameter.
B501: 4.1 " (110.4 cm) diameter.
B501 BH or B501 BHT: Sounder base assembly (13501 BHT produces a temporal pattern). Includes B501 base.
B224RB Relay Base: Screw terminals: up to 14 AWG (2.0 MM2) . Relay type: Form -C. Rating: 2.0 A @ 30 VDC
resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive. Dimensions: 6.2" (15.748 cm) x 1.2" (3.048 cm).
B524BI Isolator Base: Dimensions: 6.2" (15.748 cm) x 1.2" (3.048 cm). Maximum: 25 devices between isolator
bases.
Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate.
However, no responsibility is assumed by Fire Control Instruments for their use. Specifications subject to change without notice. C2003AII Rights Reserved
FIRE CONTROL INSTRUMENTS
16 Southwest Park, Westwood, MA 02090 USA - Tel: 781-471-3000 - Fax: 781-471-3099 - www.firecontrolinstruments.com
A Honeywell Company 9020-0559/Ver. 1.2 / Paoe 2 of 2
EY1'FIRE CONTROL
INSTRUMENTS
B'un1jhg.1ab@1Zfg=tNeWoAs
www.firecontrolinstruments.com
DESCRIPTION
The Fire Control Instruments ADP
Low_ Flow Series photoelectronic air duct
smoke sensors are capable of sensing
smoke in air velocities from 100 to 4,000
feet per minute (0.5 to 20.32 m/sec).
The ADP series features low -flow tech-
nology that enables duct smoke detection
throughout a broad range of airflow
environments. Many difficult to solve
HVAC applications occur in low airflow
duct applications where reliable smoke
detection is critical. ADP low -flow tech-
nology can detect smoke at air speed ve-
locities of 100 feet per minute or greater,
while continuing the same reliable perfor-
mance to 4,000 feet per minute.
The ADP Series sensor samples air cur-
rents passing through a duct and gives de-
pendable performance for shutdown of fans,
blowers, and air conditioning systems, pre-
venting the spread of toxic smoke and fire
gases through the protected area.
These intelligent sensors communicate
and are continuously monitored through the
signaling line circuit. Sensor sensitivity
changes caused by dirt, temperature, or
humidity are reported to the panel, allow-
ing compensation algorithms to maintain
the sensor's set sensitivity. An advance
indication at the panel specifies the sen-
or address, allowing for selected main-
tenance to be performed as needed.
Remote alarm annunciation can be
accomplished by using the RA40OZ Re-
mote Annunciator or the RTS451 or
RTS451KEY Remote Test Station. Both
these devices allow testing of the sensor
from a remote location,
The ADP series low -flow duct sensors
are designed for simplified installation and
easy maintenance. The modular construc-
tion allows for easy cleaning and uncom-
plicated field replacement of the UL rec-
ognized power and sensor boards.
AUP Series
The ADIP (non-rela y) has outputs for a
remote LED display and remote test
switch. It incorporates zener diodes to con-
serve power for commu nications to other
devices.
The ADP is a 2 -wire device that requires
signaling line circuit power only.
The ADP -R (with relay) has powered
outputs for remote LED indication with
a remote test switch and audible sounder.
Two form "C" auxiliary contacts can be
configured as a relay version or jumpered
to mimic the non -relay version. It has a
patented cover tamper trouble signal.
The ADP -R is a 4 -wire device that requires
both signaling line circuit power and either
24VAC/DC or 120/240VAC for proper op-
eration.
FEATURES
Air Velocity rating from 100 to 4000
feet per minute (0.5 to 20.32 mIsec.)
Patented Telescopic Sampling Tube
Easily accessible Code Switches
Outside Mounting Tabs
Easy and quick mounting to Round
or Rectangular Ducts from V- 12'
(0.3-3.7 meters) wide
Easy to clean
UL Recognized Field -replaceable
Power and Sensor boards
Transparent Cover for convenient
Visual Inspection
UL 268A listed
ANALOG,
ADDRESSABLE
LOW -FLOW DUCT
SENSOR
2-J, In,
0.
