HomeMy WebLinkAbout132 Towne Center Cir - BC14-000379 (FRANCESCA'S) (INTERIOR RENOVATION) (A)MI
PROJECT SUMMARY
THIS PROJECT IS A LEVEL 2 IEBC INTERIOR FINISH BUILD -OUT IN AN EXISTING RETAIL
SPACE. THE BUILD OUT CONSISTS OF A NEW STOREFRONT, NEW INTERIOR FIXTURES,
AND NEW LIGHTING THROUGHOUT. NEW ADA TOILET hOOM. EXISTING HVAC TO BE
REPLACED WITH A NEW UNITS. DUCTWORK TO BE REPLACED. NEW ELECTRICAL PANEL
WITH MINOR ELECTRICAL UPGRADES.
THIS PROJECT IS ON THE FIRST FLOOR OF A 2 STORY BUILDING
VENDOR INFORMATION
Flooring Supplier: Order from Floor Zone, 10200 Hempstead Rd. 41G, Houston, TX 77092 Sales Rep. Mr. Jeff
Megow, 713- 205- 6400, leffrnegowC)vahoo.com. Project Manager Mr. Phillip Murillo, 713-683-7003,
p1nu1il[221lo2rzonellc.c0rn
Lighting Supplier: Order frorn Weidenbach Brown, Sales Rep. Mr. Ron Doyle, 714- 982- 1538,
run doyle@whlil;ht.com ;fcsupport@wblight.com. Manufacturer: MSI. xPar 38 LED lamps at 22deg spread. "crack
Fixtures: NORA, NT -3046, NT -3].213, NT -31613, NT32613, NT -3058 or 3068.
Low Voltage Contractor: CrossCom National, 900 Deerfield Parkway, Buffalo Grove, IL 60089. Rep. Ms. Susan
Medeiros, +1 (800) 933-9203 x 6291, srnedeirosCocrosscornnatlonal.com .
L
HVAC/Thermostat Supplier: Trane, National Rep. Ms. Lauren Burns, 972-406-3661, lauren.burn�(wtrane.corn
Stockroom Door: Masonite;36 in. x80 in. Smooth 15 -Lite French Solid Core Unfinished Pine Interior Door Slab,
Horne Depot SKU 11255250
Bathroom Door: Steves and Sons Inc., 36 in. x. 80 in. Composite Unfinished 14ush Interior Door Slab, Home
Depot Model /tQ68F11FCNAC99, SKU It 334219
Door knobs for Stockroom and Bathroom doors: Kwickset; Model 1197402-553/Venetian Bronze. SKU: 8-
8335107279-3.
Toilet: American Standard Madera FloWise I -Piece 1.6 GPF Hig l TQP Spud Elongated Flush Valve Toilet with
EverCleau in White, MFG Model 11 ;3461.001.020, MFC; Part 113461.001.020;
Toilet Valve: American Standard Manual 1.26 GP1' FloWise Flush Valve for 1.5 iu. Top Spud "Toilet in Polished
Chrome. MFG Model It 6047.121.002. MFG Pat It 60417.121.002
A.F.F.
ABOVE FINISHED FLOOR
ACOUS.
ACOUSTICAL
ADJ.
ADJUSTABLE
AL.
ALUMINUM
BOT.
BOTTOM
BD.
BOARD
C.L.
CENTER LINE
CER.
ACOUSTICAL
CAB.
CABINET
CONS -FR.
CONSTRUCTION
CTR
CENTER
CL.
CENTER
COL.
COLUMN
CONT.
CONTINUOUS
DWG.
DRAWING
ELEC.
ELECTRICAL
EL. OR ELEV.
ELEVATION
EQ.
EQUAL
EQPT.
EQUIPMENT
EX. OR EXIST.
EXISTING
ETR
EXISTING TO REMAIN
FRP
FIBERGLASS REINFORCED
PANELS
FRT
FIRE RESISTANT TREATED
F.D.
FLOOR DRAIN
FDN
FOUNDATION
FTG.
FOOTING
G.C.
GENERAL CONTRACTOR
GA.
GAUGE
GEN.
GENERAL
GYP. BD.
GYPSUM BOARD
HC
HOLLOW CORE
H.M.
HOLLOW METAL
LAM.
LAMINATE
MAX.
MAXIMUM
MATL.
MATERIAL
MTL.
METAL
MIN.
MINIMUM
O.C.
ON CENTER
SC
SOLID CORE
STN. STL.
STAINLESS STEEL
STD.
STANDARD
U.N.O.
UNLESS NOTED OTHERWISE
V.I.F.
VERIFY IN FIELD
DRAWING SYMBOLS
1
A101
ELEVATION REFERENCE
1
SECTION REFERENCE
A101
APPROVED FOR BUILDING PERMIT. ANY PROPOSED DEVIATION FROM THE LANDLORD APPROVED PLANS MUST BE NUMBERED AND CLOUDED ON THE
PLANS, AND THEN RESUBMITTED BY THE TENANT TO THE LANDLORD FOR RE -APPROVAL PRIOR TO ANY CONSTRUCTION CHANGES TAKING PLACE IN
1
A101
DETAIL REFERENCE
Name
Elevation
LEVEL REFERENCE
ODEMOLITION
REFERENCE
(D
SPECIFICATION REFERENCE
OKEYNOTE
REFERENCE
17
WALL TYPE REFERENCE
ODOOR
& WINDOW REFERENCE
i t
EQUIPMENT- REFERENCE
1t
FLOOR & FINISH REFERENCE
EXISTING WALLS
NEW WALLS
3) CONTACT PROPERTY MANAGEMENT FOR CONSTRUCTION BARRICADE REQUIREMENTS, INCLUDING BARRICADE GRAPHICS.
DEMOLISHED WALLS
200 TOWNE'OTER CIRCLE
GENERAL NOTES
1) ANY DISCREPANCIES BETWEEN THE EXISTING CONDITIONS DOCUMENTS AND THE ACTUAL FIELD
CONDITIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT BEFORE PROCEEDING WITH ANY
WORK.
2) THE CONTRACTOR SHALL REVIEW ALL DOCUMENTS AND VERIFY ALL DIMENSIONS AND FIELD CONDITIONS
AND SHALL CONFIRM THAT WORK IS BUILDABLE AS SHOWN. ANY CONFLICTS OR OMISSIONS, ETC., SHALL
BE IMMEDIATELY REPORTED TO THE PROJECT MANAGER FOR CLARIFICATION PRIOR TO THE
PERFORMANCE OF ANY WORK IN QUESTION.
3) WHEN CONTRACTOR ACCEPTS DELIVERY OF ALL ITEMS NOTED ON PLANS WHETHER IN CONTRACT OR NOT
IN CONTRACT, HE SHALL BE RESPONSIBLE FOR LOSS AND/OR DAMAGE TO THESE ITEMS.
4) THE CONTRACTOR SHALL MAINTAIN FOR THE ENTIRE DURATION OF THE WORK ALL EXITS, EXIT LIGHTING,
FIRE PROTECTION DEVICES AND ALARMS IN CONFORMANCE WITH ALL APPLICABLE CODES AND
ORDINANCES.
5) 'TYP.' SHOULD MEAN THAT THE CONDITION IS REPRESENTATIVE FOR SIMILAR CONDITIONS THROUGHOUT.
UNLESS OTHERWISE NOTED, DETAILS ARE USUALLY KEYED AND NOTED 'TYP.' ONLY ONCE WHEN THEY
FIRST OCCUR.
6) DO NOT SCALE DRAWINGS. WRITTEN DIMENSIONS TAKE PRECEDENCE OVER SCALED DIMENSIONS.
7) DIMENSIONS SHOWN ON PLANS ARE TO FACE OF GYPSUM BOARD, CONCRETE COLUMNS OR GRID LINES AND
FACE OF EXTERIOR MASONRY UNLESS OTHERWISE NOTED OR DETAILED.
8) CONTRACTOR SHALL, IN THE WORK OF ALL TRADES, PERFORM ANY AND ALL CUTTING, PATCHING
RESTORING, REPAIRING AND THE LIKE NECESSARY TO COMPLETE THE WORK AND RESTORE ANY DAMAGED
SURFACES RESULTING FROM THE WORK TO THEIR ORIGINAL CONDITION.
9) EACH CONTRACTOR SHALL LEAVE THE SITE IN A NEAT, CLEAN AND ORDERLY CONDITION UPON THE
COMPLETION OF HIS WORK ON A DAILY BASIS. ALL WASTE, RUBBISH AND EXCESS MATERIALS SHALL BE
REMOVED FROM THE SITE PROMPTLY. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR
REMOVAL AND DISPOSAL OF ALL TRASH.
10) CONTRACTOR TO PROVIDE A PORTABLE FIRE EXTINGUISHER WITH A RATING OF NOT LESS THAN 2-A OR 2-
A/1 OBC WITHIN 75' TRAVEL DISTANCE TO ALL PORTIONS OF THE BUILDING DURING CONSTRUCTION.
11) THE GENERAL CONTRACTOR IS RESPONSIBLE FOR RECEIVING, SAFE STORAGE, AND COMPLETE
INSTALLATION OF ALL MILLWORK.
DEFERRED SUBMITTALS
- SIGN SUBMITTALS
CODE SUMMARY
CODE DATA - FLORIDA
I. GENERAL SITE AND PROJECT INFORMATION
A. THIS A BUILD OUT OF A TENANT SPACE IN A MULTIPLE TENANT BUILDING. THE EXISTING SHELL
BUILDING IS BEING REUSED WITH NO MODIFICATIONS TO THE EXISTING STRUCTURE.
B. THE EXISTING BUILDING IS PROTECTED THROUGHOUT BY AN AUTOMATIC FIRE SUPPRESSION SYSTEM.
C. PROVISIONS HAVE BEEN MADE SO THAT ALL EXITS DISCHARGE TO GRADE OR AT ACCESS TO GRADE.
D. THESE CONSTRUCTION DOCUMENTS INDICATE FOR ACCESSIBILITY TO BE MAINTAINED BY THE
LANDLORD FROM THE PUBLIC WAY INTO, AND THROUGHOUT, THE BUILDING TO THE LEASE SPACE.
IL GOVERNING CODES
BUILDING: 2010 FLORIDA BUILDING CODE
MECHANICAL: 2010 FLORIDA MECHANICAL CODE
ELECTRICAL: 2011 NATIONAL ELECTRICAL CODE
PLUMBING: 2010 FLORIDA PLUMBING CODE
ENERGY: 2010 FLORIDA ENERGY CONSERVATION CODE
FIRE PROTECTION: 2010 FLORIDA FIRE PREVENTION CODE
ACCESSIBILITY: 2010 FLORIDA ACCESSIBILITY CODE
III. USE AND O.CCUPANCY CLASSIFICATION
A. SEC. 309.1- THIS PROJECT IS A RETAIL SALES STORE CLASSIFIED AS MERCANTILE USE
GROUP M.
IV. TYPE OF CONSTRUCTION
A. TABLE 601- CONSTRUCTION TYPE II -8 REQUIRES NO FIRE RESISTANCE RATINGS FOR STRUCTURAL
FRAMING, BEARING WALLS, FLOOR CONSTRUCTION, ROOF CONSTRUCTION, INTERIOR NONBEARING
WALLS & PARTITIONS.
V. INTERIOR FINISHES
A. TABLE 803.9- INTERIOR WALL AND CEILING FINISHES FOR OCCUPANCY GROUP M, SPRINKL.ERED, ARE
CLASS B FOR VERTICAL EXITS AND EXIT PASSAGEWAYS, CLASS C FOR EXIT ACCESS CORRIDORS
AND OTHER EXITWAYS, AND CLASS C FOR ROOMS AND ENCLOSED SPACES.
VI. MEANS OF EGRESS
A. VALUES ARE FROM PLAN LAYOUT CONTAINED IN THESE CONSTRUCTION DOCUMENTS.
SALES 798 sq. ft.
NON -SALES 202 sg. ft.
TOTAL LEASED SQUARE FOOTAGE 1000 sq. ft.
B. OCCUPANCY CALCULATION VALUES ARE FROM TABLE 1004.1.2 AND PLAN LAYOUT CONTAINED
IN THESE CONSTRUCTION DOCUMENTS.
SALES 798 sq. ft. 30 sq. ft. per person 27 persons
NON -SALES 202 sq. ft. 300 sq. ft. per person 1 persons
TOTAL OCCUPANT LOAD: 28 persons
C. EGRESS WIDTH CALCULATION VALUES ARE FROM SEC. 1005.3.2 AND CALCULATIONS ABOVE.
SPRINKLERED BUILDING WITH A TOTAL OCCUPANT LOAD OF 28 MULTIPLIED BY 0.2" PER
OCCUPANT EQUALS 5.6" OF EXIT WIDTH REQUIRED. 96" OF EXIT WIDTH HAVE BEEN PROVIDED.
KEY PLAN
SWORD gOILDING DIVISION
NALLY
- .ESE PIANS ARE REVIEWED AND CUNDIT SHALL BE
TH
ACCEPTED FOR PERMIT. A ISSU EOQ PERMIT
TNF YVORK
DEMO PERMISSION TO PROC
CANCEL, ATTER
AND NOT AS AUTHORITY 1VO
OVIOSIONS,OF THE TECHNICAL
OR SET ASIDE ANY OF THE PR
NOR SHAT-►. ISSUANCE OF A PERMIT PREVENTNO A F
CODES,
BUILDING DIVISION FROM CHEREAFT SR CONSTRUCTION
CORRECTION OF ERRORS ON T OFT E CODE'
OR OTHER VIOLATION,
r -M A nir-Nr-C%f-% AIC%
LANDLORD GENERAL NOTES
PROJECT DIRECTORY
CONTRACTOR CON -FACT
TBD.
ARCHITECTURAL CONTACT
EMMY MCLEES
WD PARTNERS
614-634-7188
emmymiclees@wdpartners.corn
ENGINEERING CONTACT
JOHN DEBRUHL - ELECTRICAL
WD PARTNERS
614-634-7000
john.debruhl@wdpartners.corn
JEFF BOLYARD - MECHANICAL
WD PARTNERS
614-634-7000
jeff.bolyard@wdpartners.com
CLIENT CONTACT
ALBERT CHINCUANCO
FRANCESCA'S
SR. DIRECTOR OF CONSTRUCTION
713-864-1358 x1269
albertc@francescas.com
AMANDA PETTER
FRANCESCA'S
CONSTRUCTION MANAGER
832-494-2274
arnanda.petter@francescas.corn
PROPERTY OWNER
SIMON PROPERTY GROUP
225 WEST WASHINGTON STREET
INDIANAPOLIS, IN 46204
CONTACT: DAVID FLETCHER
317-263-2287
BUILDING DEPARTMENT
CITY OF SANFORD, BUILDING & FIRE PREVENTION DIVISION
300 N. PARK AVE.
SANFORD, FL 32771-1788
407-688-5150
is AIR
PARTNERS
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNERS.COM
SEMINOLE T.C.
I.
i
200 TOWNE CENTER CIRCLE,
SPACE #D11 C_
APPROVED FOR BUILDING PERMIT. ANY PROPOSED DEVIATION FROM THE LANDLORD APPROVED PLANS MUST BE NUMBERED AND CLOUDED ON THE
PLANS, AND THEN RESUBMITTED BY THE TENANT TO THE LANDLORD FOR RE -APPROVAL PRIOR TO ANY CONSTRUCTION CHANGES TAKING PLACE IN
SANFORD, FL 32771
THE FIELD.
DRAWN BY:
I WD PROJECT NUMBER
k FRCC00050
1) PLANS REVIEWED AND APPROVED BY LANDLORD'S TENANT COORDINATOR MUST BE PRESENT ON THE JOB SITE AND BE ACCOMPANIED BY PLANS
APPROVED FOR BUILDING PERMIT. ANY PROPOSED DEVIATION FROM THE LANDLORD APPROVED PLANS MUST BE NUMBERED AND CLOUDED ON THE
PLANS, AND THEN RESUBMITTED BY THE TENANT TO THE LANDLORD FOR RE -APPROVAL PRIOR TO ANY CONSTRUCTION CHANGES TAKING PLACE IN
THE FIELD.
a u
2) TENANT'S GC IS REQUIRED TO CHECK IN WITH LANDLORD'S ON SITE PROPERTY MANAGER PRIOR TO THE START OF TENANT CONSTRUCTION. CONTACT
'NOV��
10
MALL MANAGEMENT OFFICE.
3) CONTACT PROPERTY MANAGEMENT FOR CONSTRUCTION BARRICADE REQUIREMENTS, INCLUDING BARRICADE GRAPHICS.
H E ET I N ®EX
4) TENANT'S GC IS RESPONSIBLE TO COMPLY WITH ALL MALL RULES AND REGULATIONS AND AS INSTRUCTED ON SITE BY MALL MANA(3EMENT.
ISSUE DATES
5) ANY DAMAGE TO LANDLORD'S PROPERTY DURING TENANT DEMOLITION OR CONSTRUCTION (MALL FLOORING, BULKHEAD, NEUTRAL PIERS, ETC.) WILL
T1
TITLE SHEET
PRELIM SET: 10-16-2013
BE REPAIRED PER MALL SPECIFICATIONS, AT TENANT'S EXPENSE.T2
RESPONSIBILITY SCHEDULE
0 FINAL SET: 11-6-2013
6) ANY LANDLORD EQUIPMENT OR COMPONENT THAT IS EXISTING IN THE SPACE MUST REMAIN VISIBLE AND ACCESSIBLE TO THE LANDLORD. TENANT TOCC
CODE COMPLIANCE]
PERMIT SET: 11-20-2013
INSTALL ACCESS PANELS AS NECESSARY, AND PROPERLY LABEL IN SPACE.
D1
DEMO PLAN
7) ALL LANDLORD COMMENTS FROM PREVIOUS REVIEW(S) ARE TO BE ADHERED TO IN THE FIELD.
Al
3D RENDERING
a
8) ALL LANDLORD COMMENTS ON THIS SET OF DRAWINGS APPLY TO THE ENTIRE DOCUMENT SET, EVEN IF NOT REPEATED ON EVERY SHEET IN DRAWING
A1.1
FLOOR PLAN oct
S ET.
A2
i
REFLECTED CEILING PLAN
REVISIONS
9) THE RE -USE OF ANY EXISTING CONSTRUCTION, FINISHES, EQUIPMENT, OR ELECTRICAL, PLUMBING,, OR HVAC SYSTEMS CURRENTLY IN THE SPACE IS
A3
STOREFRONT ELEVATIONS
s
CONDITIONAL UPON IT BEING APPROPRIATE FOR RE -USE. ANY EXISTING-; CONDITION OR EQUIPMENT TO BE RE -USED MUST BE RESTORED TO LIKE NEW
CONDITION. THE LANDLORD MAKES NO WARRANTY ON THE RE -USE OF ANY EXISTING CONDITION IN THE SPACE.
A3.1
STOREFRONT SECTIONS
10) IF AT ANY POINT FAILURES OR UPGRADES OR IMPROVEMENTS TO EXISTING SYSTEMS OCCUR, If IS THE SOLE RESPONSIBILITY OF THE TENANT TO
A4
INTERIOR ELEVATIONS
REPAIR OR REPLACE, AT TENANT'S EXPENSE.�,/�
�`---
11) LANDLORD AND TENANT RESPONSIBILITIES ARE AS DEFINED IN LEASE AGREEMENT.
M1
MECHANICAL PLAN
12) TENANT IS REQUIRED TO INSTALL A WATERPROOF MEMBRANE IN ALL WET AREAS OF SPACE. TENANT SHALL USE A 30 MIL POLYETHYLENE CLEAVAGE
M2
MECHANICAL DETAILS
MEMBRANE (EQUAL TO NOBLESEAL TS) INSTALLED PER MANUFACTURER'S RECOMMENDATIONS AND ANSI A-108. MEMBRANE MUST BE EXTENDED UP
M3
MECHANICAL SPECIFICATIONS
THE WALL A MINIMUM OF 4" OR EQUAL TO THE HEIGHT OF THE FLOOR BASE.
=r
13) FLOOR PENE=TRATIONS:
TENANT'S GC MUST ADVISE THE PROPERTY'S OPERATIONS DIRECTOR PRIOR TO ANY SLAB CUTTING OR REMOVAL. ALL FLOOR PENETRATIONS MUST BE
E1
ELECTRICAL POWER PLAN
CORE -BORED OR SAW -CUT (NO JACK -HAMMERING IS PERMITTED). PRIOR TO WORK, TENANT'S GC MUST VERIFY THAT TENANT'S WORK WILL NOTE2
ELECTRICAL LIGHTING PLAN
DRAWING NUMBER
CONFLICT WITH EXISTING STRUCTURAL, UTILITY, OR OTHER UNDER -SLAB CONDITIONS. TENANT'S WORK MUST NOT COMPROMISE OR DAMAGE THE
EXISTING STRUCTURE. ANY DAMAGE CAUSED BY TENANT'S WORK IS TO BE REPAIRED AT TENANT'S EXPENSE.
E3
ELECTRICAL RISER AND SCHEDULES
z
14) ALL LANDLORD COMMENTS FROM PREVIOUS REVIEW(S) STILL APPLY AND ARE TO BE INCORPORATED INTO THIS SET OF DRAWINGS AND THE FINAL SET
E4
ELECTRICAL SPECIFICATION
OF DRAWINGS. LANDLORD COMMENTS FROM PREVIOUS REVIEWS ARE TO BE STRICTLY ADHERED TO, IF NOT ALREADY INCLUDED ON THE DRAWINGS.
15) ALL ROOFING, SPRINKLER, & FIRE PROTECTION WORK MUST BE PERFORMED BY LANDLORD APPROVED CONTRACTOR AT THE TENANT'S EXPENSE.
CONTACT DAVID MILLER, OPERATIONS DIRECTOR, AT 407-323-1843 FOR CONTACT INFORMATION.
E
16) PRIOR TO STARTING ANY CONSTRUCTION, THE TENANT OR TENANT'S GENERAL CONTRACTOR IS REQUIRED TO HAVE A PRECONSTRUCTION MEETING
TITLE SHEET
WITH THE PROPERTY OPERATIONS DIRECTOR OR MALL MANAGEMENT. CONTACT DAVID MILLER, OPERATIONS DIRECTOR, AT 407-323-1843.UO
_
PROJECT I N �-O
17) PLANS REVIEWED & APPROVED BY LANDLORD'S TENANT COORDINATOR MUST BE PRESENT ON THE JOBSITE & ACCOMPANIED BY THE APPROVED
BUILDING DEPARTMENT PLANS. ANY DEVIATION FROM LANDLORD APPROVED PLANS MUST BE RESUBMITTED TO LANDLORD FOR APPROVAL. CONTACT
DAVID FLETCHER AT 317-263-2287.
„ ..., ,.... ..., .
_
I
r
., .,.,.:.r .,..,.....,, ,. ..,.. ,.... „,..... ., ,r .>r. x. ,.. ,r.., .,: a..a a,w..,,a.,, ..,.,, „ ... .......... .. ...
, ,. r.,' „ :.:. :,., t: , , .z x,a, r. r.,a.xL,. vxa „ .av x..:. ...,,,.,.. ...
.'ii' ..x ,,, ,,,,, x t e4s, zx, ,.u,.. x.v .. . r ..
....
, ........, ,.,x,
, r. ;..r: 4 u. .. i .... .,, ! , , u , ..,,:,r r..,x .r:.:. ., i, x,r..;. „r. ..«i:a ..., ,.::.':. , ..,. .. ti"' . .... ... .... . a i r xaa ', ..a c n.., .. a . .i$ rt. • „
t, x.... „
V%d PARTNERS
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNERS.COM
SEMIN®LE T.C.
200 TOWNE CENTER CIRCLE
SPACE #I311C
SANFORD, PL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
ADY 2 0 2013
ISSUE DATES
PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
ED PERMIT SET: 11-20-2013
REVISIONS
FFA
DRAWING NUMBER
RESPONSIBILITY
SCHEDULE
,a,i �
,�; ,<:: a , . :!. a,,.i: 3.•; a ,:,d .; ,x-': a ,,::
,,...:r
:... .:.:. .. .. : ...: .'.< �.'.>r'•,. ...,. ��.. ... ,.: x, .,:: �. r'r 4ti 'ur n:r .. r r r .I r�i r.y Ir;;rY ui�r tj:r' ., .. .r ,. ,., .. .. ,.., .... ...
z�
F=
in
®
i
inm
RESPONSIBILITY � C H
I I
ED �J � �
�
z
in
W
m
�
rn
©
KEY
V- EXISTING F - FIXTURE VENDOR
A- ARCHITECT L- LANDLORD
C - GENERAL CONTRACTOR T - TENANT
ITEM DESCRIPTION
ITEM
DESCRIPTION
01 GENERAL REQUIREMENTS
09 FINISHES (CONTINUED)
1. PERMITS AND FEES
6. BASE
A. BLDG. PERMIT SUBMITTAL JA JAS REQUIRED BY LOCAL BLDG. DEPARTMENT
A. RESTROOM C C
REFER TO FINISH SCHEDULE FOR MATERIAL USED
B. PERMIT FEES & PICK UP C AS REQUIRED BY LOCAL BLDG. DEPARTMENT
B. STOCK ROOM C CI
REFER TO FINISH SCHEDULE FOR MATERIAL USED
C. SIGN PERMIT T BY TENANT'S COMMERCIAL SIGN COMPANY
C. SALES AREA T C
GC INSTALL, SUPPLIED BY FRANCESCA'S
D. SIGN PLAN CHECK FEE TI BY TENANT'S COMMERCIAL SIGN COMPANY
D. STOREFRONT BASE IC C
REFER TO FINISH SCHEDULE FOR MATERIAL USED
E. OTHER C ALL OTHERS AS REQUIRED BY LOCAL BLDG. & FIRE DEPARTMENTS
7. CEILING
2. INSPECTIONS C C AS REQUIRED BY LOCAL BLDG. & FIRE DEPARTMENTS
A. SALES AREA C CI
SEE RCP
3. TEMPORARY HEAT C Cl-
B. STOCK ROOM C C
SEE RCP
4. TEMPORARY ELECTRIC C C -
C. RESTROOM C C
SEE RCP
5. TEMPORARY BARRICADE C C G.C. TO CONSTRUCT PER LL REQUIREMENTS
8. WALL FINISHES
6. CLEAN UP C C DAILY SWEEP CLEANING DURING CONSTRUCTION, AND FINAL "WHITE GLOVE" CLEANING
A. PAINT IC ClAS
SHOWN ON PLANS AND ELEVATIONS
7. BUILDERS RISK INSURANCE C C AS REQUIRED BY TENANT AND LANDLORD
B. FRP AT RESTROOM WET WALLS) C C
02 SITE WORK
10 SPECIAL11ES
1. SAW CUT SLAB C C AS REQUIRED
1. RESTROOM ACCESSORIES C C
GC TO PROVIDE AND INSTALL ALL NEW ACCESSORIES IF NEEDED.
2> DEMOLITION C C AS REQUIRED TO CONSTRUCT SPACE
2. ACCESS PANEL
N/A
3. CORE DRILL C C AS REQUIRED
3. AWNING
N/A
4. KNOX BOX (KEY BOX)
N/A
03 CONCRETE WORK
5. STOREFRONT WOOD ELEMENT
VA -
1. SAND PAD
--
2. VAPOR BARRIER C C GC TO REPAIR ANY AREAS ALTERED BY DEMOLITION
11 EQUIPMENT
3. REINFORCING FABRIC
1. STOREFRONT SIGNAGE
ALL SIGNAGE SUPPLIED AND INSTALLED BY TENANT'S SIGN SUPPLIER / CONTRACTOR
4. CONCRETE SLAB C C GC TO REPAIR ANY AREAS ALTERED BY DEMOLITION
A. WALL SIGNS T T
PER LANDLORD REQUIREMENTS
5. POURED CONCRETE J
B. BLADE SIGN
N/A
6. FLOOR PATCH C C AS REQUIRED INCLUDING AT MATERIAL TRANSITIONS
2. FIRE EXTINGUISHERS C C
INSTALL PER PLAN AND / OR CODE REGULATIONS
7. IN -FILL AT STOREFRONT N/A
3. CASH REGISTERS IT TI
INSTALLATION BY TENANT REPRESENTATIVE
04 MASONRY
12 FURNISHINGS_
1. CONCRETE BLOCK N/A
1. WALL SHELVES T C
GC INSTALL, SUPPLIED BY FRANCESCA'S
2. CASH WRAP BACK WRAP AREA T C
GC INSTALL, SUPPLIED BY FRANCESCA'S
05 METALS
3. MIRRORS OTHER FURNITURE T C
GC INSTALL, SUPPLIED BY FRANCESCA'S
1. STRUCTURAL STEEL ✓
4. DISPLAY TABLE & RACK T C
SUPPLIED BY FRANCESCA'S
2. METAL STUDS C C AS REQUIRED TO CONSTRUCT SPACE
A. DEMISING WALLS ✓ L L G.C. TO PATCH AND REPAIR AS REQUIRED
13 SPECIAL CONSTRUCTION
N/A
B. INTERIOR PARTITIONS / FRAMING C C G.C. TO PROVIDE AND INSTALL NEW AS PER DRAWINGS
C. SOFFITS C C
15 MECHANICAL
D. STOREFRONT FRAMING C C G.C. TO PROVIDE AND INSTALL NEW AS PER DRAWINGS
1. HVAC C CI
SEE MECH. PLAN
E. METAL FURRING C C
2. HVAC DIFFUSERS C C
SEE MECH. PLAN.
3. DOOR OPENING FRAME
3. HVAC DUCTWORK C C
SEE MECH. PLAN
A. GLASS WOOD DOOR FRAMING C C REFER TO DOOR SCHEDULE
4. TEMPERATURE CONTROLS C C
SEE MECH. PLAN
4. REVEAL AT STOREFRONT N LA
5. EXHAUST FAN C C
SEE ELECT. AND MECH. PLAN
5. CEILING EDGE C C
6. PLUMBING
LANDLORD PROVIDE STUBS
6. FURRING STRIP C C
A. WATER C C
REFER TO MECHANICAL SHEETS
B. WASTE C C
REFER TO MECHANICAL SHEETS
06 CARPENTRY MILLWORK
C. VENT C C
REFER TO MECHANICAL SHEETS
1. BUILT --IN DISPLAY PLATFORM C C FINISH WOOD SUPPLIED BY TENANT, BUILT AND INSTALLED BY GC
7. PLUMBING FIXTURES C I C I
REFER TO MECHANICAL SHEETS
2, WALL SHELF BLOCKING C C SUPPLIED AND INSTALLED BY GC AS NEEDED AT WALL FIXTURES
8. WATER HEATER C C
REFER TO MECHANICAL SHEETS
3. STOCKROOM SHELF BLOCKING C C SUPPLIED AND INSTALLED BY GC AS NEEDED AT WALL FIXTURES
9. SPRINKLER SYSTEM
N/A
4. FITTING ROOM AND ACCESSORIES T C SUPPLIED BY TENANT, BUILT AND INSTALLED BY GC
10. WATER METER C C
REFER TO MECHANICAL SHEETS
5. WOOD BLOCKING C C ALL BLOCKING TO BE FIRE RETARDANT TO CODE
6. PLYWOOD C C FIRE RETARDANT TREATED PLYWOOD
7. STAINED WOOD AT STOREFRONT C C IF APPLICABLE, BUILT AND INSTALLED BY GC
8. TRIM C C IF APPLICABLE, BUILT AND INSTALLED BY GC
16 ELECTRICAL
LANDLORD INSTALLS EMPTY CONDUIT. TENANT GC IS RESPONSIBLE TO PULL THE WIRE
FOR ELECTRICAL AND TELEPHONE.
07 THERMAL MOISTURE CONTROL
1. SERV. TO MAIN DISCONNECT C C
REFER TO ELECTRICAL SHEETS
1. WATERPROOFING MEMBRANE C C G.C. TO SUPPLY AND INSTALL PER LL REQUIREMENTS
2. DIST. IN TENANT SPACE ✓ C C
REFER TO ELECTRICAL SHEETS
2. CAULKING C C MAINTAIN CODE REQUIRED CONDITIONS
3. METERING C C
REFER TO ELECTRICAL SHEETS
3. INSULATION ✓ C C MAINTAIN CODE REQUIRED CONDITIONS
4. PANELS C C
I G.C. TO REPLACE EXISTING PANEL WITH NEW. REFER TO ELECTRICAL SHEETS
4. FIREPROOFING C C MAINTAIN CODE REQUIRED CONDITIONS
5. TRANSFORMER
N/A
6. MAIN CONDUIT TO SPACE C C
REFER TO ELECTRICAL SHEETS
08 DOORS /WINDOWS
7. MAIN CONDUCTOR TO SPACE C C
REFER TO ELECTRICAL SHEETS
1. STOREFRONT ROLLING GRILLE C ClG.C. TO INSTALL NEW ROLLING GRILLE & HARDWARE PER DRAWINGS
8. TELEPHONE IT C
2. STOREFRONT GLAZING SYSTEM C C G.C. TO PROVIDE AND INSTALL NEW STOREFRONT MATERIALS AS SHOWN IN DRAWINGS
A. LOW VOLTAGE, J -BOXES, CONDUITS C C
GC TO INSTALL J -BOX AND CONDUIT WITH PULL STRING. READY FOR TENANTS EQUIPMENT
TO PLUG IN
A. EXISTING N/A
B. TEMPERED GLASS N/A
9. DOOR BELL AT REAR ENTRY
N/A
C. STOREFRONT METAL N/A
10. LIGHT FIXTURES
-
3. RESTROOM DOOR C C G.C. TO INSTALL NEW DOOR & HARDWARE PER DRAWINGS
A. SALES AREA T C
REFER TO ELECTRICAL SHEETS
4. STOCKROOM DOOR C C G.C. TO INSTALL NEW DOOR & HARDWARE PER DRAWINGS
B. STOCKROOM T C
REFER TO ELECTRICAL SHEETS.
5. SERVICE DOOR N/A
C. RESTROOM T C
REFER TO ELECTRICAL SHEETS
D. STOREFRONT SOFFIT T C
REFER TO ELECTRICAL SHEETS
09 FINISHES
E. TRACK FIXTURES IT C
REFER TO ELECTRICAL SHEETS
1. GYPSUM BOARD (NE C C Jr TYPE "X" GYP. BD. - TAPED AND SANDED
F. EXIT EMERGENCY LIGHTS T C
REFER TO ELECTRICAL SHEETS.
GYPSUM BOARD (EXIST.) C C EXIST. TO REMAIN - PATCH OR REPAIR AS REQ'D PRIOR TO INSTALL OF NEW FINISHES
G. TRACK RAIL T C
REFER TO ELECTRICAL SHEETS
_2.
3. BACKER BOARD C C
H. FIXTURE LAMPS T C
REFER TO ELECTRICAL SHEETS
4. FLOORING
J. WALL SCONCE & CHANDELIER T C
REFER TO ELECTRICAL SHEETS
A. SALES AREA FLOOR T C REFER TO FINISH SCHEDULE FOR MATERIAL USED
11. ELECTRICAL OUTLETS J C C
INSTALL AS PER PLANS
B. MALL FLOORING N A
12. SMOKE DETECTORS ✓ C C
INSTALL AS PER PLANS
C. RESTROOM C C REFER TO FINISH SCHEDULE FOR MATERIAL USED
13. STEREO SPEAKERS C C
COORDINATE WITH TENANT
D. STOCK ROOM C C REFER TO FINISH SCHEDULE FOR MATERIAL USED
- E. METAL TRANSITIONS C C
5. COUNTER TOP RESTROOM) N/A
V%d PARTNERS
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNERS.COM
SEMIN®LE T.C.
200 TOWNE CENTER CIRCLE
SPACE #I311C
SANFORD, PL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
ADY 2 0 2013
ISSUE DATES
PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
ED PERMIT SET: 11-20-2013
REVISIONS
FFA
DRAWING NUMBER
RESPONSIBILITY
SCHEDULE
,a,i �
,�; ,<:: a , . :!. a,,.i: 3.•; a ,:,d .; ,x-': a ,,::
,,...:r
:... .:.:. .. .. : ...: .'.< �.'.>r'•,. ...,. ��.. ... ,.: x, .,:: �. r'r 4ti 'ur n:r .. r r r .I r�i r.y Ir;;rY ui�r tj:r' ., .. .r ,. ,., .. .. ,.., .... ...
OWALKS AND SIDEWALKS
A. WALKS AND SIDEWALKS SHALL, HAVE A CONTINUOUS COMMON SURFACE NOT INTERRUPTED BY STEPS OR BY
ABRUPT CHANGES IN LEVEL EXCEEDING 1/4 INCH, AND SHALL BE A MINIMUM OF 4 FEET IN WIDTH,
B. SURFACES WITH A SLOPE OF LESS THAN 6 PERCENT GRADIENT SHALL BE AT LEAST AS SLIP RESISTANT AS THAT
DESCRIBED AS A MEDIUM SALTED FINISH.
C. SURFACES WITH A SLOPE OF 6 PERCENT GRADIENT OR GREATER SHALL BE SLIP -RESISTANT.
D. SURFACE CROSS SLOPES SHALL NOT EXCEED 1/4 INCH PER FOOT.
E. WALKS, SIDEWALKS AND PEDESTRIAN WAYS SHALL BE FREE OF GRATING WHENEVER POSSIBLE. FOR GRATINGS
LOCATED IN THE SURFACE OF ANY OF THESE AREAS, GRID OPENINGS IN GRATINGS SHALL BE PERPENDICULAR
TO THE PROMINENT DIRECTION OF TRAVEL, AND A MAXIMUM OF 1/2" IN SIZE.
F. WHEN THE SLOPE IN THE DIRECTION OF TRAVEL OF ANY WALK EXCEEDS 1 VERTICAL TO 20 HORIZONTAL IT
SHALL COMPLY WITH THE PROVISIONS FOR PEDESTRIAN RAMPS.
G. ABRUPT CHANGES IN LEVEL ALONG ANY ACCESSIBLE ROUTE SHALL NOT EXCEED 1/2 INCH. WHEN CHANGES IN
LEVEL DO OCCUR, THEY SHALL BE BEVELED WITH A SLOPE NO GREATER THAN 1:2 EXCEPT THAT LEVEL
CHANGES NOT EXCEEDING 1/4 INCH MAY BE VERTICAL. WHEN CHANGES IN LEVEL GREATER THAN 1/2 INCH ARE
NECESSARY COMPLY WITH THE REQUIREMENTS FOR CURB RAMPS.
H. WALKS SHALL BE PROVIDED WITH A LEVEL AREA NOT LESS THAN 60 INCHES BY 60 INCHES AT A DOOR OR GATE
THAT SWINGS TOWARD THE WALK, AND NOT LESS THAN 48 INCHES WIDE BY 44 INCHES DEEP THAT A DOOR OR
GATE THAT SWINGS AWAY FROM THE WALK. SUCH WALKS SHALL EXTEND 24 INCHES TO THE SIDE OF THE
STRIKE EDGE OF A DOOR OR GATE THAT SWINGS TOWARD THE WALK.
I. ALL WALKS WITH CONTINUOUS GRADIENTS SHALL HAVE LEVEL AREAS OF AT LEAST 5 FEET IN LENGTH AT
INTERVALS OF AT LEAST EVERY 400 FEET.
J. IF A WALK CROSSES OR ADJOINS A VEHICULAR WAY, AND THE WALKING SURFACES ARE NOT SEPARATED BY
CURBS, RAILINGS OR OTHER ELEMENTS BETWEEN THE PEDESTRIAN AREAS AND VEHICULAR AREAS, THE
BOUNDARY BETWEEN THE AREAS SHALL BE DEFINED BY A CONTINUOUS DETECTABLE WARNING WHICH IS 36
INCHES WIDE. SEE DETECTABLE WARNING TEXTURE DETAIL.
@TACTILE SIGNAGE_
A. SIGNS IDENTIFYING PERMANENT ROOMS OR SPACES OR PROVIDING INFORMATION OR DIRECTION, TO INCLUDE
RAISED CHARACTERS, CONTRACTED GRADE II BRAILLE AND PICTURIAL SYMBOLS.
B. WHEN SIGNS IDENTIFY, OR GIVE INFORMATION ABOUT ACCESSIBLE ELEMENTS AND FEATURE OF A BUILDING OR
SITE, THEY SHALL INCLUDE THE APPROPRIATE SYMBOL OF ACCESSIBILITY OR PICTOGRAM, WITH THE
EQUIVALENT VISUAL AND TACTILE DESCRIPTION PLACED DIRECTLY BELOW THE PICTOGRAM. THE OUTSIDE
BORDER OF THE PICTOGRAM SHALL BE MINIMUM 6" IN HEIGHT.
C. VISUAL CHARACTERS SHALL BE UPPERCASE, STANDARD SANS SERIF FONT. VISUAL CHARACTERS TO HAVE A
WIDTH -TO -HEIGHT RATION OF BETWEEN 3:5 AND 1:1 MEASURED BY THE WIDTH OF AN UPPERCASE 0 & THE
HEIGHT OF AN UPPER CASE I & A STROKE WIDTH -TO -HEIGHT RATIO OF BETWEEN1:5 & 1&10 MEASURED BY THE
WIDTH OF AN UPPERCASE I. CHARACTERS AND SYMBOLS SHALL CONTRAST WITH THEIR BACKGROUND.
CHARACTERS, SYMBOLS AND BACKGROUNDS SHALL HAVE A NON -GLARE FINISH.
D. TACTILE CHARACTERS SHALL BE UPPERCASE, STANDARD SANS SERIF FONT, RAISED 1/32" OFF THE
BACKGROUND. THE HEIGHT OF TACTILE CHARACTERS SHALL BE BETWEEN 5/8" AND 2". CHARACTERS SHALL BE
ACCOMPANIED BY GRADE II BRAILLE LOCATED 3/8 MIN. BELOW BOTTOM EDGE OF CHARACTER.
E. GRADE 2 BRAILLE SHALL HAVE DOMED OR ROUNDED DOTS RAISED 1/40" OFF THE BACKGROUND, WITH DOTS
SPACED 1/10" WITH -IN CELLS, AND 2/10" BETWEEN CELLS.
F. TACTILE SIGNS SHALL BE MOUNTED 48" MINIMUM, TO THE BASELINE OF THE LOWEST TACTILE LETTER, AND 60"
MAXIMUM ABOVE THE FLOOR TO THE BASELINE OF THE HIGHEST TACTILE LETTER. AN 18" X 18" CLEAR SPACE IS
REQUIRED IN FRONT OF THE TACTILE SIGN, BEYOND THE ARC OF ANY DOOR SWING. WHERE SIGNS ARE
MOUNTED AT DOORS, THE SIGN SHALL BE ON THE LATCH SIDE OF THE DOOR. WHERE SIGNS ARE MOUNTED AT
DOUBLE DOORS, OR WHERE THERE IS NO WALL SPACE, THE SIGN SHALL BE MOUNTED ON THE NEAREST
ADJACENT WALL, PREFERABLY THE RIGHT SIDE.