ADP
MRN
ADP -R
L
A
An ISO 9001 Compan
-1 ARRIg-s—
A Honeywell Company
FIRE CONTROL
INSTRUMENTS
COMMUNICATION
L04E
Ul LISTED CONTROL
PANEL
ADP Series
I ST DETECTOR 2ND DETECTOR
IN LOOP IN LOOP
Wiring diagram for ADP Duct Smoke Sensor
using a LIL Listed control panel
41
00
AUP nA40OZ
Wiring diagram for ADP Duct Smoke Sensor with optional RA40OZ
(Must break tab on back of RA40OZ when used with ADP.)
ADP
tOMMON
ATS45IMTSMIKEY
FOR RTS46I.TERMINAL.3 IS NOT USED.
(I'll S451 DDES NCI HAVE A YERMINAL 64
FOR RT8461KEY, TERMINA1.8, 7AND C,
ARE NOr USED -
Wiring diagram for ADP Duct Smoke Sensor with RTS451/RTS451KEY
02MMm,h%R..d
FIRE CONTROL INSTRUMENTS
16 Southwest Park, Westwood, MA02090 USA - Tel: 781471-3000 - Fax: 781-471-3099 - www�flrecontmlimstmments.com
A Honeywell Company 90-- lo
L-M2 _,1
FIRE CONTROL
INSTRUMENTS
k wilt'antm...A. AUP Series
COMMUNICATION . . ... ...
LINE
............
11 tj
EM C
j, LIVED r . ....... 61 r�_ .
Q - .] =
PANEL .11JUMPE—f ISTOETECTOR J1 JUMPER . 2ND DETECTOR
lu,Lobp IN Loop
Wiring diagram for ADP -R Duct Smoke Sensor using a UL Listed control panel
NOTE: Jumper J1 shunt must be installed for 2—ire applications. J1 shunt must be removed for power PCB
supervision.
RA4MZ
W'Wn WVA-YAOG14110�,W
Wiring diagram for ADP -R Duct Smoke Sensor with
optional RA40OZ
.. ........... ik'
mg-
T�n'r4k S ANO,� ME NOT USED.
Wiring diagram for ADP -R Duct Smoke Sensor with
RTS451/RTS451KEY
S .'x-- nd — b W — —nd— -w 0 W ww
FIRE CONTROL INSTRUMENTS
16 Southwest Park, Westwood, MA 02090 USA - Tel: 781471-3000 - Fax: 781-471-3099 - —fireconlrolinstru—t,-m
A Honeywell Cornpany
FIRE CONTROL
INSTRUMENTS
'B"'al'ing J) talLi;" tH so, 0A, AUP Series
ADP SERIES LOW -FLOW SPECIFICATIONS
Operating Temperature Range
32* to 131'F (0' to 55*C)
Operating Humidity Range
r
Storage Temperature Range
-22* to - 1 58'F 00' to +70' C)
117)
.......
...
ADP:
5 � Alaurn Signal
ADP -R:
3.90lbs. (1.8 kg)
t
7 - AW. Po.ef I-)
Width
. ..... . ....
........... ................. ........... _J
Wiring diagram for ADP
-R Duct Smoke Sensor
with optional PA400
Wiring diagram for ADP -R Duct Smoke Sensor with
optional RA40OZ
.. ........... ik'
mg-
T�n'r4k S ANO,� ME NOT USED.
Wiring diagram for ADP -R Duct Smoke Sensor with
RTS451/RTS451KEY
S .'x-- nd — b W — —nd— -w 0 W ww
FIRE CONTROL INSTRUMENTS
16 Southwest Park, Westwood, MA 02090 USA - Tel: 781471-3000 - Fax: 781-471-3099 - —fireconlrolinstru—t,-m
A Honeywell Cornpany
FIRE CONTROL
INSTRUMENTS
'B"'al'ing J) talLi;" tH so, 0A, AUP Series
ADP SERIES LOW -FLOW SPECIFICATIONS
Operating Temperature Range
32* to 131'F (0' to 55*C)
Operating Humidity Range
10% to 93% relative humidity (non -condensing)
Storage Temperature Range
-22* to - 1 58'F 00' to +70' C)
Duct Air velocity
100 - 4000 ft./min. (0.5 - 20.32 m/s)
Shipping Weight
ADP:
3.35lbs. (1.5 kg)
ADP -R:
3.90lbs. (1.8 kg)
Length
14-3/4" (37 cm)
Width
5-1/2" It 4 cm)
Depth
2-3/4" (7 cm)
ADP SPECIFICATIONS
Voltage Range 15 to 32 VDC
Standby Current 300pA @ 24 VDC (one communication every 5 seconds with LED
flash enabled)
Accessory Current Loads
Device Standby Alarm
RA40OZ OmA 10 mA Max.