@RAMPS
A. ANY PATH OF TRAVEL SHALL BE CONSIDERED A RAMP IF ITS SLOPE IS GREATER THAN 1:20 (1:12 MAXIMUM)
B. 1:12 SLOPED RAMPS WITH LENGTH GREATER THAN 72" SHALL HAVE HANDRAILS ON BOTH SIDES.
C. THE TOP LANDINGS ON A RAMP MUST BE AT LEAST 60 INCHES IN DEPTH.
D. IF A DOOR SWINGS ONTO ATOP LANDING, THE MIN. LANDING DIMENSION SHALL BE NOT LESS THAN 42 INCHES
CLEAR PLUS THE WIDTH OF THE DOOR.
E. THE TOP LANDING SHALL HAVE A WIDTH NOT LESS THAN ITS DEPTH.
F. THE TOP LANDING SHALL EXTEND NOT LESS THAN 24 -INCHES BEYOND THE STRIKE SIDE OF THE DOOR AT
EXTERIOR RAMPS AND 18 -INCHES AT INTERIOR RAMPS.
G. THE BOTTOM LANDING SHALL BE NOT LESS THAN69 INGI IEG (CA: 72 INCHES) DEEP
H. INTERMEDIATE LANDINGS SHALL BE PROVIDED AT TURNS AND WHENEVER THE CHANGE IN LEVEL EXCEEDS 30
INCHES, 60" MIN.
I. INTERMEDIATE LANDINGS ON RAMPS SHALL HAVE A DEPTH OF NOT 3" MAXI ?
LESS THAN 5'-0". WHERE A (CA: 30 DEGREE CHANGE) GHANGE IN
RAMP DIRECTION OCCURS, A MINIMUM 72" BY 72" LANDING SHALL
BE PROVIDED.
RAMP
J. RAMPS SHALL BE NOT LESS THAN 4'-0" WIDE. RAMPS SERVING A DOWN
PRIMARY ENTRANCE FOR AN OCCUPANT LOAD OF 300 OR MORE 24" EXTERIOR
PEOPLE SHALL BE NOT LESS THAN 5'-0" WIDE.
LANDING AT RAMP 18" INTERIOR
K. HANDRAILS SHALL BE PLACED ON EACH SIDE OF EACH RAMP AND SHALL BE CONTINUOUS THE FULL LENGTH OF
THE RAMP. HANDRAILS SHALL BE 34 TO 38 INCHES ABOVE THE RAMP SURFACE AND EXTEND A MINIMUM OF 1
FOOT BEYOND THE TOP AND BOTTOM OF THE RAMP.
L. SURFACES OF RAMPS SHALL BE SLIP -RESISTANT.
M. RAMPS & LANDINGS WITH DROP OFFS SHALL HAVE CURBS, WALLS, RAILING OR PROJECTING SURFACES THAT
PREVENT PEOPLE FROM SLIPPING OFF THE RAMP. CURB SHALL BE A MIN. 2" IN HEIGHT. MAXIMUM ELEVATION
CHANGE BETWEEN LANDINGS IS 30".
ODOORS
A. LATCHES AND LOCKSETS: PROVIDE LEVER TYPE, PUSH- PULL OR PANIC TYPE HARDWARE 34 INCHES TO
48 INCHES ABOVE FLOOR.
B. ADJUSTABLE CLOSURE PROVIDED WITH MAXIMUM PRESSURE FOR OPENING DOORS AS FOLLOWS:
INTERIOR DOORS - 5 POUNDS PRESSURE
EXTERIOR DOORS - 8.5 POUNDS PRESSURE
FIRE DOORS - PER ADMINISTRATIVE AUTHORITY
DOOR CLOSURES TO BE ADJUSTED TO CLOSE FROM AN OPEN POSITION OF 90 DEG IN NOT LESS THAN 5
SECONDS TO A POINT 12" FROM LATCH. ADJUST CLOSURES AFTER INSTALLATION AND TEST DOOR
COMPLIANCE.
C. FLOOR LEVEL AT DOORS
1. THRESHOLDS: THE FLOOR OR LANDING SHALL NOT BE MORE THAN 1/2 INCH LOWER THAN THE THRESHOLD
OF THE DOOR WAY. CHANGE IN LEVEL BETWEEN 1/4 INCH AND 1/2 INCH SHALL BE BEVELED WITH A SLOPE
NO GREATER THAN 1:2. (SEE BELOW).
21
�
1/2" MAX.
THRESHOLDS 1/4 MAX.
2. LEVEL FLOOR OR LANDING: THERE SHALL BE A LEVEL AND CLEAR AREA ON EACH SIDE OF AN EXIT DOOR.
THE LEVEL AREAS SHALL BE AS SHOWN BELOW. THE SPACE BETWEEN TWO CONSECUTIVE DOOR OPENING
(VESTIBULE) SHALL PROVIDE 48 INCHES OF CLEAR SPACE FROM ANY DOOR OPENING INTO SUCH SPACE
(SEE BELOW).
FPPULL SIDE I F PULL SIDE -
pw I I I I X=36"MIN IF
Y=60"
z p of 24" MIN. OR
[IX X=42"MIN IF
t I Y = 54"
I
mea ��s
LU
ZOO I pU)
o o — \ I O
I x+-24" MIN. � I24" MIN.
��¢z
z
= LPUSH SIDE J _ ¢ I PUSH SIDE
10" MIN. BOTTOM RAIL
LAFCH APPROACH HINGE APPROACH OR PROVIDE KICK
PLATE AT PUSH SIDE
F PULL SIDE
177.7
z I j
� I 18" MIN.
SPACE IS NECESSARY TO
ALLOW BACKING AND TURNING
SPACE FOR A WHEELCHAIR TO
CLEAR THE IN -SWINGING DOOR.
PROVIDE THIS 32" /
z /I
< I I ADDITIONAL SPACE IF CLR.
co DOOR IS EQUIPPED
WITH BOTH A LATCH
LUSH SICIEJ AND A CLOSER.
12" MIN.
FRONT APPROACH VESTIBULE
D. DOOR WIDTH & HEIGHT: 3 FEET WIDE AND 6 FEET 8 INCHES HIGH. CLEAR WIDTH: 32 INCHES MINIMUM WITH DOOR
OPEN 90 DEG. MEASURED FROM THE FACE OF THE DOOR TO THE OPPOSITE STOP.
E. THE BOTTOM 10 INCHES OF ALL DOORS EXCEPT AUTOMATIC AND SLIDING SHALL HAVE A SMOOTH
UNINTERRUPTED SURFACE TO ALLOW THE DOOR TO BE OPENED BY A WHEELCHAIR FOOTREST WITHOUT
CREATING A TRAP OR HAZARDOUS CONDITION.
(DPROTRUDING OBJECTS: KNEE AND TOE CLEARANCE
A. PROJECTIONS FROM WALLS WITH LEADING EDGE
BETWEEN 27" AND 80" ABOVE FLOOR MAY PROJECT 4"
MAXIMUM. LEADING EDGE AT OR BELOW 27" MAY
PROJECT ANY AMOUNT. FREE STANDING PROJECTION,
WITH LEADING EDGE BETWEEN 27" AND 80" ABOVE
FLOOR MAY PROJECT 12" MAX. PROJECTIONS MAY NO -
REDUCE MANEUVERING SPACE, OR CLEAR WIDTH OF f
ACCESSIBLE ROUTE.
B. HEAD ROOM: 80" MINIMUM.
OELECTRICAL
A. ELECTRICAL RECEPTACLES (15, 20 AND 30 AMPS) SHALL BE AT LEAST 15 INCHES ABOVE THE FLOOR.
B. SWITCHES AND CONTROLS FOR LIGHTS, APPLIANCES, COOLING, HEATING AND VENTILATING EQUIPMENT SHALL
BE NOT LESS THAN 3 FEET NOR MORE THAN 4 FEET ABOVE THE FLOOR.
C. FIRE ALARM INITIATING DEVICES SHALL BE 48 INCHES MAX ABOVE THE FLOOR, GROUND OR SIDEWALK.
OPUBLIC TELEPHONES
A. A CLEAR FLOOR OR GROUND SPACE AT LEAST 30 INCHES IN BY 48 INCHES THAT ALLOWS EITHER A FORWARD OR
PARALLEL APPROACH BY A PERSON USING A WHEELCHAIR SHALL BE PROVIDED AT TELEPHONES. BASES,
ENCLOSURES, AND FIXED SEATS SHALL NOT IMPEDE APPROACHES BY PEOPLE WHO USE WHEELCHAIRS.
B. THE HIGHEST OPERABLE PART OF THE TELEPHONE SHALL BE NO HIGHER THAN 48 INCHES ABOVE FINISH FLOOR.
@ DDS KING --FOUNTAINS
A. NOT REQUIRED -
ACCORDING TO SECTION 410.3:.... IN OTHER OCCUPANCIES, WHERE DRINKING FOUNTAINS ARE REQUIRED,
WA'T'ER COOLERS OR BOTTLED WATER DISPENSERS SHALL BE PERMITTED TO BE SUBSTITUTED FOR NOT MORE
THAN 50 PEKCENTOF THE REQUIRED NUMBER OF DRINKING FOUNTAINS.
@SANITARY FACILITIES
A. GEOMETRICAL SYMBOLS
1. UNISEX SANITARY FACILITIES SHALL BE IDENTIFIED BY A CIRCLE 1/4 INCH THICK, 12 INCH
DIAMETER, WITH A 1/4" THICK TRIANGLE SUPERIMPOSED ON THE CIRCLE AND WITHIN THE
12 INCH DIAMETER.
2. GEOMETRIC (CIRCLE AND TRIANGLE) SYMBOLS ON SANITARY DOORS SHALL BE
CENTERED ON THE DOOR AT A HEIGHT OF 60" AND THEIR COLOR AND CONTRAST SHALL
BE DISTINCTLY DIFFERENT.
3. RAISED LETTERS SHALL BE PROVIDED IN CONFORMANCE TO ANSI SECTION 703.4.2 AND
ACCOMPANIED BY GRADE II BRAILLE PER ANSI 703.5 AND SHALL BE INSTALLED ON THE
WALL ADJACENT TO THE LATCH OUTSIDE OF THE DOOR. WHERE THERE IS NO WALL
SPACE ON THE LATCH SIDE, INCLUDING AT DOUBLE LEAF DOORS, SIGNS SHALL BE
PLACED ON THE NEAREST ADJACENT WALL, PREFERABLY ON THE RIGHT. MOUNTING
HEIGHT SHALL BE SUCH THAT BRAILLE IS BETWEEN 40" AND 60" ABOVE FINISHED SIGN.
MOUNTING LOCATION SHALL BE DETERMINED SO THAT A PERSON MAY APPROACH
WITHIN 3 INCHES OF SIGNAGE WITHOUT ENCOUNTERING PROTRUDING OBJECTS OR
STANDING WITHIN THE SWING OF THE DOOR.
4. PICTORIAL SYMBOL SIGNS (PICTOGRAMS). PICTORIAL SYMBOL SIGNS (PICTOGRAMS)
SHALL BE ACCOMPANIED BY THE EQUIVALENT VERBAL DESCRIPTION PLACED DIRECTLY
BELOW THE PICTOGRAM. THE BORDER DIMENSION OF THE PICTOGRAM SHALL BE A
MINIMUM OF 6 INCHES (152 MM) IN HEIGHT.
B. WATER CLOSET: FLUSH CONTROLS ARE TO BE OPERABLE BY AN OSCILLATING HANDLE WITH
A MINIMUM OPERATING FORCE OF 5 LB/F OR BY A LOW VOLTAGE BUTTON. THE HANDLE OR
BUTTON IS TO BE LOCATED ON THE WIDE SIDE SO AS TO BE OPERABLE WITHOUT REQUIRING
EXCESSIVE BODY MOVEMENT.
C. LAVATORY: PROVIDE A CLEARANCE OF AT LEAST 29 INCHES FROM THE FLOOR TO THE
BOTTOM OF THE APRON WITH KNEE CLEARANCE UNDER THE FRONT LIP EXTENDING A
MINIMUM OF 30 INCHES WIDE, TO 8 INCHES MINIMUM DEPTH AT THE TOP. PROVIDE FOR THE
CLEARANCE AT LEAST 30 INCHES WIDE, TO 9 INCHES ABOVE THE FLOOR AND 17 INCHES
DEEP FROM THE FRONT OF THE LAVATORY. PROVIDE A CLEAR FLOOR SPACE 30 INCHES X 48
INCHES IN FRONT OF LAVATORY. THE CLEAR SPACE MAY EXTEND INTO KNEE AND TOE
SPACE UNDERNEATH THE LAVATORY, INSULATE HOT WATER AND DRAIN PIPES UNDER
LAVATORIES. NO SHARP OR ABRASIVE SURFACES ARE ALLOWED UNDER LAVATORIES.
FAUCET CONTROLS ARE REQUIRED TO BE OPERABLE WITH ONE HAND AND CANNOT
REQUIRE GRASPING, PINCHING, OR TWISTING OF THE WRIST, THE FORCE NECESSARY TO
OPERATE CONTROLS IS NOT TO EXCEED 5 LB/F.
D. ACCESSORIES: WHERE TOWEL, SANITARY NAPKIN AND WASTE RECEPTACLES AND SIMILAR
DISPENSING AND DISPOSAL FIXTURES ARE PROVIDED, AT LEAST ONE OF EACH TYPE IS TO
BE LOCATED WITH ALL OPERABLE PARTS, INCLUDING COIN SLOTS, WITHIN 40 INCHES FROM
THE FLOOR.
MOUNT MIRRORS WITH THE BOTTOM EDGE NO MORE THAN 40 INCHES FROM THE FLOOR.
LOCATE TOILET TISSUE DISPENSERS ON THE WALL WITHIN 7" MIN TO 9" MAX. FROM THE
FRONT EDGE OF THE TOILET SEAT.
E. THE STRUCTURAL STRENGTH OF GRAB BARS, FASTENERS, AND MOUNTING DEVICES SHALL
MEET THE SPECIFICATIONS OF THE AMERICAN DISABILITIES ACT.
F. SINGLE ACCOMMODATION: A CLEAR FLOOR SPACE OF AT LEAST 60 INCHES IN DIAMETER IS
REQUIRED FOR SINGLE ACCOMMODATION TOILET ROOMS.
TOILET ACCESSORIES
36" BAR MIN:
42" BAR MIN.
60" X 56" MIN
CLEAR FLOOR
SPACE
o
18"� � 1511
MIN.1 MIN.
L1728"
MI \
60"MIN. DSA.
12"
MI - MI
18"
MIN.
30" X 48"
MIN. CLEAR
FLOOR SPACE
SHOWN DASHED
PRIVACY LOCK
ON DOOR
32" MIN, CLR,
112" CLR. /1–HT-9"
---18" VERTICAL GRAB BAR
----42" GRAB BAR
W ROLL PAPER HOLDER
o WI I FIOUT STOPS
klmT E Y
NOTE: THESE FIGURES ARE ILLUSTRATIVE ONLY AND DO NOT DELINEATE THE ONLY
MEANS OF COMPLIANCE. REFER TO PLANS FOR EXACT LAYOUT OF TOILET ROOM
SUNOBSTRUCTED FORWARD/SIDE REACH
A. GEOMETRICAL SYMBOLS
1. WHERE A FORWARD REACH IS UNOBSTRUCTED, THE HIGH FORWARD REACH SHALL BE
48 INCHES MAX. AND THE LOW FORWARD REACH SHALL BE 15 INCHES MIN. ABOVE THE
FLOOR.
2. WHERE A PARALLEL APPROACH TO AN ELEMENT AND THE SIDE REACH IS
UNOBSTRUCTED, THE HIGH SIDE REACH SHALL BE 48 INCHES MAX. AND THE LOW SIDE
REACH SHALL BE 15 INCHES MIN. ABOVE THE FLOOR.
2A. EXCEPTION: EXISTING ELEMENTS SHALL BE PERMITTED AT 54 INCHES MAX. ABOVE
THE FLOOR.
z � Z
Z
4MAX, SIDE FORWARD
11 ACCESSABILE CASH WRAP
0
m
8'- 0" LENGTH
NO TUE-KICK BELOW SINK CABINET FOR
WHEELCHAIR ACCESSIBILITY
12 ACCESSIBLE DRESSING ROOM
a
co
0
60
DRESS ROOM
MIRROR 33"WX60"L
MOUNT '18" A.F.F.
('.I IRTAIIV
.1
60" X 36" 'T' I
",—,SHAPED
CLEAR AREA
CURTAIN
MIRROR 33"WX60"L
MOUNT 18" A.F.F.
-- ACCESSIIB�
z w DRESS]
O T
S W
0r_'1 IPTAINI
J
¢Q
DRESSING ROOM IS A PRE
MANUFACTURED NON -LOAD BEARING
DRESSING AREA FURNISHED BY
OWNER INSTALLED BY G.C.
C� T-0" A.F.F.
OPENING
@ T-0" A.F.F.
.F.
IWIPARTNERS
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPAHTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE #B11C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
0 2D13
REVISIONS
FIN
DRAWING NUMBER
COBE
COMPLIANCE
12 11
i..... � r, f.Yj i �. �. ri, >. •.,ie•...� , .'�. i... � :�,. ', .... .. .,. ..., i. ...3. .. r ,,... e :.,e .., s ... .. .,. .., ... .. .,,. ., . ,,... ,.., ... .. .,
ISSUE DATESNX "
j
PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
PERMIT SET: 11-20-2013
REVISIONS
FIN
DRAWING NUMBER
COBE
COMPLIANCE
12 11
i..... � r, f.Yj i �. �. ri, >. •.,ie•...� , .'�. i... � :�,. ', .... .. .,. ..., i. ...3. .. r ,,... e :.,e .., s ... .. .,. .., ... .. .,,. ., . ,,... ,.., ... .. .,
DEMO GENERAL NOTES
GENERAL CONTRACTOR SHALL PROVIDE ALL DEMOLITION AS REQUIRED FOR THE
CONSTRUCTION OF THE SPACES DETAILED IN THE ARCHITECTURAL PLANS.
ENTIRE SCOPE OF DEMOLITION WORK IS NOT NECESSARILY INDICATED IN THESE DRAWINGS.
GENERAL CONTRACTOR SHALL VISIT THE JOBSITE TO DETERMINE QUANTITY OF MATERIALS
AND COMPONENTS TO BE REMOVED TO CONSTRUCT THE PROJECT. ANY DISCREPANCIES
BETWEEN THE DRAWINGS AND EXISTING CONDITIONS SHALL BE IMMEDIATELY BROUGHT TO
THE ATTENTION OF THE CONSTRUCTION MANAGER. GENERAL CONTRACTOR TO
COORDINATE A PRE -CONSTRUCTION MEETING WITH ON-SITE MANAGEMENT PRIOR TO
BEGINNING ANY WORK.
REMOVE ALL DEBRIS ON A DAILY BASIS TO GENERAL CONTRACTOR PROVIDED CONTAINERS
IN DESIGNATED AREAS. COORDINATE WITH LANDLORD'S SITE MANAGEMENT.
DEMOLITION OF ITEMS SHALL INCLUDE COMPLETE REMOVAL OF ANY ASSOCIATED
ELECTRICAL, MECHANICAL, OR PLUMBING COMPONENTS. ABANDONED FLOOR
PENETRATIONS SHALL BE PROPERLY SEALED IN ACCORDANCE WITH LANDLORD
REQUIREMENTS PRIOR TO INSTALLATION OF NEW FLOORING, MATERIALS.
COORDINATE ALL WORK IN DEMISING WALLS, ON ROOFS AND IN FLOORS WITH THE
LANDLORD.
THE FIRE RATING AND STRUCTURAL INTEGRITY OF EXISTING FLOORS, DEMISING WALLS AND
COLUMNS SHALL BE MAINTAINED DURING DEMOLITION. CONTRACTOR TO PATCH AND
REPAIR THESE ASSEMBLIES AS REQUIRED. COORDINATE WITH THE LANDLORD.
VERIFY THE SCOPE OF DEMOLITION WORK TO DETERMINE IF ANY EXISTING EQUIPMENT IS TO
REMAIN.
SPRINKLER CONTRACTOR TO RELOCATE AND/OR PROVIDE NEW SPRINKLER HEADS AS
REQUIRED AND SO AS NOT TO INTERFERE WITH LIGHTING FIXTURES, FIVAC, GRILLES, ETC.
SEE ELECTRICAL SHEETS. ALL WORK TO CONFORM TO LOCAL AND N.F.P.A. CODES. CENTER
HEADS IN CEILING TILE. NOTIFY MALL MANAGER BEFORE ANY SHUT-OFF.
WHEN DOING DEMOLITION: NOTHING TO BE REUSED CAN BE ABANDONED. ALL UNUSED ITEMS
(INCLUDING BUT NOT LIMITED TO CONDUITS, PIPING, WIRING, EQUIPMENT, HANGERS,
DUCTWORK, ETC.) MUST BE REMOVED TO ITS POINT OF ORIGIN AND SPACE BROUGHT BACK
TO ITS ORIGINAL CONDITION.
DEMO LL NOTES
COORDINATE ALL DEMO WITH LANDLORD PRIOR TO WORK COMMENCING. NOTIFY LANDLORD
PRIOR TO DISPOSING OF FLOORING AND TRIM MATERIALS.
ANY EXISTING EQUIPMENT OR COMPONENT IN OR PERTAINING TO THE PREMISES THAT IS
BEING ABANDONED MUST BE DEMOLISHED COMPLETELY AND PROPERLY REMOVED FROM
PREMISES.
NO UTILITIES SHALL BE ABANDONED. ALL NON -UTILIZED LINES/RUNS SHALL BE REMOVED
BACK TO THE POINT OF ORIGIN.
ALL ABOVE GROUND UTILITY LINES NOT TO BE RE -USED MUST BE REMOVED TO POINT OF
ORIGIN. ALL UNDER SLAB UTILITY LINES TO BE CUT, CAPPED, AND SEALED PER CODE.
ALL ROOF MOUNTED EQUIPMENT ABOVE THE LEASED PREMISES NOT TO BE REUSED MUST
BE REMOVED BY TENANT GC AT TENANT EXPENSE. ROOF MUST BE PROPERLY PATCHED BY
MALL REQUIRED ROOFER. ROOF CURBS MUST BE REMOVED AND ROOF PATCHED - DO NOT
CAP. COORDINATE ALL WORK WITH MALL OPERATIONS DIRECTOR.
COORDINATION OF CONSTRUCTION BARRICADE AND DUMPSTERS IS TO BE COORDINATED
WITH MALL MANAGEMENT ON SITE.
FLOOR PENETRATIONS:
TENANT'S GC MUST ADVISE THE PROPERTY'S OPERATIONS DIRECTOR PRIOR TO ANY SLAB
CUTTING OR REMOVAL. ALL FLOOR PENETRATIONS MUST BE CORE -BORED OR SAW -CUT (NO
JACK -HAMMERING IS PERMITTED). PRIOR TO WORK, TENANT'S GC MUST VERIFY THAT
TENANT'S WORK WILL NOT CONFLICT WITH EXISTING STRUCTURAL, UTILITY, OR OTHER
UNDER -SLAB CONDITIONS. TENANT'S WORK MUST NOT COMPROMISE OR DAMAGE THE
EXISTING STRUCTURE. ANY DAMAGE CAUSED BY TENANT'S WORK IS TO BE REPAIRED AT
TENANT'S EXPENSE.
DEMO KEYNOTES
�1 REMOVE EXISTING FLOOR FINISHES IN THIS AREA INCLUDING ADHESIVES, GROUT,
TRANSITIONS, ETC. DOWN TO CONCRETE SLAB. PREPARE FLOOR SLAB TO MEET NEW FLOOR
COVERING MANUFACTURER'S RECOMMENDATIONS AND INFORMATION IN THESE DRAWINGS
OREMOVE EXISTING BASE MATERIALS THROUGHOUT.
OEXISTING DEMISING WALL. PATCH & REPAIR AS REQUIRED FOR NEW FINISHES. MAINTAIN
EXISTING FIRE RATINGS.
LEASE LINE.
REMOVE EXISTING CEILING IN ITS ENTIRETY.
OEXISTING CABINETS/FURNITURE TO BE REMOVED. PATCH & REPAIR AS REQUIRED FOR
APPLICATION OF NEW FINISHES.
El REMOVE RECEPTACLES, SWITCHES, CONDUITS, ETC., BACK TO THE NEXT POINT OF USE WH'CFI
ARE NOT TO BE REUSED AND RELOCATED AND ARE WITHIN WALLS TO BE DEMOLISHED.
® DEMO EXISTING LIGHT FIXTURES (LAY -IN, RECESSED AND SURFACE MOUNTED), LIGHTING
TRACKS AND TRACK HEADS, AND RELATED UNUSED CONDUIT AND CONDUCTORS BACK TO THE
NEXT POINT OF USE. VERIFY WITH A2 ANY FIXTURES TO REMAIN.
`CJ EXISTING EMERGENCY LIGHTING PACKS (CEILING AND WALL MOUNTED) TO BE REPLACED.
REFER TO ELECTRICAL PLANS
(�4 REMOVE UNUSED CONDUIT AND CONDUCTORS IN WALLS, ON WALLS, AND IN CEILING CAVITIES.
M1 EXISTING HEATING AND COOLING UNITS TO BE REMOVED AND REPLACED WITH NEW
EQUIPMENT. REFER TO MECHANICAL PLANS.
eEXISTING MECHANICAL DUCT TO BE REMOVED.
DEMOLITION PLAN
1
1 /4" = V-0"
ADJACENT TENANT
IWPARTNERS
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.6 34.7000 T
WDPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE#1311C
SANFORD, FL 32771
DRAWN BY:
/SM
WD PROJECT NUMBER
FRCC00050
NOV& 0 2013
ISSUE DATES
PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
El PERMIT SET: 11-20-2013
REVISIONS
ID
DRAWING NUMBER
DEMO PLAN
. ,r
. ,
., '. ,,., ,.. .. x,.r GI •,,, , .',,. ,.� ter ,.. r .., n. ,.. ter e. ,r 5. .( ..i ".• r,4.a'.'1; 1'u Jrf ir,•i,:r1
! -.
... 3 :.' T.. <+,`.;I JS. r,l •..r l.i 'v.i ,.,: „ (f.Y. )}.JI^,., 4 ..� !i lJ ! r �: lY l..li x, r,,.i .,, t'•'
'. •,Ji �x...',e ::, w.v.,"s, ,y :v ,,.. :..: r ,., i ... .., ,... .,•. .... .. ... ., .., e Yr4 ., ,.. :.,
FINISH LEGEND - COASTAL
MARK
DESCRIPTION
GENERAL LOCATION
VALSPAR
SALES AREA WALLS
CLR: SEA SALT BLUE
#: CI 191 SATIN
VALSPAR
SERVICE ENTRANCE-/
PT -2
CLR: SAWYER WHITE
RESTROOM
#: 1002-16 INTERIOR SEMI -GLOSS
z
VALSPAR
SALES AREA CEILING
CLR: CREME FRAICHE
a_
ff: CI 200
BEHR
STOCK ROOM DOOR/
CLR: SEASIDESAND
WOOD FRAME
ff: 740C-1 OIL BASED SEMI -GLOSS
OLYMPIC
STOREFRONT
CLR: HEIRLOOM LACE
SYSTEM
#: D 10-1
4" VINYL BASE
STOCK ROOM/
CLR: BROWN
REsTROOM
6 " WOOD BASE
SALES (SUPPLIED
SUPPLIED BY FRANCESCA'S, INSTALLED BY CI.C.
BY FRANCESCA'S)
STOREFRONT WALL TILE
STOREFRONT
0
SOLI USA - HOSI MOSAIC
CE
LL
CLR: WHITE / MULTI - PATTERN BY OWNER
Uj
Ir
0
GROUT: POLYBLEND / CUSTOM
CLR: #333 ALABASTER
12"x12" VINYL FLOORING
STOCK ROOM/
CLR: BEIGE
RESTROOM
0
0
KARNDEAN
SALES
LL
VINYL PLANK - HCO3
CLR; DUSK OAK, RANDOM PATTERN
SALES/ STOCK ROOM/
NEW 2x2 ACOUSTICAL TILE CEILING
DRESSING ROOM/
d
TEGULAR EDGE CLR: WHITE
RESTROOM
I
0
STOREFRONT
NEW GYP. BID. CEILING
NOTE: ALL FINISHES NEED TO MEET A MIN. OF A CLASS C FINISH FOR ENCLOSED SPACES,
SEE SEC V. ON CODE STUDY FOR MORE DETAILS.
NOTE:
ALL SIGNAGE SHALL BE SUBMITTED UNDER SEPARATE COVER FOR
LANDLORD REVIEW AND APPROVAL.
I
�y"
1A
�A
vid RTNERS
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE#1311C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCCO0050
NOV 51 0 2013
ISSUE DATES
PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
0 PERMIT SET: 11 -20-2013
REVISIONS
F11
DRAWING NUMBER
Z't
Al
STOREFRONT
PERSPECTIVE
Al
. .........
. ... . ... ................. ... . ... .........
DOOR
SCHEDULE
DESCRIPTION
Double Glass Cabinet measuring 2'x6' with an overall height of 100".Lower section has
DBL GS
5/8" TYPE "X" GYP
VALSPAR
5/8" TYPE "X" GYP
DOOR HARDWARE
MARK
CA -front
LOCATION
SIZE
TYPE
CA -back (18")
FRAME
DOOR
DESCRIPTION
HARDWARE
FIRE RATING
A. HARDWARE AS PROVIDED BY ROLLING GRILLE
Optional tables measure 3'3"x5'6", which are noted as 3x5
ROLL-UP8'4"
X 8'4"
U
STEEL
ALUM.
OVERHEAD DOOR SERIES 670 MANUAL
42"R
N/A
O
GRILLE
GYP.BD. G.C. TO PATCH
A
WS
FURRED WALLS,
<
PUSH-UP DOOR OR APPROVED EQUAL
A
MOISTURE RESISTANT
MANUFACTURER WITH U -CHANGE LOCK CYLINDER WITH
Two-tiered 4' wood shelves, upper shelf is hung at 76"h, bottom bench is at 18"h
& REPAIR AS REQUIRED. C
note:
3FO
MOISTURE RESISTANT
BEHR
face -out brackets
GYP ON RESTROOM
CLR: SEASIDE SAND
Stacked shelving for stockroom, 12" deep wall mounted. Shelf with pole @5'3 & Top shelf
THUMBTURN ON STORE SIDE. GC TO PROVIDE AND
INSTALL SIGNAGE ON STORE SIDE OF BOTTOM RAIL OF
#: 740C-1 OIL BASED SEMI -GLOSS
GYP ON RESTROOM
Stk. Shelv.
OLYMPIC
NEW DESIGN STANDARD - JELDWEN 15
Shelf
(1) 24" wide shelf mounted at 60" a.f.f. for loss prevention equipment
Q
Small microwave & fridge for stockroom
STOCK ROOM
3'-0" X 6'-8" X 1 3/8"
B
Custom built displays for storefront, standard height is 24"aff, 36"d, variable length,
5/AD.1
WD
PANEL LITE DOOR. PAINT PT -4.
g
N/A
GRILLE STATING "GRILLE TO REMAIN IN FULL OPEN
CLR: BROWN
3 5/8" X 20 GA.
Wood Bench for ADA Dressing room, attached to wall, with front legs.
ADA Bench
METAL STUDS @
QC
TEMPERED GLAZING TO BE FROSTED.
POSITION DURING STORE HOURS WHEN OCCUPIED BY
THE GENERAL PUBLIC."
5/8"
WOOD BASE
SALES (SUPPLIED
16" O.C. TO DECK16"
®6"
SUPPLIED BY FRANCESCA'S, INSTALLED BY G.C.
RESTROOM
O
RESTROOM
3'-0" X 6'-8" X1 3/8"
C
5/8"
5/AD 1
WD
N"l PT -2
C
N/A
'
SEE SECTION 4/A1.114
0
O
GROUT: POLYBLEND / CUSTOM
SEE SECTION 3/A1.1
1-
C/)
CLR: #333 ALABASTER
B. DECORATIVE PRIVACY LOCKSET - G.C. SHALL NOT
12"x12" VINYL FLOORING
STOCK ROOM/
O
VCT -1
CLR: BEIGE
RESTROOM
INSTALL CLOSER.
0
KARNDEAN
SALES
LL
VP -1
VINYL PLANK - HCO3
CLR: DUSK OAK, RANDOM PATTERN
C. PRIVACY LOCKSET - G.C. SHALL NOT INSTALL CLOSER.
SALES/ STOCK ROOM/
CLG-1
NEW 2x2 ACOUSTICAL TILE CEILING
DRESSING ROOM/
dj
TEGULAR EDGE CLR: WHITE
RESTROOM
J
U
STOREFRONT
C)�
NEW GYP. BD. CEILING
CLEAR Of=ETIING WIDTH
TENSION —,,,DRNE
END
----------------
END
- - -
PT -4
PT -2
P -2
FROSTED
TEMPERED
GLAZING
ao
-
i�
U
-
NOTE:
DOOR HARDWARE SHALL BE EASY TO GRASP AND SHALL
=
NOT REQUIRE GRASPING, TIGHT PINCHING, OR TWISTING
OF WRIST. ALL DOORS SHALL HAVE LEVER HARDWARE,
- -
PANIC RELEASES,OR PUSH-PULL PLATES CENTERED
A
B
(�
BETWEEN 30-44" A.FF. ALL LOCKING DEVICES MUST MEET
ANSI AND TAS STANDARDS.
5/8" GYP. BD. TRIM
DBL- 3 5/8" METAL
STUDS. 22 GA. TYP. DOOR JAN
r -
FRT WOOD
BLOCKING
5 DOOR HEAD & JAMB DETAIL
3 =1-0
FRAME
DOOR
5/8" GYP. BD.
DBL. 3 5/8" METAL
STUDS. 22 GA. TYP
TRIM
FRT WOOD
BLOCKING
DOORJAMB
FRAME
WALL
LEGEND
DESCRIPTION
Double Glass Cabinet measuring 2'x6' with an overall height of 100".Lower section has
DBL GS
5/8" TYPE "X" GYP
VALSPAR
5/8" TYPE "X" GYP
BD. TO 6" ABOVE
CA -front
BD. TO 6" ABOVE
CA - back
CEILING - OMIT GYP.
CA -back (18")
CEILING -OMIT GYP. BD.
Standard wood tables measure 2'9"x5'3", with an overall height of 2'6"
T
BD. ON ONE SIDE AT
Optional tables measure 3'3"x5'6", which are noted as 3x5
EXISTING 5/8" TYPE "X"
Rectangle island, measure 72"w x 30"d x 42"h.
U
ON ONE SIDE AT
A
36" round wood tables with drop leaf, 2'6"h
42"R
FURRED WALLS,
B
SQ
Square island, measure 25 1/2"w x 25 1/2"d x 36 1/2"h
GYP.BD. G.C. TO PATCH
Wood shelves, measuring 12"d, available in 4',6',8' lengths
WS
FURRED WALLS,
<
Wood shelving is hung in doubles, the lower one at 66"h and upper at 79"h
4WS
MOISTURE RESISTANT
a.
Two-tiered 4' wood shelves, upper shelf is hung at 76"h, bottom bench is at 18"h
& REPAIR AS REQUIRED. C
note:
3FO
MOISTURE RESISTANT
BEHR
face -out brackets
GYP ON RESTROOM
CLR: SEASIDE SAND
Stacked shelving for stockroom, 12" deep wall mounted. Shelf with pole @5'3 & Top shelf
MAINTAIN ALL EXISTING
#: 740C-1 OIL BASED SEMI -GLOSS
GYP ON RESTROOM
Stk. Shelv.
OLYMPIC
WALLS
Shelf
(1) 24" wide shelf mounted at 60" a.f.f. for loss prevention equipment
FIRE RATINGS. INSTALL
Small microwave & fridge for stockroom
File
WALLS
Display
Custom built displays for storefront, standard height is 24"aff, 36"d, variable length,
3 5/8" X 20 GA.
4" VINYL BASE
Three-piece unit composed of right/left/center, with wood or glass shelves, lights
ON TENANT SIDE IF NOT
Side units measure 16"d x 35"w x 100"h
CLR: BROWN
3 5/8" X 20 GA.
Wood Bench for ADA Dressing room, attached to wall, with front legs.
ADA Bench
METAL STUDS @
QC
EXISTING
METAL STUDS @
5/8"
WOOD BASE
SALES (SUPPLIED
16" O.C. TO DECK16"
®6"
SUPPLIED BY FRANCESCA'S, INSTALLED BY G.C.
(E) 6" METAL 5/8"
O.C. TO 8'-6"
STOREFRONT WALL TILE
STOREFRONT
O
5/8"
LlSTUD.
U-
CLR: WHITE / MULTI - PATTERN BY OWNER
'
SEE SECTION 4/A1.114
0
O
GROUT: POLYBLEND / CUSTOM
SEE SECTION 3/A1.1
NEW WALLS DEMISING WALLS
USE 20GA. MTL STUDS UNLESS OTHERWISE NOTED
J -MOLD ON
TOP OF GYP. BD.
NEW WALLS
@ RESTROOM
° 16 GA. MIN. MTL. TRACK
18 GAUGE CONT DEFLECTION (� TOP AND BUTTON
TRACK W/ 1-1/2" MINIMUM _ +8'-6" A.F.F.
DEEP LEGS - ATTACHMENT T.O. WALL
PER SCHEDULE
r 9
FASTEN STUD TO
RUNNER W/ (1) #10-16
SCREW PER FLANGE 20 GAUGE CONT 8'-0" A.F.F.
I! TRACK TO MATCH
B ACT CEIL
TO DECK WALL STUD WIDTH SCHEDULED PER
t
20 GAUGE CONT.
TRACK TO MATCH 3 5/8" MTL. STUDS & GYP. BD. a
WALL STUD WIDTH WALL SYSTEM.
WALL BASE, SEE
FINISH SCHEDULEWALL ANCHOR, SEE 6B/-
(1) #10-16 SCREW
TRACK ATTACHMENT PER STUD BASE, WHERE OCCURS. SEE
PER SCHEDULE FLANGE, TYP. FINISH SCHEDULE
NEW CONCRETE
jk +0'-0" SLAB BY G.C.
FINISH FLOOR
A TO SLAB
WALL ATTACHMENT DETAIL 3 RESTROOM WALL DETAIL
6O" CLR.
18" 24" MIN
0
36" GRAB BAR -
GZ. TO INSTALL 72
BLOCKING IN WALL
1z idab.o
d = 5/A4
48" CLR -
IOD
7/A4
I
42" GRAB BAR -
G.G. TO INSTALL
BLOCKING IN WALL.
LA
Wr= 504 -IMT A4 I ��C
FOR IRESTROOM
ELEVATIONS I
,
ll N I h. GEN. NOTES CONSTRUCTION KEYNOTES
1. DIMENSIONS ARE TO FINISH SURFACES UNLESS NOTED ® LEASE LINE.
OTHERWISE.
O
2. THE G.C. IS RESPONSIBLE FOR CONFIRMING OVERALL EXISTING DEMISING WALL. G.C. TO PATCH & REPAIR AS REQUIRED.
DIMENSIONS AND STRUCTURAL CONDITIONS PRIOR TO BEGINNING WORK. ANY DISCREPANCIES O ALL FIXTURES PROVIDED BY MILLWORK VENDOR.
OR PROBLEMATIC CONDITIONS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE G.C..
ALL
3. REPORT ALL SHELL BUILDING DEFECTS "EO "EHE G.C. O BEFORE WALLS RE COVERED FROM FLOOR TO CEILING WITH PAINT. ALL WALLS TO BE BROUGHT TO A LEVEL 3 FINISH
G.
IMMEDIATELY UPON DISCOVERY.
LL GENERAL NOTES
T.G.C. IS TO OBTAIN APPROVAL AND REQUIREMENTS FROM ON SITE TENANT COORDINATOR
PRIOR TO ANY CUTTING OR DRILLING OF EXISTING FLOOR.
TENANT IS RESPONSIBLE TO FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS IN THE
SPACE. FAILURE TO PROPERLY FIELD VERIFY EXISTING CONDITIONS DOES NOT RELIEVE THE
TENANT OF ANY EXPENSES OR RESPONSIBILITIES RESULTING FROM THAT FAILURE.
NOTHING IS PERMITTED TO BE ATTACHED TO, BE SUSPENDED FROM, OR PENETRATE THE ROOF
DECK. TENANTS MAY ATTACH TO JOIST(S), AT PANEL POINTS, UR TO THE STRUCTURAL STEEL.
ALL WALL CONSTRUCTION SHALL BE SUPPORTED IN THIS MANNER. NO WELDING TOR
SHOOTING INTO THE STRUCTURE IS PERMITTED.
STRUCTURAL REINFORCING DETAILS MUST BE PROVIDED BY A REGISTERED STRUCTURAL
ENGINEER TO TENANT COORDINATION FOR EQUIPMENT SUPPORT OR SUSPENSION, SERVICE
PLATFORMS, DECK PENETRATIONS, ETC. - FOR LANDLORD'S RECORDS.
ANY LANDLORD EQUIPMENT OR COMPONENT THAT IS EXISTING IN THE SPACE MUSE REMAIN
VISIBLE AND ACCESSIBLE TO THE LANDLORD. TENANT TO INSTALL ACCESS PANELS AS
NECESSARY, AND PROPERLY LABEL IN SPACE. COORDINATE PLACEMENT WITH MALL
OPERATIONS DIRECTOR.
TENANT'S STOCKROOM MAY NOT BE VISIBLE FROM THE SALES AREA. DOOR(S) LEADING TO THE
STOCKROOM MUST HAVE AN AUTOMATIC CLOSURE.
ALL CONCRETE PATCHING MUS -T BE LEVEL WITH THE EXISTING CONCRETE FLOOR.
ALL FLOORING TRANSITIONS MUST BE SMOOTH & FLUSH. THE USE OF PLASTIC, VINYL, OR
RUBBER TRANSITION STRIPS IS STRICTLY PROHIBITED. TENANTS MUST UTILIZE A HARD
SURFACE TRANSITION.
NO RUBBER OR VINYL BASE IS PERMITTED IN THE SALES AREA OF THE PREMISES
Item
Description
DESCRIPTION
Double Glass Cabinet measuring 2'x6' with an overall height of 100".Lower section has
DBL GS
_ 1 '4"ZZ
VALSPAR
sliding wood doors with inner shelf. Upper section consists of glass shelves, with lights
Front Cashwrap meets ADA requirements with a center drop-down section measuring 36"
CA -front
wide at a height of 33" aff. Overall dimensions are 96"I x 36" d x overall height of 44".
CA - back
Back Cashwrap; 8' long version, 2'4"d x 44"h.
CA -back (18")
OPTIONAL Back Cashwrap; 6' long, 18"d x 44"h
Standard wood tables measure 2'9"x5'3", with an overall height of 2'6"
T
SERVICE ENTRANCE/
Optional tables measure 3'3"x5'6", which are noted as 3x5
IS
Rectangle island, measure 72"w x 30"d x 42"h.
U
36" round unfinished tables, 2'6"h
DL
36" round wood tables with drop leaf, 2'6"h
42"R
42" round wood tiered table
SQ
Square island, measure 25 1/2"w x 25 1/2"d x 36 1/2"h
Z
Wood shelves, measuring 12"d, available in 4',6',8' lengths
WS
SALES AREA CEILING
<
Wood shelving is hung in doubles, the lower one at 66"h and upper at 79"h
4WS
4' Wood shelf elevation, shelves are hung at 24",40",5611,72"
a.
Two-tiered 4' wood shelves, upper shelf is hung at 76"h, bottom bench is at 18"h
#: CI 200
note:
3FO
* There needs to be 3" gaps on either side to allow for the hangers to hang freely on the
BEHR
face -out brackets
* Do not attach the lower bench to the wall
CLR: SEASIDE SAND
Stacked shelving for stockroom, 12" deep wall mounted. Shelf with pole @5'3 & Top shelf
SS
#: 740C-1 OIL BASED SEMI -GLOSS
at 7' aff, variable lengths
Stk. Shelv.
OLYMPIC
(4) 12" deep wall mounted shelving for stock room spaced equally with top shelf at 7' aff
Shelf
(1) 24" wide shelf mounted at 60" a.f.f. for loss prevention equipment
M/F
Small microwave & fridge for stockroom
File
Small file for stockroom
Display
Custom built displays for storefront, standard height is 24"aff, 36"d, variable length,
finished with trim
4" VINYL BASE
Three-piece unit composed of right/left/center, with wood or glass shelves, lights
Armoire
Side units measure 16"d x 35"w x 100"h
CLR: BROWN
Center unit measures 20"d x 36"w x 100"h
Wood Bench for ADA Dressing room, attached to wall, with front legs.
ADA Bench
Measuring 42"wx18"hx20"w
NOTE:
PROVIDE CONCEALED F.R.T. WOOD BLOCKING
AT ALL RETAIL FIXTURES ANCHORED TO WALLS.
Hi
O PREP CONCRETE SLAB FOR INSTALLATION OF NEW FLOOR FINISH PER MANUFACTURERS RECOMMENDATION. ALL
FLOORING TRANSITIONS TO BE LEVEL AND FLUSH AND COMPLY WITH ANSI A117.1 & CALIFORNIA BUILDING CODE.
O NEW ELECTRICAL PANEL. G.C. TO PULL SERVICE TO SPACE FROM LANDLORDS DESIGNATED LOCATION. SEE ELEC.
O NEW INTERIOR WALLS. SEE WALL TYPE SCHEDULE FOR DETAILS.
O NEW STOREFRONT SYSTEM. SEE ELEVATIONS FOR MORE INFO.
O NEW ADA RESTROOM. SEE DETAIL THIS SHEET AND ELEVATIONS ON A4 FOR MORE INFORMATION. SEE PLUMBING
FOR FIXTURE SPECS.
10 APPROXIMATE LOCATION OF FIRE EXTINGUISHER. GC TO COORDINATE WITH FIRE MARSHAL FOR PREFERRED
LOCATIONS
11 CUT FLOOR (CORE DRILL ON ELEVATED FLOORS) 6'4" FROM WALL FOR RECEPTACLE & CAT5 FOR CASHWRAP,
SEE ELECTRICAL FOR DETAILS. T.G.C. TO OBTAIN L.L. REQUIREMENTS BEFORE CUTTING
1� NEW DEMISING WALL BY LL. G.C. TO INSTALL 5/8" TYPE'X' GYP. BD. ON TENANT SIDE AND PROVIDE BLOCKING AS
NECESSARY.
13 MESH WALL GRID BEHIND CASHWRAP. G.C. TO PROVIDE HORIZONTAL BLOCKING @ 24" O.C.-SCREW BOTTOM OF
MESH TO MITIGATE MOVEMENT FROM WALL.
ADJACENT TENANT
a%i'-Q 'd/All
FINISH LEGEND - COASTAL
NOTE: ALL FINISHES NEED TO MEET A MIN. OF A CLASS C FINISH FOR ENCLOSED SPACES.
SEE SEC V. ON CODE STUDY FOR MORE DETAILS,
T
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
W DPARTN ERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE #D11 C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCCO0050
NOV . 0 2013
ISSUE DATES
PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
Q PERMIT SET: 11-20-2013
*
MARK
DESCRIPTION
GENERAL LOCATION
1 1/2-
_ 1 '4"ZZ
VALSPAR
SALES AREA WALLS
PT -1
CLR: SEA SALT BLUE
#: CI 191 SATIN
.. )...:)% -... .., .'..,....r.. ., ,<..,, ,,,. :. ✓.,; ..':.ry:rt,. .,J i,! i wM1 .,if ,..i �, r.':,.l i., .:I:. ,., f' ,..:
i..4 rl Y.r � i,f r✓w��wr«,.. r)�,.r .r.f,r 4, 1. : i✓., s., Citi': lel er riX.. t.i. ', 1J.1'� ,Y .. '.� �i .. !: '..!
VALSPAR
SERVICE ENTRANCE/
PT -2
CLR: SAWYER WHITE
RESTROOM
#: 7002-16 INTERIOR SEMI -GLOSS
Z
VALSPAR
SALES AREA CEILING
<
PT -3
CLR: CREME FRAICHE
a.
#: CI 200
BEHR
STOCK ROOM DOOR/
PT -4
CLR: SEASIDE SAND
WOOD FRAME
#: 740C-1 OIL BASED SEMI -GLOSS
OLYMPIC
STOREFRONT
PT -5
CLR: HEIRLOOM LACE
SYSTEM
#: D10-1
4" VINYL BASE
STOCK ROOM/
B-1
CLR: BROWN
RESTROOM
QC
WOOD BASE
SALES (SUPPLIED
®6"
SUPPLIED BY FRANCESCA'S, INSTALLED BY G.C.
BY FRANCESCA'S)
STOREFRONT WALL TILE
STOREFRONT
O
WT -1
SOLI USA - HOSI MOSAIC
U-
CLR: WHITE / MULTI - PATTERN BY OWNER
0
O
GROUT: POLYBLEND / CUSTOM
1-
C/)
CLR: #333 ALABASTER
12"x12" VINYL FLOORING
STOCK ROOM/
O
VCT -1
CLR: BEIGE
RESTROOM
0
KARNDEAN
SALES
LL
VP -1
VINYL PLANK - HCO3
CLR: DUSK OAK, RANDOM PATTERN
SALES/ STOCK ROOM/
CLG-1
NEW 2x2 ACOUSTICAL TILE CEILING
DRESSING ROOM/
dj
TEGULAR EDGE CLR: WHITE
RESTROOM
J
U
STOREFRONT
C)�
NEW GYP. BD. CEILING
NOTE: ALL FINISHES NEED TO MEET A MIN. OF A CLASS C FINISH FOR ENCLOSED SPACES.
SEE SEC V. ON CODE STUDY FOR MORE DETAILS,
T
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
W DPARTN ERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE #D11 C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCCO0050
NOV . 0 2013
ISSUE DATES
PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
Q PERMIT SET: 11-20-2013
*
3"=
V-0"
1 1/2-
_ 1 '4"ZZ
:
.. )...:)% -... .., .'..,....r.. ., ,<..,, ,,,. :. ✓.,; ..':.ry:rt,. .,J i,! i wM1 .,if ,..i �, r.':,.l i., .:I:. ,., f' ,..:
i..4 rl Y.r � i,f r✓w��wr«,.. r)�,.r .r.f,r 4, 1. : i✓., s., Citi': lel er riX.. t.i. ', 1J.1'� ,Y .. '.� �i .. !: '..!
FINISH LEGEND - COASTAL
COMMENTS
MARK
DESCRIPTION
GENERAL LOCATION
REFER TO SHEET E2 FOR
SURFACE MOUNT
VALSPAR
SALES AREA WALLS
REFER TO SHEET E2 FOR
PT 1
CLR: SEA SALT BLUE
DISPLAY AREA
IF: Cl 191 SATIN
FOR EMERGENCY FIXTURES
ENTRY/
VALSPAR
SERVICE ENTRANCE/
REFER TO SHEET E2 FOR
PT -2
CLR: SAWYER WHITE
RESTROOM
#: 7002-16 INTERIOR SEMI -GLOSS
REFER TO SHEET E2 FOR
c@ 90" A.F.F.
F --
z
SALES-
VALSPAR
SALES AREA CEILING
a.(
PT 3
CLR: CREME FRAICHE
LL.
#:C1200
BEHR
STOCK ROOM DOOR/
PT 4
CLR: SEASIDE SAND
WOOD FRAME
#: 7400-1 OIL BASED SEMI -GLOSS
OLYMPIC;
STOREFRONT
PT -5
CLR: HEIRLOOM LACE
SYSTEM
#: D10-1
STOCK ROOM/
B-1
4" VINYL BASE
RESTROOM
CLR: BROWN
6" WOOD BASE
SALES (SUPPLIED
B_z
SUPPLIED BY FRANCESCA'S, INSTALLED BY G.C.
BY FRANCESCA'S)
z
STOREFRONT WALL TILE
STOREFRONT
0
W_i-1
SOLI USA - HOSI MOSAIC
CLR: WHITE / MULTI - PATTERN BY OWNER
U-
w
w
GROUT: POLYBLEND / CUSTOM
CLR: #333 ALABASTER
STOCK ROOM/
12"x12" VINYL FLOORING
RESTROOM
�
VCT -1
CLR: BEIGE
O
0
KARNDEAN
SALES
L
VP -1
VINYL PLANK - HCO3
CLR: DUSK OAK, RANDOM PATTERN
SALES/ STOCK ROOM/
NEW 2x2 ACOUSTICAL TILE CEILING
DRESSING ROOM/
CLG-1
TEGULAR EDGE CLR: WHITE
RESTROOM
0
J
STOREFRONT
U
CLG-2
NEW GYP. BD. CEILING
NOTE: ALL FINISHES NEED TO MEET A MIN. OF A CLASS C FINISH FOR ENCLOSED SPACES.
SEE SEC V. ON CODE STUDY FOR MORE DETAILS.
LIGHTING SCHEDULE
MARK DESCRIPTION
0 0 0 o TRACK LIGHTING
WHITE
TRACK LIGHTING
6" RECESSED CAN
0 LIGHT
O CHANDELIER
SCONCE
1x4 FLUORESCENT
LIGHTING
LOCATION
COMMENTS
SALES AREA
REFER TO SHEET E2 FOR
SURFACE MOUNT
SPECIFICATIONS.
REFER TO SHEET E2 FOR
STOREFRONT
SPECIFICATIONS.
DISPLAY AREA
FOR EMERGENCY FIXTURES
ENTRY/
CONNECT TO INVERTER.
SALES AREA
REFER TO SHEET E2 FOR
SPECIFICATIONS.
SALES -CENTER
OVER CASH WRAP
REFER TO SHEET E2 FOR
c@ 90" A.F.F.
SPECIFICATIONS.
SALES-
REFER TO SHEET E2 FOR
ABOVE DRESSING
SPECIFICATIONS.
a 82" A.F.F.
REFER TO SHEET E2 FOR
STOCK ROOM SPECIFICATIONS.
NOTE:
INSTALL CHANDELIER ONLY AFTER THE CASHWRAP
HAS BEEN PROPERLY POSITIONED. NO EXCEPTIONS,
SPRINKLER NOTES
1) SIMON PROPERTY GROUP REQUIRES ALL TENANTS TO USE MALL CONTRACTOR FOR ALL SPRINKLER
WORK.
2) AT TIME OF BIDDING, TENANT OR T.G.C. SHOULD CONTACT SIMPLEX GRINNELL'S NATIONAL ACCOUNTS
REPRESENTATIVE TO OBTAIN DIRECTION FOR PRICING AND SCHEDULING. 1-800-299-4377, OPTION 4.
TENANT OR T.G.C. IS REQUIRED TO CONTRACT WITH AND PAY FOR ALL TENANT SPRINKLER WORK
DIRECTLY WITH SIMPLEX GRINNELL.
3) SPRINKLER SYSTEM MUST BE FULLY CHARGED AND OPERATIONAL WHENEVER CONTRACTOR IS NOT
ON SITE.
4) ALL SPRINKLER WORK (SHOP DRAWINGS) TO BE APPROVED BY LANDLORD'S INSURER. SUBMIT PLANS
TO: GLOBAL RISK CONSULTANTS
ATTN: LORI MEYER/ SIMON TENANT PLAN REVIEW
1003 REGENCY MANOR DRIVE
BALLWIN, MO 63011
636-891-9052
lori.meyer a globalriskconsultants.com
5) TENANT TO CONTACT MALL OPERATIONS DIRECTOR, DAVID MILLER, AT 407-323-1843 FOR LIST OF MALL
APPROVED ROOFING & SPRINKLER CONTRACTORS.
6) FIRE PROTECTION CONTRACTOR IS LIABLE FOR COMPLIANCE WITH ALL NATIONAL, STATE, AND LOCAL
FIRE PROTECTION REQUIREMENTS.
7) TENANT'S SPRINKLER SYSTEM SHALL BE TESTED IN ACCORDANCE WITH NFPA 13.
8) UPON COMPLETION OF SPRINKLER SYSTEM MODIFICATIONS AND TESTS, CONTRACTOR SHALL SUBMIT
A WRITTEN CERTIFICATE TO THE LANDLORD FOR THE UNDERWRITER STATING THAT THE SYSTEM HAS
BEEN HYDROSTATICALLY TESTED, INSPECTED AND APPROVED.
9) ALL SPRINKLER HEADS IN STOREFRONT DISPLAY & ENTRANCES AREAS ARE TO BE FULLY RECESSED
WITH FACTORY FINISHED COVER PLATES. SPRINKLER HEADS IN SALES AREA CAN BE FULLY
CONCEALED OR SEMI RECESSED PENDANT CHROME HEADS AS A MIN.
w
MARK
'f�
0
Ell
DESCRIPTION
EMERGENCY
LIGHTING
REMOTE HEAD
LOCATION COMMENTS
THROUGHOUT REFER TO SHEET E2 FOR
SPECIFICATIONS.
RESTROOM
RESTROOM FAN/ I RESTROOM
LIGHT
EXIT LIGHT THROUGHOUT
EDGE LIT C7a SALES
COMBO EXIT/STOCK ROOM
EMERGENCY LIGHT
REFER TO SHEET E2 FOR
SPECIFICATIONS.
REFER TO SHEET M1 FOR
SPECIFICATIONS.
EXISTING TO REMAIN.
REFER TO SHEET E2 FOR
SPECIFICATIONS.
-REFER TO SHEET E2 FOR
SPECIFICATIONS.
CEILING KEYNOTES
0 G.C. TO INSTALL J -BOX CENTERED EQUALLY OVER CASH COUNTER
FOR INSTALLATION OF CHANDELIER.
2 NEW TRACK LIGHTS MOUNTED TO CEILING.
3 NEW RECESSED LED CAN LIGHTS FOR EMERGENCY LIGHTING, TYP.
4 NEW WALL MOUNTED FITTING ROOM SCONCE FIXTURES CENTERED
OVER MIRROR
18 5 NEW EMERGENCY EGRESS / EXIT LIGHTS. REFER TO ELECTRICAL
6 NEW CEILING MOUNTED STOCKROOM LIGHTS, TYP.
7 NEW CEILING MOUNTED RESTROOM LIGHTING.
NEW FAN/LIGHT COMBO IN RESTROOM.
CEILING NOTES
VERIFY HEIGHT OF EXISTING DUCT WORK.
ALL SUPPORTS ARE ATTACHED FROM THE STRUCTURAL JOISTS & BEAMS
ABOVE. DO NOT ATTACH TO DECK.
ONLY THE CEILING SHALL BE SUSPENDED FROM THE STRUCTURE ABOVE.
ANY ITEM TO BE SUSPENDED FROM THE STRUCTURE MUST RECEIVE PRIOR
WRITTEN APPROVAL BY THE LANDLORD.
COORDINATE ALL CEILING WORK WITH THE LANDLORD PRIOR TO
COMMENCING.
ADJACENT TENANT '6
,
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE#1311C
SANFORD, FL 32771
DRAWN BY:
/SM
WD PROJECT NUMBER
FRCC00050
livY ;I V L.U1J
s
llll ISSUE DATES
[] PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
j PERMIT SET: 11-20-2013
REVISIONS
0
DRAWING NUMBER
REFLECTED CEILING PLAN
I
1/411 = 1'-0"
., ..x Y
.. ,.. a... a ,
.... - z ,., r ., ., � , n r Y r r na
.. .. .. t ..
,.,,,, ,, ,.e'- x....a.. ,.: ,,, ..�,. ,, ,, ,.,.'z ., .>�.,x..,,. ..,,,s:i ..x .., ..i .x ..... ,.,� •,,.,.,:: .. ... ..:. .. .. .... ,.,. ...., ,,,.,,., .x,s 3: e, ......,. u „x. �,.,., ,,,.,,, s. ,, .., ... ... .. ...... .. � ...•...., .. ,. .,. .., .. .,., r w u w r Ywr r
ELEVATION LWOLDE®
n STOREFRONT ELEVATION (FRONT)
3/4" = V-0"
12'-10" A.F.F.
T.O. BULKHEAD
11'-0" A. F. F. AN
T.O. GLAZING
8'-0" A.F.F.
T.O. GRILLE
0'-0" A.F.F.
T.O. SLAB
is MR
PARTNERS
brand : operations : build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
W DPARTN ERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE#13111C
SANFORD, EL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
NOV 2 0 2013
ISSUE DATES
0 PRELIM SET: 10-16-2013
0 FINAL SET: 11-6-2013
0 PERMIT SET: 11-20-2013
REVISIONS
0
DRAWING NUMBER
STOREFRONT KEYNOTES
OLEASE LINE, TYP.
0 EXISTING MALL BULKHEAD TO REMAIN.
ONEW STYLMARK WALLMAKER ANODIZED ALUMINUM STOREFRONT
SYSTEM, PAINTED PT -5, W/ 1/2" TEMPERED GLAZING.
0 SIGN LEDGE W/ LED COVE LIGHTING. BREAK METAL (MT -1) OVER
5/8" FRT PLYWOOD ON 2 1/2" METAL STUDS. SIGNAGE BY VENDOR.
ONEW 3"H VINYL SAFETY GRAPHICS APPLIED TO INSIDE OF GLAZING,
CENTERED IN GLAZING.
0 WALL TILE (WT -1) FRANCESCA'S WILL PROVIDE TILES AND SHIP TO
SITE.
OBREAK METAL WRAPPED STUD POSTS. PAINT PT -5
0 WOOD TRIM (POPLAR) TO BE PAINTED PT -5
0 GYP. BD. SOFFIT. PAINT PT -5
FINISH LEGEND - COASTAL
MARK
DESCRIPTION
GENERAL LOCATION
VALSPAR
SALES AREA WALLS
PT -1
CLR: SEA SALT BLUE
#: CI 191 SATIN
VALSPAR
SERVICE ENTRANCE/
PT -2
CLR: SAWYER WHITE
RESTROOM
#: 7002-16 INTERIOR SEMI -GLOSS
F--
VALSPAR
SALES AREA CEILING
CLR: CREME FRAICHE
#:01200
BEHR
STOCK ROOM DOOR/
PT 4
CLR: SEASIDE SAND
WOOD FRAME
#: 740C-1 OIL BASED SEMI -GLOSS
OLYMPIC
STOREFRONT
PT -5
CLR: HEIRLOOM LACE
SYSTEM
#: D10-1
4" VINYL BASE
STOCK ROOM/
B-1
CLR: BROWN
RESTROOM
CL
6" WOOD BASE
SALES (SUPPLIED
SUPPLIED BY FRANCESCA'S, INSTALLED BY G.C.
BY FRANCESCA'S)
STOREFRONT WALL TILE
STOREFRONT
O
WT -1
SOLI USA - HOSI MOSAIC
°C
CLR: WHITE / MULTI - PATTERN BY OWNER
Lu
0
U
GROUT: POLYBLEND / CUSTOM
U)
CLR: #333 ALABASTER
12"x12" VINYL FLOORING
STOCK ROOM/
VCT -1
CLR: BEIGE
RESTROOM
O
0
KARNDEAN
SALES
LL
VP -1
VINYL PLANK - HCO3
CLR: DUSK OAK
CLG-1
NEW 2x2 ACOUSTICAL TILE CEILING
SALES/ STOCK ROOM/
DRESSING ROOM/
TEOULAR EDGE CLR: WHITE
RESTROOM
J
U
STOREFRONT
CLG-2
NEW GYP. BD. CEILING
NOTE: ALL FINISHES NEED TO MEET A MIN. OF A CLASS C FINISH FOR ENCLOSED SPACES.
SEE SEC V. ON CODE STUDY FOR MORE DETAILS.
LL STOREFRONT NOTES
1) IF NOT ALREADY EXISTING, TENANT MUST PROVIDE A SEALED
PARTITION ABOVE THE STOREFRONT TO SEPARATE THE COMMON AREA
CEILING FROM THE TENANT'S SPACE. (SHALL BE RATED IF REQUIRED BY
CODE.)
2) STOREFRONT GRILLES ARE EXPRESSLY PROHIBITED BY THE
LANDLORD. IF EXISTING IN THE SPACE FROM A PRIOR OCCUPANT,
TENANT SHALL BE REQUIRED TO REMOVE AS PART OF DEMOLITION. NO
EXCEPTIONS WILL BE PERMITTED.
3) SLAT WALL MAY NOT BE USED WITHIN THE FIRST 5'-0" OF THE SPACE.
4) VERTICAL GLASS JOINTS SHALL BE FRAMELESS BUTT JOINTS.
5) PAINTED DRYWALL IS NOT AN ACCEPTABLE STOREFRONT FINISH.
6) ANY DAMAGE TO MALL PROPERTY OR ADJACENT TENANTS DURING
CONSTRUCTION MUST BE REPAIRED TO MALL SPECIFICATIONS AT
TENANT'S EXPENSE.
7) STOREFRONT SIGN MUST BE ON A 7 -DAY, 24-HOUR TIME CLOCK.
ILLUMINATED SIGNS MUST REMAIN ILLUMINATED DURING ALL MALL
HOURS.
8) APPROVAL OF THE TENANT'S DESIGN OR WORKING DRAWINGS BY
THE LANDLORD SHALL NOT CONSTITUTE REVIEW AND APPROVAL OF
THE TENANT'S SIGNAGE. SIGN SHOP DRAWINGS MUST BE SUBMITTED
SEPARATELY BY THE TENANT FOR LANDLORD REVIEW AND APPROVAL
PRIOR TO FABRICATION AND INSTALLATION OF THE SIGN.
is MR
PARTNERS
brand : operations : build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
W DPARTN ERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE#13111C
SANFORD, EL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
NOV 2 0 2013
ISSUE DATES
0 PRELIM SET: 10-16-2013
0 FINAL SET: 11-6-2013
0 PERMIT SET: 11-20-2013
REVISIONS
0
DRAWING NUMBER
016 B.O. MALL Bl
EL = 12'-10”
5/8" GYP. BD, OVEF
G" METAL STUD
FRAYING, PAINT PT
OgL T.O. STOREFR
EL = 11'-0"
BOX BEAN HEADER:
HITH GOOT125-33 TRS
ATTACH TRACK HI -IT
@ 12" O.C. EACH FLAI
BOX BEANS HITH ON
STUD 6005162-33 AN
STUD 6005162-33 TY
ALUM. STOREFRONT
SYSTEM HITH 1/2"
TENPERED GLAZING
„,,.v ....,.... „ ,,..., ,, .,, ,,. .,, .�, a, v,,.w ., .....,tea , w.,r ,..,., ,,.,.,x ,.,,.,,,v, r x ., �.� n i i. r . ..� .� rY ....w. .. www....+.., r..n. ,...,, n. •. wr. ...w.x .w r.. ,.. . .,, ..... r. ,.. .. ..r ... ,,, .rxw ......,. w.www.aw � .w.wrr rx Y r xs, t s , ,. , .. , , , . ,... ....... ..i . ...... ... ., . , , .a .'ri
GID CEILING
' CLG. WIRE @
6
TYP.
B.O. ENTRY
EL = 8'-0"
'. BD. OVER
1ETAL STUD
@ 16" O.C.,
NALL BUILKHEAC
5/8" GYP. BD. G
G" METAL STUD
FRAMING, PAINT
PT -5
BOX BEAN HEAL
HITH GOOT125-3?
ATTACH -TRACK
@ 12" O.C. EACH
BOX BEANS HITT
STUD 6005162-3'.
STUD 5005162-3
5/8" GYP. BD. G
6" METAL STUD
FRAMING, PAINT
PT -5
WALL TILE (WT -1)
1/2" CEMENT �304I
METAL STUD FR
COVE LIGHTING,
SPECIFIED BY H.
EDGE MOUNTED
SIGN BY SIGN
VENDOR
BOX BEAM HEAD
6005162--33 WITH
TRACKS T4B. A'I
HITH 410-16 SIRE
EACH FLANGE. S
BEAMS HITH ONI
STUD 3525162--3:
BEDDING STUD
TYP. EACH END
MANUAL ROLL -U
SEE AI.I FOR MC
NG RIGID CEILING
"H 412 CLG. WIRE @
O.C.
) 410-16
`EHS, TYP.
B.O. ENTRY
EL = 8'-0"
11L AL
PARTNERS
In
wm
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNER S.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE #1311 C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
NOV 9 0 2013
ISSUE DATES
0 PRELIM SET: 10-16-2013
0 FINAL SET: 11-6-2013
PERMIT SET: 11-20-2013
REVISIONS
0
DRAWING NUMBER
G.G. IS TO SET CASH WRAP FIXTURE OVER (2) 1/4"D ANCHOR PINS
INTO CONCRETE SLAB TO PREVENT THE FIXTURE FROM SLIDING
OUT OF POSITION. BORE FIXTURE FEET TO ACCEPT ANCHOR.
NOTE: FOOT IS DESIGNED TO BE SCREWED INTO FIXTURE.
0 CASHWRAP PIN DETAIL
1" = 1'-01,
BENCH DETAIL
NOT TO SCALE
w
......_. .... .. ,..:,... r , . ,,:,.::. •., .. ,:..e. „ mii, as �„ w„+:.•. ,. „,
DSALES WALL ELEVATION
3/8" = V-0"
10'-6" A. F. F. J
B.O. CEILINGY
8'-0" �A.F.Fj4
B.O. SOFFIT Y
0'-0" A.F.F.
T.O. SLAB
3 �V Y Y, 1#,L LLL Y I % 1 1 yr m
3/8" = 1'-0"
2' X 3' MIRROR -
INSTALL MIRROR
DIRECT TO GiYP. E3D. —
T-0"
Ole
12" 2'-0"
LU
A
Q
10'-6" A.F.F.
B.O. CEILING A.
0'-0" A.F�F.A
T.O. SLAB V
NOTE TO G.C.:
ALL SHELVES WITH A CLOTHING ROD MUST
BE SUPPORTED ONLY WITH BRACKETS
PROVIDING HANG BAR SUPPORT
FINISH LEGEND - COASTAL
6' -WS
T FO
Ll
�\
61
GENERAL LOCATION
W
e
VALSPAR
SALES AREA WALLS
PT -1
10'-6" A.F.F.
B.O. CEILING A.
0'-0" A.F�F.A
T.O. SLAB V
NOTE TO G.C.:
ALL SHELVES WITH A CLOTHING ROD MUST
BE SUPPORTED ONLY WITH BRACKETS
PROVIDING HANG BAR SUPPORT
FINISH LEGEND - COASTAL
6' -WS
T FO
Ll
MARK
DESCRIPTION
GENERAL LOCATION
4" VINYL
WS 8' -WS 6' -WS
VALSPAR
SALES AREA WALLS
PT -1
CLR: SEA SALT BLUE
WATER AND DRAIN
WATER AND DRAIN BA5E
#: CI 191 SATIN
c3It
VALSPAR
SERVICE ENTRANCE/
PT -2
CLR: SAWYER WHITE
RESTROOM
RESTROOM ELEVATION
#: 7002-16 INTERIOR SEMI -GLOSS
5
3/8 = 1 -0
6
-3/8'- V-0"
Z
I
VALSPAR
SALES AREA CEILING
r..r-]:., '. .., :r{,' ', ,.:: .d, !'f.,.,,,. •,
� �. •t-, ,,... :,, ,. ,.t r..� II t, r' .4r a a .i
..::•..; ,+, t ..: ... v. rv.. ';...ii
CLR: CREME FRAICHE
LL
#: CI 200
BEHR
STOCK ROOM DOOR/
PT 4
CLR: SEASIDE SAND
WOOD FRAME
#: 740C-1 OIL BASED SEMI -GLOSS
OLYMPIC
STOREFRONT
PT -5
CLR: HEIRLOOM LACE
SYSTEM
#: D.10-1
4" VINYL BASE
STOCK ROOM/
B 1
CLR: BROWN
RESTROOM
WOOD BASE
SALES (SUPPLIED
®6"
B z
SUPPLIED BY FRANCESCA'S, INSTALLED BY G.C.
BY FRANCESCA'S)
STOREFRONT WALL TILE
STOREFRONT
GO
WTI
SOLI USA - HOSI MOSAIC
m
CLR: WHITE / MULTI - PATTERN BY OWNER
U_
W
0
0
GROUT: POLYBLEND / CUSTOM
F-
CLR: #333 ALABASTER
STOCK ROOM/
1211x121' VINYL FLOORING
RESTROOM
cc
VCT -1
CLR: BEIGE
O
O
KARNDEAN
SALES
LL
VP 1
VINYL PLANK - HCO3
CLR: DUSK OAK, RANDOM PATTERN
SALES/ STOCK ROOM/
NEW 2x2 ACOUSTICAL TILE CEILING
DRESSING ROOM/
CLG-1
TEGULAR EDGE CLR: WHITE
RESTROOM
�
U
STOREFRONT
CLG 2
NEW GYP. BD. CEILING
NOTE: ALL FINISHES NEED TO MEET A MIN. OF A CLASS C FINISH FOR ENCLOSED SPACES.
SEE SEC V. ON CODE STUDY FOR MORE DETAILS.
ELEVATION UNFOLDED
ENTRY ELEVATION
2 3/8" = 1 '-0"
10'-6" A.F.F.
B.O. CEILING
8'-0" A.F.F.
B.O. SOFFIT
0'-0" A*F '
F. F. "111,T.O. SLAB
CLG-1
PT -3
PT -1
6' -WS
T FO
Ll
L--4" VINYL I�®6��
� -- INSUI-ATE EXP05ED
INSULATE EXPOSED 4" VINYL
4" VINYL
WS 8' -WS 6' -WS
;
-1" 1�11N.
t�vjp_jinB-2
SALES WALL ELEVA I ION
4 3/8" = 1'-0"
AR
'APER
SER
10'-6" A.F.F.
B.O. CEILING
_ 0'-0" A.F.F.
T.O. SLAB
IWPARTNERS
brand: operations * build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000'r
WDPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE #B11C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
NOV-2 0 2013
ISSUE DATES
PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
PERMIT SET: 11-20-2013
REVISIONS
DRAWING NUMBER
L--4" VINYL I�®6��
� -- INSUI-ATE EXP05ED
INSULATE EXPOSED 4" VINYL
4" VINYL
��+ vuv
qgE
;
-1" 1�11N.
g,gSE
WATER AND DRAIN
WATER AND DRAIN BA5E
5,45E
c3It
PIPES
PIPES
RESTROOM ELEVATION
RESTROOM ELEVATION
RESTROOM ELEVATION
8 RESTROpOM ELEVATION
5
3/8 = 1 -0
6
-3/8'- V-0"
I
r..r-]:., '. .., :r{,' ', ,.:: .d, !'f.,.,,,. •,
� �. •t-, ,,... :,, ,. ,.t r..� II t, r' .4r a a .i
..::•..; ,+, t ..: ... v. rv.. ';...ii
IWPARTNERS
brand: operations * build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000'r
WDPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE #B11C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
NOV-2 0 2013
ISSUE DATES
PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
PERMIT SET: 11-20-2013
REVISIONS
DRAWING NUMBER
VAV BOX SCHEDULE
EXHAUST FAN SCHEDULE
TAG
MANUFACTURER
INLET
CFMSIZE
O.A.
TAG
MAKE
MODEL NO.
NOTES
Sales
NOTES
DESCRIPTION
15
CFM
CFM
HP
NOTES
MAX
MIN
EF -1
VAV-1
TRANE
VCCF12
12"
1000
300
1,2
NOTES:
1. FACTORY PROVIDED DISCONNECT SWITCH, CONTROL
TRANSFORMER.
2. PROVIDE NEW THERMOSTAT. COORDINATE WITH
LANDLORD FOR THERMOSTAT MANUFACTURER AND MODEL
INFORMATION.
VENTILATION RATE SCHEDULE
Mechanical Ventilation Schedules
Based upon ASHRAE 62.1, 2007
EXHAUST FAN SCHEDULE
TAG
MANUFACTURER
MODEL
NOMINAL
O.A.
FAN
VOLTAGE
MCA/MOCP
NOTES
Sales
"SAG
DESCRIPTION
15
CFM
CFM
HP
NOTES
MANUFACTURER
MODEL
EF -1
SEE ELEC.
WASTE
SEE ELEC.
90
-
130 WATTS
120/1/60
-
1
NOTES:
WATER CLOSET
AMERICAN
CADET
1. CEILING EXHAUST FAN.
90 CFM a 0.375" ESP. FURNISHED WITH FACTORY MOUNTED DISCONNECT AND BACKDRAFT
DAMPER.
2"
3/4°
CWR
VENTILATION RATE SCHEDULE
Mechanical Ventilation Schedules
Based upon ASHRAE 62.1, 2007
PLUMBING FIXTURE SCHEDULE
Roorn Name
Classification
Room Area
(sq.ft.)
Area OA Rate
(cfm/sq.ft.)
FIXTURE
VALVE/FAUCET
People OA Rate
(cfm/person)
CONNECTIONS
Sales Area
Sales
"SAG
DESCRIPTION
15
12
7.5
187
NOTES
MANUFACTURER
MODEL
MANUFACTURER
MODEL
WASTE
VENT
CW
HW
Restroorn
64
-
-
WC -1
WATER CLOSET
AMERICAN
CADET
Total (square feet)
1 954
4"
2"
3/4°
CWR
1, 2, 3
RD
RETURN DIFFUSER
ADA
STANDARD
#2467.016, WHITE
RESISTOR
DC
DIRECT CURRENT
RG
RETURN GRILLE
DI
DIGITAL INPUT
RTU
LAV -1
LAVATORY
AMERICAN
LUCERNE
AMERICAN
RELIANT
2"
1.1/2"
1/2"
1/2"
4, 5, 10
SD
SUPPLY DIFFUSER
ADA
STANDARD
#0355.012, WHITE
STANDARD
#7385.050
FIRE ALARM CONTROL PANEL
SMD
SMOKE DETECTOR
FCU
FAN COIL UNIT
SR
FD -1
FLOOR DRAIN
JAY R. SMITH
2O05A-P050
-
-
3"
1-1/2"
-
-
9
UH
FCO
FLOOR CLEAN
JAY R. SMITH
SERIES 4000 TO
VOLT
FSD
FIRE SMOKE DAMPER
VA
-
-
7
VAC
VOLT ALTERNATING CURRENT
OUT
HOT
SUITE FLOOR FINISH
VARIABLE AIR VOLUME
HAC
HEATED AIR CURTAIN
VD
VOLUME DAMPER
HOA
HAND OFF AUTO
WAP
EWH-1
POINT -OF -USE
CHRONOMITE
M -20L/208
-
L
-
WUH
3/8
3/8
6
X
TRANSFORMED
WATER HEATER
MINIMUM OR MODULATING DAMPER
XMFR
TRANSFORMER
MIN
MINIMUM
WMS
WIRE MESH SCREEN
NOTES:
1.
PROVIDE WITH BEMIS MANUFACTURING MODEL 1955SSC STANDARD WHITE OPEN FRONT SEAT.
2.
PRESSURE ASSISTED TANK TYPE.
3.
FURNISH RIGHT AND LEFT HAND MODELS AS REQUIRED PER ADA.
4.
PROVIDE WITH JAY R. SMITH #0700 FLOOR MOUNT CONCEALED -ARM LAVATORY CARRIER.
S.
PROVIDE WITH TRUEBRO LAV GUARD.
6.
20 AMPS, 208 VOLT SINGLE PHASE, 4160 WATTS, 57°F TEMPERATURE RISE @ 0.5 GPM.
7.
PROVIDE POLISHED NICKEL BRONZE COVER WITH ZARB-1470-A CLEANOUT PLUG.
8.
CAST IRON CLEANOUT TEE WITH STAINLESS STEEL ROUND COVER. PLUG TO BE GAS AND WATERTIGHT.
9.
PROVIDE FLOOR DRAIN WITH 1/2" TRAP PRIMER AND ACCESS DOOR IN WALL FOR ACCESS.
10. PROVIDE LEONARD 270 THERMOSTATIC MIXING VALVE, ASSE 1017 AND ASSE 1070 RATED.
VENTILATION RATE SCHEDULE
Mechanical Ventilation Schedules
Based upon ASHRAE 62.1, 2007
1z:1
Roorn Name
Classification
Room Area
(sq.ft.)
Area OA Rate
(cfm/sq.ft.)
Default Occupancy
(4/1000 sq.ft.)
Occupancy
(#)
People OA Rate
(cfm/person)
Total OA
(cfin)
Sales Area
Sales
804
0.12
15
12
7.5
187
Storage
Storage Room
86
0.12
-
-
-
10
Restroom (1 fixture)
Restroorn
64
-
-
-
-
-
PT
Total (square feet)
1 954
2. 1/2" X 1/2" X 1/2" EGGCRATE RETURN AIR GRILLE.
RA
197
LANDLORD NOTES
I ANY CHANGES AND/ OR UPGRADES TO TENAN'T'S EXISTING
MECHANICAL SYSTEMS SHALL COMPLY WITH ALL CODES AND
MALL CRITERIA. EXISTING SYSTEMS SHALL POSSESS THE
CAPACITY TO HANDLE ANY AND ALL CHANGES IN LOAD.
2. NO PITCH POCKETS ARE PERMITTED ON THE ROOF FOR ANY
CONDENSATE DRAINS, REFRIGERANT PIPING, POWER, OR
CONTROL WIRING. ALL CONNECTIONS ARE TO BE MADE
INSIDE THE EQUIPMENT CURB OR THROUGH
PRE -MANUFACTURED PIPING CURB.
3. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED
FROM, OR PENETRATE THE ROOF DECK. YOU MAY ATTACH TO
OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE
STRUCTURAL STEEL WHICH EXISTS ABOVE THE TENANT
SPACE.
4. ALL PENETRATIONS TO ROOF MUST BE APPROVED BY
LANDLORD. ALL RELATED ROOF WORK MUST BE DONE BY THE
MALL'S DESIGNATED ROOFING CONTRACTOR AT TENANT'S
EXPENSE. COORDINATE ALL WORK WITH PROPERTY
MANAGEMENT ON SITE.
S. TENANT MUST REMOVE ALL ABANDONED ROOFTOP AND/ OR
MECHANICAL EQUIPMENT ABOVE THE LEASED PREMISES AND
WITHIN THE LEASE PREMISES, AT TENANTS EXPENSE. PATCH
AND REPAIR ROOF AS NEEDED.
6. T'ENANT'S GC TO LABEL ALL ROOF TOP EQUIPMENT WITH
TENANT NAME SPACE NUMBER AND EQUIPMENT
IDENTIFICATION (I.E. RTU -1, EF -1), PER MALL SPECIFICATIONS/
STANDARDS.
7. ALL PIPING_ ON ROOF SHALL BE SUPPORTED ON
PRE -MANUFACTURED PIPE SUPPORTS INSTALLED ON CARRY
TREAD, SPACED PROPERLY TO SUPPORT PIPING. TREATED
WOOD SUPPORTS ARE NOT PERMITTED.
8. ALL UNEXPOSED SUPPLY AIR AND OUTSIDE AIR DUCTWORK
SHALL BE EXTERNALLY INSULATED WITH 1-1/2" THICK FOIL
FACE INSULATION. INTERNALLY LINED DUCTWORK MAY BE
USED FOR ACOUSTIC PURPOSES ONLY, NOT AS A SUBSTITUTE
FOR EXTERNAL INSULATION.
9. ALL DUCTWORK SHALL BE SHEET METAL. FLEX DUCT MAY
ONLY BE USED IN RUNS OF 54" OR LESS.
10. AT CONCLUSION OF PROJECT, HVAC SYSTEM MUST BE
TESTED AND BALANCED BY A LICENSED CONTRACTOR, COPY
OF BALANCE REPORT MUST BE PROVIDED TO PROPERTY
MANAGEMENT OFFICE ON SITE.
,, _z
R 0 01
EF -1/7\
90
- LAV -1
C9A/LJ A / f,
DRAWING LEGEND
1z:1
SUPPLY DIFFUSER
0
RETURN GRILLE / REGISTER
, TAG
MODEL
SD -1
AIR DEVICE DESIGNATION
150
TYPE
'�F-- CFM
AUX
AUXILLIARY
EXHAUST FAN / LIGHT COMBO
Q
THERMOSTAT
®
SPRINKLER HEAD
(E)
EXISTING TO REMAIN
(R)
EXISTING TO BE RELOCATED
(N)
NEW
M101MECHANICAL PLAN
®" SCALE: 1/4"=1'-0"
AIR DEVICE SCHEDULE
TAG
MOUNTING
I DESCRIPTION
FINISH
MANUFACTURER
MODEL
SIZE
NOTES
ANALOG OUTPUT
TYPE
NORMALLY CLOSED
AUX
AUXILLIARY
NO.
NORMALLY OPEN
AWG
SD -1
LAY -IN
SUPPLY
WHITE
TITUS
OMNI
24x24
1
RG -1
LAY -IN
RETURN
WHITE
TITUS
5OF
2424
2
NOTES:
PT
1. PROVIDE AG -75 DAMPER.
CV
2. 1/2" X 1/2" X 1/2" EGGCRATE RETURN AIR GRILLE.
AHU
AIR HANDLING UNIT
MOD
MODULATING
Al
ANALOG INPUT
N
NEUTRAL
AO
ANALOG OUTPUT
NO
NORMALLY CLOSED
AUX
AUXILLIARY
NO
NORMALLY OPEN
AWG
AMERICAN WIRE GAUGE
OA
OUTDOOR AIR
CD
CONTROL DAMPER
OL
OVERLOAD
COM
COMMON
OVR
OVERRIDE
CU
CONDENSING UNIT
PC
PHOTOCELL
CV
CONTROL VALVE
PT
PROGRAMMABLE THERMOSTAT
CV
VALVE COEFFICIENT
RA
RETURN AIR
CWR
CONDENSER WATER RETURN
RD
RETURN DIFFUSER
CWS
CONDENSER WATER SUPPLY
RES
RESISTOR
DC
DIRECT CURRENT
RG
RETURN GRILLE
DI
DIGITAL INPUT
RTU
ROOFTOP UNIT
DO
DIGITAL OUTPUT
RVR
REVERSING VALVE, RELAY
EA
EXHAUST" AIR
S
TEMPERATURE SENSOR
EF
EXHAUST FAN
SD
SUPPLY DIFFUSER
EOL
END OF LINE
SEF
SMOKE EXHAUST FAN
FACP
FIRE ALARM CONTROL PANEL
SMD
SMOKE DETECTOR
FCU
FAN COIL UNIT
SR
SUPPLY REGISTER
FD
FIRE DAMPER
TC
TIME CLOCK
FDM
FLOW DISPLAY MODULE
TDM
TEMPERATURE DISPLAY MODULE
FM
FLOW METER
UH
UNIT HEATER
FPB
FAN POWERED BOX
V
VOLT
FSD
FIRE SMOKE DAMPER
VA
VOLT" AMPERE
OND
GROUND
VAC
VOLT ALTERNATING CURRENT
H
HOT
VAV
VARIABLE AIR VOLUME
HAC
HEATED AIR CURTAIN
VD
VOLUME DAMPER
HOA
HAND OFF AUTO
WAP
WIRELESS ACCESS POINT
HR
HEATING RELAY
WSHP
WATER SOURCE HEAT PUMP
L
LINE VOLTAGE
WUH
WALL UNIT HEATER
LS
LIQUID SENSOR
X
TRANSFORMED
MD
MINIMUM OR MODULATING DAMPER
XMFR
TRANSFORMER
MIN
MINIMUM
WMS
WIRE MESH SCREEN
d
r
CHANGES TO THE DESIGN OF ANY SYSTEM IDENTIFIED ON
THESE DRAWINGS OR SPECIFICATIONS SHALL BE SUBMITTED
TO THE ENGINEER OF RECORD FOR REVIEW AND APPROVAL
PRIOR TO THE FABRICATION AND INSTALLATION. ANY
MODIFICATIONS WITHOUT THE ORIGINATING ENGINEER'S
WRITTEN AUTHORIZATION AND APPROVAL SHALL BE THE
RESPONSIBILITY, AS WELL AS THE COST TO CORRECT SUCH
MODIFICATION, OF THE CONTRACTOR.