RTS451 /RTS451 KEY OmA 7.5 mA Max.
ADP -R SPECIFICATIONS
Current Requirements (using no accessories)
Power supply voltage: 20-30VDC 24 VAC, 50-60HZ 120VAC, 50-6OHz
220/240 VAC, 50-60Hz
Max. standby current: 26 mA 65 mA RMS 44 mA RMS
25 mA RMS
Max. alarm current: 87 mA 182 mA RMS 52 mA RMS
30 mA RMS
Alarm response tim:e 3 to 10 sec. 3 to 10 sec. 3 to 10 sec.
3 to 10 sec.
Power up time: 2 sec. 2 sec. 2 sec.
2 sec.
Contact Ratings
Alarm auxiliary contacts* (DPDT)
10 A @ 30 VDC
10 A @ 277 VAC (0.75 power factor)
240 VA @ 249 VAC (0.4 power factor)
1/8 HP @ 120 VAC
1/4 HP @ 240 VAC
Supervisory contact IS PST)
2.0 A @ 30 VDC (resistive)
*Minimum switching current for auxiliary contact must be 100 mA DC minimum 5 VDC.
Accessory Current Loads at 24 VDC
Device Standby Alarm
PA400 0 mA 15 mA Max.
RA40OZ OmA 12 mA Max.
RTS451/RTS451KEY OmA 10 mA Max.
Pnd.. .1— b
FIRE CONTROL INSTRUMENTS
16 Southwest Park, Westwood, MA 02090 USA - Tel: 781-471-3000 - Fax: 781-471-3099 - www.firecontrolinsfirUrnents.corn
A Honeywell Cmpany
ff'-'Yl'F'IRE CONTROL
INSTRUMENTS
B.'Wj'q' Mtan#_tN...&' ABP Series
ORDERING INFORMATION
Part N
Description
Remote test station
Analog addressable low -flow photoeiectronic non -relay duct smoke sensor
ADP -R
Analog addresable low -flow photoelectronic with relay duct smoke sensor
ST -1.5
Metal sampling tube duct widths V-2'
ST -3
Metal sampling tube duct widths 2'-4'
Replacement filters
Metal sampling tube duct widths 4'-8'
ST -10
Metal sampling tube duct widths 8'- 12'
A5053
Replacement photoelectric sensor board
A5060
Replacement power board for ADP -R (w/relay)
A5067
Replacement power board fprADP (w/o relay)
Accessories
Description
RTS451
Remote test station
RTS451KEY
Remote test station w1key
^'—RX4ddZ__-
Remote LED
P460
Mini -Alert' Sounder- Note: Device cannot be wired directly to ACID (non -relay).
F36-09-11
Replacement filters
M02-04-00
Test magnet
P48-21 -00
End cap for metal sampling tube
P48-61 -00
End cap for plastic sampling tube
S08-39-01
Replacement photo insect screen
TBO-71-00
Replacement plastic sampling tube
S�ffi
spm�Wnedt.� 0-aefta-
FIRE CONTROL INSTRUMENTS
16 Southwest Park, westwood, VA 02090 USA - Tel: 781-471-3000 - Fax: 781-471-3099 - www.fireconholinstruments,com
A Honeywell Company
FIRE CONTROL
INSTRUMENTS
WWW.FIRECONTROLINSTRUMENTS.COM
DESCRIPTION
The Addressable Output Relay Control Module
(AOM -2R) allows an FC1 analog addressable fire alarrn con-
trol to switch discrete relay contacts by code command. The
relayprovides two (2) isolated sets of Form -C contacts which
transfer simultaneously. Circuit connections to the relay con-
tacts are not supervised by the module.
TheAOM-2Rmodule is designed for installation in the sig-
naling line circuit of any FCI analog addressable control
panel, The signaling line circuits of FCT analog addressable
control panels are designed to accommodate up to 98 control
modules per circuit.
The module contains a panel controlled LED.
The AOM -2R is designed to mount in a 4" square j unction
box 2 1/8" deep.
AGENCY APPROVALS
UL S1949
Factory Mutual 3006398
CSFM NYC -MEA
A.OM-2R � (R
ADDRESSABLE OUTPUT RELAY,�
CONTROL MODULE
APPROVED
FEATURES
Two (2) Sets of Form "C" Contacts
Compact Size Allows Easy Installation
aw -
p,
Current Rating__
Maximum Volta2e
Load Description
b; tion
pjL _a____
3A
30 VDC
Resistive
Non Coded
2A
30 VDC
Resistive
Coded
0.9A
110VDC
Resistive
Non Coded
0.5A
125 VAC
Resistive
Non Coded
0.5A
30 VDC
Inductive (L/R=5ms)
Coded
IA
30 VDC
Inductive (L/R=2ms)
Coded
0.5A
125 VAC
Inductive (PF=.35)
Non Coded
0.7A
75 VAC
Inductive (PF=.35)
Non Coded
TECHNICAL INFORMATION
Supervisory current .00030 amp.
Alarm current .00030 amp.
Operating temperature 32 to 1200 F (0 to 49) C)
Relative humidity 10 to 93% relative humidity (non -condensing)
Dimensions 4 1/2" IJ x 4" W x 1 1/4" D ( 3.3 x 5.5 x 1.25 cm)
ORDERING INFORMATION
Part Number Model Description
190-90022 AOM -2R Addressable output relay control module
I ec,�,calcon, n,,,,ti ended to be used for installation PUMOSes. and are believed to be accurate. However. no responsibility is assamed by Fire Control In-
st nen"
for 'bri, u, c R ina a vithout notice.- CD 2001 All Right, RE,E,,ed
16 Southwest Park, Westwood, MA 02090 USA TEL: (7811) 471-3000 FAX: (781) 471-3099
An ISO 9001 Certified Corepany 9020-0520,,,Ver. 1.2
0
FIRE CONTROL
INSTRUMENTS
DESCRIPTION
The Addressable Monitor Module AMM -2 features a single
Style B, Class B initiating circuit with end of line resistor. This
module provides an address for any device or group of devices
connected to this circuit. Any alarm initiating devices with nor-
mally open (N.O.) dry contacts, such as heat detectors,
linear heat detection devices, projected beam smoke detectors,
4 -wire smoke detectors, water flow switches, tamper switches,
manual stations, etc. may be installed in this circuit.
The AMM -2 module is designed for installation in the signal-
ing line circuit of any FC1 analog addressable control panel.
The signaling line circuits of FC1 analog addressable panels are
designed to accommodate tip to 99 monitor modules per circuit.
The initiating circuit of the AMM -2 has a maximum line resis-
tance of 1,200 ohms, allowing the module to accommodate a
substantial number of initiating devices located at consider-
able distances from the module.
The compact size facilitates the installation of the module in-
side manual stations, or mounting boxes of various types of
alarm initiating devices.
AGENCYAPPROVALS
tL S1949
IM OVOA4.AY
NYGMEA MEA427-91-EVol.111
ICSFM Approved
U(D L
AMM -2 )
ADDRESSABLE MONITORMODULE
AWROWD
FEATURES
- Compact Size Allows Easy
Installation
- Class B, Style B Initiating
Circuit
0 1,200 Ohm Line Resistance for
Initiating Circuit
- Accommodates any N/O Dry
Contact Device
TECHNICAL INFORMATION
Supervisory current
.0004 amp.
Alarm current
.0006 amp.
Operating temperature
32 to 120'F ( 0 to 49, Q
Relative humidity
10 to 93 % (non -condensing)
Dimensions
1.3" H x 2.75" W x 0.5" D (3.3 x 5.5 x 1.25 cm)
ORDERING INFORMATION
Part Number Model Description
190-00002 AMM -2 Addressable Monitor Module, Single circuit, Style B, Class B
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed
by Fire Control Instruments, Inc. for their use. Specifications subject to change without notice, c2000 All Rights Reserved
301 2nd Ave Waltham, MA 02451-1133 USA TEL: (781) 487-0088 FAX: (781) 3 70-4132
9020-0502Ner. 1.0
FIRE CONTROL Slystem Sensor
INSTRUMENTS
SpectrAlert Sevies
Operates on either -12 VDC or 24 VDC
www.firecontrolinstruments.com
WidestRange ofCandela Options:
to
SELECTABLE OUTPUT
1211., 15 amd 15175 candela
STROBES AND HORNS
Description
MODELS P.1224MC,.-
The System Sensor Spectralert' select-
17/a" backbox using the universal mount-
S1224MC
able output strobes and horn/strobes offer
ing plate included with each Spectralert
enhanced features that include the widest
unit.