GENERAL NOT S:
1.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTING CONDITIONS PRIOR TO
SUBMITTING A BID. SUBMISSION OF A BID SERVES AS EVIDENCE THAT THE CONTRACTOR HAS
No 43722
VISITED THE SITE AND HAS ACCOUNTED FOR ALL EXISTING CONDITIONS IN THE BID.
2.
BEFORE COMMENCING ANY WORK, CONTRACTOR SHALL REVIEW THE MOST RECENT NATIONAL,
2.
STATE, AND LOCAL CODE REQUIREMENTS, AND PERFORM THE WORK IN STRICT" ACCORDANCE WITH
It STATF rn.92
('HESE.
3.
CONTRACTOR IS REQUIRED TO READ THE SPECIFICATIONS AND REVIEW THE DRAWINGS FOR ALL
DIVISIONS OF WORK AND IS RESPONSIBLE FOR THE COORDINATION OF THIS WORK AND THE WORK
OF ALL SUBCONTRACTORS WITH ALL DIVISIONS OF WORK.
4.
CONTRACTOR SHALL ADHERE TO LANDLORD SPECIFICATIONS AND TENANT DESIGN CRITERIA.
5.
CONTRACTOR SHALL PROVIDE ALL EQUIPMENT, MATERIAL, LABOR, AND SUPERVISION NECESSARY
TO COMPLETE THE WORK IN ACCORDANCE WITH THE SPECIFICATIONS AND STANDARDS AS
OUTLINED HEREIN.
6.
UPON COMPLETION OF THE WORK, CONTRACTOR SHALL VERIFY THE PROPER WORKING ORDER OF
THE SYSTEM(S) AND MAKE ANY ADJUSTMENTS AS REQUIRED.
7.
PROVIDE ALL LOW VOLTAGE CONTROL WIRING FOR THE TEMPERATURE CONTROL SYSTEM.
COORDINATE WITH THE ELECTRICAL CONTRACTOR FOR CONTROL SYSTEM CONDUIT AND POWER
�5
REQUIREMENTS. COORDINATE EXACT LOCATIONS WITH THE GC FOR ALL TEMPERATURE CONTROL
COMPONENTS.
8.
THE CONTRACTOR SHALL ENSURE THAT ALL EQUIPMENT, PIPING, AND DUCTWORK, NOT BEING USED
OR SHOWN TO REMAIN, IS FULLY REMOVED AND NOT ABANDONED. COORDINATE REQUIREMENTS
WITH GC AND LANDLORD. VERIFY SCOPE OF WORK WITH GC PRIOR TO BID AND INCLUDE ALL COSTS
IN BID.
9.
PROVIDE IDENTIFICATION FOR EQUIPMENT" LOCATED ON THE ROOF OR OUTSIDE OF THE DEMISED
PREMISES. PROVIDE STENCIL WITH A MINIMUM OF 4" HIGH BLACK SPRAY PAINTED LETTERS,
INDICATING TENANT'S NAME, HVAC UNIT NUMBER AND SPACE NUMBER. VERIFY ADDITIONAL
0
REQUIREMENTS WITH LANDLORD.
10.
ALL RETURN GRILLES IN CONSTRUCTION AREAS MUST BE COVERED WITH FILTER MEDIA WHILE
HVAC SYSTEM IS RUNNING. REPLACE FILTER MEDIA WHEN IT GETS DIRTY.
11.
CERTIFIED TAB CONTRACTOR TO REBALANCE NEW AND EXISTING AIR DEVICES TO CFM AS
DESIGNATED ON PLAN.
SPRINKLER GN L NOT
1.
FIRE PROTECTION PLANS, SPRINKLER DRAWINGS, MUST BE ENGINEERED AND WET SIGNED BY A
LANDLORD APPROVED, LICENSED REGISTERED FIRE PROTECTION CONTRACTOR IN THE LOCAL
No 43722
JURISDICTION. FINAL INSTALLATION MUST COMPLY WITH NFPA 13 AND STATE AND LOCAL
AUTHORITIES HAVING JURISDICTION.
2.
INSTALL SPRINKLER HEADS ABOVE AND BELOW DUCTWORK AND OTHER OBSTRUCTIONS AS
It STATF rn.92
REQUIRED BY NFPA 13. COORDINATE INSTALLATION OF HEADS WITH FIVAC CONTRACTOR AND GC.
3.
SPRINKLER HEAD LAYOUT IS A SUGGESTED LAYOUT AND/OR A REPRESENTATION OF THE
APPROXIMATE LOCATIONS OF EXISTING HEADS. COORDINATE SPRINKLER HEAD LAYOUT AND PIPE
ROUTING WITH ARCHITECTURAL PLANS, STRUCTURAL PLANS, HVAC CONTRACTOR, ELECTRICAL
CONTRACTOR, AND GC. THE FIRE SPRINKLER CONTRACTOR SHALL INCLUDE IN THE BID AND BE
RESPONSIBLE FOR THE EXACT QUANTITY OF SPRINKLER HEADS REQUIRED FOR COVERAGE AND
FINAL APPROVAL.
KEYED NOTES:
0
CONNECT NEW SANITARY LINE INTO THE EXISTING SANITARY SERVICE. PROVIDE ADDITIONAL
CLEANOUTS AS REQUIRED. FIELD VERIFY EXACT LOCATION AND SIZE OF SANITARY LINE AND
No 43722
INVERT PRIOR TO BID. THIS CONTRACTOR IS RESPONSIBLE FOR ANY CUTTING AND PATCHING OF
THE FLOOR THAT MAY BE REQUIRED AS IT RELATES TO THE PLUMBING SCOPE OF WORK. REFER
TO WASTE AND VENT RISER DIAGRAM AND PLUMBING SPECIFICATIONS FOR ADDITIONAL
It STATF rn.92
REQUIREMENTS.
CONNECT NEW COLD WATER LINE INTO THE EXISTING COLD WATER TAP. NOTIFY G.C. IF TAP IS
SMALLER THAN SHOWN. REFER TO WATER RISER DIAGRAM AND PLUMBING SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS. COORDINATE BACKFLOW PREVENTER REQUIREMENTS WITH
LANDLORD AND LOCAL AUTHORITY HAVING JURISDICTION. CONTRACTOR SHALL PURCHASE
WATER METER AND REMOTE READER FROM LANDLORD'S TENANT COORDINATOR. INSTALL PER
LANDLORD AND LOCAL AUTHORITY'S REQUIREMENTS.
PROVIDE NEW THERMOSTAT FOR VAV-1. COORDINATE MAKE AND MODEL NUMBER WITH
LANDLORD TO TIE INTO EXISTING MALL DDC SYSTEM.
DEMOLISH EXISTING VAV BOX, VERIFY EXACT LOCATION IN THE FIELD. NEW VAV BOX TO BE
INSTALLED IN LOCATION SHOWN. INSTALL VAV BOX IN ACCORDANCE WITH THE MANUFACTURER'S
GUIDELINES AND MAINTAIN ALL REQUIRED SERVICE CLEARANCES.
�5
CONNECT NEW MEDIUM PRESSURE DUCT TO EXISTING; LANDLORD SUPPLY DUCT SYSTEM. VERIFY
EXACT LOCATION IN THE FIELD PRIOR TO VAV BOX INSTALLATION.
6
PRIOR TO BID, CONTRACTOR SHALL VISIT THE SITE AND FIELD VERIFY THE EXISTING CONDITIONS
OF THE SPRINKLER SYSTEM AND DETERMINE EXACT SCOPE/EXTENT OF SPRINKLER
MODIFICATIONS WITH LANDLORD AND LOCAL FIRE MARSHAL. INCLUDE ALL COSTS IN BID FOR
REQUIRED SPRINKLER MODIFICATIONS. EXISTING SPRINKLER HEADS IN EXISTING CEILINGS CAN
BE REUSED WHERE APPROPRIATE. NEW SPRINKLER HEADS SHALL BE INSTALLED IN NEW CEILING_;
OR IN OPEN STRUCTURE AREAS (STOCKROOM) AS REQUIRED. PROVIDE NEW SPRINKLER PIPE AS
NEEDED. ENSURE PROPER COVERAGE PER NFPA 13.
0
EXISTING RETURN AIR TRANSFER GRILLE THRU DEMISING WALL SHALL BE REUSED. VERIFY EXACT
LOCATION IN THE FIELD. VERIFY EXISTING FIRE DAMPER IS IN COMPLETE WORKING ORDER.
REPAIR OR REPLACE AS REQUIRED.
PROVIDE NEW POINT OF USE ELECTRIC WATER HEATER. INSTALL AND MAKE PIPING CONNECTIONS
PER DETAIL M2-01 ON SHEET M2 AND MANUFACTURER INSTALLATION INSTRUCTIONS.
0
NEW CEILING EXHAUST FAN/LIGHT COMBO BY ELECTRICAL CONTRACTOR. FAN CONTROL SHALL
BE WIRED THROUGH THE LIGHT SWITCH SERVING THE RESTROOM. COORDINATE INSTALLATION
WITH ELECTRICAL CONTRACTOR. EXTEND 6"0 DUCT FROM THE NEW EXHAUST FAN AND CONNECT
TO EXISTING MALL EXHAUST SYSTEM. VERIFY EXACT LOCATION IN THE FIELD.
10
EXTEND NEW VENT PIPING TO MALL VENT SYSTEM. VERIFY MALL VENT SYSTEM LOCATION IN THE
FIELD PRIOR TO WORK. REFER TO WASTE AND VENT" RISER DIAGRAM AND PLUMBING
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
LANDLORD NOTES:
1. G.C. SHALL VERIFY TRANSFER AIR OPENINGS EXIST AND MEET
MALL CRITERIA FOR VAV/HVAC COMPLIANCE.
2. GC. SHALL UTILIZE A LL APPROVED CONTRACTOR FOR ALL
INTERFACE CONNECTIONS TO CURRENT MALL JOHNSON EMS
SYSTEM. CONTACT MALL OPERATIONS TO VERIFY.
3. EXTERNALLY INSULATED FLEXIBLE DUCT, NOT TO EXCEED 5'-0"
IN LENGTH, MAY BE USED FOR VERI-( CAL CONNECTIONS TO
SUPPLY DIFFUSERS ONLY.
4. EXTERNAL FOIL WRAP INSULATION IS MANDATORY FOR ALL
SUPPLY AIR DUCT WORK IN CLOSED CEILING AREAS AND NOT
IN LIEU OF INTERNAL DUCT LINER.
LANDLORD NOTES:
1. NO PVC OR PEX ABOVE GRADE.
2. PLUMBING IS NOT PERMITTED IN LANDLORDS DEMISING
WALLS. FURR OUT WALLS WHEN NECESSARY.
3. ALL TOILET ROOMS TO HAVE FLOOR DRAINS WITH TRAP
PRIMERS.
4. G.C. TO COORDINATE ALL FLOOR CUTS AND CONNECTIONS TO
LL WATER AND SANITARY MAINS WITH MALL OPERATIONS.
V%d PARTNERS
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE #B11C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
R N
No 43722
%
0
It STATF rn.92
; sft A
NOV 20 2013
ISSUE DATES
PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
Q PERMIT SET: 11-20-2013
REVISIONS
0
DRAWING NUMBER
i�
i. ,z ,sr, <, , .,x. „� .. > ::. i' 3 ro.x �..�.a .,,.,+.a . ,a.. , ,r x»x. ,� „ r,... . a . . „ar.. , ,,, ,.., ,��r , .. „ .. . ... ... .... .. ., .. ,..
. ; . re r,'.: .,,',:i' r ; r ,;i,;, ,x..x., ,,, ,....w ........ .... .. .^. .,. .. ,,.r, .. a..,. �s r..,r ,. >„, ... .,,, ., a, Vii',.
i i I:,. ., .. .nom. .x r ,,,, +. .......... ...... ...
, „i .. . .. w..,r d x e... .:: ,I. .. A..,: ,,,.,..„..a .., �,w. .:: ..... .. .. .....::................ .. .. r ....... .....s r..„ ..xi.., .., Y .: r:'... .. . , .... .,
,,, ,... ,.....,...::; , : i ..:.... ...... Y,r+..,.,,i'.i w. r... .�^ .: ,,, .,. .... ,..,
WEATHER DATA
Design Parameters:
CityName..........................................................................................................
Orlando
CFM
Location..............................................................................................................
Florida
CFM
Latitude....................................................................................................................
28.4
Deg.
Longitude.................................................................................................................
81.3
Deg.
Elevation.............................................................
................................................. 105.0
ft
Summer Design Dry-Bulb........................................................................................
94.0
IF
Summer Coincident Wet-Bulb..................................................................................
76.0
IF
SummerDaily Range...............................................................................................
16.6
IF
Winter Design Dry-Bulb...........................................................................................
37.0
IF
Winter Design Wet-Bulb..........................................................................................
31.1
IF
Atmospheric Clearness Number..............................................................................
0.90
MBH
Average Ground Reflectance..................................................................................
0.20
CFM
Soil Conductivity....................................................................................................
0.800
BTU/(hr-ft-°F)
Local Time Zone (GMT +/- N hours)..........................................................................
5.0
hours
Consider Daylight Savings Time.................................................................................
No
1003 ft2 0
SimulationWeather Data..................................................................................
noneN/A
Current Data is......................................................................
2001 ASHRAE Handbook
Design Cooling Months...............................................................
January to December
gprn
HVAC LOAD CALCULATIONS
Air System Information
Air System Name ................................
BLOCK LOAD
CFM
Equipment Class ............................................
UNDEF
CFM
Air System Type ..................................................
VAV
CFM/ft2
Sizing Calculation Information
79,6/67.6
IF
Zone and Space sizing Method:
0
CFM
Zone CFM .......................... Peak zone
sensible load
CFM/ft2
Space CFM .................. Individual peak
space loads
IF
Central Cooling Coil Sizing Data
0.100
Zone
Total coil load .........................................................
1.9
Tons
Total coil load .......................................................
23.3
MBH
Sensible coil load .................................................
19.8
MBH
Coil CFM at Jan 1300 ............................................
944
CFM
Max block CFM .....................................................
944
CFM
Surn of peak zone CFM .........................................
944
CFM
Sensible heat ratio ..............................................
0.851
1003 ft2 0
11:2/Ton.................................................................
516.9
BTU/(hr-ft2)...........................................................
23.2
Water flow @ 10.0 IF rise .....................................
4.66
gprn
Supply Fan Sizing Data
Actual rnax CFM ....................................................
944
CFM
StandardCFM .......................................................
940
CFM
Actual max CFM/ft2...............................................
0.94
CFM/ft2
Outdoor Ventilation Air Data
79,6/67.6
IF
Design airflow CFM ...................................................
0
CFM
CFM/ft2.................................................................0.00
55.0/53.9
CFM/ft2
Number of zones.......................................................... 1
Floor Area............................................................ 1003.0 ft2
Location ............................................... Orlando, Florida
Calculation Months .......................................
Jan to Dec
Design
Sizing Data ..............................................
User -Modified
Maximum
Load occurs at .................................................
Jan 1300
HEATING DATA AT DES HTG
HEATING OA DB / WB 37.0 'F / 31.1 IF
OADB/WB...................................................
79,6/67.6
IF
Entering DB / WB ...........................................
74.5/62.5
IF
Leaving DB / WB ...........................................
55.0/53.9
IF
CoilADP..................................................................
52.8
IF
Bypass Factor........................................................
0.100
Zone
ResultingRH..............................................................
52
%
Design supply temp .................................................
55.0
IF
Zone T -stat Check ..............................................
f) of 1
OK
Max zone temperature deviation ..................
944
213
Fan motor BHP ........................................................ 0.10 BHP
Fan motor kW .......................................................... 0.08 kW
Fanstatic................................................................. 0.75 in wg
CFM/person........................... ..................... I............ 0.00 CFM/person
HVAC LOAD CALCULATIONS
Air System Information
Air System Narne................................ BLOCK LOAD
Equipment Class ............................................ UNDEF
Air System Type .................................................. VAV
Sizing Calculation Information
Zone and Space Sizing Method:
Zone CFM .......................... Peak zone sensible load
Space CFM .................. Individual peak space loads
Zone Sizing Data
Number of zones........................................................... 1
Floor Area........................................................... 1003.0 ft%
Location ............................................... Orlando, Florida
Calculation Months ....................................... Jan to Dec
Sizing Data ............................................. User -Modified
Zone Terminal Sizing Data
No Gone '? errninai Sizing Datarequired for this ,3ysten'l.
Space Loads and Airflows
Zone Name /
Space Name
Maximum
Design
Minimum
Time
Maximum
Zone
Zone 7
HEATING DATA AT DES HTG
HEATING OA DB / WB 37.0 'F / 31.1 IF
Cooling
Air
Air
of
Heating
Floor
1
13.0
Sensible
Flow
Flow
Peak
Load
Area
Zone
Zone Name
(MBH)
(CFM)
(CFM)
Load
(MBH)
(ft2)
CFM/ft2
Zone 1
17.3
944
213
Jan 1900
0.0
1003.0
0.94
Zone Terminal Sizing Data
No Gone '? errninai Sizing Datarequired for this ,3ysten'l.
Space Loads and Airflows
Zone Name /
Space Name
Mult.
Cooling
Sensible
(MBH)
Time Air
of Flow
Load (CFM)
Heating
Load
(MBH)
Floor
Area
(ft2)
Space
CFM/ft2
Zone 7
HEATING DATA AT DES HTG
HEATING OA DB / WB 37.0 'F / 31.1 IF
ZONE LOADS
Sensible Latent
Details (BTU/hr) (BTU/hr)
Sensible Latent
Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads
Sales
1
13.0
Jan 1900 709
0.0
799.0
0.89
Stock Room
1
3.9I
Jan 21001 211
0.0
144.0
1.46
Restroom
1
0.51
Jan 21001 25
0.0
60,0
0.42
["_� -
3/4"
1/2" 3/4"
1/2"
LAV -'1
EWH-1 1/2"
WC -1 1/2"
(TO TRAP PRIMER)
WATER RISER
M2.04 SCALE: NTS
SECTIONS
SIDE VIEWS
5/16" DIA. ALL THREAD
SECURED TO STRUCTURE
ABOVE.
ROUND RIGID DUCT
(SPIRAL SEAM)
1 1/2" WIDE, 16 GA.
SUPPORT STRAP WITH 61-0"
MAX. SPACING, WITH
WASHERS AND LOCK
NUTS.
SUPPORT WIRE SECURED
TO STRUCTURE ABOVE.
ROUND RIGID DUCT
(LOGITUDINAL SEAM)
1" WIDE, 18 GA. SUPPORT
STRAP WITH 5'-0" MAX.
SPACING.
SUPPORT WIRE SECURED
TO STRUCTURE ABOVE.
FLEXIBLE DUCT, 5'-0"
MAXIMUM LENGTH
2" WIDE SUPPORT STRAP
WITH 3'-0" MAX. SPACING.
ROUND DUCT SUPPORT
M21-,®2 SCALE: NTS
LANDLORD PLUMBING NOTES:
1. ANY CHANGES AND/ OR UPGRADES TO TENANT'S EXISTING
PLUMBING SYSTEMS SHALL COMPLY WITH ALL CODES AND
MALL CRITERIA. EXISTING SYSTEMS SHALL POSSESS THE
CAPACITY TO HANDLE ANY AND ALL CHANGES IN LOAD.
2. ALL WATER LINES SHALL BE COPPER - PVC IS NOT PERMITTED.
THERE SHALL BE NO PIPING JOINTS OR FITTINGS INSTALLED IN
WATER PIPING BELOW THE FLOOR SLAB.
3. ALL DRAIN, WASTE AND VENT FITTINGS ABOVE GRADE MUST BE
CAST IRON PIPE.
4. PLUMBING IS NOT PERMITTED IN ANY DEMISING PARTITIONS.
FURR OUT THE WALL AS NECESSARY.
5. EXHAUST AND PLUMBING VENTS SHALL BE LOCATED A MINIMUM
OF 10'-0" FROM ANY OUTSIDE AIR INTAKE, AND 5'41 FROM ANY
DEMISING WALL VERTICAL PLANE.
6. ALL FLOOR DRAINS ARE REQUIRED TO HAVE TRAP PRIMERS.
7. COORDINATE ALL CONCRETE TRENCHING/ CORING TO ENSURE
THAT ANY UNDER SLAB UTILITIES, ETC., ARE NOT DAMAGED
DURING FLOOR CUT. ANY DAMAGES TO BE REPAIRED AT
TENANTS EXPENSE. PRIOR TO APPROVAL AND COORDINATION
WITH PROPERTY MANAGEMENT IS REQUIRED FOR ALL
CONCRETE CUTTING.
8. ANY UNUSED PLUMBING EQUIPMENT, PIPING, ETC., WITHIN OR
SERVING THE PREMISES MUST BE COMPLETELY REMOVED TO
POINT OF ORIGIN. DO NOT ABANDON IN PLACE.
9. ALL FLOOR PENETRATIONS MUST BE CORE BORED, SLEEVED,
GROUTED, SEALED AND MADE WATERPROOF. SLEEVES MUST
EXTEND A MINIMUM OF 4" AFF.
10. IF NOT ALREADY EXISTING, INSTALL A SHUT OFF VALVE ON
DOMESTIC WATER LINE INSIDE SPACE.
11. TENANT IS REQUIRED TO INS -PALL A WATERPROOF MEMBRANE
IN ALL WET AREAS OF THE SPACE. TENANT HALL USE A 30 MIL
POLYETHYLENE CLEAVAGE MEMBRANE (EQUAL TO NOBLESEAL
TS) INSTALLED PER MANUFACTURERS RECOMMENDATIONS
AND ANSI A108. MEMBRANE MUST BE EXTENDED UP THE WALL
A MINIMUM OF 4" OR EQUAL TO THE HEIGHT OF THE FLOOR
BASE.
LANDLORD NOTES:
1. NO PVC OR PEX ABOVE GRADE.
2. PLUMBING IS NOT PERMITTED IN LANDLORDS DEMISING
WALLS. FURR OUT WALLS WHEN NECESSARY.
3. ALL TOILET ROOMS TO HAVE FLOOR DRAINS WITH TRAP
PRIMERS.
4. G.C. TO COORDINATE ALL FLOOR CUTS AND CONNECTIONS TO
LL WATER AND SANITARY MAINS WITH MALL OPERATIONS.
2"
FCO LAV -1
FDA
WC -1 3..
2" 2rr
4" \ 0-/
4"
WASTE AND VENT RISER
M2.03 SCALE: NTS
(E) COLD WATER
DOWN IN CHASE
(E) VENT UP IN WALL
E LAV
1 COLD WATER TO
l FAUCET
1
HOT WATER TO
FAUCET -
3 -WAY ANGLE
STOP VALVE
`-(E) WASTE PIPE
DRAIN-----.,- FLOOR
PLUG
PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT
FIELD CONDITIONS. SET HEATER THERMOSTAT TO 104
DEGREES.
POINT OF USE WATER HEATER
M2=01 SCALE: NTS
"d PARTNERS
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE#1311C
SANFORD, FE 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
i
a�• No 43722 3'�
E
V s
CONAL
''�i+a�v't�+�
NOV 2 0 2013
ISSUE DATES
PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
PERMIT SET: 11-20-2013
REVISIONS
DRAWING NUMBER
MM 2
MECHANICAL
DETAILS
rl 11"', ,4 '.��; r�, a �. Boa v , a :x';':: a :: „ , , ,,, .::: ,: .. ':, ., x r.. „x„x .... . .. .... ..... ....... . .... .... ,.. ,..,... > . W ,, a.. ,, .a ...a. .,.:,.r ,..�, ,.,,,, ,,,. .,,. :.:„ ,,,, .:a,..., ,,,,,,, .., , ., ..,.: ,. ,. :......,.:... .. ,.. .. .,. . , ....., „.. .. .., .., : ,...,, .,..,,.. ., ,.., ... : <.,., .,..: x, ,,, .:. , :.,, : , .. . ,.,.. .., .. .a. x, ,,.:,, :. „, ,:, ,. ., ,., . ,.,. ,,.,, „ ... . ,..... ...,.. ,. .. ,....... < e,
DESIGN COOLING
DE(:,3IGN HEATING
COOLING DATA AT Jan 1300
COOLING OA DB / WB 79.6 IF / 67.6 IF
HEATING DATA AT DES HTG
HEATING OA DB / WB 37.0 'F / 31.1 IF
ZONE LOADS
Sensible Latent
Details (BTU/hr) (BTU/hr)
Sensible Latent
Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads
0 ft2 0
0 ft2 -
Wall Transmission
0 ft2 0
0 ft2 0
Roof Transmission
0 ft2 0
0 ft2 0
Window Transmission
0 ft2 0
0 ft2 0
Skylight Transmission
0 ft2 0
0 ft2 0
Door Loads
0 ft2 0
0 ft2 0
Floor Transmission
1003 ft2 0
1003 ft2 0
Partitions
0 ft2 0
0 ft2 0
Ceiling
0 ft2 0
0 ft2 0
Overhead Lighting
1059 W 2925
0 0
Task Lighting
1598 W 4341
0 0
Electric Equipment
1250 W
0 0
People
_4197
15 J 2498
3007
0 0
0
Infiltration
- 0
0
- 0
0
Miscellaneous
0
0
- 0
0
Safety Factor
15%/15% 2094
451
10% 0
0
>> Total Lone Loads
16055
3458
0
0
Zone Conditioning
- 19544
3458
- -1709
0
Plenum Wall Load
0% 0
-
0 0
Plenum Roof Load
0% 0
0 0
Plenum Lighting Load
0% 0
0 0
Return Fan Load
944 CFM 0
-
213 CFM 0
Ventilation Load
0 CFM 0
0
0 CFM 0
0
Supply Fan Load
944 CFM 283
-
213 CFM -99
Space Fan Coil Fans
- 0
- 0
Duct Heat Gain / Loss
0% 0
-
0% 0
>> Total System Loads
19827
3458
-1808
0
Central Cooling Coil
19827
3458
-1808
0
>> Total Conditioning
19827
3458
-1808
0
Key:
Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
Negative values are clg loads
["_� -
3/4"
1/2" 3/4"
1/2"
LAV -'1
EWH-1 1/2"
WC -1 1/2"
(TO TRAP PRIMER)
WATER RISER
M2.04 SCALE: NTS
SECTIONS
SIDE VIEWS
5/16" DIA. ALL THREAD
SECURED TO STRUCTURE
ABOVE.
ROUND RIGID DUCT
(SPIRAL SEAM)
1 1/2" WIDE, 16 GA.
SUPPORT STRAP WITH 61-0"
MAX. SPACING, WITH
WASHERS AND LOCK
NUTS.
SUPPORT WIRE SECURED
TO STRUCTURE ABOVE.
ROUND RIGID DUCT
(LOGITUDINAL SEAM)
1" WIDE, 18 GA. SUPPORT
STRAP WITH 5'-0" MAX.
SPACING.
SUPPORT WIRE SECURED
TO STRUCTURE ABOVE.
FLEXIBLE DUCT, 5'-0"
MAXIMUM LENGTH
2" WIDE SUPPORT STRAP
WITH 3'-0" MAX. SPACING.
ROUND DUCT SUPPORT
M21-,®2 SCALE: NTS
LANDLORD PLUMBING NOTES:
1. ANY CHANGES AND/ OR UPGRADES TO TENANT'S EXISTING
PLUMBING SYSTEMS SHALL COMPLY WITH ALL CODES AND
MALL CRITERIA. EXISTING SYSTEMS SHALL POSSESS THE
CAPACITY TO HANDLE ANY AND ALL CHANGES IN LOAD.
2. ALL WATER LINES SHALL BE COPPER - PVC IS NOT PERMITTED.
THERE SHALL BE NO PIPING JOINTS OR FITTINGS INSTALLED IN
WATER PIPING BELOW THE FLOOR SLAB.
3. ALL DRAIN, WASTE AND VENT FITTINGS ABOVE GRADE MUST BE
CAST IRON PIPE.
4. PLUMBING IS NOT PERMITTED IN ANY DEMISING PARTITIONS.
FURR OUT THE WALL AS NECESSARY.
5. EXHAUST AND PLUMBING VENTS SHALL BE LOCATED A MINIMUM
OF 10'-0" FROM ANY OUTSIDE AIR INTAKE, AND 5'41 FROM ANY
DEMISING WALL VERTICAL PLANE.
6. ALL FLOOR DRAINS ARE REQUIRED TO HAVE TRAP PRIMERS.
7. COORDINATE ALL CONCRETE TRENCHING/ CORING TO ENSURE
THAT ANY UNDER SLAB UTILITIES, ETC., ARE NOT DAMAGED
DURING FLOOR CUT. ANY DAMAGES TO BE REPAIRED AT
TENANTS EXPENSE. PRIOR TO APPROVAL AND COORDINATION
WITH PROPERTY MANAGEMENT IS REQUIRED FOR ALL
CONCRETE CUTTING.
8. ANY UNUSED PLUMBING EQUIPMENT, PIPING, ETC., WITHIN OR
SERVING THE PREMISES MUST BE COMPLETELY REMOVED TO
POINT OF ORIGIN. DO NOT ABANDON IN PLACE.
9. ALL FLOOR PENETRATIONS MUST BE CORE BORED, SLEEVED,
GROUTED, SEALED AND MADE WATERPROOF. SLEEVES MUST
EXTEND A MINIMUM OF 4" AFF.
10. IF NOT ALREADY EXISTING, INSTALL A SHUT OFF VALVE ON
DOMESTIC WATER LINE INSIDE SPACE.
11. TENANT IS REQUIRED TO INS -PALL A WATERPROOF MEMBRANE
IN ALL WET AREAS OF THE SPACE. TENANT HALL USE A 30 MIL
POLYETHYLENE CLEAVAGE MEMBRANE (EQUAL TO NOBLESEAL
TS) INSTALLED PER MANUFACTURERS RECOMMENDATIONS
AND ANSI A108. MEMBRANE MUST BE EXTENDED UP THE WALL
A MINIMUM OF 4" OR EQUAL TO THE HEIGHT OF THE FLOOR
BASE.
LANDLORD NOTES:
1. NO PVC OR PEX ABOVE GRADE.
2. PLUMBING IS NOT PERMITTED IN LANDLORDS DEMISING
WALLS. FURR OUT WALLS WHEN NECESSARY.
3. ALL TOILET ROOMS TO HAVE FLOOR DRAINS WITH TRAP
PRIMERS.
4. G.C. TO COORDINATE ALL FLOOR CUTS AND CONNECTIONS TO
LL WATER AND SANITARY MAINS WITH MALL OPERATIONS.
2"
FCO LAV -1
FDA
WC -1 3..
2" 2rr
4" \ 0-/
4"
WASTE AND VENT RISER
M2.03 SCALE: NTS
(E) COLD WATER
DOWN IN CHASE
(E) VENT UP IN WALL
E LAV
1 COLD WATER TO
l FAUCET
1
HOT WATER TO
FAUCET -
3 -WAY ANGLE
STOP VALVE
`-(E) WASTE PIPE
DRAIN-----.,- FLOOR
PLUG
PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT
FIELD CONDITIONS. SET HEATER THERMOSTAT TO 104
DEGREES.
POINT OF USE WATER HEATER
M2=01 SCALE: NTS
"d PARTNERS
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE#1311C
SANFORD, FE 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
i
a�• No 43722 3'�
E
V s
CONAL
''�i+a�v't�+�
NOV 2 0 2013
ISSUE DATES
PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
PERMIT SET: 11-20-2013
REVISIONS
DRAWING NUMBER
MM 2
MECHANICAL
DETAILS
rl 11"', ,4 '.��; r�, a �. Boa v , a :x';':: a :: „ , , ,,, .::: ,: .. ':, ., x r.. „x„x .... . .. .... ..... ....... . .... .... ,.. ,..,... > . W ,, a.. ,, .a ...a. .,.:,.r ,..�, ,.,,,, ,,,. .,,. :.:„ ,,,, .:a,..., ,,,,,,, .., , ., ..,.: ,. ,. :......,.:... .. ,.. .. .,. . , ....., „.. .. .., .., : ,...,, .,..,,.. ., ,.., ... : <.,., .,..: x, ,,, .:. , :.,, : , .. . ,.,.. .., .. .a. x, ,,.:,, :. „, ,:, ,. ., ,., . ,.,. ,,.,, „ ... . ,..... ...,.. ,. .. ,....... < e,
„. , ,...„ exR R , ..., .. .,.,x.,v„a :.,, eo ..+.a er � uveu„ .. e,, .., ,,w. ,, ,.. ..... ,
., r ,, vv ,:xx , cz.,., x ,, , .. ..ot ' ... , ., .. @ ^... .. . .w . . .^., r r w. s nr..rw. wtau....,,... ... .,, ,..,r
. , r . n„ ,. ,^, ,.,..r,e xr!4 4t ti.Ar rwxrw r.. rR<n, rr n..,,: a^w,w .,w., r ..r,.mu..w.w. r uu.. ..wrru,+lv,ru.u. , ....
1
.
DIVISION 15000 - MECHANICAL
SECTION 15001 - BASIC MECHANICAL REQUIREMENTS
A. GENERAL CONDITIONS
1. DRAWINGS AND GENERAL PROVISIONS OF CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY
CONDITIONS AND ALL OTHER SPECIFICATION SECTIONS, APPLY TO THIS AND THE OTHER SECTIONS OF DIVISION
15000.
2. THE CONTRACTOR FOR THIS WORK IS REQUIRED TO READ THE SPECIFICATIONS AND REVIEW DRAWINGS FOR ALL
DIVISIONS OF WORK AND IS RESPONSIBLE FOR THE COORDINATION OF THEIR WORK AND THE WORK OF THEIR
SUBCONTRACTOR'S WITH ALL DIVISIONS OF WORK. IT IS THIS CONTRACTOR'S RESPONSIBILITY TO PROVIDE THEIR
SUBCONTRACTORS WITH A COMPLETE SET OF BID DOCUMENTS.
3. THIS CONTRACTOR IS RESPONSIBLE FOR SCHEDULING THE COMPLETION AND INSPECTION OF THEIR WORK AND
THE WORK OF THEIR SUBCONTRACTORS WORK TO COMPLY WITH THE SCHEDULE AND THE PROJECT COMPLETION
DATE.
4. THIS CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTAL OF BID TO DETERMINE CONDITIONS AFFECTING
THE WORK ANY ITEMS WHICH ARE NOT COVERED IN THE BID DOCUMENTS OR ANY PROPOSED SUBSTITUTIONS
SHALL BE LISTED SEPARATELY AND QUALIFIED IN THE CONTRACTOR'S BID. SUBMITTAL OF BID SHALL SERVE AS
EVIDENCE OF KNOWLEDGE OF EXISTING CONDITIONS AND ANY MODIFICATIONS WHICH ARE REQUIRED TO MEET
THE INTENT OF THE DRAWINGS AND SPECIFICATIONS. FAILURE TO VISIT THE SITE DOES NOT RELIEVE THE
CONTRACTOR OF RESPONSIBILITY IN PERFORMANCE OF WORK.
5. REFER TO RESPONSIBILITY SCHEDULE ON THE ELECTRICAL DRAWINGS FOR INFORMATION IN REGARD TO
RESPONSIBILITY OF WORK OR ITEMS WHICH MAY AFFECT BID.
SECTION 16002 - GENERAL REQUIREMENTS
A. THIS CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, SERVICES, TOOLS, TRANSPORTATION,
INCIDENTALS AND DETAILS NECESSARY TO PROVIDE COMPLETE MECHANICAL SYSTEM AS SHOWN ON THE
DRAWINGS, CALLED FOR IN THE SPECIFICATIONS, AND AS REQUIRED BY JOB CONDITIONS. ALL WORK NOT
SPECIFICALLY NOTED AS BEING BY THE LANDLORD, OR TENANT SHALL BE PROVIDED BY THE ELECTRICAL
CONTRACTOR. CLOSELY COORDINATE THE ENTIRE INSTALLATION WITH LANDLORD, AND THE TENANT PROJECT
MANAGER AS REQUIRED,
B. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL OR
LABOR CALLED FOR IN ONE SHALL BE PROVIDED EVEN THOUGH NOT SPECIFICALLY MENTIONED IN BOTH. ANY
MATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS,
BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK OR WHICH IS USUALLY INCLUDED IN WORK OF
SIMILAR CHARACTER, SHALL BE PROVIDED AS PART OF CONTRACT.
C. WHERE THE DRAWINGS OR SPECIFICATIONS CALL FOR ITEMS WHICH EXCEED CODES OR THE LANDLORD'S
TENANT CRITERIA, THE CONTRACTOR IS RESPONSIBLE FOR FURNISHING AND INSTALLING THE SYSTEM WITH THE
MORE STRINGENT REQUIREMENTS AS DESIGNED AND DESCRIBED ON THESE DRAWINGS, UNLESS SPECIFICALLY
NOTED OTHERWISE.
D. ALL MECHANICAL WORK SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR OPERATING, SERVICING,
MAINTAINING AND REPAIRING. THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING SUFFICIENT SERVICE ACCESS
TO ALL EQUIPMENT.
E. ALL WORK SHALL BE PERFORMED IN A NEAT PROFESSIONAL MANNER USING GOOD ENGINEERING AND
CONSTRUCTION PRACTICES.
F. UNLESS SPECIFICALLY NOTED OTHERWISE, MATERIALS, PRODUCTS, AND EQUIPMENT, INCLUDING ALL
COMPONENTS THEREOF, SHALL BE NEW, UNDERWRITERS LAEORATORIES LISTED AND LABELED AND SIZED IN
CONFORMITY WITH REQUIREMENTS OF STATE AND LOCAL CODES, WHICHEVER IS MORE STRINGENT.
SECTION 15003 - CODES
A. ALL WORK SHALL CONFORM TO THE LANDLORDS' CRITERIA, THE STATE'S, COUNTY'S, CITY'S AND LOCAL CODES
AND ORDINANCES, SAFETY AND HEALTH CODES, NFPA CODES, ENERGY CODES AND ALL OTHER APPLICABLE
CODES AND REQUIREMENTS. THIS CONTRACTOR SHALL INQUIRE INTO AND COMPLY WITH ALL APPLICABLE
CODES, ORDINANCES, AND REGULATIONS. THIS CONTRACTOR SHALL INCLUDE ANY CHANGES REQUIRED BY
CODES IN THE BID AND IF THESE CHANGES ARE NOT INCLUDED IN THE BID, THEY MUST BE QUALIFIED AS A
SEPARATE LINE ITEM IN THE BID. AFTER CONTRACT IS ISSUED, NO ADDITIONAL COST DUE TO CODE ISSUES
SHALL BE REIMBURSED BY THE OWNER TO THE CONTRACTOR,
SECTION 15004 - LICENSES, PERMITS, INSPECTIONS & FEES
A. THIS CONTRACTOR SHALL OBTAIN AND PAY FOR ALL LICENSES, PERMITS, INSPECTIONS, AND FEES REQUIRED OR
RELATED TO THEIR WORK.
B. FURNISH TO THE TENANT'S PROJECT MANAGER ALL CERTIFICATES OF INSPECTION AND FINAL INSPECTION
APPROVAL AT COMPLETION OF PROJECT.
SECTION 15005 - TRADE NAMES, MANUFACTURERS AND SHOP DRAWINGS
A. WHERE TRADE NAMES AND MANUFACTURERS ARE USED ON THE DRAWINGS OR IN THE SPECIFICATIONS, THE
EXACT EQUIPMENT SHALL BE USED AS A MINIMUM FOR THE BASE BID. MANUFACTURERS CONSIDERED AS AN
EQUAL OR BETTER IN ALL ASPECTS TO THAT SPECIFIED WI'_L BE SUBJECT TO APPROVAL IN WRITING BY TENANT'S
PROJECT MANAGER THROUGH PRIOR SHOP DRAWING SUBMITTAL PROCESS, FOR ACCEPTANCE. THE USE OF ANY
UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO REMOVAL AND REPLACEMENT AT THE CONTRACTOR'S
EXPENSE.
SECTION 15010 - CUTTING AND PATCHING
A. THE CONTRACTOR SHALL PERFORM ALL CUTTING AND PATCHING AS REQUIRED FOR THE INSTALLATION OF THE
WORK UNDER THIS SPECIFICATION. NO CUTTING OF THE STRUCTURE SHALL BE PERMITTED WITHOUT WRITTEN
APPROVAL OF THE LANDLORD AND ARCHITECT OR ENGINEER.
B. PATCHING SHALL BE OF THE SAME WORKMANSHIP, MATERIAL AND FURNISH AND SHALL MATCH ACCURATELY ALL
SURROUNDING CONSTRUCTION IN A MANNER SATISFACTORY TO THE ARCHITECT AND TENANT'S PROJECT
MANAGER.
C. EXISTING UTILITIES, ETC, THAT ARE DAMAGED DURING THE CONSTRUCTION PERIOD, WHETHER OR NOT DUE TO
THE CONTRACTOR'S NEGLIGENCE SHALL BE REPAIRED OR REPLACED BY THE CONTRACTOR AND LEFT IN A
CONDITION SUITABLE TO THE LANDLORD AND TENANT'S PROJECT MANAGER.
SECTION 15011 - SLEEVES
A. THIS CONTRACTOR SHALL PROVIDE SLEEVES TO PROJECT EQUIPMENT OR FACILITIES IN THE INSTALLATION.
EACH SLEEVE SHALL EXTEND THROUGH IT'S RESPECTIVE FLOOR, WALL OR PARTITION AND SHALL BE CUT FLUSH
WITH EACH SURFACE EXCEPT SLEEVES THAT PENETRATE THE FLOOR, WHICH SHALL EXTEND 2" ABOVE THE
FLOOR. CONTRACTOR MUST COORDINATE THROUGH THE LANDLORD ANY CORE DRILLING OR CUTTING OF
OPENINGS IN MASONRY FLOORS OR WALLS.