range of Gandela options available,and the
An optional strobe sychronization mod -
capability to recognize and self -adjust for
ule is available for compliance the Ameri-
either 12'or 24 volt operation.
cans with Disabilities Act (ADA). The MDL
Spectralert selectable candela wall-
(red) MDLW (white) synchronizes the
mounted strobes and horn/strobes offer
strobes at 1 Hz and the horns to a tempo- fi
key performance features long associated
ral 3 coded pattern. The synchronization
with the Spectralert name. The selectable
modules mounts on a 4 '74' x 4 x Al
candela strobes and horn/strobes offer av-
2 'A" backbox and supports two (2) Style
erage current draws that are not only
Y (Class B) or one (1) Style Z (Class A)
lower than conventional fixed -candela
notification appliance circuit. A separate
Spectralert products, but also lower
horn control input is available to allow
than similar products by others. By con-
silenceable audible devices and non-
suming less current, the ability to con-
nect even more devices per circuit is pos-
silenceable visual devices on the same pair
or wires.
sible, resulting in lower installed cost.
Spectralert selectable candela strobes and
horn/strobes offer the same installation -
friendly features synonymous with the
Spectralert name, such as the option of
2- and 4 -wire operation; the ability to use
standard size backboxes with no encroach-
ment into the box; and universal mounting
incorporating the labor-saving QuickClick-
feature. Such labor-saving features make wire
connections simple and fast, further
reducing installed cost.
These strobes and horntstrobes offer the
broadest range of candela options. In ad-
dition, they can operate�on either 12V or
24V with no settings required. The device
recognizes and self -adjusts to the correct
current automatically. Temporal 3 or con-
tinuous tone options continue to be avail-
able, in either an electro -mechanical or
3 kHz pattern
These strobes and horn/strobes incor-
porate the same stylish, low profile design
of the conventional Spectralert products,
for a consistent and aesthetically pleasing
appearance across the entire product
line. The selectable strobe and horn/
strobe is available in either red or white.
Thedevicesmountona standard4"x
4"xll/2"backboxorasinglegang2"x4"x
Features
Operates on either -12 VDC or 24 VDC
WidestRange ofCandela Options:
to
1211., 15 amd 15175 candela
�
24V., 15,15,75,30,75 110candela
i
Easy Candela Selection
Easy DIP Switch Selection for Horn
Options
Eask Mounting with QulcJ�Clfckl
Synchronization avalable with optional
MDL Sync�Clrcult- module
<
Meets UL1971, NFPA72, and ADA
Signaling ReqEdrements
MEA
An ISO 9001 Comoanv
�._'Al 1,.104
A Honeywell Company
FIRE CONTROL
INSTRUMENTS
Strobe only
Horn/ Strobe 15 cd:
Horn/ Strobe 30 cd
Sound output guide
SpectrAlert
Selectable Ouput
Strobe and Horn/Strobe
Spectralert Current Tables
Horn/ Strobe 75 cd
Horn/ Strobe 15175 cd:
Horn/ Strobe 110 cd:
* This tone only suitable for pilvate
mode use at rated voltage tested by UL.
FIRE CONTROL INSTRUMENTS
16 Southwest Park, Westwood, VIA 02090 USA - Tel: 781-471-3000 - Fax: 781-471-3099 - www�firecontmlinstruments.com
A Honeywell Company W�M6- 1.1 1 1�2d'
a SpectrAlert
1zFIRE CONTROL Selectable Ouput
INSTRUMENTS
Bu,g1!3gJbWn4entNobvks Strobe and Horn/Strobe
Strobe only:
lllllm�m�
WMIMNIMMMEMMM�Mmmm
a mmmmmamomol
mmmmommmmomm
Mo Mmmmm=Mm
MM MMEOMMEM
IMMIMMIMMM01
Horn] Strobe 15 cd:
Current measurements (Average RMS method)
NOTE: The 12V 15/75 cd strobe was tested at the 9.5-17.5
volt-FWP/DC limits. All other 12 V strobes were tested at the
8-17.5 volt-FWR/DC limits. All 24V strobes were tested at the
16-33 volt-FWR/DC limits. This does not include the 80% low
end or 110% high end voltage limits.
Hom/ Strobe 15/75 cd:
Moo = WE N
no =M=mmi
Horl Strobe 30 cd:
Horn/ Strobe 75 cd:
Em
moon
moon
OM
M mo mom
Memo
m on oino
om
E
a!= M
ommomm
Horn/ Strobe 110 cd:
NEWN-WE
MW Moo
FIRECONTROL INSTRUMENTS
16 Southwest Park, Westwood, MA02090 USA - Tel: 781-471-3GOO - Fax: 781-471-3099 - wwwfireconholinstruments.com
A Honeywell Company
EFIRE CONTROL
INSTRUMENTS
?3'B'.M,hgMW2Z#antN.tv..ks
Specifications
Walk Test
SpectrAlert horn/strobe and horn only work on
1� walk tests" with time durations of4 seconds
or greater
Input terminals
12 to 18 AWG
Dimensions
Strobe and horn/strobe with universal plate
5" x 5 5/8" x 2 15/is"
Strobe and hom/strobe with small
footprint plate
3 3/s" x 5 sh" x 2 clis"
Hom with universal mounting plate
5" x 5 5/a" x 1 5/16"
Horn without mounting plate
2 `hs" x 5'/11," x 1shli"
Weight, horn only
7.2 Oz.
Weight, strobe and hornistrobe
&8oz.
Ordering Information
SpectrAlert
Selectable Ouput
Strobe and Noru/Strobe
Mounting
4" x 4"x 1 1/2" or 2" x 4" x 17/6"
standard boxes
Indoor operating temperature
32'F to 120'F (O*C to 49'C)
Maximum humidity
95% as tested per UL464
Weatherproof (horn and horn/strobe)
Operating temperature
32*F to 150'F (O'C to 6l
(outdoor strobe only)
-40'F to 158*F (-40'C to 70*C)
Voltages
12 or 24VDC and FWR unfiltered
Operating Voltage Range*
12V: 10.5-17V 24V: 20-30V
Operating Vbl�ge Range
(with Sync -Circuit module MDL)
12V: 11-17V; 24V: 20-30V
* These products should be operated within their rated
voltage range; UL does test functional integrity to -20%
and �10% of manufacturer's stated ranges.
Red W hib, C—d.� Avg.— Av,A- ,
0 N—.VDC 0 K.. VDC--
1`122414- .224MCW 12/-A -rbl�
1q,15/75,30,75,11011
T..22�IC a224MC14 12�'14
A—i-
S���Moduh ADL ADfN 12/2,t NA 1D/11 22/15
Sr. &11�tpmi M'"Iting P- Ji 9+1 P sm� N A N A NA
X � Bo� �xt bBS BB91 NA A NA NP,
U.1Ml±qPat. D�P D�w 1 A N A NA NA
hpl— en�'
H- SPWffl_..rj._ N.—t—,
FIRE CONTROL INSTRUMENTS
16 Southwest Park, Westwood, MA02090 USA - Tel; 781-471-3000 - Fax: 781-471-3099 - wwwfirecontrolinstruments.com
A Honeywell Company I I I . _.
_VV
RATING
- UL listed NEC type FPL
inch �vrn inch - Constructed in accordance
Egg with UL standard 1424
961 1 16 Solid .091 2.31 Black, Green,
Brown, White, - Complies with UL 1581
4.1 QX Red, Orange, Vertical Tray Flame Test
962 1 14 Solid .020 .51 .104 2.64 Yellow
- Temperature range:
2.6 QX
1 —20' C to 105' C
Standard spool size 1000 feet dry locations
- Meets 300 volt requirement
nt c arifind in KIP Artirin 7CZA
Standard spool size 1000 feet
r
APPLICATIONS
Indoor (non—conduit per NEC) for:
- Power— Limited Fire
Protective Circuits
WEST PENN WIRE /CDT--<- 61
Ell
�E"A a
F "'
af?
ANI,11,;A 0.