B. ALL SLEEVES AND OPENINGS THROUGH FIRE RATED WALLS AND/OR FLOORS SHALL BE FIRE SEALED WITH
CALCIUM SILICATE, SILICONE "RTV" FOAM, "3M" FIRE RATED SEALANTS OR EQUAL, SO AS TO RETAIN THEIR FIRE
RATING.
C. SLEEVES IN BEARING AND MASONRY WALLS, FLOORS AND PARTITIONS SHALL BE STANDARD WEIGHT STEEL PIPE
FINISHED WITH SMOOTH EDGES. FOR OTHER THAN MASONRY PARTITIONS, THROUGH SUSPENDED CEILINGS, OR
FOR CONCEALED VERTICAL CONDUIT, SLEEVES SHALL BE NO 22 U.S.G GALVANIZED STEEL MINIMUM.
SECTION 15012 - HANGERS
A. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, WIRE, UNISTRUT, C -CLAMPS WITH
RETAINING CLIPS, CHANNELS, HANGER RODS, ETC., NECESSARY FOR THE INSTALLATION OF WORK.
B. HANGERS SHALL BE FASTENED TO BUILDING STEEL, CONCRETE, OR MASONRY, BUT NOT TO PIPING. HANGING
FROM METAL DECK IS NOT PERMITTED. HANGERS MUST BE ATTACHED TO UPPER CHORD OF BAR JOIST. WHERE
INTERFERENCES OCCUR, AND IN ORDER TO SUPPORT DUCTWORK OR PIPING, THE CONTRACTOR MUST INSTALL
TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL BE LOCATED WHERE THEY DO NOT INTERFERE WITH
ACCESS TO FIRE DAMPERS, VALVES, AND OTHER EQUIPMENT. HANGER TYPES AND INSTALLATION METHODS ARE
ALSO SUBJECT TO LANDLORD CRITERIA,
C. HANGERS FOR ALL INSULATED PIPING SHALL BE SIZED AND INSTALLED FOR THE OUTER DIAMETER OF
INSULATION. INSTALL 6" LONG SPLIT CIRCLE GALVANIZED SADDLE BETWEEN THE HANGER AND THE PIPE
INSULATION.
D. HANGERS AND PIPING OF DISSIMILAR METALS SHALL BE DI -ELECTRICALLY SEPARATED.
DIVISION 15300 - FIRE PROTECTION (IF APPLICABLE)
SECTION 15301 - SUMMARY OF WORK
A. THIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT, ETC. NECESSARY FOR, REASONABLY
IMPLIED AND INCIDENTAL TO, THE FURNISHING, INSTALLATION, COMPLETION AND TESTING OF ALL THE WORK FOR
THE SPRINKLER SYSTEMS AS CALLED FOR IN THE SPECIFICATIONS, AND AS REQUIRED BY JOB CONDITIONS, TO
DE
IN LU BUT NOT BE LIMITED TO THE FOLLOWING:
INCLUDE,
1 r MODIFICATIONS TO EXISTING WET SPRINKLER SYSTEM AS REQUIRED TO PROVIDE COVERAGE IN ACCORDANCE,
NFPA-13, LOCAL CODES, AND LANDLORD'S CRITERIA.
2. TAPS, RISERS, LATERALS, BRANCHES, VALVES, ALARMS, SPRINKLER HEADS AND ALL COMPONENTS REQUIRED
FOR A COMPLETE SYSTEM.
3. DESIGN DRAWINGS, HYDRAULIC CALCULATIONS, SUBMITTALS AND APPROVALS.
4. PERMITS, FEES, INSPECTIONS AND CHARGES.
5. TESTS AND TEST CERTIFICATES.
6. IT IS INTENDED THAT THE CONTRACTOR SHALL PROVIDE A COMPLETE AND FUNCTIONAL SYSTEM..
B. THIS FIRE PROTECTION CONTRACTOR IS RESPONSIBLE FOR SUBMITTING COORDINATED DRAWINGS, HYDRAULIC
CALCULATION, HEAD TYPE AND COLORS TO ALL AUTHORITIES HAVING JURISDICTION FOR APPROVAL. NO WORK
SHALL BEGIN UNTIL ALL APPROVALS HAVE BEEN RECEIVED.
SECTION 16202 - MATERIALS
A. SPRINKLER HEADS:
1. ALL SPRINKLER HEADS SHALL BE NEW U.L., F.M. LISTED AND APPROVED AUTOMATIC SPRAY TYPE AS
MANUFACTURED BY GRINNELL, RELIABLE, STAR, OR VIKING.
2. ALL SPRINKLER HEADS SHALL BE RATED FOR 165°F UNLESS INDICATED OTHERWISE ON DRAWINGS OR REQUIRED
BY LOCAL CODES.
3. VERIFY HEAD TYPES AND COLORS WITH TENANT AND SUBMIT WITH SPRINKLER DRAWINGS FOR PERMIT.
4. LOCATIONS OF ALL HEADS SHOULD BE APPROVED BY TENANT AND THE LOCAL FIRE PROTECTION OFFICIAL
BEFORE INSTALLATION.
a. SALES/TOILET ROOMS AT GYP. BD. CLG - FULLY RECESSED WITH COVER PLATES TO MATCH GYP. BD. FINISH.
b. SALES AREA AT A.G.T. CLG. - SEMI -RECESSED CHROME WITH WHITE ESCUTCHEONS.
c. STOCKROOM/CORRIDOR -BRASS PENDANT.
d. STOREFRONT - FULLY RECESSED HEADS WITH COVER PLATES TO MATCH GYP. BD. FINISH.
B PIPING:
3. INTERIOR CONDENSATE PIPING SHALL BE TYPE "L" HARD DRAWN COPPER TUBE WITH 95-5 TIN -ANTIMONY
SOLDERED JOINTS AND WROUGHT COPPER FITTINGS WITH DIELECTRIC SEPARATION BETWEEN DISSIMILAR
METALS. EXTERIOR CONDENSATE PIPING MAY BE SCHEDULE 40 PVC PIPING WITH SOLVENT WELDED FITTINGS IF
APPROVED FOR USE BY THE LANDLORD.
C. POTABLE WATER PIPING
1. BELOW GRADE: TYPE W, ANNEALED TEMPERED COPPER TUBE FOR PIPE SIZES 2 INCHES AND SMALLER. BRAZE
ALL JOINTS.
2.ALL OTHER: TYPE'U HARD DRAWN COPPER TUBE WITH SWEAT JOINTS AND CAST WROUGHT COPPER FITTINGS
AND 95-5 TIN -ANTIMONY SOLDER.
D. PIPING OF DISSIMILAR METALS MUST BE DI -ELECTRICALLY SEPARATED.
E. INSULATE ALL HOT WATER, COLD WATER AND INTERIOR CONDENSATE PIPING WITH 1" THICK (K=0.23 @ 75"F) PIPE
INSULATION WITH AN ALL SERVICE JACKET TO MEET LOCAL CODES AND UL FLAME SPREAD AND SMOKE
DEVELOPED RATINGS. OWENS-CORNING OR EQUAL.
F. INSULATE THE TRAP, SANITARY AND SUPPLY PIPES UNDER LAVATORY WITH 1/2" ARMSTRONG "ARMAFLEX" PIPING
INSULATION OR TRUEBRO MODEL 102W WHITE "HAND LAV GUARD" INSULATION KIT TO COMPLY WITH ADA
REQUIREMENTS.
G. INSTALL AIR CHAMBER SHOCK ABSORBERS IN BOTH HOT AND COLD LINES OF PIPING SYSTEM TO PREVENT NOISE
AND DAMAGE DUE TO WATER HAMMER. SIOUX CHIEF 650 SERIES ALL STAINLESS STEEL, OR EQUAL. J.R. SMITH
"HYDROTROLS", INSTALLED IN AN UPRIGHT POSITION.
H. ALL BRANCH PIPING SYSTEM SHALL HAVE ACCESSIBLE SERVICE VALVE. PROVIDE SHUT OFF VALVES IN THE
SUPPLY PIPING TO EVERY FIXTURE. PROVIDE ACCESS DOORS WHERE NECESSARY.
1. INSTALL ALL NECESSARY PIPE HANGERS, SADDLES, AND CARRIERS TO PROPERLY SUPPORT ALL PIPING AND
FIXTURES. HANGERS SHALL SUIT TYPE OF PIPING INSTALLED AND BE SPACED AT A MAXIMUM SPAN OF 5 FEET.
PROVIDE SWAY AND SEISMIC BRACING WHERE REQUIRED BY CODES.
J. STERILIZE WATER SYSTEM IN ACCORDANCE WITH LOCAL CODES.
K. CLEAWOUTS AND FLOOR DRAINS SHALL BE INSTALLED PER LOCAL CODES. ALL FLOOR DRAINS SHALL HAVE DEEP
SEAL TRAPS. PROVIDE TRAP PRIMERS FOR FLOOR DRAINS.
L. ESCUTCHEONS SHALL BE CHROME PLATED, SIZE AS REQUIRED AND PLACED AT ALL PIPE PENETRATIONS AT
WALLS, FLOORS. AND CEILINGS IN FINISHED AREAS.
M. LEAKAGE TESTS SHALL BE PER LOCAL CODES.
N. FLASHING SHALL BE SEALED WATERTIGHT AND PERFORMED IN ACCORDANCE TO THE LANDLORD'S CRITERIA.
USE A LANDLORD APPROVED ROOFING CONTRACTOR WHERE APPLICABLE AND INCLUDE ALL COSTS IN BID.
0. PROVIDE WATER METER AND REMOTE READER PER LANDLORD'S CRITERIA OR LOCAL UTILITIES REQUIREMENTS
IF APPLICABLE. -.
P. GAS PIPING:
1. PROVIDE A COMPLETE GAS PIPING SYSTEM IF APPLICABLE. REFER TO PLANS TO DETERMINE IF A GAS SYSTEM IS
REQUIRED.
2. GAS LINES SHALL BE BLACK STEEL, SCHEDULE 40, ASTM A-120, WITH MALLEABLE THREADED FITTINGS FOR 2" AND
SMALLER, AND WITH WELDED JOINTS FOR 2-1/2" AND LARGER.
3. PROVIDE A GAS COCK, DIRT LEG, AND UNION CONNECTION TO EACH PIECE OF EQUIPMENT,
4. PITCH PIPING AT A UNIFORM GRADE OF 1/4" IN 15 FEET UPWARD IN DIRECTION OF FLOW. SUPPORT PIPING EVERY
5 FEET. SUPPORT AS REQUIRED BY LANDLORD CRITERIA, AS DETAILED ON DRAWINGS, OR BY STANDARD
INDUSTRY PRACTICE, WHICHEVER IS MORE STRINGENT.
5. GAS PIPING EXPOSED ON ROOF MUST BE PRIMED AND PAINTED WITH RUST -INHIBITING PAINT.
6. GAS PIPING INSTALLED IN RETURN AIR PLENUMS SHALL BE SLEEVED AND VENTED OR WELDED IN ACCORDANCE
WITH THE LOCAL GAS COMPANY, LOCAL CODE, AND APPLICABLE NFPA 54 CODES.
7. TESTING AND PURGING OF GAS PIPING SHALL BE DONE PER THE REQUIREMENTS OF THE LOCAL GAS COMPANY,
LOCAL CODES, AND APPLICABLE NFPA 54 CODES.
8. CONTACT AND COORDINATE GAS SERVICE AND METER REQUIREMENTS WITH THE LOCAL GAS COMPANY AND THE
MALL'S OPERATIONS MANAGER PRIOR TO BID. INCLUDE INSTALLATION OF GAS METER AND REGULATOR COSTS IN
BID.
DIVISION 15500 - HEATING, VENTILATING, AIR CONDITIONING
SECTION 15501 - SUMMARY OF WORK
A. THIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT, ETC. NECESSARY FOR, REASONABLY
IMPLIED AND INCIDENTAL TO, THE FURNISHING, INSTALLATION, COMPLETION AND TESTING OF ALL THE WORK FOR
THE HVAC SYSTEMS AS CALLED FOR IN THE SPECIFICATIONS, SHOWN ON DRAWINGS AND AS REQUIRED BY JOB
CONDITIONS, TO INCLUDE, BUT NOT BE LIMITED TO THE FOLLOWING:
1. NEW WATER SOURCE HEAT PUMP, EXISTING EXHAUST FAN, SUPPLY, RETURN AND EXHAUST DUCTWORK WITH ALL
CONTROLS AND ACCESSORIES SPECIFIED TO REMAIN.
2. THE AIR DEVICES AS NOTED ON THE PLANS SHALL BE PURCHASED BY THE CONTRACTOR. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR SCHEDULING, RECEIVING, VERIFYING QUANTITIES AND INSPECTING FOR DAMAGE
AND FILING OF ANY CLAIM FORMS. REFER TO RESPONSIBILITY SCHEDULE AND AIR DEVICE SCHEDULE ON PLANS.
3, ALL MATERIALS SHALL BE NEW AND SHALL FIT THE SPACE AVAILABLE. VERIFY ALL DIMENSIONS AT THE SITE.
4. ALL VALVES, DAMPERS, ETC. SHALL BE SO LOCATED AND INSTALLED TO PERMIT ACCESS FOR SERVICE WITHOUT
DAMAGE TO BUILDING OR FINISHED MATERIALS.
SECTION 15502 - MATERIALS
AS MINIMUM.
H: DUCTWORK INSULATION
1. INSTALL INSULATION PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S WRITTEN INSTRUCTIONS, AND IN
ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES. INSULATION MUST COMPLY WITH NFPA 90A.
2. DUCT SIZES SHOWN ON DRAWINGS ARE INSIDE CLEAR DIMENSIONS. ALL SUPPLY AND RETURN AIR DUCTWORK
SHALL BE EXTERNALLY INSULATED WITH 1 '/2" THICK, 1-1/2 LB. DENSITY DUCT WRAP WITH VAPOR BARRIER. VAPOR
BARRIER IS TO BE MAINTAINED THROUGHOUT DUCT SYSTEM. ALL JOINTS MUST BE TAPED SO THAT NO
INSULATION FIBER IS VISIBLE, EXTEND DUCTWORK INSULATION WITHOUT INTERRUPTION THROUGH WALLS,
FLOORS, AND SIMILAR PENETRATIONS.
3. ALL ROUND, MEDIUM PRESSURE AND OUTSIDE AIR DUCTWORK SHALL BE EXTERNALLY INSULATED WITH A
MINIMUM OF 2" THICJ, 1 LB. DENSITY (R=5.6) DUCT WRAP WITH VAPOR BARRIER. VAPOR BARRIER IS TO BE
MAINTAINED THROUGHOUT DUCT SYSTEM. ALL JOINTS MUST BE TAPED SO THAT NO INSULATION FIBER IS VISIBLE.
EXTEND DUCTWORK INSULATION WITHOUT INTERRUPTION THROUGH WALLS, FLOORS, AND SIMILAR
PENETRATIONS.
K. TESTING, ADJUSTING, AND BALANCING
1. CONTRACTOR SHALL BALANCE, ADJUST & TEST EQUIPMENT TO PROVIDE DESIGN AIR QUANTITIES AND ASSURE
PROPER OPERATION OF SYSTEMS. CONTRACTOR SHALL SUBMIT COPIES OF BALANCE/TEST REPORT TO
OWNER FOR REVIEW PRIOR TO COMPLETION OF PROJECT. IF A CERTIFIED TEST AND BALANCE REPORT IS
REQUIRED BY LANDLORD, CONTRACTOR SHALL COORDINATE ALL REQUIREMENTS WITH LANDLORD AND LOCAL
AUTHORITY HAVING JURISDICTION, CONTRACT DIRECTLY WITH AN APPROVED TESTING AND BALANCING
AGENCY, AND PROVIDE COMPLETE REPORT TO OWNER AND LANDLORD.
2. IF REQUIRED BY THE LANDLORD OR THE LOCAL AUTHORITY HAVING JURISDICTION THE BALANCE REPORT
SHALL BE ON THE AABC NATIONAL STANDARD REPORT FORMS OR THE NEBB CERTIFIED REPORT FORMS AS
PUBLISHED IN THEIR MOST CURRENT EDITIONS AND SHALL INCLUDE AS A MINIMUM TH EFOLLOWING
INFORMATION:
a. AABC OR NEBB CERTIFICATION NUMBER AND SIGNATURE OF BALANCING CONTRACTOR.
b. B. COPY OF A CERTIFICATE OF CONFORMANCE WITH NATIONAL STANDARDS FOR THIS PROJECT.
c. INSTRUMENTATION LIST WITH LAST CALLIBRATION DATES.
d. MAKE AND MODEL NUMBERS OF ALL HVAC EQUIPMENT TESTED.
e. AIR CFM AND STATIC PRESSURE READINGS (DISCHARGE AND SUCTION) AS MEASURED BY PITOT TUBE DUCT
TRAVERSE AT THE UNIT.
f. MONITOR NAMEPLATE DATA WITH ACTUAL FIELD VOLTAGE AND AMPERAGE READINGS FOR EACH LEG.
g. MOTOR AND FAN RPMS, SHEAVE SIZES AND BELT SIZES.
h. OUTSIDE, RETURN, MIXED AND SUPPLY AIR TEMPERATURES AND VOLUMES SHALL BE MEASURED AT FULL
COOLING WITH MINIMUM OUTSIDE AIR. RETURN/RELIEF/SMOKE EVACUATION AIRFLOW SHALL BE BALANCED
AND MEASUREMENTS RECORDED BY PITOT DUCT TRAVERSE AT FULL ECONOMIZER AND POWER EXHAUST.
L MAKE AND MODEL NUMBERS OF ALL AIR DISTRIBUTION EQUIPMENT.
j. FINAL BALANCED AIR VOLUMES AT ALL OUTLETS (INCLUDING RETURNS WHERE DUCTED).
k. INDEXED PLAN WITH DIFFUSED AND RETURN LOCATIONS. ALSO INDICATE IF DIFFUSER IS 3 -WAY OR 2 -WAY.
I. FINAL BALANCED GPM AT ALL UNITS FOR CHILLED/HOT/CONDENSER WATER WHEN APPLICABLE.
m.CHILLED/HOT/CONDENSER ENTERING AND LEAVING WATER TEMPERATURES WHEN APPLICABLE.
n. PRESSURE DROP THROUGH COILS AND CONTROL VALVES WHEN APPLICABLE.
3. IF REQUIRED BY THE LANDLORD OR THE LOCAL AUTHORITY HAVING JURISDICTION THE GENERAL CONTRACTOR
SHALL ARRANGE FOR THE TEST AND BALANCE A MINIMUM OF TWO WEEKS PRIOR TO THE REQUIRED DATE AFER
RETURNING TABC'S "START UP CHECK LIST". ALL WORK SHALL BE COMPLETED PRIOR TO SCHEDULING AIR
BALANCE. IN ADDITION, THE BALANCE CONTRACTOR WILL INSPECT AND PREPARE A FINAL PUNCH LIST. THE HVAC
CONTRACTOR SHALL REPAIR OR REPLACE ANY DEFECTIVE MATERIALS, EQUIPMENT OR WORKMANSHIP PRIOR TO
TENANT'S FINAL WALK THRU AND BEFORE FINAL PAYMENT WILL BE MADE.
4. FOUR COPIES OF THE BALANCE REPORT SHALL BE SUBMITTED TO TENANT AND FOUR COPIES TO THE LANDLORD
FOR APPROVAL.
5. OPERATION AND MAINTENANCE DOCUMENTATION MUST BE PROVIDED TO THE OWNER THAT INCLUDES AT LEAST
THE FOLLOWING INFORMATION:
a. EQUIPMENT CAPACITY (INPUT AND OUTPUT) AND REQUIRED MAINTENANCE ACTIONS.
b. EQUIPMENT OPERATION AND MAINTENANCE MANUALS.
c. HVAC SYSTEM CONTROL MAINTENANCE AND CALIBRATION INFORMATION, INCLDING WIRING DIAGRAMS,
SCHEMATICS, AND CONTROL SEQUENCE DESCRIPTIONS; DESIRED OR FIELD -DETERMINED SET POINTS MUST
BE PERMANENTLY RECORDED ON CONTROL DRAWINGS, AT CONTROL DEVICES, OR, FOR DIGITAL CONTROL
SYSTEMS, IN PROGRAMMING COMMENTS,
d. COMPLETE NARATIVE OF HOW EACH SYSTEM IS INTENDED TO OPERATE.
ALL PIPING SHALL WITHSTAND AIR PRESSURE TESTING PER GOVERNING PLUMBING CODE.
A. HYDRONIC PIPING
1. HYDRONIC PIPING FOR CHILLED WATER, CONDENSER WATER AND/OR HEATING WATER SHALL BE ASTM A-53,
SCHEDULE 40, ERW, BLACK STEEL PIPE WITH PLAIN ENDS. INSTALL STEEL PIPE WITH WELDED JOINTS WHERE PIPE
IS 2-1/2 INCH AND LARGER. INSTALL STEEL PIPE WITH THREADED JOINTS AND FITTINGS. INSTALL TYPE "K" COPPER
PIPE FOR 2 INCH AND SMALLER PIPE. PROVIDE DIELECTRIC UNIONS BETWEEN DISSIMILAR METALS. ALL PIPING
SHALL BE IN STRICT CONFORMANCE WITH ASTM, ASA, AND LANDLORD'S REQUIREMENTS. WHICHEVER IS MOST
STRINGENT, UNIONS OR FLANGES MUST BE USED AT EQUIPMENT CONNECTIONS WHERE SERVICE OR REMOVAL
MAY BE REQUIRED.
2. ALL PIPING AND EQUIPMENT SHALL BE PRESSURE TESTED WITHOUT LEAKAGE AT A MINIMUM PRESSURE OF 125
PSI.
3. ALL HYDRONIC PIPING AND EQUIPMENT CONNECTED TO THE HVAC PIPING SYSTEM SHALL BE CLEANED AND
FLUSHED. REMOVE, CLEAN, AND REPLACE STRAINER SCREENS. FILL TENANT'S SYSTEM WITH DOMESTIC WATER
AND VENT ALL PIPING AND EQUIPMENT PRIOR TO CONNECTION TO THE LANDLORD'S SYSTEM. CONTRACTOR
LL TENANT'S SYSTEM WITH WATER FROM THE LANDLORD'S SYSTEM UNLESS SPECIFICALLY
IWPARTNERS
brand: operations : build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
W DPARTN E RS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE #B11 C
SANFOR®, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
,iI
�3 ��W���
B. MECHANICAL CONTRACTOR SHALL SUBMIT ONLY SUBSTITUTION REQUESTS TO TENANT'S PROJECT MANAGER S 0 S G DED AND SEAMLESS,B-36-10-700 Ar REFER TO PLANS FOR SCHEDULES OF EQUIPMENT. ALL EQUIPMENT SHALL BE COMPLETE IN EVERY RESPECT SHALL NOT FI ,oe� ��..;RNlST �'.fs,
1. SCHEDULE 40, BLACK STEEL PIPE, A TM A-53 F R FERROU PIPIN , WEL N AMLE , ANSI F R INSTRUCTED TO DO SO FROM THE LANDLORDS FIELD REPRESENTATIVE. ANY RUNS THRU A CHASE OR SHAFT v' P ,.•
FOR APPROVAL. SUBMISSIONS SHALL BE MADE EARLY ENOUGH IN PROJECT TO ALLOW FOUR (4) WORKING DAYS WROUGHT STEEL PIPE. WITH ALL DEVICES APPURTENANCES, AND ACCESSORIES PROVIDED TO MEET THE DESIGN INTENT AND � �C•E•N19 41-. ®I
FOR TENANT'S PROJECT MANAGER'S REVIEW WITHOUT CAUSING DELAYS OR CONFLICTS TO THE JOB'S CAST IRON OR MALLEABLE IRON SCREWED FITTINGS FOR PIPES 2 INCHES AND SMALLER. SCREWED OR CAST OPERATION OF THE SYSTEMS SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN, EQUIPMENT SHALL BE WILL BE DONE WITH FEWEST JOINTS POSSIBLE USING THE LONGEST LENGTH OF HARD COPPER PIPE AVAILABLE. =` �C�; ,
PROGRESS. SUBMITTALS SHALL BEAR "THE STAMP OF GENERAL CONTRACTOR AND THE SUB -CONTRACTOR 2' SHOULD A JOINT BE REQUIRED, CONTRACTOR SHALL MAKE ALL EFFORTS TO KEEP THE JOINTS IN ACCESSIBLE;' No 43 722 >
IRON FLANGED JOINTS FOR PIPES LARGER THAN 2 INCHES. INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. ALL AIR CONDITIONING U� 1
SHOWING THAT THEY HAVE REVIEWED AND CONFIRMED THAT THE SUBMITTALS ARE IN CONFORMANCE WITH THE 3. GALVANIZED OR BLACK MELLEABLE IRON WITH BRASS SEAT SCREWED UNIONS FOR PIPES 2 INCHES AND EQUIPMENT MUST BE TRAPPED IN ACCORDANCE WITH MANUFACTURERS DATA. AREAS. -- * * r * = I
CONTRACT DRAWINGS AND SPECIFICATIONS OR INDICATE WHERE EXCEPTIONS HAVE BEEN TAKEN. _ �
SMALLER. 4. PRIOR TO CONNECTION TO THE LANDLORD'S SYSTEM, CONTRACTOR SHALL OBTAIN WRITTEN CONFIRMATION 17� 00
4. VICTAULIC TYPE COUPLINGS ARE ACCEPTABLE, WHERE APPROVED BY CODE AND THE LANDLORD. B. METAL DUCTWORK - NO FIBERGLASS DUCT ALLOWED. 1 AT
SECTION 15006 - GUARANTEE 1. EXCEPT AS OTHERWISE INDICATED FABRICATE AND INSTALL RECTANGULAR AND ROUND DUCTWORK WITH FROM 'TME LANDLORD'S FIELD REPRESENTATIVE, THAT ALL TESTING, FLUSHING, AND PROPER FILLING OF THE
5. HANGERS SHALL COMPLY WITH LANDLORD AND CODE REQUIREMENTS. TENANT'S SYSTEM HAS BEEN COMPLETED IN ACCORDANCE TO THE LANDLORD'S REQUIREMENTS AND THAT THE r3 ,> ` v'
GALVANIZED STEEL, IN ACCORDANCE WITH SMACNA 'HVAC DUCT CONSTRUCTION STANDARDS' OF THE LATEST �� S I � %
A. THIS CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORK PROVIDED UNDER THEIR CONTRACT AND EDITION.
TENANT's SYSTEM IS READY TO BE CONNECTED TO THE LANDLORD's SYSTEM. 6 "' F %o
SHALL MAKE GOOD, REPAIR OR REPLACE AT THEIR OWN EXPENSE, ANY DEFECTIVE WORK MATERIAL, OR C. SPRINKLER SPACING SHALL NOT EXCEED 130 SQ. FT. IN "SALES" AREAS AND 100 SQ. FT. IN "STOCK" AREAS. i��o�l N At 1�s
COMPLY WITH LANDLORD'S DESIGN CRITERIA. PIPE SIZING SHALL BE BASED ON NFPA ORDINARY HAZARD. 2. INSTALL TURNING VALVES IN ALL RIGHT ANGLE ELBOWS IN ALL DUCTS.
EQUIPMENT WHICH MAY BE DISCOVERED WITHIN A PERIOD OF 12 MONTHS FROM THE DATE OF ACCEPTANCE (IN 3. INSTALL RIGIT ROUND AND RECTANGULAR METAL DUCT WITH SUPPORT SYSTEMS INDICATED IN SMACNA 5. PRESSURE/TEMPERATURE TEST PLUGS (PETE S PLUG) - 1/4 INCH NPT FITTINGS TO RECEIVE EITHER A
WRITING) OF THE INSTALLATION BY THE TENANT'S PROJECT MANAGER. EXTENDED WARRANTIES ARE SPECIFIED STANDARDS. PROVIDE SWAY AND SEISMIC BRACING AS REQUIRED BY STATE AND LOCAL CODES OR BY TEMPERATURE OR PRESSURE PROBE, 1/8 INCH O.D. FITTING AND CAPS SHALL BE BRASS WITH VALVE CORE OF
WITH INDIVIDUAL EQUIPMENT. D. ALL SPRINKLER LINES SHALL BE INSTALLED CONCEALED, AVOIDING INTERFERENCE WITH OTHER TRADES. LANDLORD. NORDEL, RATED AT 400 PSIG, 0 TO 200 DEGREES F. r= NOV 2 0 201
E. WHERE POSSIBLE, REWORK THE EXISTING SPRINKLER SYSTEM TO MEET THE NEW REQUIREMENTS OF THIS 4. ALL JOINTS AND SEAMS SHALL BE SEALED WITH UNITED MCGILL DUCT SEALER OR EQUAL. 125 PSIG CAST IRON BODY WITH PERFORATED STAINLESS STEEL SCREEN,
SECTION 15007 RECORD DRAWINGS DESIGN AND INCLUDE ALL COSTS TO RAISE OR RELOCATE EXISTING PIPING TO OBTAIN CEILING HEIGHTS SHOWN a. ALL JOINTS, LONGITUDINAL AND TRANSVERSE SEAMS, AND CONNECTIONS IN DUCTWORK MUST BE SECURELY 6. STRAINERS - "Y" PATTERN STRAINERS,
ON DRAWINGS. IN NEW CONSTRUCTION THE LANDLORD MAY PROVIDE ONLY A STUB -IN TO THE SPACE. THE SEALED USING WELDMENTS; MECHANICAL FASTENERS WITH SEALS, CASKETS, OR MASTICS; MESH AND THREADED FOR 2 INCHES AND SMALLER, FLANGED FOR 2 112 INCHES AND LARGER. SCREEN OPENING SIZE AT
A. THIS CONTRACTOR SHALL MAIN -FAIN ONE COPY OF DRAWINGS ON THE JOB SITE TO RECORD DEVIATIONS FROM 0.033 INCH FOR HEATING AND 1/8 INCH FOR CHILLED OR CONDENSER WATER. PROVIDE WITH BLOWDOWN VALVEI ISSUE DATES
CONTRACT DRAWINGS, SUCH AS: CONTRACTOR SHALL CONNECT AND EXTEND NEW PIPING AS REQUIRED, VERIFY ALL REQUIREMENTS PRIOR TO MASTIC SEALING SYSTEMS; OR TAPES. TAPES AND MASTICS MUST BE LISTED AND LABELLED IN WITH HOSE END FITTING..10
BID. ACCORDANCE WITH UL 181A OR UL 1818. ALL LONGITUDINAL AND TRANSVERSE JOINTS, SEAMS AND PRELIM SET: 10-16-2013
1. LOCATION OF CONCEALED PIPING VALVES AND DUCTS. FINAL SET: 11-6-2013
2. REVISIONS, ADDENDUMS, AND CHANGE ORDERS. CONNECTIONS OF SUPPLY AND RETURN DUCTS OPERATING AT STATIC PRESSURE LESS THAN OR EQUAL TO B. HYDRONIC PIPING GENERAL INSTALLATION qll
D
F. PROVIDE AND INSTALL A VALVED TEST CONNECTION IN AN ACCESSIBLE LOCATION FOR THE SPRINKLER SYSTEM
3. SIGNIFICANT DEVIATIONS MADE NECESSARY BY FIELD CONDITIONS, APPROVED EQUIPMENT SUBSTITUTIONS, AND 2" W.G. SHALL BE SECURELY FASTENED AND SEALED WITH WELDS GASKETS, MASTICS (ADHESIVES), Q PERMIT SET: 11-20-2013
CONTRACTOR'S COORDINATION WITH OTHER TRADES. AS REQUIRED OR REQUESTED BY THE MALL, LOCAL INSPECTOR, OR TENANT'S INSURANCE CARRIER. MASTIC -PLUS -EMBEDDED FABRIC SYSTEMS OR TAPES INSTALLED IN ACCORDANCE WITH MANUFACTURER'S 1. INSTALL WATER MAINS WITHOUT PITCH. USE ECCENTRIC REDUCING COUPLINGS AT CHANGES IN SIZE WITH THE
TOP OF PIPES AT SAME ELEVATION.
G. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR DAMAGE CAUSED BY LEAKS IN ANY OF THE EQUIPMENT INSTALLATION INSTRUCTIONS. y
B. AT COMPLETION OF PROJECT AND BEFORE FINAL APPROVAL, THE CONTRACTOR SHALL MAKE ANY FINAL INSTALLED BY THEM. ALL REPAIRS OR REPLACEMENT OF DAMAGES SHALL BE AT THIS CONTRACTOR'S EXPENSE. b. MECHANICAL FASTENERS AND SEALS, MASTICS, OR GASKETS MUST BE USED WHEN CONNECTING DUCTS TO .
CORRECTIONS TO DRAWINGS AND CERTIFY THE ACCURACY OF EACH PRINT BY SIGNATURE THEREON. ONE COPY 2. BRANCHES TO UNITS BELOW MAINS TO BE TAKEN FROM BOTTOM OF MAINS AT A 45 DEGREE ANGLE, PITCH
FANS ND OTHER AIR DISTRIBUTION EQUIPMENT
OF THE MOST RECENT SET OF DRAWINGS WITH TEMPERATURE CONTROL DRAWINGS INCLUDED SHALL BE . DOWNWARD TOWARD UNITS. BRANCHES TO UNITS ABOVE MAINS TO BE TAKEN FROM TOP OF MAINS AT A 45 At
DELIVERED TO TENANT'S PROJECT MANAGER. H. PROPERLY COMPLETED AND SIGNED "SPRINKLER CONTRACTOR'S MATERIAL AND TEST CERTIFICATES" SHALL BE 5. ALL DUCTWORK SHALL BE INSTALLED WITH INSIDE CLEAR DIMENSIONS AS NOTED ON DRAWINGS. WHERE DEGREE ANGLE PITCHED UPWARD TOWARDS UNITS. PITCH NOT LESS THAN 1" TO 10 FEET.
FURNISHED TO THE LANDLORD AND AUTHORITIES HAVING JURISDICTION, DUCTWORK SIZE IN LARGER THAN CONNECTED DEVICE SMOOTH DUCT TRANSITIONS SHALL BE INSTALLED JUST REVISIONS
SECTION 15008 -DISCREPANCIES IN DOCUMENTS PRIOR TO DEVICE CONNECTION. 3. SEE MECHANICAL DETAIL DRAWINGS FOR APPLICABLE DETAILS. 0
SPECIFICATIONS, AND DETAILS ARE DIAGRAMMATIC AND INDICATE THE GENERAL LOCATION 111
DIVISION 15400 -PLUMBING C. MEDIUM PRESSURE DUCT: 4. PROVIDE UL LISTED FIRE STOPPING SYSTEM AROUND ALL PIPING PENETRATIONS THROUGH RATED WALLS.
A. DRAWINGS (PLANS, ) 1. WHERE DUCTWORK IS SPECIFICALLY NOTED AS MEDIUM PRESSURE IT SHALL BE CONSTRUCTED IN ACCORDANCE PENETRATIONS SHALL MEET THE REQUIREMENTS OF UL DETAILS WL1001 UNINSULATED WALL
AND INTENT OF THE MECHANICAL SYSTEMS. WHERE DRAWINGS, EXISTING SITE CONDITIONS, SPECIFICATIONS OR SECTION 15401 SUMMARY OF WORK ( ) AND WL5039
OTHER TRADES CONFLICT OR ARE UNCLEAR, ADVISE TENANT'S PROJECT MANAGER, IN WRITING OF VARIATIONS WITH SMACNA STANDARDS FOR A PRESSURE RATING OF 4 INCHES WATER COLUMN MINIMUM OR LARGER AS (INSULATED WALL).
TO CONTRACT DOCUMENTS PRIOR TO SUBMITTAL OF BID. OTHERWISE, TENANT'S PROJECT MANAGER'S REQUIRED BY LANDLORD.
A. THIS CONTRACTOR SHALL FURNISH ALL LABOR
INTERPRETATION OF CONTRACT DOCUMENTS OR CONDITIONS SHALL BE FINAL WITH NO ADDITIONAL , MATERIALS, EQUIPMENT, ETC. NECESSARY FOR, REASONABLY 2, ALL GAUGES AND REINFORCEMENT MUST MEET WITH THE LA"FEST EDITION OF SMACNA STANDARDS FOR MEDIUM C. HYDRONIC PIPING INSULATION
COMPENSATION PERMITTED. IMPLIED AND INCIDENTAL TO, THE FURNISHING, INSTALLATION, COMPLETION AND TESTING OF ALL THE WORK FOR PRESSURE DUCT AND WITH THE LANDLORD'S CRITERIA.
THE PLUMBING SYSTEMS AS CALLED FOR IN THE SPECIFICATIONS, AND AS REQUIRED BY JOB CONDITIONS, TO,3. CONNECTIONS TO THE LANDORD'S MEDIUM PRESSURE DUCTWORK SHALL BE MADE WITH "LO -LOSS" SADDLE TEE 1. ALL HYDRONIC PIPING FOR CHILLED WATER AND/OR HEATING WATER (NOT INCLUDING CONDENSER WATER
SECTION 16009 -DEMOLITION INCLUDE, BUT NOT BE LIMITED TO THE FOLLOWING: TAPS BY UNITED MCGILL CORP., ORAS OTHERWISE REQUIRED BY THE LANDLORD, UNLESS SPECIFICALLY NOTED OTHERWISE), VALVES, FITTINGS, AND ACCESSORIES SHALL BE INSULATED. FOR
4. ALL OTHER ITEMS FROM METAL DUCTWORK SPECIFICATION SECTION APPLY TO THIS SECTION, WITH THE PIPE SIZES UP TO 2 INCHES, INSULATE WITH 1 INCH THICK (K=0.23 @ 75°F) FIBERGLASS INSULATION WITH ALL
A. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF THE DEMOLITION OF EXISTING WORK 1. CONTRACTOR SHALL DETERMINE THE LOCATION OF EXISTING WATER SUPPLY AND DRAIN LINES AND MAKE EXCEPTION THAT ALL MEDIUM PRESSURE DUCTWORK MUST BE WRAPPED INSULATION, NOT LINED. SERVICE JACKET AND VAPOR BARRIER. FOR PIPE SIZES 2-1/2 INCHES AND LARGER, INSULATE WITH 1-1/2 INCH
PROPER CONNECTIONS, THERETO, INCLUDING VENTS. THICK K=0 23 75°F FIBERGLASS INSULATION WITH ALL SERVICE JACKET AND VAPOR BARRIER.
AND THE DEMOLITION PROVIDED BY THE GENERAL CONTRACTOR. COORDINATE WITH THE GENERAL 2, ALL MATERIALS SHALL BE NEW AND SHALL FIT THE SPACE AVAILABLE. VERIFY ALL DIMENSIONS AT THE SITE. ( @ )
D. FLEXIBLE COLLARS AT EQUIPMENT SHALL BE PROVIDED IN ALL CONNECTIONS BETWEEN VIBRATING EQUIPMENT
CONTRACTOR ANY EXISTING EQUIPMENT REQUIRED TO BE LEFT INTACT. 3. ALL VALVES, CLEANOUTS, ETC. SHALL BE SO LOCATED AND INSTALLED TO PERMIT ACCESS FOR SERVICE DRAWING NUMBER
AND DUCTS OR CASINGS. FLEXIBLE CONNECTIONS SHALL CONSTRUCTED OF NEOPRENE -COATED FLAMEPROOF 2. INSULATION AT ALL HANGERS FOR PIPING 21/2 INCHES AND LARGER SHALL BE HARD AND NON-COMPRESSIBLE.
B. EACH CONTRACTOR SHLL VERIFY SCOPE OF WORK WITH THE GENERAL CONTRACTOR FOR THE REMOVAL OF ALL WITHOUT DAMAGE TO BUILDING OR FINISHED MATERIALS: FABRIC, PROVIDE ADEQUATE JOINT FLEXIBILITY TO ALLOW FOR MOVEMENT AND PREVENT THE TRANSMISSION OF
EXISTING FIRE PROTECTION, PLUMBING FIXTURES PIPING HVAC UNITS, REFRIGERANT RECAPTURE EXHAUST VIBRATION. 3. ALL INSULATION SHALL HAVE A FLAME SPREAD RATING OF NOT MORE THAN 25 AND A SMOKE DEVELOPED RATING
FANS, ETC. AND ASSOCIATED ROOF CURBS NOT BEING REUSED ON THIS PROJECT, UNLESS SPECIFICALLY NOTED SECTION 15402 - MATERIALS OF NO HIGHER THAT 50 TO CONFORM WITH THE REQUIREMENTS OF THE NFPA. 1
OTHERWISE. CONTRACTOR MUST VERIFY WITH THE LANDLORD ALL PRESUMED ABANDONED EQUIPMENT, PIPES, E, FLEXIBLE AIR DUCT AT AIR DEVICES SHALL BE MIN. R-5 INSULATED CLASS 1 AND RATED FOR THE OPERATING
A. REFER TO PLANS FOR SCHEDULES OF EQUIPMENT AND FIXTURES. AMERICAN STANDARD, KOHLER AND CRANE PRESSURE OF THE SYSTEM. DUCT CONSTRUCTION MATERIAL MUST ADHERE TO LOCAL CODES AND LANDLORD'S 4. PROVIDE ZESTON OR EQUAL INSULATION FITTINGS FOR ALL TEES, ELLS OR SPECIALTY FITTINGS.
DUCTWORK, AND EQUIPMENT PRIOR TO REMOVAL. ROOF CURBS SHALL BE REMOVED AND THE ROOF PATCHED. ARE CONSIDERED ACCEPTABLE AS EQUALS. ALL PLUMBING EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE
�.', m 3
ALL EXTRANEOUS ITEMS IN THE SPACE OR ON THE ROOF NOT APPLICABLE TO THE NEW WORK MUST BE WITH THE MANUFACTURER'S RECOMMENDATION. REQUIREMENTS.
REMOVED AND ROOF/WALL/FLOOR PATCHED/REPAIRED TO MATCH EXISTING STRUCTURE. EXISTING ABANDONED
PIPES, DUCTS, OR EQUIPMENT IN THE FLOOR, EMBEDDED IN CONCRETE, OR OTHERWISE INACCESSIBLE ARE TO B. SANITARY PIPING F. PROVIDE MANUAL LOCKING QUADRANT VOLUME CONTROL DAMPERS WITH HANDLE OPERATORS IN EACH BRANCH
BE CUT OFF AND SEALED BELOW OR WITHIN FLOOR OR WALL LEVEL WHEN THEY ARE NOT TO BE REUSED IN THIS DUCT AND AS SHOWN ON PLANS TO FACILITATE AIR BALANCING. ALL RECTANGULAR DAMPERS IN OUTSIDE AIR, 8 MECHANICAL
PROJECT. IF REQUIRED BY LANDLORD OR CODES, ABANDONED PIPING AND/OR DUCTWORK MUST BE REMOVED 1 • WASTE, DRAIN AND VENT PIPING SHALL BE SERVICE WEIGHT CAST IRON HUB AND SPIGOT BELOW; NO HUB ABOVE RELIEF AIR, OR RETURN AIR DUCTS ARE TO BE OF OPPOSED BLADE TYPE. SPECIFICATIONS
TO POINT OF ORIGIN. CONFIRM THE EXTENT OF DEMOLITION WITH THE GENERAL CONTRACTOR AND TENANT GROUND. VENT PIPING ABOVE FLOOR 2" OR SMALLER MAY BE GALVANIZED STEEL.