'dz
18 Solid
_0110
Red, White,
6.5 QX
Orange, Brown,
Blue, Black
16 Solid '
E
White, Red, Black
4.1 QX
14 Solid
White, Red, Black
2.6 QX
'HEM
12 Solid
White, Red, Black
Standard spool size 1000 feet
r
APPLICATIONS
Indoor (non—conduit per NEC) for:
- Power— Limited Fire
Protective Circuits
WEST PENN WIRE /CDT--<- 61
Power -Limited Multiple Conductor/Unshielded
988
10
18 Solid
.010
.25-
.020
.51
.294
SPECIAL NOTES
DESCRIPTION
6.5 QX
• Select cables are available in
ASTM bare copper
PVC insulation - Twisted pair or
990
1
cabled construction - PVC fillers as required
Polyester binders as required -
Overall 75' C PVCjacket
1�;TINO
Pair
.010
.25
.020
.5
.165
See AquasealO product line
I
4.1 Q/M'
• UL listed NEC type FPLR
I
• Constructed in accordance with
992
4
16 Solid
.010
.25
.020
.51
.213
• Orange ripcord underjacket
UL Standard 1424
4.1 QX
inch
rru�_
inch
mm
inch
n1m
• Complies with UL 1666 Vertical
1
1084
6
22 Solid
.010
.25,
.020
.51,
.179
Shaft (riser) Flame Test
2.6 QX
17.5 Q/M'
Green, White or Yellowjacket
700
4
• Temperature range-,
.012
1086
8
22 Solid
.010
'.25
.020
.51
.193
4.90,
- 20 * C to 75 0 C dry locations
17.5 Q/M'
998
1
12 Solid
-
.012
• Meets 300 volt requirements as
. rO2 5
-
980
1
18 Solid
.010
25"
.020
'.51
.156
3'06,
specified in Section 760 of the NEC
Pair
6.5 LVM'
COLOR CODE
APPLICATIONS
Standard spool size 1000 feet
982
4
18 Solid
.010
.25
.020
.51
.188
4.78,
Indoor (non -conduit per NEC) for:
6.5 f2/M'
• Audio circuits
984
6
18 Solid
.010
.25
.020
�.51
.224
5.139',
• Control circuits
6.5 n/M'
• Initiating circuits
986
8
18 Solid
.010
.25
.020
-_51,"
.252
40
• Notification circuits
6.5 K2/M'
Al
1 1 Black 6 1 Yellow
2 Red 7 Purple
3 Brown 8 Green
4 Blue 9 Red/Black
5 Orange 10 Red/White
50 --V- WEST PENN WIRE /CDT JACKET: Red
988
10
18 Solid
.010
.25-
.020
.51
.294
SPECIAL NOTES
6.5 QX
• Select cables are available in
990
1
16 Solid
1
outdoor and direct burial versions.
Pair
.010
.25
.020
.5
.165
See AquasealO product line
I
4.1 Q/M'
I
for details
992
4
16 Solid
.010
.25
.020
.51
.213
• Orange ripcord underjacket
4.1 QX
• Catalog No. 980, 982, and 990
994
1
14 Solid
.012
30
.025
-.64-
.205
are also available with a Blue,
Pair
2.6 QX
Green, White or Yellowjacket
700
4
14 Solid
.012
'30,
.025
1 64
.250
2.6 K2X
998
1
12 Solid
-
.012
TO
. rO2 5
"".64',-
.235
Pair
1.8 f2/m,
COLOR CODE
Standard spool size 1000 feet
1 1 Black 6 1 Yellow
2 Red 7 Purple
3 Brown 8 Green
4 Blue 9 Red/Black
5 Orange 10 Red/White
50 --V- WEST PENN WIRE /CDT JACKET: Red
, ELK- 1280 Sealed Lead Acid Battery
Sealed Lead Acid Battery
1EIK-1280 ) 12 Volts, 8 Ah
ELK Sealed Lead Acid Batteries are excellent for the
following applications with regard to size, Amp hour rating,
and proper terminal connections: battery backup (for
Access Control Systems, Fire Alarm Systems, and
Security Alarm Systems), emergency lights, lighted exit
signs, and uninterruptible power supplies.
SPECIFICATIONS:
• Nominal Voltage:
12 Volts
• Rated Capacity:
8 AH (20 hour rate)
• Length:
5.94" (151 mm)
• Width:
2.56" (65mm)
• Height:
3.74 (95mm)
• Total Height:
3.98" (110 1 mm)
• Weight:
6.17 lbs (2.8kg)
- Terminals:
F1 -Faston Tab No. 187,
U.L. Recognized
Two Year -Warranty
ELECTRICAL SPECIFICATIONS:
20 hour rate (0.375A)
8AH
Capacity
10 hour rate (0.71A)
7.1AH
77'F(25 -C)
5 hour rate (1.27A)
6.37AH
1 hour rate (4.5A)
4.5AH
Internal Resistance,
1 Omn
Fully Charged Battery (77'F)
104-F (40-C)
102%
Capacity affected by
77-F (25-C)
100%
Temperature (20 hour rate)
32-F (0-C)
85%
5-F (-15'C)
65%
Cycle: Initial Charging Current less than 2.25A
Charge Constant Voltage
Voltage 14AV - 15.OV at 77'F(25'C)
I
Standby: Voltage 13.5V - 13.8V at 77'F(25'C)
http://www.elkproducts.com/products/elk- I 280.htm
Page I of 2
11/12/04
ELK- 1280 Sealed Lead Acid Battery
�Dbebarge Churacteristits (WC, 6rF)
U
10
.12
Q )
tL— ' L --L--L . ..........
5 10 20 30 66 2 3 5 10 " 10 �Wice 1,6 is 30
Discbne Time Discharge Current
To order the ELK -1280
Call your nearest distributor or ELK at 1-800-797-9355 for more information
(,:Imrwcftr*fics MC/32"F,
7
[ Home ]
ELK Products, Inc. P.O. Box 100, Hildebran, N.C. 28637 USA (828) 397-4200
Copyright@2004 All rights reserved Terms and Conditions
http://www.elkproducts.com/products/elk- 1280.htm
Page 2 of .2
11/12/04
, ELK- 12120 Sealed Lead Acid Battery
ELK -12120 12 Volts, 12 Ah
ELK Sealed Lead Acid Batteries are excellent for the
following applications with regard to size, Amp hour rating,
and proper terminal connections: battery backup (for
Access Control Systems, Fire Alarm Systems, and
Security Alarm Systems), emergency lights, lighted exit
signs, and uninterruptible power supplies.
SPECIFICATIONS:
• Nominal Voltage:
12 Volts
• Rated Capacity:
12 AH (20 hour rate)
• Length:
5.94" (151 mm)
• Width:
3.90" (99mm)
• Height:
3.78" (96mm)
• Total Height
3.94" (1 00mm)
Weight:
8.82 lbs (4.Okg)
• Terminals:
F1 -Faston Tab No. 187
U.L. Recognized
Two Year Warranty
ELECTRICAL SPECIFICATIONS:
20 hour rate (0.6A)
12AH
Capacity
10 hour rate (1. 14A)
11AAH
77'F(25 -C)
5 hour rate (1.9A)
9.5AH
1 hour rate (7.2A)
7.2AH
Internal Resistance,
20mO
Fully Charged Battery (77'F)
104-F (40-C)
102%
Capacity affected by
77-F (25-C)
100%
Temperature (20 hour rate)
32-F (0-C)
85%
5-F (-15'C)
65%
Cycle: Initial Charging Current less than 3.6A
Charge Constant Voltage
Voltage 14AV - 15.OV at 77*F(25'C)
I
Standby: Voltage 13.5V - 13.8V at 77*F(25'C)
Dimensions(mm)
Page I of 2
http://www.elkproducts.com/products/elk- I 2120.htm 11/12/04
ELK- 12120 Sealed Lead Acid Battery
10
V
DiSebarge characteristics (20-c' WT)
DiscbaW Time
14,
3
2
I wk
Ln5cnarge 4.�namcftmsucs
1pl�
To order the ELK -12120
Call your nearest distributor or ELK at 1-800-797-9355 for
more information
[ Home ]
ELK Products, Inc. P.O. Box 100, Hildebran, N.C. 28637 USA (828) 397-4200
Copyright@2004 All rights reserved Terms and Conditions
Page 2 ef,2
http://www.elkproducts.com/products/elk- I 2120.htm 11/12/04