2. INSULATE ALL HORIZONTAL RUNS OF PIPING LOCATED IN CEILING SPACES OF TENANTS IN SPACES BELOW, WHEN G. PROVIDE PRIMARY FIRE DAMPERS WHERE INDICATED OR REQUIRED BY CODES. FIRE DAMPERS SHALL BE UL
PRIOR TO BID AND INCLUDE IN BID PROPOSAL AS DIRECTED BY THE GENERAL CONTRACTOR AND TENANT. APPLICABLE. INSULATION TO BE AS SPECIFIED FOR WATER PIPING.
LABELED. FIRE DAMPERS SHALL HAVE THE BLADES OUT OF THE AIRSTREAM AND A 165 F FUSIBLE LINK, TYPE B,
11
., :.r , e .,,, .. ,,, err , ,. xe,. r<:: , ; „'e .r ,. , , , : > , .. .. , ,,, w,,,,, ,, ,, ,, ,, ,,, , .. ^ ,., ,... .. "''^.3. ^ . .. ^ . „i ,.., .x , < >r" a„ {,:
,, r .. u,,.,,,,', ..Kr,H n.:: rrrrry 5 4, „,.':: , ,r ,. , .....,.... .. . z. r z , r„ , ,., ,u, ,,, ,,,, ,,,,,, ...,...., ,.,,,,,.. ., „ .., a ,. ,., a „uxe ,.,,,.. e,,,, ,e ,,, a ,.R,..,e , ... .,,.�.. ,e <s ,.), .: err r .r e,nv,r.0 v v ,r .,, ,e .. <, ... ^, , a rr x,x ..a : a,f, xxu. ro ,,,, .,„ .:., ,<,,.,.,, ..,,.,,, w .,.. „ ..,, ., , ,,, ,:.. ., „,,,, ^,. ,.
.r' 'vt o::: s ., e,. ,, .H:v. r , .., .,, ,..,ct -rir: n v., :':i ;,. ,:: -
, .:. . .:
e
. 1. ... .. rs..
. 11� . : e , .,,.< :: .l <
-0
ELECTRICAL COMMENTS:
• ABSOLUTELY NO FLEXIBLE CONDUIT IS PERMITTED IN DEMISING WALLS. FLEXIBLE CONDUIT IS PERMITTED FOR SHORT, FINAL CONNECTIONS ONLY
(6-0" OR LESS).
• EXPOSED CONDUIT SHALL BE INSTALLED IN STRAIHGT LINES, PARALLEL OR IN RIGHT ANGLES TO THE BUILDING STRUCTURE. DO NOT LOOP EXCESS
FLEXIBLE CONDUIT IN CEILING SPACE OR WALL CAVITY.
• CABLE TYPES AC OR NM CABLES ARE NOT ACCEPTABLE. TYPE MC CABLE, ELECTRIC METALLIC TUBING (EMT), AND RIGID GALVANIZED CONDUIT ARE
PERMITTED.
• ALL EQUPMENT, DEVICES, AND FIXTURES SHALL BE GROUNDED IN COMPLIANCE WITH NEC AND UL REQUIREMENTS.
• ALL PANEL.) TO BE UL LABELED WITH BOLT -ON TYPE CIRCUIT BREAKERS.
• 7 -DAY, 24-HOUR TIME CLOCK IS REQUIRED TO CONTROL STOREFRONT ENRTY LIGHTS, SHOW WINDOW, SHOW WINDOW LIGHTS, SHOW WINDOW
RECEPTACLES, AND STOREFRONT SIGNAGE. ILLUMINATED STOREFRONT SIGNS MUST REMAIN LIT DURING ALL MALL BUSINESS HOURS.
• TENANT IS REQUIRED TO MAKE A FIELD SURVEY OF THE EXISTING ELECTRICAL SERVICE TO ENSURE THAT THE TOTAL CONNECTED LOAD DOES NT
EXCEED THE ELECTRICAL SERVICE. ANY/ALL MODIFICATIONS OR UPGRADES NEEDED ARE SUBJECT TO LANDLORD'S PRIOR APPROVAL, AND WILL
BE COMPLETED BY TENANT/TENANT'S G.C., AT TENANT'S SOLE EXPENSE.
• ALL ELECTRICAL PANELS TO BE MOUNTED ON PLYWOOD BACKER BOARD.
• PANEL PHASE LOADS TO BE BALANCED WITHIN 10%.
• ELECTRICAL PANELS MAY NOT BE RECESSED IN DEMISING PARTITIONS. SURFACE MOUNT OR FUR OUT WALL TO ACHIEVE FLUSH APPEARANCE.
• ONLY 30KVA AND SMALLER TRANSFORMERS MAY BE SUSPENDED FROM BUILDING STRUCTURE. ALL OTHER TRANSFORMERS NUST BE FLOOR
MOUNTED.
• FLOOR PENETRATIONS
TENANT'S G.C. MUST ADVISE THE PROPERTY'S OPERATIONS DIRECTOR PRIOR TO ANY SLAB CUTTING OR REMOVAL. ALL FLOOR PENETRATIONS
MUST BE CORE -BORED OR SAW -CUT (NO JACK -HAMMERING PERMITTED). PRIOR TO WORK, TENANT'S G.C. MUST VERIFY THAT TENANT'S WORK WILL
NOT CONFLICT WITH EXISTING, STRUCTURAL, UTILITY, OR OTHER UNDER SLAB CONDITIONS. TENANT'S WORK MUST NOT COMPROMISE OR DAMAGE
THE EXISTING STRUCTURE. ANY DAMAGE CAUSED BY TENANT'S WORK IS TO BE REPAIRED AT TENANT'S EXPENSE.
ADJACENT TENANT
..,., .ata ........ ......... ,.. ,, . .. ...,. .,... .
' AA 20,22
{ WH -1
.....�" 9
A-10
i
LU
f
n YY aa.w :xi.w\�a\�AA�u3a1Wa
)
t A-8 I
'- POINT "B"
v 1 6
Q!A-1 A-1°'2
13 1I _
..�.
A-4 6 ,
Es ... a.aaaa
60A DISC:SV
— 30KVA XFMR
POINT "A"
A-1 I
POWER PLAN
El mOl SCALE: 1/4"=V-0"
14
N)P1
FIRE ALARM SYSTEM SYMBOLS
FF—AC-p-1
FIRE CONTROL PANEL +72" A.F.F. TO TOP OF DEVICE
I
REMOTE POWER SUPPLY +72" A.F.F. TO TOP OF DEVICE
i
FIRE TERMINAL CABINET
FSA
FIRE SYSTEM ANUNCIATOR +48" A.F.F. TO TOP OF DEVICE
Zc
14
N)P1
VIA`,SjW T-
A -12
A 12 +14 . (A-1,)
ADJACENT TENANT
A-14,16
+18'
A-1'
m
�i
A-17
O��...VIA SW f' r,
..�,�.{{,,A 18 I A-1 26+14"
ll!! L.1...
,
E
STANDARD 20A, 120/277V-1 O SPST TOGGLE SWITCH MOUNTED AT +48" A.F.F.
$OS WALL MOUNTED INFRA -RED OCCUPANCY SENSOR.
�S CEILING MOUNTED ULTRASONIC OCCUPANCY SENSOR.
STANDARD 20A, 120V-10 GROUNDING TYPE SIMPLEX RECEPTACLE MOUNTED AT
+18" A.F.F.
STANDARD 20A, 120V-10 GROUNDING TYPE DUPLEX RECEPTACLE MOUNTED AT
+18" A.F.F.
(bW.P STANDARD 20A, 120V-10 GROUNDING TYPE WEATHER PROOF (NEMA 3R) DUPLEX
RECEPTACLE MOUNTED AT +18" A.F.F.
STANDARD 20A, 120V-10 GROUNDING TYPE DUPLEX RECEPTACLE CEILING
MOUNTED AT STORE FRONT
STANDARD 20A, 120V-10 GROUNDING TYPE FOUR-PLEX RECEPTACLE MOUNTED AT
+18" A.F.F.
STANDARD 20A, 120V-10 GROUNDING TYPE "GROUND FAULT INTERRUPTER" (G.F.I.)
RECEPTACLE MOUNTED AT +'18" A.F.F.
STANDARD 20A, 120V-10 ISOLATED GROUND TYPE DUPLEX RECEPTACLE,MOUNTED
AT +18" A.F.F.
STANDARD 20A, 120V-10 ISOLATED GROUND TYPE QUADRAPLEX
RECEPTACLE, MOUNTED AT+18" A.F.F.
STANDARD 15A, 120V-10 SIMPLEX CLOCK RECEPTACLE.
La FUSED DISCONNEC-f SWITCH. AMPS, POLES AND FUSE SIZE AS INDICATED.
OPEN- INDICATES NON-FUSED
W.P. - INDICATES NEMA 3R ENCLOSURE
LN COMBINATION DISCONNECT SWITCH/MAGNETIC MOTOR STARTER. AMPS, POLES,
FUSE SIZE, AND NEMA SIZE AS INDICATED. PROVIDE COMPLETE WITH THERMAL
OVERLOAD PROTECTION PER MOTOR NAMEPLATE DATA, 120V CONTROL COIL -
U.O.N., AND H.O.A. (HAND -OFF -AUTO) SWITCH. W.P. - INDICATES NEMA 3R
ENCLOSURE.
® MAGNETIC MOTOR STARTER. POLES AND NEMA SIZE AS INDICATED. PROVIDE
COMPLETE WITH THERMAL OVERLOAD PROTECTION PER MOTOR NAMEPLATE
DATA, 120V CONTROL COIL - U.O.N., AND H.O.A. (HAND -OFF -AUTO) SWITCH.
W.P. - INDICATES NEMA 3R ENCLOSURE
MANUAL MOTOR STARTER SWITCH. HORSEPOWER RATED -120V - 10 -U.O.N.
M PROVIDE COMPLETE WITH THERMAL OVERLOAD PROTECTION.
O JUNCTION BOX. SIZED BY THE CONTRACTOR PER ACTUAL NUMBER OF CONDUITS
AND/OR CONDUCTORS PASSING THRU.
10 MOTOR OUTLET. H.P. OR F.L.A. - VOLTS & PHASE AS INDICATED.
TRANSFORMER AS SPECIFIED.
TIME CLOCK.
DELIVERY BUZZER.
a DELIVERY BUZZER PUSH BUTTON MOUNTED AT 54" A.F.F.
TELEPHONE PLYWOOD BACKBOARD.
(1 THERMOSTAT FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR.
]� PROVIDE J -BOX AT +48" A.F.F.
(� VOLUME CONTROL MOUNTED AT +48" AFF.
`t TELEPHONE OUTLET WITH (1) RJ11 PORT. JACK COLOR- GRAY.
XO DATA OUTLET WITH RJ45 PORTS (X) AMOUNT OF DATA PORTS. JACK COLOR -
ORANGE.
IF COMBINATION TELE/DATA OUTLET WITH (1) RJ11 AND AND (2) RJ45 PORTS. JACK
COLOR - GRAY AND ORANGE.
® TELEPHONE OUTLET WITH (1) RJ11 PORT WITH TWO TELEPHONE LINES. JACK
COLOR - BLUE.
CONDUIT CONCEALED WITHIN BUILDING WALLS OR CEILING SPACE.
CONDUIT ROUTED BELOW FINISHED GRADE AND / OR CONCRETE SLAB.
HOMERUN TO DESTINATION AS INDICATED. REFER TO CONDUIT SYMBOL ABOVE.
FLEXIBLE CONDUIT CONNECTION FROM JUNCTION BOX.
GENERAL ELECTRICAL SAFETY REQUIREMENTS:
A. ALL ELECTRICAL WORK PRACTICES MUST COMPLY WITH APPLICABLE
SECTIONS OF THE OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION (OSHA), NATIONAL FIRE PROTECTION ASSOCIATION
(NFPA), NATIONAL ELECTRICAL CODE (NFPA 70 & 70E), NATIONAL
ELECTRICAL SAFETY CODE (NESC) AND STATE AND LOCAL ADOPTED
ELECTRICAL CODES.
ELECTRICAL N D
B. THE GENERAL CONTRACTOR,CTRI AL C CONTRACTOR AN ALL
APPLICABLE TRADES ARE RESPONSIBLE FOR STRICT ADHERENCE TO
ALL ELECTRICAL SAFETY REQUIREMENTS.
LANDLORD REQUIREMENTS:
• ALL HOME RUNS TO TENANT'S PANELS SHALL BE IN RIGID STEEL
CONDUIT OR EMT.
• ALL EXPOSED WIRING IN CEILINGS OR INTERIOR WALLS MUST BE IN
RIGID STEEL CONDUIT OR EMT.
• ALL WIRING IN LANDLORD DEMISING WALLS MUST BE IN RIGID STEEL
CONDUIT OR EMT.
• COORDINATE ALL FLOOR CUT MEANS AND METHODS OF ROUTING
CONDUIT THROUGH THE FLOOR WITH MALL OPERATIONS.
• NO CONDUIT TO BE SUPPORTED FROM THE ROOF DECK.
GENERAL NOT
A. THE CONTRACTOR FOR THIS WORK IS REQUIRED TO READ THE
SPECIFICATIONS REVIEW DRAWINGS OF ALL DIVISIONS OF WORK AND IS
RESPONSIBLE FOR THE COORDINATION OF THIS WORK AND THE WORK OF
ALL SUBCONTRACTORS WITH ALL DIVISIONS OF WORK, IT IS THE
CONTRACTOR'S RESPONSIBILITY TO PROVIDE ALL SUBCONTRACTORS
WITH A COMPLETE SET OF BID DOCUMENTS.
B. CIRCUITING INDICATED ON PLAN IS PARTIALLY DIAGRAMMATIC FOR
CLARITY, CIRCUITING SHALL BE "THRU-WIRING" WHERE AND WHENEVER
POSSIBLE.
C. FIELD VERIFY EXACT LOCATION AND ELECTRICAL REQUIREMENTS OF ALL
HVAC EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO ORDERING
ELECTRICAL EQUIPMENT.
D. ALL RECEPTACLE CIRCUITS UP TO 100'-0" SHALL UTILIZE #12 CONDUCTORS
MINIMUM. ALL RECEPTACLE CIRCUITS FROM 101'-0" TO 150'-0" IN LENGTH
SHALL UTILIZE #10 CONDUCTORS MINIMUM. CIRCUITS ABOVE 251'-0" SHALL
UTILIZE #6 CONDUCTORS MINIMUM.
E. PLACEMENT OF ALL RECEPTACLES IN THE "SALES" AREA SHALL BE
INTENTIONAL (I.E. - CENTERED ON COLUMNS, WALL FEATURES OR TIGHT
TO CORNERS AND AT 18" A.F.F UNLESS OTHER WISE NOTED). IF THE
RECEPTACLE IS NOT SHOWN IN A DESIRABLE LOCATION, FIELD VERIFY
EXACT PLACEMENT OF RECEPTACLE WITH TENANT'S PROJECT MANAGER
PRIOR TO ROUGH-iN.
F. ELECTRICAL CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS AS
REQUIRED FOR A FULLY COMPLETE AND OPERABLE SYSTEM.
G. WHERE DRYWALL CEILINGS ARE USED IN THE "SALES" AREA, THE
ELECTRICAL CONTRACTOR SHALL ARRANGE CIRCUITS TO AVOID THE USE
OF JUNCTION BOXES IN INACCESSIBLE LOCATIONS. THE USE OF JUNCTION
BOXES ABOVE LAY -IN CEILINGS ARE ACCEPTABLE.
H. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO INQUIRE WITH THE
LANDLORD'S REPRESENTATIVE ON ANY FIRE ALARM SYSTEMS IN USE AT
THE MALL AT THE TIME OF THE BID. IF THE FIRE ALARM SYSTEM IS NOT
ADEQUATELY DESCRIBED ON THE DRAWINGS, THE ELECTRICAL
CONTRACTOR IS RESPONSIBLE TO INFORM THE GENERAL CONTRACTOR
AND INCLUDE THE COST AS A SEPARATE LINE ITEM IN THE BID. NO
ADDITIONAL MONEY SHALL BE AWARDED FOR TIE-IN REQUIREMENTS TO A
LANDLORD'S FIRE ALARM SYSTEM THAT IS IN EXISTENCE AT THE TIME OF
THE BID, WITHOUT A SEPARATE LINE ITEM FOR THE FIRE ALARM SYSTEM
AT THE TIME OF THE BID.
I. INSTALL ENGRAVED BAKELITE NAMEPLATE ON SERVICE DISCONNECT
SWITCH IN LANDLORD'S SWITCH GEAR WITH DEMISED PREMISES' SPACE
NUMBER.
J. NO HANGERS, SUPPORTS, JUNCTION BOXES, ETC. SHALL BE ATTACHED TO
ROOF DECK..
K. COORDINATE ALL ROOF PENETRATIONS WITH THE LANDLORD. WRITTEN
PERMISSION FROM THE LANDLORD SHALL BE RECEIVED PRIOR TO ANY
WORK BEING PERFORMED. ALL ROOF PENETRATIONS TO BE BY
LANDLORD'S CONTRACTOR AT TENANT'S ELECTRICAL CONTRACTOR'S
EXPENSE.
L. ELECTRICAL CONTRACTOR IS TO CUT FLOOR (CORE DRILL ON ELEVATED
FLOORS) AS REQUIRED TO INSTALL CONDUITS TO CASHWRAP UNITS AND
PATCH FLOOR TO MATCH EXISTING. COORDINATE ALL WORK WITH
LANDLORD PRIOR TO STARTING WORK.
M. ELECTRICAL CONTRACTOR IS TO FURNISH AND INSTALL TYPE WRITTEN
PANEL DIRECTORIES IN ALL PANEL BOARDS.
N. ALL RECEPTACLES TO BE MOUNTED VERTICALLY, NOT HORIZONTALLY.
0. RECEPTACLE COVER PLATES SHALL BE WHITE EXCEPT AT WAINSCOT,
WHERE THEY SHALL BE IVORY
P. "G.C. IS TO REVIEW STRUCTURE BELOW OUR SPACE PRIOR TO
CONSTRUCTION FOR CONDITIONS PREVENTING FLOOR PENETRATIONS AS
SHOWN. OBSTRUCTIONS THAT PREVENT LAYOUT AS SHOWN SHALL BE
BROUGHT TO THE ATTENTION OF THE ARCHITECT IMMEDIATELY AND
PRIOR TO FRAMING."
KEYED NOTES:
0 GROSSCOM TO RUN TWO (2) CAT5E WIRES BETWEEN POINTS "A" & "B"
BETWEEN POINTS "B" AND "C", AND BETWEEN POINTS "C" AND "A'.
COORDINATE ALL ROUTING PRIOR TO ROUGH -IN.
0 PROVIDE RECEPTACLE AT BACK CASH WRAP FOR STEREO EQUIPMENT,
VERY EXACT LOCATION WITH OWNER. G.C. TO INSTALL STEREO AND RUN
SPEAKER WIRE, G.C. TO RUN WIRE BEHIND FURNITURE, SPEAKERS
INSTALLED ON TOP OF FURNITURE TO RIGHT AND LEFT OF BACK
CASHWRAP. SPEAKERS TO MUTE WHEN FIRE ALARM IS ACTIVATED. (�,.C. TO
VERIFY ALL REQUIREMENTS WITH LANDLORD AND TO COORDINATE WITH
FIRE ALARM CONTRACTOR AS REQUIRED.
0DUPLEX RECEPTACLE WITH COVER PLATE MOUNTED IN SOFFIT ABOVE
WINDOW. CONTROL RECEPTACLE WITH TIME CLOCK AND SWITCHES AT
MANAGER'S DESK. RECEPTACLE AND COVER PLATE TO MATCH
SURROUNDING WALL COLOR.
�4 NEW PANEL "A" 208Y/120V, 3PH, 4W WITH A 100A MAIN CIRCUIT BREAKER.
REFERTO SHEET E-3 FOR MORE DETAIL.
5 NEW TIME CLOCK FOR LIGHTING AND RECEPTACLES. REFER TO SHEET E2
FOR MODEL NUMBER. COORDINATE EXACT LOCATION PRIOR -f0 BID.
2'X 4'X 3/4" TELECOMM. BOARD WITH DEDICATED QUADRAPLEX
RECEPTACLE AND CIRCUIT WITH ISOLATED GROUND. VERIFY SYSTEM
GROUNDING AND ALL OTHER REQUIREMENTS WITH LOCAL TELEPHONE Q
COMPANY. EXTEND 1" TELEPHONE CONDUIT WITH PULL WIRE FROM
SERVICE ENTRANCE AT DEMISING WALL TO TELECOMM. BOARD. VERIFY
EXACT LOCATION IN FIELD. SEE SHEET E3 FOR FRANCESCA'S NOTES AND
DETAILS.
0 RECEPTACLE, DATA AND TELEPHONE OUTLET MOUNTED IN CASHWRAP
MILL WORK. COORDINATE EXACT PLACEMENT OF DEVICE AND WIRE
ROUTING IN CASHWRAP WITH MILLWORK DRAWINGS.
C) (1) 1" CONDUIT FOR POWER AND (1) 1" CONDUITS FOR TELEPHONE/DATA
UNDERFLOOR FROM CASHWRAP TO NEARBY WALL OR COLUMN, UP TO
ABOVE CEILING AND TO ELECTRICAL PANEL OR ,TELEPHONE BOARD AS
LABELED. STUB CONDUITS UP 16" ABOVE FINISHED FLOOR AT CASHWRAP.
SEE E3 FOR FRANCESCA'S NOTES AND DETAILS.
ELECTRIC WATER HEATER. CIRCUIT AS SHOWN.
1U PROVIDE WHIP AT 8'-6" AFF FOR FURNITURE. COORDINATE EXACT
PLACEMENT OF QUAD RECEPTACLE AND WIRE ROUTING WITH MILLWORK
DRAWINGS. SEE SHEET E2. FOR SWITCH LOCATION.
1.� PROVIDE WHIP AT 8'-6" AFF FOR FURNITURE. COORDINATE EXACT
PLACEMENT OF DUPLEX RECEPTACLE AND WIRE ROUTING WITH MILLWORK
DRAWINGS. MOUNT RECEPTACLE HORIZONTALLY, SEE SHEET E2. FOR
SWITCH LOCATION.
12 NEW VAV-1, CIRCUIT AS SHOWN. FIELD VERIFY EXACT CONNECTION
REQUIREMENTS PRIOR TO BID.
13 ONE (1) CAT5E LINE ROUTED ABOVE THE CEILING FROM A JUNCTION BOX IN
CONDUIT FROM THIS LOCATION TO THE TELEPHONE BOARD. LEAVE 12'-0"
OF SLACK AT EACH BOX. COORDINATE JUNCTION BOX LOCATION AND
CONDUIT ROUTING PRIOR TO INSTALLATION.
14 NEW 60A, 600V, FUSED DISCONNECT FUSED AT 60A TO FEED NEW 30KVA
TRANSFORMER. REFER To ONE -LINE DIAGRAM, SHEET E3 FOR ADDITIONAL
INFORMA'HON.
15 NEW 30KVA 48UV-TO-208Y/120V TRANSFORMER. MOUNT TRANSFORMER ON
WALL ABOVE PANEL.
PARTNERS
brand . operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE#1311C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
s
ee
N �.
0 67023 d
5�.+ • /+_ QVC
���rBd11999ASa�'®e
1 it 6AA �fl `2
ISSUE DATES
PRELIM SET: 10-16-2013
x FINAL SET: 11-6-2013
'Y PERMIT SET: 11-20-2013
REVISIONS
1
DRAWING NUMBER
I�
POWER PLAN
,3 !.v','{1
FIRE ALARM SYSTEM SYMBOLS
FF—AC-p-1
FIRE CONTROL PANEL +72" A.F.F. TO TOP OF DEVICE
RPS
REMOTE POWER SUPPLY +72" A.F.F. TO TOP OF DEVICE
F—FT-C-1
FIRE TERMINAL CABINET
FSA
FIRE SYSTEM ANUNCIATOR +48" A.F.F. TO TOP OF DEVICE
Zc
CONTROL MODULE
Zr
RELAY MODULE CONTROL RELAY, SPDT, W/ LED
❑I
MONITOR MODULE
n
PULL STATION +48" A.F.F. TO TOP OF DEVICE
Q
WATER FLOW SWITCH
TS
TAMPER SWITCH
DH
DOOR HOLD OPEN DEVICE
24VDC HORN +90" A.F.F. TO TOP OF DEVICE
R1
SUPERVISION RELAY
O L
DETECTOR 120 VAC W/9VDC BATTERY
O
PHOTOELECTRIC SENSOR
®
HEAT SENSOR W/ RATE -OF -RISE
('7T(
DUCT DETECTOR
2
IN -DUCT DETECTOR
CD
.24VDC AUDIBLE/STROBE UNIT (15CD) +80" A.F.F. TO TOP OF DEVICE (CD=CANDELA)
CD
24VDC STROBE UNIT (15CD) +80" A.F.F. TO TOP OF DEVICE (CD=CANDELA)
VIA`,SjW T-
A -12
A 12 +14 . (A-1,)
ADJACENT TENANT
A-14,16
+18'
A-1'
m
�i
A-17
O��...VIA SW f' r,
..�,�.{{,,A 18 I A-1 26+14"
ll!! L.1...
,
E
STANDARD 20A, 120/277V-1 O SPST TOGGLE SWITCH MOUNTED AT +48" A.F.F.
$OS WALL MOUNTED INFRA -RED OCCUPANCY SENSOR.
�S CEILING MOUNTED ULTRASONIC OCCUPANCY SENSOR.
STANDARD 20A, 120V-10 GROUNDING TYPE SIMPLEX RECEPTACLE MOUNTED AT
+18" A.F.F.
STANDARD 20A, 120V-10 GROUNDING TYPE DUPLEX RECEPTACLE MOUNTED AT
+18" A.F.F.
(bW.P STANDARD 20A, 120V-10 GROUNDING TYPE WEATHER PROOF (NEMA 3R) DUPLEX
RECEPTACLE MOUNTED AT +18" A.F.F.
STANDARD 20A, 120V-10 GROUNDING TYPE DUPLEX RECEPTACLE CEILING
MOUNTED AT STORE FRONT
STANDARD 20A, 120V-10 GROUNDING TYPE FOUR-PLEX RECEPTACLE MOUNTED AT
+18" A.F.F.
STANDARD 20A, 120V-10 GROUNDING TYPE "GROUND FAULT INTERRUPTER" (G.F.I.)
RECEPTACLE MOUNTED AT +'18" A.F.F.
STANDARD 20A, 120V-10 ISOLATED GROUND TYPE DUPLEX RECEPTACLE,MOUNTED
AT +18" A.F.F.
STANDARD 20A, 120V-10 ISOLATED GROUND TYPE QUADRAPLEX
RECEPTACLE, MOUNTED AT+18" A.F.F.
STANDARD 15A, 120V-10 SIMPLEX CLOCK RECEPTACLE.
La FUSED DISCONNEC-f SWITCH. AMPS, POLES AND FUSE SIZE AS INDICATED.
OPEN- INDICATES NON-FUSED
W.P. - INDICATES NEMA 3R ENCLOSURE
LN COMBINATION DISCONNECT SWITCH/MAGNETIC MOTOR STARTER. AMPS, POLES,
FUSE SIZE, AND NEMA SIZE AS INDICATED. PROVIDE COMPLETE WITH THERMAL
OVERLOAD PROTECTION PER MOTOR NAMEPLATE DATA, 120V CONTROL COIL -
U.O.N., AND H.O.A. (HAND -OFF -AUTO) SWITCH. W.P. - INDICATES NEMA 3R
ENCLOSURE.
® MAGNETIC MOTOR STARTER. POLES AND NEMA SIZE AS INDICATED. PROVIDE
COMPLETE WITH THERMAL OVERLOAD PROTECTION PER MOTOR NAMEPLATE
DATA, 120V CONTROL COIL - U.O.N., AND H.O.A. (HAND -OFF -AUTO) SWITCH.
W.P. - INDICATES NEMA 3R ENCLOSURE
MANUAL MOTOR STARTER SWITCH. HORSEPOWER RATED -120V - 10 -U.O.N.
M PROVIDE COMPLETE WITH THERMAL OVERLOAD PROTECTION.
O JUNCTION BOX. SIZED BY THE CONTRACTOR PER ACTUAL NUMBER OF CONDUITS
AND/OR CONDUCTORS PASSING THRU.
10 MOTOR OUTLET. H.P. OR F.L.A. - VOLTS & PHASE AS INDICATED.
TRANSFORMER AS SPECIFIED.
TIME CLOCK.
DELIVERY BUZZER.
a DELIVERY BUZZER PUSH BUTTON MOUNTED AT 54" A.F.F.
TELEPHONE PLYWOOD BACKBOARD.
(1 THERMOSTAT FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR.
]� PROVIDE J -BOX AT +48" A.F.F.
(� VOLUME CONTROL MOUNTED AT +48" AFF.
`t TELEPHONE OUTLET WITH (1) RJ11 PORT. JACK COLOR- GRAY.
XO DATA OUTLET WITH RJ45 PORTS (X) AMOUNT OF DATA PORTS. JACK COLOR -
ORANGE.
IF COMBINATION TELE/DATA OUTLET WITH (1) RJ11 AND AND (2) RJ45 PORTS. JACK
COLOR - GRAY AND ORANGE.
® TELEPHONE OUTLET WITH (1) RJ11 PORT WITH TWO TELEPHONE LINES. JACK
COLOR - BLUE.
CONDUIT CONCEALED WITHIN BUILDING WALLS OR CEILING SPACE.
CONDUIT ROUTED BELOW FINISHED GRADE AND / OR CONCRETE SLAB.
HOMERUN TO DESTINATION AS INDICATED. REFER TO CONDUIT SYMBOL ABOVE.
FLEXIBLE CONDUIT CONNECTION FROM JUNCTION BOX.
GENERAL ELECTRICAL SAFETY REQUIREMENTS:
A. ALL ELECTRICAL WORK PRACTICES MUST COMPLY WITH APPLICABLE
SECTIONS OF THE OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION (OSHA), NATIONAL FIRE PROTECTION ASSOCIATION
(NFPA), NATIONAL ELECTRICAL CODE (NFPA 70 & 70E), NATIONAL
ELECTRICAL SAFETY CODE (NESC) AND STATE AND LOCAL ADOPTED
ELECTRICAL CODES.
ELECTRICAL N D
B. THE GENERAL CONTRACTOR,CTRI AL C CONTRACTOR AN ALL
APPLICABLE TRADES ARE RESPONSIBLE FOR STRICT ADHERENCE TO
ALL ELECTRICAL SAFETY REQUIREMENTS.
LANDLORD REQUIREMENTS:
• ALL HOME RUNS TO TENANT'S PANELS SHALL BE IN RIGID STEEL
CONDUIT OR EMT.
• ALL EXPOSED WIRING IN CEILINGS OR INTERIOR WALLS MUST BE IN
RIGID STEEL CONDUIT OR EMT.
• ALL WIRING IN LANDLORD DEMISING WALLS MUST BE IN RIGID STEEL
CONDUIT OR EMT.
• COORDINATE ALL FLOOR CUT MEANS AND METHODS OF ROUTING
CONDUIT THROUGH THE FLOOR WITH MALL OPERATIONS.
• NO CONDUIT TO BE SUPPORTED FROM THE ROOF DECK.
GENERAL NOT
A. THE CONTRACTOR FOR THIS WORK IS REQUIRED TO READ THE
SPECIFICATIONS REVIEW DRAWINGS OF ALL DIVISIONS OF WORK AND IS
RESPONSIBLE FOR THE COORDINATION OF THIS WORK AND THE WORK OF
ALL SUBCONTRACTORS WITH ALL DIVISIONS OF WORK, IT IS THE
CONTRACTOR'S RESPONSIBILITY TO PROVIDE ALL SUBCONTRACTORS
WITH A COMPLETE SET OF BID DOCUMENTS.
B. CIRCUITING INDICATED ON PLAN IS PARTIALLY DIAGRAMMATIC FOR
CLARITY, CIRCUITING SHALL BE "THRU-WIRING" WHERE AND WHENEVER
POSSIBLE.
C. FIELD VERIFY EXACT LOCATION AND ELECTRICAL REQUIREMENTS OF ALL
HVAC EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO ORDERING
ELECTRICAL EQUIPMENT.
D. ALL RECEPTACLE CIRCUITS UP TO 100'-0" SHALL UTILIZE #12 CONDUCTORS
MINIMUM. ALL RECEPTACLE CIRCUITS FROM 101'-0" TO 150'-0" IN LENGTH
SHALL UTILIZE #10 CONDUCTORS MINIMUM. CIRCUITS ABOVE 251'-0" SHALL
UTILIZE #6 CONDUCTORS MINIMUM.
E. PLACEMENT OF ALL RECEPTACLES IN THE "SALES" AREA SHALL BE
INTENTIONAL (I.E. - CENTERED ON COLUMNS, WALL FEATURES OR TIGHT
TO CORNERS AND AT 18" A.F.F UNLESS OTHER WISE NOTED). IF THE
RECEPTACLE IS NOT SHOWN IN A DESIRABLE LOCATION, FIELD VERIFY
EXACT PLACEMENT OF RECEPTACLE WITH TENANT'S PROJECT MANAGER
PRIOR TO ROUGH-iN.
F. ELECTRICAL CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS AS
REQUIRED FOR A FULLY COMPLETE AND OPERABLE SYSTEM.
G. WHERE DRYWALL CEILINGS ARE USED IN THE "SALES" AREA, THE
ELECTRICAL CONTRACTOR SHALL ARRANGE CIRCUITS TO AVOID THE USE
OF JUNCTION BOXES IN INACCESSIBLE LOCATIONS. THE USE OF JUNCTION
BOXES ABOVE LAY -IN CEILINGS ARE ACCEPTABLE.
H. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO INQUIRE WITH THE
LANDLORD'S REPRESENTATIVE ON ANY FIRE ALARM SYSTEMS IN USE AT
THE MALL AT THE TIME OF THE BID. IF THE FIRE ALARM SYSTEM IS NOT
ADEQUATELY DESCRIBED ON THE DRAWINGS, THE ELECTRICAL
CONTRACTOR IS RESPONSIBLE TO INFORM THE GENERAL CONTRACTOR
AND INCLUDE THE COST AS A SEPARATE LINE ITEM IN THE BID. NO
ADDITIONAL MONEY SHALL BE AWARDED FOR TIE-IN REQUIREMENTS TO A
LANDLORD'S FIRE ALARM SYSTEM THAT IS IN EXISTENCE AT THE TIME OF
THE BID, WITHOUT A SEPARATE LINE ITEM FOR THE FIRE ALARM SYSTEM
AT THE TIME OF THE BID.
I. INSTALL ENGRAVED BAKELITE NAMEPLATE ON SERVICE DISCONNECT
SWITCH IN LANDLORD'S SWITCH GEAR WITH DEMISED PREMISES' SPACE
NUMBER.
J. NO HANGERS, SUPPORTS, JUNCTION BOXES, ETC. SHALL BE ATTACHED TO
ROOF DECK..
K. COORDINATE ALL ROOF PENETRATIONS WITH THE LANDLORD. WRITTEN
PERMISSION FROM THE LANDLORD SHALL BE RECEIVED PRIOR TO ANY
WORK BEING PERFORMED. ALL ROOF PENETRATIONS TO BE BY
LANDLORD'S CONTRACTOR AT TENANT'S ELECTRICAL CONTRACTOR'S
EXPENSE.
L. ELECTRICAL CONTRACTOR IS TO CUT FLOOR (CORE DRILL ON ELEVATED
FLOORS) AS REQUIRED TO INSTALL CONDUITS TO CASHWRAP UNITS AND
PATCH FLOOR TO MATCH EXISTING. COORDINATE ALL WORK WITH
LANDLORD PRIOR TO STARTING WORK.
M. ELECTRICAL CONTRACTOR IS TO FURNISH AND INSTALL TYPE WRITTEN
PANEL DIRECTORIES IN ALL PANEL BOARDS.
N. ALL RECEPTACLES TO BE MOUNTED VERTICALLY, NOT HORIZONTALLY.
0. RECEPTACLE COVER PLATES SHALL BE WHITE EXCEPT AT WAINSCOT,
WHERE THEY SHALL BE IVORY
P. "G.C. IS TO REVIEW STRUCTURE BELOW OUR SPACE PRIOR TO
CONSTRUCTION FOR CONDITIONS PREVENTING FLOOR PENETRATIONS AS
SHOWN. OBSTRUCTIONS THAT PREVENT LAYOUT AS SHOWN SHALL BE
BROUGHT TO THE ATTENTION OF THE ARCHITECT IMMEDIATELY AND
PRIOR TO FRAMING."
KEYED NOTES:
0 GROSSCOM TO RUN TWO (2) CAT5E WIRES BETWEEN POINTS "A" & "B"
BETWEEN POINTS "B" AND "C", AND BETWEEN POINTS "C" AND "A'.
COORDINATE ALL ROUTING PRIOR TO ROUGH -IN.
0 PROVIDE RECEPTACLE AT BACK CASH WRAP FOR STEREO EQUIPMENT,
VERY EXACT LOCATION WITH OWNER. G.C. TO INSTALL STEREO AND RUN
SPEAKER WIRE, G.C. TO RUN WIRE BEHIND FURNITURE, SPEAKERS
INSTALLED ON TOP OF FURNITURE TO RIGHT AND LEFT OF BACK
CASHWRAP. SPEAKERS TO MUTE WHEN FIRE ALARM IS ACTIVATED. (�,.C. TO
VERIFY ALL REQUIREMENTS WITH LANDLORD AND TO COORDINATE WITH
FIRE ALARM CONTRACTOR AS REQUIRED.
0DUPLEX RECEPTACLE WITH COVER PLATE MOUNTED IN SOFFIT ABOVE
WINDOW. CONTROL RECEPTACLE WITH TIME CLOCK AND SWITCHES AT
MANAGER'S DESK. RECEPTACLE AND COVER PLATE TO MATCH
SURROUNDING WALL COLOR.
�4 NEW PANEL "A" 208Y/120V, 3PH, 4W WITH A 100A MAIN CIRCUIT BREAKER.
REFERTO SHEET E-3 FOR MORE DETAIL.
5 NEW TIME CLOCK FOR LIGHTING AND RECEPTACLES. REFER TO SHEET E2
FOR MODEL NUMBER. COORDINATE EXACT LOCATION PRIOR -f0 BID.
2'X 4'X 3/4" TELECOMM. BOARD WITH DEDICATED QUADRAPLEX
RECEPTACLE AND CIRCUIT WITH ISOLATED GROUND. VERIFY SYSTEM
GROUNDING AND ALL OTHER REQUIREMENTS WITH LOCAL TELEPHONE Q
COMPANY. EXTEND 1" TELEPHONE CONDUIT WITH PULL WIRE FROM
SERVICE ENTRANCE AT DEMISING WALL TO TELECOMM. BOARD. VERIFY
EXACT LOCATION IN FIELD. SEE SHEET E3 FOR FRANCESCA'S NOTES AND
DETAILS.
0 RECEPTACLE, DATA AND TELEPHONE OUTLET MOUNTED IN CASHWRAP
MILL WORK. COORDINATE EXACT PLACEMENT OF DEVICE AND WIRE
ROUTING IN CASHWRAP WITH MILLWORK DRAWINGS.
C) (1) 1" CONDUIT FOR POWER AND (1) 1" CONDUITS FOR TELEPHONE/DATA
UNDERFLOOR FROM CASHWRAP TO NEARBY WALL OR COLUMN, UP TO
ABOVE CEILING AND TO ELECTRICAL PANEL OR ,TELEPHONE BOARD AS
LABELED. STUB CONDUITS UP 16" ABOVE FINISHED FLOOR AT CASHWRAP.
SEE E3 FOR FRANCESCA'S NOTES AND DETAILS.
ELECTRIC WATER HEATER. CIRCUIT AS SHOWN.
1U PROVIDE WHIP AT 8'-6" AFF FOR FURNITURE. COORDINATE EXACT
PLACEMENT OF QUAD RECEPTACLE AND WIRE ROUTING WITH MILLWORK
DRAWINGS. SEE SHEET E2. FOR SWITCH LOCATION.
1.� PROVIDE WHIP AT 8'-6" AFF FOR FURNITURE. COORDINATE EXACT
PLACEMENT OF DUPLEX RECEPTACLE AND WIRE ROUTING WITH MILLWORK
DRAWINGS. MOUNT RECEPTACLE HORIZONTALLY, SEE SHEET E2. FOR
SWITCH LOCATION.
12 NEW VAV-1, CIRCUIT AS SHOWN. FIELD VERIFY EXACT CONNECTION
REQUIREMENTS PRIOR TO BID.
13 ONE (1) CAT5E LINE ROUTED ABOVE THE CEILING FROM A JUNCTION BOX IN
CONDUIT FROM THIS LOCATION TO THE TELEPHONE BOARD. LEAVE 12'-0"
OF SLACK AT EACH BOX. COORDINATE JUNCTION BOX LOCATION AND
CONDUIT ROUTING PRIOR TO INSTALLATION.
14 NEW 60A, 600V, FUSED DISCONNECT FUSED AT 60A TO FEED NEW 30KVA
TRANSFORMER. REFER To ONE -LINE DIAGRAM, SHEET E3 FOR ADDITIONAL
INFORMA'HON.
15 NEW 30KVA 48UV-TO-208Y/120V TRANSFORMER. MOUNT TRANSFORMER ON
WALL ABOVE PANEL.
PARTNERS
brand . operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE#1311C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
s
ee
N �.
0 67023 d
5�.+ • /+_ QVC
���rBd11999ASa�'®e
1 it 6AA �fl `2
ISSUE DATES
PRELIM SET: 10-16-2013
x FINAL SET: 11-6-2013
'Y PERMIT SET: 11-20-2013
REVISIONS
1
DRAWING NUMBER
I�
POWER PLAN
,3 !.v','{1
ADJACENT TENANT'
Y
p
{
s
F
a
1
CO C -CO
1
a
C !
E a. ....v
® . I.,. DW(4)
..
........,..
CCa
I E $
3
E � � a
I i 1
q IA A A
A-19 T(IR 4 -011
' ... .,,u SW "h'I
2
1
0S D
rtm�emim" E
8 -0 jJF
A,
iii
z
!
! I
n I QW(5) DW 5; A1b
F 18'-0"
} IX4 _ ) I DW 5
L! ! ]j
u! , I f f g�
F ?
Q
Q A-15 1
E
THRU;
SWITCH 'V'i
41E
,
I
s
E
n 5
p n
,
X7
B -CO
5
..,a
A- d
3 3
s X QW U4 1 A-1aE
-..........0
11
LIGHTING FIXTURE SCHEDULE
SYMBOL
DESCRIPTION
MANUFACTURER
MODEL NUMBER
LAMP
WATTAGE
VOLTS
MOUNTING
FURNISHED BY
2.
6" RECESSED NEW CONSTRUCTION LED DOWNLIGHT ON
A-18
"THRU-WIRING" WHERE AND WHENEVER POSSIBLE. MULTIPLE CONNECTIONS TO A SINGLE LIGHT
A-19
FIXTURE FOR VOLTAGE DROP CONDITIONS OR AS A RESULT OF A FIELD CONDITION ARE
SALES
ACCEPTABLE. LIGHTING FIXTURES SHALL BE MANUFACTURED TO ACCOMMODATE "THRU-WIRING".
SALES
A
SALES FLOOR. 1000 LUMEN, 90+ CRI, 3000K, WITH WHITE
DMF
#DLE16/DM10930-L60W
LED INCLUDED
15
120V
RECESSED
FRANCESCA'S
FURNITURE
ENSURE THE ADJUSTABILITY OF ALL DIRECTIONAL FIXTURES AFTER INSTALLATION AND AIM THEM.
ROOM
LIGHT FIXTURE SPECIFICATION MAY VARY. IF CEILING SYSTEMS ARE FIRE RATED, CONTRACTOR IS
LIGHTS
TO CLOSELY COORDINATE FIXTURE REQUIREMENTS WITH TENANT'S LIGHTING SUPPLIER.
.5.
EMERGENCY AND EXIT LIGHTS SHALL BE INSTALLED AND CIRCUITED PER THE LATEST NATIONAL
COLLECTIONS
ELECTRIC CODE AND ALL LOCAL CODES. ALL EMERGENCY AND EXIT FIXTURES SHALL BE DUAL
METAL TRIM
VOLTAGE WITH BATTERY BACKUP (120/277 VOLT INPUT). CLOSELY COORDINATE INSTALLATION WITH
TENANT'S CONSTRUCTION MANAGER.
6.
ALL LIGHTING CIRCUITS UP TO 100'-0" IN LENGTH SHALL UTILIZE #12 CONDUCTORS MINIMUM. ALL
LIGHTING CIRCUITS FROM '101'-0" TO 150'-0" IN LENGTH SHALL UTILIZE #10 CONDUCTORS MINIMUM.
LIGHTS
PEY'I"ON SAL -SPRAY COLLECTION 6+3 LIGHT
CIRCUITS ABOVE 251'-0" SHALL UTILIZE #6 CONDUCTORS MINIMUM.
MARTEK (9)
ELECTRICAL CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS AS REQUIRED FOR A FULLY
CHAIN HUNG @ 7'-6"
FRANCESCA'S
B -GO
CHANDELIER IN WHITE FINISH
MURRAY-FIESS
#F2534/6+3WH
#nLED-JFF-2700K-DIM-ALU
32
120V
AFF
COLLECTIONS
CONFLICTS. JUNCTION BOXES ABOVE LAY -IN CEILINGS ARE ACCEPTABLE.
9.
EXIT/EMERGENCY LIGHTS AT STOREFRONT ARE TO BE CEILING MOUNTED AND CENTERED OVER
OPENING (TYPICAL U.N.0). EXIT/EMERGENCY LIGHTS AT DOOR TO "NON -SALES" SHALL BE CENTERED
ON WALL ABOVE DOOR. FIELD VERIFY EXACT LOCATION AND MOUNTING HEIGHT WITH TENANTS
C -CO
PEYTON SALTSPRAY COLLECTION 1 LIGHT WALL SCONCE
MURRAY FIESS
#WB1486SGW
SATCO
60
120V
WALL MOUNTED
FRANCESCA'S
IN WHITE FINISH
(1) 601310/F -130V
COLLECTIONS
DW
WHITE PAR38 FRONTLOAD GIMBAL TRACK HEAD
NORA
#NTH -148W
MSI
(1) XPAR383025114TN
14
120V
TRACK MOUNTED
FRANCESCA'S
COLLECTIONS
D -TW
WHITE 8'1 CIRCUIT TRACK. CONTACTOR TO FIELD CUT
NORA
#NT -304W
-
120V
TRACK MOUNTED
FRANCESCA'S
TO LENGTH
COLLECTIONS
USHIO
E
BATHROOM FAN/LIGHT COMBO IN WHITE FINISH, 110CFM
CRAFTMADE
#TV110SL
(2) CF18DE/835
39
120V
SURFACE
FRANCESCA'S
(INCLUDED)
COLLECTIONS
4FT TWO LAMP SURFACE MOUNTED WRAP AROUND
USHIO
ELECTRICAL
F
FIXTURE FOR STOCKROOM
COLUMBIA
#WC4 232 -EU
(2) #F32 -F8/83058
120V
SURFACE
CONTRACTOR
PUBLIC AREA LED EDGE LIT EXIT SIGN CEILING/WALL
X1
SURFACE MOUNT WITH RED LETTERING ON CLEAR BACK
BEST
#ELXTEUI RCAEM
INCLUDED
-
120V
SEE PLAN - MOUNT ON
FRANCESCA'S
GROUND, SILVER FINISH, AND EMERGENCY BATTERY
WALL OR CEILING
COLLECTIONS
BACK OF HOUSE LED PLASTIC EMERGENCY/EXIT COMBO
X3
SIGN CEILING/WALL SURFACE NOUN WITH RED
BEST
#CXTEU2RW
INCLUDED
-
120V
SEE PLAN - MOUNT ON
FRANCESCA'S
LETTERING, WHITE FINISH, AND EMERGENCY BATTERY
WALL OR CEILING
COLLECTIONS
PUBLIC AREA EMERGENCY BUG EYE FIXTURE WITH
X4
STANDARD LUMEN 5AW MR16 LAMPS IN A WHITE FINISH.
BEST
#RMR-16
(2) 5AW MR16 FLOOD
-
120V
SEE PLAN - MOUNT ON
FRANCESCA'S
FOR USE IN CEILINGS/WALLS 12FT AND UNDER
LAMPS INCLUDED
WALL OR CEILING
COLLECTIONS
125W 120V EMERGENCY POWER INVERTER WITH
FRANCESCA'S
X7
SWITCHABLE INPUT. WILL SUPPORT UP TO 8
ISOLITE
#IMI -125 -LC -VI -TB
-
125
120V
SURFACE(WALL)
COLLECTIONS
DOWNLIGHTS.
NOTE: ALL FIXTURES INDICATED AS EMERGENCY (EM OR SHADED) SHALL BE PROVIDED WITH EMERGENCY BATTERY PACKS. BATTERY PACKS SHALL BE AS FOLLOWS:
- LINEAR T8 FLUORESCENT LAM PS -BOD INE#B50/1350 LUMENS MINIMUM -2/1 LAMP OPERATION
- COMPACT FLUORESCENT LAMPS-BODINE#B84C/1000 LUMENS MINIMUM -2/1 LAMP OPERATION.
- COMBINATION TEST SWITCH/CHARGE LIGHT.
ALTERNATE OR EQUALS TO BE PRE -APPROVED BY ARCHITECT AND ELECTRICAL ENGINEER.
PROVIDE EMERGENCY REFLECTORS OR HOUSINGS WHEN OPTION IS AVAILABLE FROM MANUFACTURER TO ALLOW FOR INSTALLATION OF BATTERY PACKS, TEST SWITCHES, PILOT LIGHTS, ETC. WITHIN FIXTURE.
WHEN OPTIONAL EMERGENCY REFLECTORS OR HOUSINGS ARE NOT AVAILABLE, REMOTE BATTERY PACKS, TEST SWITCHES, PILOT LIGHTS, ETC. ARE TO BE INSTALLED IN THE MOST CONSPICUOUS LOCATION AS ALLOWED BY
CODE AND LOCAL AHJ REQUIREMENTS. IF NECESSARY, COORDINATE LOCATION WITH ARCHITECT AND/OR ELECTRICAL ENGINEER PRIOR TO ANY ROUGH -IN.
ADJACENT TENANT'
Y
p
{
s
F
a
1
CO C -CO
1
a
C !
E a. ....v
® . I.,. DW(4)
..
........,..
CCa
I E $
3
E � � a
I i 1
q IA A A
A-19 T(IR 4 -011
' ... .,,u SW "h'I
2
1
0S D
rtm�emim" E
8 -0 jJF
A,
iii
z
!
! I
n I QW(5) DW 5; A1b
F 18'-0"
} IX4 _ ) I DW 5
L! ! ]j
u! , I f f g�
F ?
Q
Q A-15 1
E
THRU;
SWITCH 'V'i
41E
,
I
s
E
n 5
p n
,
X7
B -CO
5
..,a
A- d
3 3
s X QW U4 1 A-1aE
-..........0
11
LIGHTING PLAN
E2m01 SCALE: 1/4"=1'-0"
F
8'0"
I
A-7 THRU
SWITCH
.,.,.,.,... ..
j E
i
i
x s
.. A' I
1
DW(4) $. -.O
6'-0.. :
{
, r
Ij
2 'A_1 b
If
P'
A-1 s I1x
�d
1.
X1 � E ,
A ' , ' >
,. I I
� 3.s Q� `I � I��`• .
-1a
� a1
4
F p•
-Alb',
a
1
, 3
AQ DW(4)
4
`
A-1 b 15 6 0" ��i\\' DW(3)
w..N,. D...5 4,,0113.
_I $, "N
�.�. 7
ZZ-1-99Ly
=^"
1 'QW(3)
A-3 )THRU I ` a—
A-13 THRU
TIMECLOCK
LANDLORD REQUIREMENTS:
• ALL HOME RUNS TO TENANT'S PANELS SHALL BE IN RIGID STEEL
CONDUIT OR EMT.
• ALL EXPOSED WIRING IN CEILINGS OR INTERIOR WALLS MUST BE IN
RIGID STEEL CONDUIT OR EMT.
• ALL WIRING IN LANDLORD DEMISING WALLS MUST BE IN RIGID STEEL
CONDUIT OR EMT.
•
COORDINATE ALL FLOOR GUT MEANS AND METHODS OF ROUTING
CONDUIT THROUGH THE FLOOR WITH MALL OPERATIONS.
NO CONDUIT TO BE SUPPORTED FROM THE ROOF DECK.
NOTE TO BIDDERS/CONTRACTOR
THESE DRAWINGS WERE PREPARED AS ACCURATELY AS POSSIBLE UTILIZING EXISTING DRAWINGS. IT
SHALL BE THE CONTRACTORS RESPONSIBILITY TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO THE
BIDDING AND COMMENCEMENT OF THE PROJECT. CLAIMS FOR EXTRAS RESULT FROM LACK OF
COMPLIANCE WILL BE DENIED.
GENERAL NOT S:
1.
I
E !
2
s
LIGHTING PLAN
E2m01 SCALE: 1/4"=1'-0"
F
8'0"
I
A-7 THRU
SWITCH
.,.,.,.,... ..
j E
i
i
x s
.. A' I
1
DW(4) $. -.O
6'-0.. :
{
, r
Ij
2 'A_1 b
If
P'
A-1 s I1x
�d
1.
X1 � E ,
A ' , ' >
,. I I
� 3.s Q� `I � I��`• .
-1a
� a1
4
F p•
-Alb',
a
1
, 3
AQ DW(4)
4
`
A-1 b 15 6 0" ��i\\' DW(3)
w..N,. D...5 4,,0113.
_I $, "N
�.�. 7
ZZ-1-99Ly
=^"
1 'QW(3)
A-3 )THRU I ` a—
A-13 THRU
TIMECLOCK
LANDLORD REQUIREMENTS:
• ALL HOME RUNS TO TENANT'S PANELS SHALL BE IN RIGID STEEL
CONDUIT OR EMT.
• ALL EXPOSED WIRING IN CEILINGS OR INTERIOR WALLS MUST BE IN
RIGID STEEL CONDUIT OR EMT.
• ALL WIRING IN LANDLORD DEMISING WALLS MUST BE IN RIGID STEEL
CONDUIT OR EMT.
•
COORDINATE ALL FLOOR GUT MEANS AND METHODS OF ROUTING
CONDUIT THROUGH THE FLOOR WITH MALL OPERATIONS.
NO CONDUIT TO BE SUPPORTED FROM THE ROOF DECK.
NOTE TO BIDDERS/CONTRACTOR
THESE DRAWINGS WERE PREPARED AS ACCURATELY AS POSSIBLE UTILIZING EXISTING DRAWINGS. IT
SHALL BE THE CONTRACTORS RESPONSIBILITY TO FIELD VERIFY EXISTING CONDITIONS PRIOR TO THE
BIDDING AND COMMENCEMENT OF THE PROJECT. CLAIMS FOR EXTRAS RESULT FROM LACK OF
COMPLIANCE WILL BE DENIED.
GENERAL NOT S:
1.
THE CONTRACTOR FOR THIS WORK IS REQUIRED TO READ THE SPECIFICATIONS AND REVIEW
DRAWINGS OF ALL DIVISIONS OF WORK AND IS RESPONSIBLE FOR THE COORDINATION OF THIS
2
WORK AND THE WORK OF ALL SUBCONTRACTORS WITH ALL DIVISION OF WC)HK. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO PROVIDE ALL SUBCONTRACTORS WITH A COMPLETE SET OF
OE.C.
BID DOCUMENTS.
2.
LIGHTING SHALL BE CIRCUITED EXACTLY AS SHOWN ON PLANS. CIRCUITING SHALL BE
A-18
"THRU-WIRING" WHERE AND WHENEVER POSSIBLE. MULTIPLE CONNECTIONS TO A SINGLE LIGHT
A-19
FIXTURE FOR VOLTAGE DROP CONDITIONS OR AS A RESULT OF A FIELD CONDITION ARE
SALES
ACCEPTABLE. LIGHTING FIXTURES SHALL BE MANUFACTURED TO ACCOMMODATE "THRU-WIRING".
SALES
ANY RELATED COSTS FOR MULTIPLE CONNECTIONS SHALL BE INCLUDED IN BID.
3.
SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION AND QUANTITY OF LIGHTING
CHANGING
FIXTURES.
4.
ELECTRICAL CONTRACTOR'S BID SHALL INCLUDE THE INSTALLATION OF ALL LIGHT FIXTURES AND
DECORATIVE
ASSOCIATED LAMPS FURNISHED BY TENANT. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO
FURNITURE
ENSURE THE ADJUSTABILITY OF ALL DIRECTIONAL FIXTURES AFTER INSTALLATION AND AIM THEM.
ROOM
LIGHT FIXTURE SPECIFICATION MAY VARY. IF CEILING SYSTEMS ARE FIRE RATED, CONTRACTOR IS
LIGHTS
TO CLOSELY COORDINATE FIXTURE REQUIREMENTS WITH TENANT'S LIGHTING SUPPLIER.
.5.
EMERGENCY AND EXIT LIGHTS SHALL BE INSTALLED AND CIRCUITED PER THE LATEST NATIONAL
LIGHTS
ELECTRIC CODE AND ALL LOCAL CODES. ALL EMERGENCY AND EXIT FIXTURES SHALL BE DUAL
GENERAL
VOLTAGE WITH BATTERY BACKUP (120/277 VOLT INPUT). CLOSELY COORDINATE INSTALLATION WITH
TENANT'S CONSTRUCTION MANAGER.
6.
ALL LIGHTING CIRCUITS UP TO 100'-0" IN LENGTH SHALL UTILIZE #12 CONDUCTORS MINIMUM. ALL
LIGHTING CIRCUITS FROM '101'-0" TO 150'-0" IN LENGTH SHALL UTILIZE #10 CONDUCTORS MINIMUM.
LIGHTS
ALL LIGHTING CIRCUITS FROM 150'-0" TO 250'-0" IN LENGTH SHALL UTILIZE #8 CONDUCTORS MINIMUM.
CIRCUITS ABOVE 251'-0" SHALL UTILIZE #6 CONDUCTORS MINIMUM.
7.
ELECTRICAL CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS AS REQUIRED FOR A FULLY
COMPLETE AND OPERABLE SYSTEM.
8.
WHERE DRY WALL CEILINGS ARE USED IN THE "SALES" AREA, THE ELECTRICAL CONTRACTOR SHALL
ARRANGE CIRCUITS TO AVOID THE USE OF JUNCTION BOXES IN INACCESSIBLE LOCATION. THE USE
OF JUNCTION BOXES ABOVE DRY WALL CEILINGS SHALL BE LIMITED TO LOCATIONS NEAR ACCESS
FRAMES USED FOR DIFFUSERS AND RETURN AIR GRILLES OR ACCESS PANELS AS LOCATED ON
PLANS. FIELD COORDINATE WITH TENANT'S PROJECT MANAGER PRIOR TO ROUGH -IN TO AVOID ANY
CONFLICTS. JUNCTION BOXES ABOVE LAY -IN CEILINGS ARE ACCEPTABLE.
9.
EXIT/EMERGENCY LIGHTS AT STOREFRONT ARE TO BE CEILING MOUNTED AND CENTERED OVER
OPENING (TYPICAL U.N.0). EXIT/EMERGENCY LIGHTS AT DOOR TO "NON -SALES" SHALL BE CENTERED
ON WALL ABOVE DOOR. FIELD VERIFY EXACT LOCATION AND MOUNTING HEIGHT WITH TENANTS
CONSTRUCTION MANAGER PRIOR TO ROUGH -IN.
10.
ELECTRICAL CONTRACTOR TO FURNISH AND INSTALL A POLY PULL STRING IN ALL EMPTY CONDUITS
N
CONFIGURATION
FOR FUTURE USE. SECURE PULL STRING AT BOTH ENDS OF CONDUIT.
KEYED NOTES:
1
PROVIDE JUNCTION BOX WITH DISCONNECT SWITCH IN CONCEALED LOCATION FOR CONNECTION
TO STORE FRONT SIGN LIGHTING. LOCATE DISCONNECT PER NEC 600.6
2
CIRCUIT NIGHT, EMERGENCY, AND EXIT LIGHTING FIXTURES AHEAD OF CONTROLS. PROVIDE NEW
BALLAST AS REQUIRED.
OE.C.
TO PROVIDE CURRENT -LIMITING BREAKER AT END OF TRACK.
A-5
REFER TO SWITCH BANK DETAIL, THIS SHEET, FOR LIGHTING CONTROLS FOR THE SPACE.
A-18
CONNECT LIGHT TO EMERGENCY INVERTER'X8' FOR EMERGENCY LIGHTING IN THIS SPACE.
E2mO3 SWITCH BANK
SCALE: NTS.
TIME CLOCK: TORK #1847AW, OR
'ALF -NT BY PARAGON.
E, 20 AMP, 600V., MECHANICALLY HELD
1NG CONTACTOR WITH 2 -WIRE CONTROL
( AND 120V AC COIL - SQUARE D CLASS
_X SERIES OR EQUAL.
BLEARING CONTACTS (SUPPLIED)
i UNLATCH i
A-13 i i I SIGN `
SPARE I� j SPARE
SPARE
SPARE E `
LIGHTING CONTROLS DIAGRAM
E2"02
SCALE: N.T.S.
IWPARTNERS
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE #1311C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
ISSUE DATES
PRELIM SET: 10-16-2013
�� FINAL SET: 11-6-2013
© PERMIT SET: 11-20-2013
REVISIONS
LIGHTING
PLAN
lf:e!'I
i'IjYI
,. .. ,.. ... .. i.. .. ;.. :. r..: ,.�.. ... .... .... .. ... .. :... ..", ,. ,.. :� .:.� �,.. ..
A-1
A-1
A-3
A-5
A-15
A-18
A-%
A-19
SALES
SALES
SALES
SALES
BACK
SALES
SALES
CHANGING
GENERAL
GENERAL
DISPLAY
DECORATIVE
ROOM
FURNITURE
DISPLAY
ROOM
LIGHTS
LIGHTS
LIGHTS
LIGHTS
LIGHTS
LIGHTS
LIGHTS
GENERAL
LIGHTS
NOTE:-
T F
CONTRACTOR O VERIFY E I Y XA T E C
N
CONFIGURATION
REQUIRED WITH H SPACE AVAILABLE.
PROVIDE LABELS
AS DIRECTED
BY OWNER. SWITCHES SHALL NOT BE MOUNTED HIGHER THAN 48".
E2mO3 SWITCH BANK
SCALE: NTS.
TIME CLOCK: TORK #1847AW, OR
'ALF -NT BY PARAGON.
E, 20 AMP, 600V., MECHANICALLY HELD
1NG CONTACTOR WITH 2 -WIRE CONTROL
( AND 120V AC COIL - SQUARE D CLASS
_X SERIES OR EQUAL.
BLEARING CONTACTS (SUPPLIED)
i UNLATCH i
A-13 i i I SIGN `
SPARE I� j SPARE
SPARE
SPARE E `
LIGHTING CONTROLS DIAGRAM
E2"02
SCALE: N.T.S.
IWPARTNERS
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE #1311C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
ISSUE DATES
PRELIM SET: 10-16-2013
�� FINAL SET: 11-6-2013
© PERMIT SET: 11-20-2013
REVISIONS
LIGHTING
PLAN
lf:e!'I
i'IjYI
,. .. ,.. ... .. i.. .. ;.. :. r..: ,.�.. ... .... .... .. ... .. :... ..", ,. ,.. :� .:.� �,.. ..
A-1
A-1
A-3
A-5
A-15
A-18
A-%
A-19
SALES
SALES
SALES
SALES
BACK
SALES
SALES
CHANGING
GENERAL
GENERAL
DISPLAY
DECORATIVE
ROOM
FURNITURE
DISPLAY
ROOM
LIGHTS
LIGHTS
LIGHTS
LIGHTS
LIGHTS
LIGHTS
LIGHTS
GENERAL
LIGHTS
E2mO3 SWITCH BANK
SCALE: NTS.
TIME CLOCK: TORK #1847AW, OR
'ALF -NT BY PARAGON.
E, 20 AMP, 600V., MECHANICALLY HELD
1NG CONTACTOR WITH 2 -WIRE CONTROL
( AND 120V AC COIL - SQUARE D CLASS
_X SERIES OR EQUAL.
BLEARING CONTACTS (SUPPLIED)
i UNLATCH i
A-13 i i I SIGN `
SPARE I� j SPARE
SPARE
SPARE E `
LIGHTING CONTROLS DIAGRAM
E2"02
SCALE: N.T.S.
IWPARTNERS
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE #1311C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
ISSUE DATES
PRELIM SET: 10-16-2013
�� FINAL SET: 11-6-2013
© PERMIT SET: 11-20-2013
REVISIONS
LIGHTING
PLAN
lf:e!'I
i'IjYI
,. .. ,.. ... .. i.. .. ;.. :. r..: ,.�.. ... .... .... .. ... .. :... ..", ,. ,.. :� .:.� �,.. ..
NEC ELECTRICAL LOAD SUMMARY
SIZE: 100 AMP MCB FEEDER: # 3 W/#8 G IN 11/4" C CU SETS: 1 OPTIONS: NONE NEMA: 1
ELECTRICAL LOAD
MOUNTING: SURFACE VOLTAGE: 208Y/120V CONFIG: 3 PHASE 4 WIRE NEUTRAL: 100% TVSS: NO
CONNECTED
NEC DEMAND
USE
NEC REFERENCE
LIGHTING ZONE -L1 VA/FT2
0.00
730
913
KW PER PHASE
220.12,42
LIGHTING ZONE -1_2 VA/FT2
0.00
0
0
U)
w
a
220.12,42
LIGHTING ZONE -L3 VA/FT2
0.00
0
0
220.12,42
TRACK - TL (FT)
96
952
6,840
220.43(B)
SIGNS - S (EA)
1
1,000
1,250
�
220.14(F)
SHOW WINDOW - SW (FT)
RATING
_ 0
0
220.14(G),43(A)
DF = DIVERSITY FAC TOR
RECEPTACLES - R
3,780
3,780
100%
220.14(H,I & K),44
KITCHEN RESISTIVE - KR
2,100
2,100
_
100%u
220.56
KITCHEN MOTORS - KM
0
0
100%
220.56
COOLING MOTORS - C
0
0
100%
220.40,50,60
HEATING - H
0
0
_
100%
220.40,50,51,60
OTHER MOTORS - OM
MAX MOTOR HP 0
0
N/A
0
0
100%
220.40,50
220.40,50
WATER HEATERS - WH
4,160
4,160
100%
220.40
OTHER - 0
100
100
100%
220.40
LTG - SALES TRACK
j---
0.43
` `
TOTAL KW
12.8
19.1
POWER FACTOR: 99%
LIGHTING AREA - Al
5.0
FT2 LIGHTING - L1
0.00
W/FT2
LIGHTING AREA - A2
20
FT2 _i
LIGHTING - L2
0.00
W/FT2
LIGHTING AREA - A3
FT2
LIGHTING - L3
0.00
W/FT2
LIGHTING AREA
0
FT2
TOTAL LIGHTS:
0.00
W/FT2
COOLING AREA
0
FT2 COOLING - C
0.00
W/FT2
HEATING AREA
CONNECTED:
0
0.00
FT2 HEATING - H
W/FT2 NEC DEMAND:
0.00 W/FT2
0.00 W/FT2
SYSTEM VOLTAGE; 480
VOLTS PHASES: 3
CONNECTED: 15.6
AMPS NEC DEMAND: 23.3
AMPS
MOTOR CONTRIBUTION: 0.0
KW CONFIGURATION: 3 PHASE 4 WIRE
�= PANELBOARD: A
SIZE: 100 AMP MCB FEEDER: # 3 W/#8 G IN 11/4" C CU SETS: 1 OPTIONS: NONE NEMA: 1
SERVICE ENTRANCE: NO LENGTH: 50 FT CCNDUIT TYPE: ST TYPE: LIGHTING & APPLIANCE VOLTAGE DROP: 0.37%
MOUNTING: SURFACE VOLTAGE: 208Y/120V CONFIG: 3 PHASE 4 WIRE NEUTRAL: 100% TVSS: NO
LOCATION: ELECTRIC ROOM FED FROM: DP DIRECTION: TOP BRANCH MOUNT: BOLT -ON BUS MATERIAL: CU
CIRCUIT
OC
w
co
a
w
a
w
o
DESCRIPTION
KW PER PHASE
KW PER PHASE
DESCRIPTION
o
0
U)
w
a
OC
CIRCUIT
N0.
RATING
a
z
2-1
�
¢
a
RATING
NO.
q
g
C
A
B
C
1
20
1
2.1
L1
LTG - SALES
0.25
' -
0.36
--
RECEPT. - MGR'S DESK
R
3.0
1
20
2
3
20
1
3.8
TL
LTG - SALES TRACK
j---
0.43
` `
0.60
` -
REFRIGERATOR
KR
5.0
1
ZO
4
5
20
1
1.9
L1
LTG - DECORATIVE
'
.21
__
_
1.50
MICROWAVE
KR
_
12.5
1
20
6
7
20
1
4.5
TL
LTG - SALES TRACK
0.52
0.36
-_
-__
RECEPT. - PHONE BOARD
R
3.0
1
20
8
9
20
1
SPARE
-
-__
___
0.54
><
RECEPT. - BOH
R _
4.5
1
20
10
11
20
1
1.5
R
RECEPT. - BACKWRAP
`' -
-_
0.18
-
-__
0.72
RECEPT. - SALES
T
R
6.0
1
20
12
13
20
1
8.8
S
STOREFRONT SIGN
1.00
-__
'` ___
0.18
_
i
RECEPT. - CASHWRAP
R
1.5
1
20
14
15
20
2.0
L1
LTG - BOH
` -__
0.18
` --
1
20
1
0.22
RECEPT. - CASHWRAP
R
1.5
16
20
1
4.5
R
RECEPT. - STOREFRONT
-
0.54
�' `
0.72
RECEPT. - FURNITURE
R
6.0
1
20
18
r2l
20
1
0.4
L1T
LTG - FITTING ROOM
0.05
jam
�'
'�
2.08
'` `
WATER HEATER
WH
20.0
_
2
30
20
SPARE
\
2.08
WATER HEATER
WH
20.0
2
30
22
23
SPARE.
-_
�.
0.10
VAV-1
0
0.8
1
20
24
25
SPARE
_
!�
SPARE
26
27
SPARE
_
SPARE
28
29
_
SPARE
f.
SPARE
30
GROUND: SOLID
DIVERSITY: 105% 4.8 KW -A 4.1 KW -B 4.0 KW -C
SCCR: 42 kAIC
BALANCE: 87% CONNECTED: 12.8 KW 36.0 AMPS
SPEC. SECTION 262416
PF: 99% DEMAND: 13.5 KW 37.9 AMPS
TYPE: H -HEATING, C -COOLING, KR -KITCHEN RESISTIVE, KM -KITCHEN MOTOR, WH -WATER HEATER, OM -OTHER MOTOR, L1,L2 OR 1 -3 -LIGHTING, TL -TRACK LIGHTING, S -SIGNS, SW-SHUVV WINUUW,
R -RECEPTACLES, SF -SUB FEED, 0 -OTHER, E-EXISITNG SIZE: MLO -MAIN 1.UG ONLY, MCB-MAIN CIRCUIT BREAKER NOTE: GF -GROUND FAULT, AF -ARC FAULT, E -EXISTING
TC -VIA TIME CLOCK, ST -SHUNT TRIP, LC -LOCK ON, PC -PHOTO CELL CONTROLLED OPTIONS: SFL-SUB FEED LUGS, FTL•FEED THRU LUGS
(2) #1
A-24
" "' EEDER (3) #6 &
3ND IN 1 "C BY E.C.
UIJI.rui\wiLki I JVVI I url
WITH 60A FUSES.
ONE -LINE DIAGRAM
E3.01 SCALE: N.T.S.
NEW 60A, 3 -POLE
DISCONNECT SWITCH
WITH 60A FUSES.
I
I
I-LANDLORD'S EXISTING
480Y/277V, 3 -PH, 4W
DISTRIBUTION PANEL
GENERAL NOTE:
A. CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH THE EXISTING
CONDITIONS UNDER WHICH HE IS TO PERFORM HIS WORK. NO ALLOWANCE WILL BE MADE
FOR FAILURE TO COMPLY.
B. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE 1993 (OR LA -TEST
ADOPTED) NATIONAL ELECTRICAL CODE AND ALL APPLICABLE FEDERAL, STATE AND LOCAL
CODES AND ORDINANCES.
C. VERIFY EXACT LOCATION, MOUNTING HEIGHT AND ELECTRICAL REQUIREMENTS OF ALL
EQUIPMENT PROVIDED BY OTHERS (INCLUDING HVAC EQUIPMENT) PRIOR TO ROUGH -IN AND
PROVIDE ALL REQUIRED FUSIBLE SWITCHES, TRANSFORMERS, STARTERS NECESSARY FOR
PROPER OPERATION OF EQUIPMENT.
E. DUPLEX RECEPTACLES MOUNTED WITHIN 6FT. OF SINK TO BE A GFI RECEPTACLE.
F. ALL WIRING SHALL BE COPPER, THHN/THWN OR XHHW INSULATED IN CONDUIT. MINIMUM
CONDUIT SIZE TO BE 1/2". PROVIDE INSULATED COPPER BOND WIRE ON ALL CIRCUITS.
G. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF LIGHT FIXTURES. VERIFY
CEILING TYPES AND PROVIDE NECESSARY MOUNTING HARDWARE TO ACCOMMODATE LIGHT
FIXTURES USED. PROVIDE SLOPE CEILING ADAPTERS WHERE REQUIRED.
H. ADDITIONAL EXIT SIGNS AND EMERGENCY LIGHTING MAY BE REQUIRED. ADDITIONAL
FIXTURES SHALL BE LOCATED AS DIRECTED BY THE LOCAL BUILDING AUTHORITY.
ACCESSIBLE NOTE:
LIGHT SWITCHES, ELECTRICAL OUTLETS, -THERMOSTATS AND OTHER ENVIRONMENTAL
CONTROLS SHALL HAVE OPERABLE PARTS OF THE CONTROLS LOCATED NO HIGHER THAN 48"
AND NO LOWER THAN 15" ABOVE THE FLOOR. IF THE REACH IS OVER AN OBSTRUCTION BETWEEN
20" AND 25" IN DEPTH. THE MAXIMUM HEIGHT IS REDUCED -TO 44" FOR FORWARD APPROACH OR
46" FOR SIDE APPROACH, PROVIDED THE OBSTRUCTION IS NO MORE THAN 24" IN DEPTH.
OBSTRUCTIONS SHALL NOT EXTEND MORE'THAN 25" FROM'THE WALL BENEATH A CONTROL,
LANDLORD REQUIREMENTS:
• PRIOR TO BID, TENANT IS REQUIRED TO VERIFY THAT -THE LANDLORD'S
EXISTING AVAILABLE ELECTRICAL SERVICE MEETS THE TENANTS TOTAL
CONNECTED LOAD.
• TGC TO SURVEY ALL EXISTING ELECTRICAL EQUIPMENT AND VERIFY
ANY ADDITIONAL LANDLORD WORK TO BE COMPLETED. VERIFY WITH
MALL OPERATIONS.
• COORDINATE ALL NEW ROUTING OF CONDUIT, FEEDER CABLES, AND
CONNECTIONS TO LANDLORD'S MAIN ELECTRICAL GEAR WITH MALL
OPERATIONS..
• ANY AND ALL UPGRADES TO EXISTING EQUIPMENT SHALL BE AT TGC AT
TENANTS EXPENSE.
mdPARTNERS
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OH 43017
614.634.7000 T
WDPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE #R11 C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
Ova ®.4e ff
D
S• K
C E /VSA°. �<j
No 67p23
O °o905 tl.
4
e;...., �,o9ZONAL e"
fid, I I I M 11110
NOV 2 0 20J3
ISSUE DATES
PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
PERMIT SET: 11-20-2013
REVISIONS
All
DRAWING NUMBER
ELEC. RISER &
SCHEDULES
u., - -
x :;'.:. '.�} a +...e.,r.. .., ,.�. ': ...., ., ...41 r7 :.: :�, Y.yt,, r> •.. ., is '.; Y', r.. >..r ,.�:.. >.e '.S ..4 xn .... ., . , ., .
I r' �
DIVISION 16000 - ELECTRICAL
SECTION 16001 - BASIC ELECTRICAL REQUIREMENTS
A. GENERAL CONDITIONS
1. DRAWINGS AND GENERAL PROVISIONS OF CONTRACT, INCLUDING GENERAL AND
SUPPLEMENTARY CONDITIONS AND ALL OTHER SPECIFICATION SECTIONS, APPLY TO THIS AND THE
OTHER SECTIONS OF DIVISION 16000.
2. THE CONTRACTOR FOR THIS WORK IS REQUIRED TO READ THE SPECIFICATIONS AND REVIEW
DRAWINGS FOR ALL DIVISIONS OF WORK AND IS RESPONSIBLE FOR THE COORDINATION OF THEIR
WORK AND THE WORK OF THEIR SUBCONTRACTOR'S WITH ALL DIVISIONS OF WORK. IT IS THIS
CONTRACTOR'S RESPONSIBILITY TO PROVIDE THEIR SUBCONTRACTORS WITH A COMPLETE SET OF
BID DOCUMENTS.
3. THIS CONTRACTOR IS RESPONSIBLE FOR SCHEDULING THE COMPLETION AND INSPECTION OF
THEIR WORK AND THE WORK OF THEIR SUBCONTRACTORS WORK TO COMPLY WITH THE SCHEDULE
AND THE PROJECT COMPLETION DATE.
4. THIS CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMITTAL OF BID TO DETERMINE CONDITIONS
AFFECTING THE WORK ANY ITEMS WHICH ARE NOT COVERED IN THE BID DOCUMENTS OR ANY
PROPOSED SUBSTITUTIONS SHALL BE LISTED SEPARATELY AND QUALIFIED IN THE CONTRACTOR'S
BID. SUBMITTAL OF BID SHALL SERVE AS EVIDENCE OF KNOWLEDGE OF EXISTING CONDITIONS AND
ANY MODIFICATIONS WHICH ARE REQUIRED TO MEET THE INTENT OF THE DRAWINGS AND
SPECIFICATIONS. FAILURE TO VISIT THE SITE DOES NOT RELIEVE THE CONTRACTOR OF
RESPONSIBILITY IN PERFORMANCE OF WORK.
5. REFER TO RESPONSIBILITY SCHEDULE ON THE ELECTRICAL DRAWINGS FOR INFORMATION IN
REGARD TO RESPONSIBILITY OF WORK OR ITEMS WHICH MAY AFFECT BID.
SECTION 16002 - GENERAL REQUIREMENTS
A. THIS CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, EQUIPMENT, SERVICES, TOOLS,
TRANSPORTATION, INCIDENTALS AND DETAILS NECESSARY TO PROVIDE COMPLETE ELECTRICAL
SYSTEMS AS SHOWN ON THE DRAWINGS, CALLED FOR IN THE SPECIFICATIONS, AND AS REQUIRED BY
JOB CONDITIONS. ALL WORK NOT SPECIFICALLY NOTED AS BEING BY THE LANDLORD, OR TENANT
SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR. CLOSELY COORDINATE THE ENTIRE
INSTALLATION WITH LANDLORD, AND THE TENANT PROJECT MANAGER AS REQUIRED.
B. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY
MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE PROVIDED EVEN THOUGH NOT SPECIFICALLY
MENTIONED IN BOTH. ANY MATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR
CALLED FOR IN THE SPECIFICATIONS, BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE
WORK OR WHICH IS USUALLY INCLUDED IN WORK OF SIMILAR CHARACTER, SHALL BE PROVIDED AS
PART OF CONTRACT.
C. WHERE THE DRAWINGS OR SPECIFICATIONS CALL FOR ITEMS WHICH EXCEED CODES OR THE
LANDLORD'S TENANT CRITERIA, THE CONTRACTOR IS RESPONSIBLE FOR FURNISHING AND INSTALLING
THE SYSTEM WITH THE MORE STRINGENT REQUIREMENTS AS DESIGNED AND DESCRIBED ON THESE
DRAWINGS, UNLESS SPECIFICALLY NOTED OTHERWISE.
D. ALL ELECTRICAL WORK SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR OPERATING,
SERVICING, MAINTAINING AND REPAIRING. THIS CONTRACTOR IS RESPONSIBLE FOR PROVIDING
SUFFICIENT SERVICE ACCESS TO ALL EQUIPMENT.
E. ALL WORK SHALL BE PERFORMED IN A NEAT PROFESSIONAL MANNER USING GOOD ENGINEERING AND
CONSTRUCTION PRACTICES.
F. UNLESS SPECIFICALLY NOTED OTHERWISE, MATERIALS, PRODUCTS, AND EQUIPMENT, INCLUDING ALL
COMPONENTS THEREOF, SHALL BE NEW, UNDERWRITERS LABORATORIES LISTED AND LABELED AND
SIZED IN CONFORMITY WITH REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, STATE AND LOCAL
CODES, WHICHEVER IS MORE STRINGENT.
SECTION 16003 - CODES
A. ALL WORK SHALL CONFORM TO THE LATEST ADOPTED EDITION OF THE NATIONAL ELECTRICAL CODE,
LANDLORD'S CRITERIA, THE STATE'S, COUNTY'S, CITY'S AND LOCAL CODES AND ORDINANCES, SAFETY
AND HEALTH CODES, NFPA CODES, ENERGY CODES, AND ALL OTHER APPLICABLE CODES AND
REQUIREMENTS. THIS CONTRACTOR SHALL INQUIRE INTO AND COMPLY WITH ALL APPLICABLE CODES,
ORDINANCES, AND REGULATIONS. THIS CONTRACTOR SHALL INCLUDE ANY CHANGES REQUIRED BY
CODES IN THE BID AND IF THESE CHANGES ARE NOT INCLUDED IN THE BID, THEY MUST BE QUALIFIED
AS A SEPARATE LINE ITEM IN THE BID. AFTER CONTRACT IS ISSUED, NO ADDITIONAL COST DUE TO
CODE ISSUES SHALL BE REIMBURSED BY THE OWNER TO THE CONTRACTOR.
SECTION 16004 - LICENSES, PERMITS, INSPECTIONS & FEES
A. THIS CONTRACTOR SHALL OBTAIN AND PAY FOR ALL LICENSES, PERMITS, INSPECTIONS, AND FEES
REQUIRED OR RELATED TO THEIR WORK.
B. FURNISH TO THE TENANT'S PROJECT MANAGER ALL CERTIFICATES OF INSPECTION AND FINAL
INSPECTION APPROVAL AT COMPLETION OF PROJECT.
SECTION 16005 - TRADE NAMES, MANUFACTURERS AND SHOP DRAWINGS
A. WHERE TRADE NAMES AND MANUFACTURERS ARE USED ON THE DRAWINGS OR IN THE
SPECIFICATIONS, THE EXACT EQUIPMENT SHALL BE USED AS A MINIMUM FOR THE BASE BID.
ADDITIONALLY, ONLY MANUFACTURERS CONSIDERED AS AN EQUAL OR BETTER IN ALL ASPECTS TO
THAT SPECIFIED WILL BE REVIEWED. ALL SUBSTITUTIONS ARE SUBJECT TO APPROVAL IN WRITING, BY
TENANT'S PROJECT MANAGER THROUGH PRIOR SHOP DRAWING SUBMITTAL PROCESS FOR
ACCEPTANCE. THE USE OF ANY UNAUTHORIZED EQUIPMENT SHALL BE SUBJECT TO REMOVAL AND
REPLACEMENT AT THE CONTRACTOR'S EXPENSE.
B. ELECTRICAL CONTRACTOR SHALL SUBMIT ONLY SUBSTITUTION REQUESTS TO TENANT'S PROJECT
MANAGER FOR APPROVAL. SUBMISSIONS SHALL BE MADE EARLY ENOUGH IN PROJECT TO ALLOW
FOUR (4) WORKING DAYS FOR TENANT'S PROJECT MANAGER'S REVIEW WITHOUT CAUSING DELAYS OR
CONFLICTS TO THE JOB'S PROGRESS SUBMITTALS SHALL BEAR THE STAMP OF THE GENERAL
CONTRACTOR AND THE SUB -CONTRACTOR SHOWING THAT THEY HAVE REVIEWED AND CONFIRMED
THAT THE SUBMITTALS ARE IN CONFORMANCE WITH THE CONTRACT DRAWINGS AND SPECIFICATIONS
OR INDICATE WHERE EXCEPTIONS HAVE BEEN TAKEN.
SECTION 16006 - GUARANTEE
A. THIS CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORK PROVIDED UNDER THEIR
CONTRACT AND SHALL MAKE GOOD, REPAIR OR REPLACE AT THEIR OWN EXPENSE, ANY DEFECTIVE
WORK, MATERIAL, OR EQUIPMENT WHICH MAY BE DISCOVERED WITHIN A PERIOD OF 12 MONTHS FROM
THE DATE OF ACCEPTANCE (IN WRITING) OF THE INSTALLATION BY THE TENANT'S PROJECT MANAGER.
EXTENDED WARRANTIES ARE SPECIFIED WITH INDIVIDUAL EQUIPMENT.
B. TENANT SHALL PROVIDE A COMPLETE 12 -MONTH WARRANTY FOR ALL PARTS ON EQUIPMENT
PROVIDED BY TENANT AND TENANT'S VENDORS. THIS CONTRACTOR SHALL NOT BEAR ADDITIONAL
WARRANTIES BEYOND A COMPLETE WORKING SYSTEM, AND AS SUCH, NO ADDITIONAL MONIES
SHOULD BE INCLUDED IN THE BID.
SECTION 16007 - RECORD DRAWINGS
A. THIS CONTRACTOR SHALL MAINTAIN ONE COPY OF DRAWINGS ON THE JOB SITE TO RECORD
DEVIATIONS FROM CONTRACT DRAWINGS, SUCH AS:
1. LOCATION OF CONCEALED CONDUIT AND WIRING.
2. LOCATION OF JUNCTION BOXES.
3. REVISIONS, ADDENDUMS, AND CHANGE ORDERS.
4. SIGNIFICANT DEVIATIONS MADE NECESSARY BY FIELD CONDITIONS, APPROVED EQUIPMENT
SUBSTITUTIONS, AND CONTRACTOR'S COORDINATION WITH OTHER TRADES.
B. AT COMPLETION OF PROJECT AND BEFORE FINAL APPROVAL, THE CONTRACTOR SHALL MAKE ANY
FINAL CORRECTIONS TO DRAWINGS AND CERTIFY THE ACCURACY OF EACH PRINT BY SIGNATURE
THEREON. ONE COPY OF THE MOST RECENT SET OF DRAWINGS WITH TEMPERATURE CONTROL
DRAWINGS INCLUDED SHALL BE DELIVERED TO TENANT'S PROJECT MANAGER.
SECTION 16008 - DISCREPANCIES IN DOCUMENTS
A. DRAWINGS (PLANS, SPECIFICATIONS, AND DETAILS) ARE DIAGRAMMATIC AND INDICATE THE GENERAL
LOCATION AND INTENT OF THE ELECTRICAL SYSTEMS. WHERE DRAWINGS, EXISTING SITE CONDITIONS,
SPECIFICATIONS OR OTHER TRADES CONFLICT OR ARE UNCLEAR, ADVISE TENANT'S PROJECT
MANAGER, IN WRITING OF VARIATIONS TO CONTRACT DOCUMENTS PRIOR TO SUBMITTAL OF BID.
OTHERWISE, TENANT'S PROJECT MANAGER'S INTERPRETATION OF CONTRACT DOCUMENTS OR
CONDITIONS SHALL BE FINAL WITH NO ADDITIONAL COMPENSATION PERMITTED.
SECTION 16009 - DEMOLITION
A. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF THE DEMOLITION OF
EXISTING WORK AND THE DEMOLITION PROVIDED BY THE GENERAL CONTRACTOR COORDINATE WITH
THE GENERAL CONTRACTOR ANY EXISTING EQUIPMENT REQUIRED TO BE LEFT INTACT.
B. THIS CONTRACTOR SHALL VERIFY SCOPE OF WORK WITH THE GENERAL CONTRACTOR FOR THE
REMOVAL OF ALL EXISTING LIGHT FIXTURES, RECEPTACLES, SWITCHES, ETC. NOT BEING REUSED ON
THIS PROJECT UNLESS SPECIFICALLY NOTED OTHERWISE. CONTRACTOR MUST VERIFY WITH THE
LANDLORD ALL PRESUMED ABANDONED EQUIPMENT PRIOR TO REMOVAL. ALL EXTRANEOUS ITEMS IN
THE SPACE OR ON THE ROOF NOT APPLICABLE TO THE NEW WORK MUST BE REMOVED AND
ROOF/WALL/FLOOR PATCHED/REPAIRED TO MATCH EXISTING STRUCTURE. EXISTING ABANDONED
CONDUIT OR EQUIPMENT IN THE FLOOR, EMBEDDED IN CONCRETE, OR OTHERWISE INACCESSIBLE,
ARE TO BE CUT OFF AND SEALED BELOW OR WITHIN FLOOR OR WALL LEVEL WHEN THEY ARE NOT TO
BE REUSED IN THIS PROJECT. IF REQUIRED BY LANDLORD OR CODES, ABANDONED CONDUIT MUST BE
REMOVED TO POINT OF ORIGIN. CONFIRM EXTENT OF DEMOLITION WITH THE GENERAL CONTRACTOR
PRIOR TO BID PROPOSAL AS DIRECTED BY THE GENERAL CONTRACTOR AND TENANT. ALL UNUSED
x EXISTING PLENUM RATED CABLING IS TO BE REMOVED COMPLETELY.
SECTION 16010 - CUTTING AND PATCHING
#: A. THE CONTRACTOR SHALL PERFORM ALL CUTTING AND PATCHING AS REQUIRED FOR THE
INSTALLATION OF THE WORK UNDER THIS SPECIFICATION. NO CUTTING OF THE STRUCTURE SHALL BE
PERMITTED WITHOUT WRITTEN APPROVAL OF THE LANDLORD AND ARCHITECT OR ENGINEER.
B. PATCHING SHALL BE OF THE SAME WORKMANSHIP, MATERIAL AND FURNISH AND SHALL MATCH
ACCURATELY ALL SURROUNDING CONSTRUCTION IN A MANNER SATISFACTORY TO THE ARCHITECT
AND TENANT'S PROJECT MANAGER.
C. EXISTING UTILITIES, ETC. THAT ARE DAMAGED DURING THE CONSTRUCTION PERIOD, WHETHER OR
E NOT DUE TO THE CONTRACTOR'S NEGLIGENCE SHALL BE REPAIRED OR REPLACED BY THE
CONTRACTOR AND LEFT IN A CONDITION SUITABLE TO THE LANDLORD AND TENANT'S PROJECT
MANAGER.
'. SECTION 16011 -SLEEVES
A. THIS CONTRACTOR SHALL PROVIDE SLEEVES TO PROTECT EQUIPMENT OR FACILITIES IN THE
INSTALLATION. EACH SLEEVE SHALL EXTEND THROUGH IT'S RESPECTIVE FLOOR, WALL OR
PARTITION AND SHALL BE CUT FLUSH WITH EACH SURFACE EXCEPT SLEEVES THAT PENETRATE
THE FLOOR, WHICH SHALL EXTEND 2" ABOVE THE FLOOR. CONTRACTOR MUST COORDINATE THROUGH
THE LANDLORD ANY CORE DRILLING OR CUTTING OF OPENINGS IN MASONRY FLOORS OR WALLS.
B. ALL SLEEVES AND OPENINGS THROUGH FIRE RATED WALLS AND/OR FLOORS SHALL BE FIRE SEALED
WITH CALCIUM SILICATE, SILICONE "RTV" FOAM, "3M" FIRE RATED SEALANTS OR EQUAL, SO AS TO
RETAIN THEIR FIRE RATING.
C. SLEEVES IN BEARING AND MASONRY WALLS, FLOORS AND PARTITIONS SHALL BE STANDARD
WEIGHT STEEL PIPE FINISHED WITH SMOOTH EDGES. FOR OTHER THAN MASONRY PARTITIONS,
THROUGH SUSPENDED CEILINGS, OR FOR CONCEALED VERTICAL CONDUIT, SLEEVES SHALL BE NO
22 U.S.G GALVANIZED STEEL MINIMUM.
SECTION 16012 - HANGERS
A. HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL SUCH AS ANGLE IRON, WIRE, UNISTRUT,
C -CLAMPS WITH RETAINING CLIPS, CHANNELS, HANGER RODS, ETC., NECESSARY FOR THE
INSTALLATION OF WORK.
F B. HANGERS SHALL BE FASTENED TO BUILDING STEEL, CONCRETE, OR MASONRY, BUT NOT TO PIPING.
HANGING FROM METAL DECK IS NOT PERMITTED. HANGERS MUST BE ATTACHED TO UPPER CHORD OF
BAR JOIST. WHERE INTERFERENCES OCCUR, IN ORDER TO SUPPORT CONDUIT OR BOXES, THE
CONTRACTOR MUST INSTALL TRAPEZE TYPE HANGERS OR SUPPORTS WHICH SHALL BE LOCATED
I WHERE THEY DO NOT INTERFERE WITH ACCESS TO FIRE DAMPERS, VALVES, JUNCTION BOXES,
ACCESS DOORS, OTHER EQUIPMENT SERVICE REQUIREMENTS AND/OR OTHER TRADES. HANGER
TYPES AND INSTALLATION METHODS ARE SUBJECT TO LANDLORD CRITERIA.
DIVISION 16200 - ELECTRICAL
SECTION 16201 - SUMMARY OF WORK
A. THIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT NECESSARY FOR REASONABLY
IMPLIED AND INCIDENTAL TO, THE FURNISHING, INSTALLATION, COMPLETION AND TESTING OF ALL THE WORK
FOR THE ELECTRICAL SYSTEMS AS CALLED FOR IN THE SPECIFICATIONS, AND AS REQUIRED BY JOB
CONDITIONS, TO INCLUDE, BUT NOT BE LIMITED TO THE FOLLOWING:
1. WORK IN THE LANDLORD'S MAIN DISTRIBUTION EQUIPMENT ROOM SHALL BE AS INDICATED, AND/OR
REQUIRED BY EXTENDING SERVICE TO THE LEASED SPACE.
2. COMPLETE POWER AND LIGHTING DISTRIBUTION SYSTEMS INCLUDING ALL PANELS AND COMPLETE BRANCH
CIRCUIT WIRING SYSTEM.
3. COMPLETE LIGHTING FIXTURE INSTALLATION.
4. COMPLETE TELEPHONE CONDUIT SYSTEM, INCLUDING SERVICE CONDUIT FROM POINT OF CONNECTION TO
LANDLORDS SYSTEM AND ALL TERMINAL DEVICES, BOXES, CONDUIT, PLATES, ETC.
5. TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR CONSTRUCTION.
6. WIRING AND FINAL CONNECTION TO ALL SIGNS AND GRAPHICS, FURNISHED BY THE OWNER.
7. PROVISIONS FOR FIRE ALARM/SMOKE EVACUATION SYSTEM AND EXTENSION OF LANDLORD SYSTEM (IF
APPLICABLE).
8. TESTING OF ALL CABLES AND CIRCUIT WIRING AFTER INSTALLATION. k
9. TESTING OF ALL ELECTRICAL EQUIPMENT.
10. WARRANTY OF ALL WORK FOR A PERIOD OF ONE YEAR FROM DATE OF PROJECT CLOSE-OUT.
B. PROVIDE ELECTRICAL SERVICE AS INDICATED ON THE DRAWING. ALL WORK NOT SPECIFICALLY NOTED AS
BEING BY THE LANDLORD OR THE POWER COMPANY SHALL BE PROVIDED BY THE ELECTRICAL CONTRACTOR
CLOSELY COORDINATE ENTIRE INSTALLATION WITH THE LANDLORD AND THE POWER COMPANY.
CONTRACTOR SHALL MAKE ARRANGEMENT WITH THE POWER COMPANY FOR INSTALLATION OF METERING AS
REQUIRED BY THE LANDLORD.
C. CONTRACTOR SHALL MAKE ARRANGEMENTS WITH THE LOCAL TELEPHONE UTILITY FOR TELEPHONE SERVICE ;
TO THE SPACE, CONDUIT SYSTEM FOR TELEPHONE DISTRIBUTION TO THE LEASED PREMISES SHALL BE
PROVIDED WHERE REQUIRED FOR UTILITY COMPANY WIRES. COORDINATE INSTALLATION OF TELEPHONE t
WORK AND INSTALL ALL CONDUIT (IF REQUIRED BY LANDLORD OR LOCAL CODE) FOR TELEPHONE SYSTEM
WITHIN THE LEASED SPACE. OUTLET BOXES SHALL BE 4" SQUARE MINIMUM WITH SINGLE DEVICE COVER AND
TELEPHONE PLATE.
D. FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND TOOLS TO PERFORM ELECTRICAL WORK SHOWN, NOTED
OR SCHEDULED FOR A COMPLETE AND FINISHED INSTALLATION.
SECTION 16202 - MATERIALS 1
A. MATERIALS PRODUCTS AND EQUIPMENT, INCLUDING COMPONENTS THEREOF, SHALL BE NEW AND SUCH AS
APPEARS ON THE UNDERWRITER'S LABORATORY LIST OF APPROVED ITEMS AND SHALL MEET THE
REQUIREMENTS OF RECOGNIZED STANDARDS.
B. CONDUIT SHALL BE STANDARD STEEL, IC OR EMT (THIN WALL) ACCORDING TO CODE REQUIREMENTS.
CONDUIT SHALL BE CONCEALED IN FINISHED AREAS EXCEPT AS OTHERWISE APPROVED BY TENANT'S 1
PROJECT MANAGER. EMT CONNECTIONS SHALL BE COMPRESSION TYPE. MINIMUM SIZES OF CONDUIT SHALL
BE 3/4", EXCEPT 1/2" FOR SWITCH LEGS. EMT SHALL BE GALVANIZED OR ELECTRO -GALVANISED. EMT SHALL
BE USED FOR FEEDERS AND BRANCH CIRCUITS RUN ABOVE THE SUSPENDED CEILING OR CONCEALED IN
INTERIOR PARTITIONS. EMT SHALL NOT BE CONCEALED IN POURED CONCRETE FLOOR OR WALLS. USE IMC
FOR UNDER SLAB INSTALLATIONS. IMG IS PERMITTED WITH SCREW CONNECTIONS. FLEXIBLE METALLIC
TUBING MAY BE USED IN LIEU OF EMT FOR CONCEALED BRANCH CIRCUIT WIRING ONLY, WHERE PERMITTED
BY LOCAL AUTHORITIES. FLEXIBLE METAL CONDUIT MAY BE USED ONLY FOR SHORT CONNECTIONS TO
FIXTURES AND EQUIPMENT PERMITTED BY CODE.
C. ALL CONDUCTORS SHALL BE SOFT DRAWN, ANNEALED COPPER, WITH 600 VOLT INSULATION.
1. #10 AND SMALLER -SOLID, #8 AND LARGER -STRANDED. MINIMUM WIRE SHALL BE #12, EXCEPT #14 MAYBE
,,
USED FOR CONTROL APPLICATIONS.
2. ALL WIRE AND CABLE SHALL BE NEW AND SHALL BE BROUGHT TO THE SITE IN UN BROKEN PACKAGES.
3. GENERAL WIRING SHALL HAVE THHN INSULATION.
I
4. ALUMINUM CONDUCTORS, ROMEX OR BX ARE NOT PERMITTED.
5. WIRE CONNECTORS SHALL BE EQUAL TO SCOTCH - LOCK FOR #8 AND SMALLER, AND T &BLOCK TIE FOR #6
AND LARGER.
6. WIRES SHALL BE COLOR CODED IN KEEPING WITH LANDLORD'S CONVENTION.
D. OUTLET BOXES AND COVERS SHALL BE ONE PIECE, GALVANIZED OR SHERARDIZED STEEL, 4" x 4" KNOCK -
OUT TYPE WITH FIXTURE STUDS AS REQUIRED. JUNCTION BOXES, PULL BOXES AND COVERS SHALL BE
GALVANIZED STEEL, CODE GAUGE AND SIZE.
E. WIRING DEVICES:
1. DEVICES AND COVER PLATES SHALL BE SPECIFICATION GRADE WITH A MINIMUM RATING OF 20 AMPS. COLOR
OF DEVICES AND COVER PLATES IN SALES AREA GYP BOARD, TOILET ROOM AND STOCK ROOM "f0 BE WHITE. };
IN SALES AREA WAINSCOT AND MILLWORK THEY ARE TO BE IVORY. DEVICES AND COVERPLATES TO BE
MANUFACTURED BY HUBBELL. EQUALS BY LEVITON OR COOPER WIRING DEVICES / EAGLE ELECTRIC.
DUPLEX RECEPTACLE : HUBBELL #5262.
QUADRAPLEX RECEPTACLE: HUBBELL #5262 UNDER ONE (TWO GANG -TYPE) COVER PLATE.
ISOLATED GROUND RECEPTACLE : HUBBELL #IG -5262.
QUADRAPLEX ISOLATED GROUND RECEPTACLE: (2)HUBBEL MG -5262 UNDER ONE (TWO GANG
TYPE) COVER PLATE.
WEATHER PROOF RECEPTACLE: HUBBELL #GF -5262-1 WITH "WP26" ALUMINUM COVER PLATE.
SPST SWITCH: HUBBELL #HBL-1221.
THREE WAY SWITCH: HUBBELL #HBL-1223.
%
F. THIS CONTRACTOR SHALL PROVIDE, INSTALL AND CONNECT A COMPLETE SYSTEM OF GROUNDING FOR ALL
EQUIPMENT AND STRUCTURES. A GOOD MECHANICAL AND ELECTRICAL CONNECTION SHALL BE MADE WITH
APPROVED GROUNDING CONNECTIONS, ELECTRICAL SYSTEM AND EQUIPMENT GROUNDS SHALL COMPLY
WITH ALL LOCAL, STATE AND N.E.C. CODES AND REGULATIONS. PANELS, CONDUIT SYSTEMS, MOTOR FRAMES,
LIGHTING FIXTURES AND OTHER EQUIPMENT THAT ARE PART OF THIS INSTALLATION SHALL BE SECURELY
GROUNDED BOTH MECHANICALLY AND ELECTRICALLY IN ACCORDANCE WITH ALL CODES. MAIN GROUNDING
SYSTEM SHALL BE SIZED TO CONFORM WITH SECTION 250 OF THE NATIONAL ELECTRIC CODE. PROVIDE
CONDUIT 'TO PROTECT GROUND WIRE FROM DAMAGE TO A HEIGHT OF 6 FEET ABOVE FLOOR. MAKE ALL
JOINTS AND CONNECTIONS OF THE CONDUIT SYSTEM TIGHT TO MAINTAIN CONTINUITY OF MECHANICAL AND
ELECTRICAL GROUND THROUGH ENTIRE SYSTEM. GROUND ALL THREE WIRE RECEPTACLES TO THE OUTLET
BOXES. GROUND NEUTRAL FROM THE TRANSFORMER CONNECTED TO BUILDING STEEL. GROUND
CONDUCTOR SHALL BE SUPPLIED IN ALL NON-METALLIC CONDUIT. A SEPARATE ISOLATED, INSULATED
E GROUND SYSTEM SHALL BE INSTALLED FOR ELECTRONIC CASH REGISTER.
G. ALL PASTEBOARDS SHALL BE STANDARD DEAD -FRONT CONSTRUCTION WITH SIZE AND NUMBER OF SINGLE
AND MULTI -POLE BOLT -ON BRANCH BREAKERS AS INDICATED ON THE PANEL SCHEDULE, AND WITH MAIN
BREAKER AND MAIN LUGS AS INDICATED ON THE DRAWINGS, PANEL BUSSING SHALL BE COPPER. PANEL
BOARDS SHALL BE COMPLETE WITH TRIM, DOOR, CONCEALED HINGES, FLUSH LOCK, DIRECTORY FRAME AND
NEATLY TYPED CO PLETED DIRECTORY CARDS. ALL PANEL BOARDS SHALL HAVE DISTRIBUTED BUSSING AND
SEQUENCE NUMBERING WITH NO TWO CONSECUTIVE CIRCUIT NUMBERS TIED TO THE SAME BUS OR PHASE.
ALL PANELS AND BREAKERS ARE PRE -PURCHASED AND SHALL BE GET AS PART TENANT'S NATIONAL
ACCOUNT RELATIONSHIP AND SHIPPED TO THE JOB SITE FOR INSTALLATION BY THE ELECTRICAL
CONTRACTOR. ALL CIRCUIT BREAKERS USED FOR CONTROL OF LIGHTING CIRCUITS SHALL BE "SWD" RATED.
H. DRY TYPE STEP - DOWN TRANSFORMER SHALL HAVE NEMA CLASS F INSULATION ON UNITS BELOW 30 KVA
AND NEMA CLASS H INSULATION ON UNITS 30 KVA AND ABOVE. TRANSFORMER TO BE GENERAL PURPOSE
VENTILATED TYPE WITH ALUMINUM WINDINGS. TRANSFORMER IS PRE PURCHASED AND SHALL BE GE AS
PART TENANT'S NATIONAL ACCOUNT RELATIONSHIP AND SHIPPED TO THE JOB SITE FOR INSTALLATION BY
THE ELECTRICAL CONTRACTOR.
I. DISCONNECT SWITCHES AND COMBINATION STARTER DISCONNECT SWITCHES SHALL BE HEAVY DUTY TYPE,
600 VOLT RATED, QUICK-MAKE/QUICK-BREAK, WEATHER PROOF (WHERE APPLICABLE), FUSED/NON FUSED AS
SHOWN ON THE DRAWINGS. SWITCHES USED FOR SERVICE ENTRANCE SHALL BE "SE" RATED. STARTERS
SHALL BE MINIMUM NEMA SIZE 1. DISCONNECT SWITCHES AND COMBINATION STARTER DISCONNECT
SWITCHES ARE PURCHASED AND INSTALLED BY THE ELECTRICAL CONTRACTOR AND SHALL BE GE.
J. ELECTRICAL CONTRACTOR SHALL PROVIDE ELECTRIC SERVICE AND MAKE CONNECTIONS TO THE HVAC
EQUIPMENT, SIGNS AND GRILLE MOTORS (IF APPLICABLE) AS SHOWN ON THE DRAWINGS.
K. THE ISOLATED CIRCUIT OUTLETS AT CASH WRAP AREAS SHALL BE CLEARLY AND COMPLETELY MARKED FOR
UNMISTAKABLE IDENTIFICATION BY THE OWNER'S EMPLOYEES.
L. TEMPORARY WIRING SHALL BE REMOVED WHEN WORK IS COMPLETED.
M. NO CONDUIT SHALL BE RUN THROUGH HVAC DUCTS.
N. FINALLY
1. IT IS THE INTENT THAT THE FOREGOING WORK SHALL BE COMPLETED IN EVERY RESPECT AND THAT ANY
MATERIAL OR WORK NOT SPECIFICALLY MENTIONED OR SHOWN ON THE DRAWINGS BUT NECESSARY TO
FULLY COMPLETE THE WORK SHALL BE FURNISHED. THE LOCATION OF RECEPTACLES AND FIXTURES
SHOWN ON THE DRAWING ARE APPROXIMATE AND THE OWNER SHALL HAVE THE RIGHT TO RELOCATE ANY
RECEPTACLE OR FIXTURES BEFORE THEY ARE INSTALLED WITHOUT ANY ADDITIONAL COST.
IWPARTNERS
brand: operations: build
7007 DISCOVERY BLVD
DUBLIN, OR 43017
614.634.7000 T
W DPARTNERS.COM
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE
SPACE #1311 C
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
�®iwo9et�B®®
J
(D'; STATE OF .' Qom.
'RI -fee I
7010
)joy 20 7-013
ISSUE DATES
PRELIM SET: 10-16-2013
FINAL SET: 11-6-2013
PERMIT SET: 11-20-2013
REVISIONS
ID
DRAWING NUMBER
DOOR SCHEDULE
Description
I DESCRIPTION
Double Glass Cabinet measuring 2'x6' with an overall height of 100".Lower section has
DBL GS
VALSPAR
DOOR HARDWARE
MARK
LOCATION
SIZE
TYPE
CA - back
FRAME
DOOR
DESCRIPTION
HARDWARE
FIRE RATING
A. HARDWARE AS PROVIDED BY ROLLING GRILLE
SERVICE ENTRANCE/
ROLL-UPO
8'-U" X 8 U'
IS
STEEL
ALUM.
OVERHEAD DOOR SERIES 670 MANUAL
DL
N/A
42"R
GRILLE
SQ
A
Z_
Wood shelves, measuring 12"d, available in 4',6',8' lengths
WS
PUSH-UP DOOR OR APPROVED EQUAL
A
Wood shelving is hung in doubles, the lower one at 66"h and upper at 79"h
MANUFACTURER WITH U -CHANGE LOCK CYLINDER WITH
4' Wood shelf elevation, shelves are hung at 24",40",56",72"
Two-tiered 4' wood shelves, upper shelf is hung at 76"h, bottom bench is at 18"h
note:
3FO
* There needs to be 3" gaps on either side to allow for the hangers to hang freely on the
BEHR
CLR: SEASIDE SAND
face -out brackets
THUMBTURN ON STORE SIDE. GC TO PROVIDE AND
INSTALL SIGNAGE ON STORE SIDE OF BOTTOM RAIL OF
Stacked shelving for stockroom, 12" deep wall mounted. Shelf with pole @5'3 & Top shelf
SS
OLYMPIC
at 7' aff, variable lengths
NEW DESIGN STANDARD - JELDWEN 15
PT -5
CLR: HEIRLOOM LACE
OB
STOCK ROOM
T-0" X 6'-8" X 1 3/8"
B
Small microwave & fridge for stockroom
5/A1D 1
WD
PANEL LITE DOOR. PAINT PT -4.
g
N/A
GRILLE STATING "GRILLE TO REMAIN IN FULL OPEN
CLR: BROWN
Three-piece unit composed of right/left/center, with wood or glass shelves, lights
Armoire
Side units measure 16"d x 35"w x 100"h
Center unit measures 20"d x 36"w x 100"h
TEMPERED GLAZING TO BE FROSTED.
ADA Bench
Measuring 42"wx18"hx20"w
POSITION DURING STORE HOURS WHEN OCCUPIED BY
THE GENERAL PUBLIC."
6" WOOD BASE
SALES (SUPPLIED
RESTROM
BY FRANCESCA'S)
C
RESTROOM
3'-0" X 6'-8" X 1 3/8"
C
0
5/AD 1
WD
DOOR, PA NT PT -2
C
N/A
CLR: WHITE / MULTI - PATTERN BY OWNER
w
0
GROUT: POLYBLEND / CUSTOM
B. DECORATIVE PRIVACY LOCKSET - G.C. SHALL NOT
CLR: #333 ALABASTER
12"x12" VINYL FLOORING
STOCK ROOM/
pC
VCT 1
CLR: BEIGE
RESTROOM
INSTALL CLOSER.
0
KARNDEAN
SALES
�
VP 1
VINYL PLANK - HCO3
C. PRIVACY LOCKSET - G.C. SHALL NOT INSTALL CLOSER.
CLR: DUSK OAK, RANDOM PATTERN
SALES/ STOCK ROOM/
CLG-1
NEW 2x2 ACOUSTICAL TILE CEILING
DRESSING ROOM/
d
TEGULAR EDGE CLR: WHITE
RESTROOM
J
U
CLEAR OFENINCa WIDTH
STOREFRONT
TEtd510N —�
NEW GYP. BD. CEILING
-------
DRIVE
END
--
END
PT -4
PT -2
r
r
PT -2
FROSTED
TEMPERED
GLAZING
U
IFTI
NOTE:
DOOR HARDWARE SHALL BE EASY TO GRASP AND SHALL
g
NOT REQUIRE GRASPING, TIGHT PINCHING, OR TWISTING
OF WRIST. ALL DOORS SHALL HAVE LEVER HARDWARE,
RELEASES,OR PUSH-PULL PLATES CENTERED
APANIC
B
(,
BETWEEN 30-44" A.FF. ALL LOCKING DEVICES MUST MEET
ANSI AND TAS STANDARDS.
5/8" GYP. BD.
DBL. 3 5/8" METAL
/ TRIM
DOOR JAN
FRT WOOD
BLOCKING
5 DOOR HEAD & JAMB DETAIL
311 =1-0
11
WALL LEGEND
5/8" TYPE "X" GYP
BD. TO 6" ABOVE
CEILING - OMIT GYP.
BD. ON ONE SIDE AT
FURRED WALLS,
A MOISTURE RE SISTANT
GYP ON RESTROOM
WALLS
3 5/8" X 20 GA.
METAL STUDS @
16" O.C. TO DECK
SEE SECTION 4/A1.1
FRAME
5/8" GYP. BD.
DBL. 3 5/8" METAL
STUDS. 20 GA. TYP.
TRIM
FRT WOOD
BLOCKING
DOORJAMB
FRAME
EXISTING 5/8" TYPE "X"
GYP.BD. - G.C. TO PATCH
& REPAIR AS REQUIRED. C
MAINTAIN ALL EXISTING
FIRE RATINGS. INSTALL
ON TENANT SIDE IF NOT
EXISTING
(E) 6" METAL 5/8"
STUD
NEW WALLS DEMISING WALLS NEW WALLS
USE 20GA. MTL STUDS UNLESS OTHERWISE NOTED CW RESTROOM
5/8" TYPE "X" GYP
BD. TO 6" ABOVE
CEILING, - OMIT GYP. BD
ON ONE SIDE AT
FURRED WALLS,
MOISTURE RESISTANT
GYP ON RESTROOM
WALLS
3 5/8" X 20 GA.
METAL STUDS @
16" O.C. TO 8'-6"
5/8"
SEE SECTION 3/A1.1
J -MOLD ON
TOP OF GYP. BD.
3 5/8x20 GA DIAGONAL
DEEP LEG (18 GA MIN) CONT. EL BRACING AT 48" O.C.
SLOTTED DEFLECTION TRACK `t ATTACH TO TOP OF
(CLARK-DIETRICH SLP -TRK) W/ cJ WALL WITH SIMPSON L30
ATTACHMENT TO STEEL U +8'-6" A.F.F. rik
LU
CLIPS. ATTACH BRACING
JOISTS FRAMING ABOVE PER TO FRAMING ABOVE PER T.O. WALL
DETAILS ON A3.1. DO NOT DETAILS ON A3.1.
ATTACH TO METAL DECK.
+8'-0" A.F.F.
OB U P TO DECK AC f CEILING PER
SCHEDULE
20 GAUGE CONT. 3 5/8", 20 GA MTL. STUDS &
TRACK TO MATCH GYP. BD. WALL SYSTEM.
WALL STUD WIDTH
Ap (2) 0.145" DIA HILTI X -DNI
WALL BASE, SEE UNIVERSAL PAF @ 16" OC
FINISH
3CHEDULEif (1-1/4" EMBED).
(2) 0.145" DIA HILTI X -DNI (1) #10-16 SCREW
PER STUD BASE, WHERE OCCURS. SEE
UNIVERSAL PAF @ 16" OC FINISH SCHEDULE
(1-1/4" EMBED). FLANGE, TYP.
NEW CONCRETE
+0'-0" SLAB BY G.C.
FINISH FLOOR
A TO SLAB
WALL ATTACHMENT DETAIL 3 RESTROOM WALL DETAIL
3'= 1, 0, 1 112" = 11-011
60" CLR
IS" 24" MIN
36" CWAB BAR - -� I
G.C. To INSTALL
BLOCKIN[s IN WALL I F
0� I o
= 5/A4 `
LIN- r
48" CLR -
7/A4
1
42" CsRAB BAR -
IG.C. To INSTALL }'
BLOCKING IN WALL.
I B„jk; Frrs
�'a
SEE SHEET A4 1„\ C y'
FOR �STROOM
ELEVATIONS 1 .....<>
ENLARGED RESTROOM PLAN
Francesca's FIXTURE SCHEDULE
�CONSTR.GEN.NOTES CONSTRUCTION KEYNOTES
1. DIMENSIONS ARE TO FINISH SURFACES UNLESS NOTED
OTHERWISE.
2. THE G.C. IS RESPONSIBLE FOR CONFIRMING OVERALL
DIMENSIONS AND STRUCTURAL CONDITIONS PRIOR TO BEGINNING WORK. ANY DISCREPANCIES
OR PROBLEMATIC CONDITIONS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE G.C..
3. REPORT ALL SHELL BUILDING DEFECTS TO THE G.C.
IMMEDIATELY UPON DISCOVERY.
T.G.C. IS TO OBTAIN APPROVAL AND REQUIREMENTS FROM ON SITE TENANT COORDINATOR
PRIOR TO ANY CUTTING OR DRILLING OF EXISTING FLOOR.
TENANT IS RESPONSIBLE TO FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS IN THE
SPACE. FAILURE TO PROPERLY FIELD VERIFY EXISTING CONDITIONS DOES NOT RELIEVE THE
TENANT OF ANY EXPENSES OR RESPONSIBILITIES RESULTING FROM THAT FAILURE.
NOTHING IS PERMITTED TO BE ATTACHED TO, BE SUSPENDED FROM, OR PENETRATE THE ROOF
DECK. TENANTS MAY ATTACH TO JOIST(S), AT PANEL POINTS, OR TO THE STRUCTURAL STEEL.
ALL WALL CONSTRUCTION SHALL BE SUPPORTED IN THIS MANNER. NO WELDING TOR
SHOOTING INTO THE STRUCTURE IS PERMITTED.
STRUCTURAL REINFORCING DETAILS MUST BE PROVIDED BY A REGISTERED STRUCTURAL
ENGINEER TO TENANT COORDINATION FOR EQUIPMENT SUPPORT OR SUSPENSION, SERVICE
PLATFORMS, DECK PENETRATIONS, ETC. - FOR LANDLORD'S RECORDS.
ANY LANDLORD EQUIPMENT OR COMPONENT THAT IS EXISTING IN THE SPACE MUST REMAIN
VISIBLE AND ACCESSIBLE TO THE LANDLORD. -I-ENANI” "I"O INS-fALL ACCESS PANELS AS
NECESSARY, AND PROPERLY LABEL IN SPACE, COORDINATE PLACEMENT WITH MALL
OPERATIONS DIRECTOR.
TENANT'S STOCKROOM MAY NOT BE VISIBLE FROM THE SALES AREA. DOOR(S) LEADING TO THE
STOCKROOM MUST HAVE AN AUTOMATIC CLOSURE.
ALL CONCRETE PATCHING MUST BE LEVEL WITH THE EXISTING CONCRETE FLOOR.
ALL FLOORING TRANSITIONS MUST BE SMOOTH & FLUSH. THE USE OF PLASTIC, VINYL, OR
RUBBER TRANSITION STRIPS IS STRICTLY PROHIBITED. TENANTS MUST UTILIZE A HARD
SURFACE TRANSITION.
NO RUBBER OR VINYL BASE IS PERMITTED IN THE SALES AREA OF THE PREMISES.
Item
Description
I DESCRIPTION
Double Glass Cabinet measuring 2'x6' with an overall height of 100".Lower section has
DBL GS
VALSPAR
sliding wood doors with inner shelf. Upper section consists of glass shelves, with lights
Front Cashwrap meets ADA requirements with a center drop-down section measuring 36"
CA -front
wide at a height of 33" aff. Overall dimensions are 96"1 x 36" d x overall height of 44".
CA - back
Back Cashwrap; 8' long version, 2'4"d x 44"h.
CA -back (18")
OPTIONAL Back Cashwrap; 6' long, 18"d x 44"h
Standard wood tables measure 2'9"x5'3", with an overall height of 2'6"
T
SERVICE ENTRANCE/
Optional tables measure 3'3"x5'6", which are noted as 3x5
IS
Rectangle island, measure 72"w x 30"d x 42"h.
U
36" round unfinished tables, 2'6"h
DL
36" round wood tables with drop leaf, 2'6"h
42"R
42" round wood tiered table
SQ
Square island, measure 25 1/2"w x 25 1/2"d x 36 1/2"h
Z_
Wood shelves, measuring 12"d, available in 4',6',8' lengths
WS
SALES AREA CEILING
Q
Wood shelving is hung in doubles, the lower one at 66"h and upper at 79"h
4WS
4' Wood shelf elevation, shelves are hung at 24",40",56",72"
Two-tiered 4' wood shelves, upper shelf is hung at 76"h, bottom bench is at 18"h
note:
3FO
* There needs to be 3" gaps on either side to allow for the hangers to hang freely on the
BEHR
CLR: SEASIDE SAND
face -out brackets
* Do not attach the lower bench to the wall
Stacked shelving for stockroom, 12" deep wall mounted. Shelf with pole @5'3 & Top shelf
SS
OLYMPIC
at 7' aff, variable lengths
Stk. Shelv.
PT -5
CLR: HEIRLOOM LACE
(4) 12" deep wall mounted shelving for stock room spaced equally with top shelf at 7' aff
Shelf
(1) 24" wide shelf mounted at 60" a.f.f. for loss prevention equipment
M/F
Small microwave & fridge for stockroom
File
Small file for stockroom
Display
Custom built displays for storefront, standard height is 24"aff, 36"d, variable length,
finished with trim
CLR: BROWN
Three-piece unit composed of right/left/center, with wood or glass shelves, lights
Armoire
Side units measure 16"d x 35"w x 100"h
Center unit measures 20"d x 36"w x 100"h
Wood Bench for ADA Dressing room, attached to wall, with front legs.
ADA Bench
Measuring 42"wx18"hx20"w
NOTE:
PROVIDE CONCEALED F.R.T. WOOD BLOCKING
AT ALL RETAIL FIXTURES ANCHORED TO WALLS.
H
�1 LEASE LINE.
�2 EXISTING DEMISING WALL. G.C. TO PATCH & REPAIR AS REQUIRED.
O ALL FIXTURES PROVIDED BY MILLWORK VENDOR.
® ALL WALLS ARE COVERED FROM FLOOR TO CEILING WITH PAINT. ALL WALLS TO BE BROUGHT TO A LEVEL 3 FINISH
BEFORE PAINTING.
OPREP CONCRETE SLAB FOR INSTALLATION OF NEW FLOOR FINISH PER MANUFACTURERS RECOMMENDATION. ALL
FLOORING TRANSITIONS TO BE LEVEL AND FLUSH AND COMPLY WITH ANSI A117.1 & CALIFORNIA BUILDING CODE.
6� NEW ELECTRICAL PANEL. G.C. TO PULL SERVICE TO SPACE FROM LANDLORDS DESIGNATED LOCATION. SEE ELEC.
7O NEW INTERIOR WALLS. SEE WALL TYPE SCHEDULE FOR DETAILS.
8O NEW STOREFRONT SYSTEM. SEE ELEVATIONS FOR MORE INFO.
9� NEW ADA RESTROOM. SEE DETAIL THIS SHEET AND ELEVATIONS ON A4 FOR MORE INFORMATION. SEE PLUMBING
FOR FIXTURE SPECS.
10 APPROXIMATE LOCATION OF FIRE EXTINGUISHER. GC TO COORDINATE WITH FIRE MARSHAL FOR PREFERRED
LOCATIONS
11 CUT FLOOR (CORE DRILL ON ELEVATED FLOORS) 6'-6" FROM WALL FOR RECEPTACLE & CAT5 FOR CASHWRAP,
SEE ELECTRICAL FOR DETAILS. T.G.C. TO OBTAIN L.L. REQUIREMENTS BEFORE CUTTING
12 NEW DEMISING WALL BY LL. G.C. TO INSTALL 5/8" TYPE'X' GYP. BD. ON TENANT SIDE AND PROVIDE BLOCKING AS
NECESSARY.
13 MESH WALL GRID BEHIND CASHWRAP. G.C. TO PROVIDE HORIZONTAL BLOCKING @ 24" O.C. SCREW BOTTOM OF
MESH TO MITIGATE MOVEMENT FROM WALL.
ADJACENT TENANT
FINISH LEGEND - COASTAL
NOTE: ALL FINISHES NEED TO MEET A MIN. OF A CLASS C FINISH FOR ENCLOSED SPACES
SEE SEC V. ON CODE STUDY FOR MORE DETAILS.
PARTNERS
brand: operations: build
I Z�
���II
7007 DISCOVER Yi BLVDro
DUBLIN, OH 43017 r.)
614.634.7000 T �I
11 tJ
W D P A R T N E R S. G O M----.----:—)
SEMiN�LE T.C.
200 TOVIINE CENTER CIRCLE
SPACE #11311 C
SANFOR®, FL 3271
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
JAI 0 8 lO jjr
MARK
I DESCRIPTION
GENERAL LOCATION
VALSPAR
SALES AREA WALLS
PT -1
CLR: SEA SALT BLUE
#: Cl 191 SATIN
VALSPAR
SERVICE ENTRANCE/
PT -2
CLR: SAWYER WHITE
RESTROOM
#: 7002-16 INTERIOR SEMI -GLOSS
Z_
VALSPAR
SALES AREA CEILING
Q
PT 3
CLR: CREME FRAICHE
#: U1200
PT -4
BEHR
CLR: SEASIDE SAND
STOCK ROOM DOOR/
WOOD FRAME
#: 7400-1 OIL BASED SEMI -GLOSS
OLYMPIC
STOREFRONT
PT -5
CLR: HEIRLOOM LACE
SYSTEM
#: D10-1
4" VINYL BASE
STOCK ROOM/
B-1
CLR: BROWN
RESTROOM
cc
6" WOOD BASE
SALES (SUPPLIED
SUPPLIED BY FRANCESCA'S, INSTALLED BY G.C.
BY FRANCESCA'S)
STOREFRONT WALL TILE
STOREFRONT
0
WT -1
SOLI USA - HOSI MOSAIC
LL
CLR: WHITE / MULTI - PATTERN BY OWNER
w
0
GROUT: POLYBLEND / CUSTOM
CLR: #333 ALABASTER
12"x12" VINYL FLOORING
STOCK ROOM/
pC
VCT 1
CLR: BEIGE
RESTROOM
O
0
KARNDEAN
SALES
�
VP 1
VINYL PLANK - HCO3
CLR: DUSK OAK, RANDOM PATTERN
SALES/ STOCK ROOM/
CLG-1
NEW 2x2 ACOUSTICAL TILE CEILING
DRESSING ROOM/
d
TEGULAR EDGE CLR: WHITE
RESTROOM
J
U
STOREFRONT
C
NEW GYP. BD. CEILING
NOTE: ALL FINISHES NEED TO MEET A MIN. OF A CLASS C FINISH FOR ENCLOSED SPACES
SEE SEC V. ON CODE STUDY FOR MORE DETAILS.
PARTNERS
brand: operations: build
I Z�
���II
7007 DISCOVER Yi BLVDro
DUBLIN, OH 43017 r.)
614.634.7000 T �I
11 tJ
W D P A R T N E R S. G O M----.----:—)
SEMiN�LE T.C.
200 TOVIINE CENTER CIRCLE
SPACE #11311 C
SANFOR®, FL 3271
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
JAI 0 8 lO jjr
PARTNERS
brand - operations: build
7007 DISCOVEF Y BLVD �1
DUBLIN, OH 4317 3;:;.
614.634.7000 T _:_01
WDPARTNERS'.COMc
1I
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE_
SPACE #13110
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
ATTACH STUD FRAMING
ATTACH STUD FRAMING
z
TO STEEL JOIST FRAMING
TO STEEL JOIST FRAMING
ABOVE PER DETAIL THIS
ABOVE PER DETAIL THIS
SHEET. DO NOT ATTACH
SHEET. DO NOT ATTACH
SCREWS A
TO METAL DECK.
TO METAL DECK.
(2)1110-16 I
16" AT EXISTING
(2)410-16 SCREWS AT
BULKHEAD STUDS.
16" AT EXISTING
'
BULKHEAD STUDS.
,
r1ALL BUILKNEAD -------""�
,'� •
/•
MALL
�•
B.O. MALL BULKHEAD
33 MILS BUILKNEAD
3 5/8", 33 MILS
EL = 1'L' -1U"
,
' ��
DIAGONAL BRACE
@ 48" O.C. MAX. 5/8„ GYP. BD. OVER
,
DIAGONAL BRACE
@ 48” O.C. MAX.
6" METAL STUD
'
---------
_--
FRAMING, PAINT
----------
PT--5 PT --5
,--,
5/8" GYP. BD. OVER
•
`-------
---
HANG RIGID CEILING
WITH #12 CLG. WIRE @
BOX BEAM HEADER: (2) 6005162-33
-------
HANG RIGID CEILING '
611 METAL STUD
48" O.C. WITH 60OT125--33 TRACKS TSB.
WITH 412 CLG. WIRE @
FRAMING, PAINT PT -5
ATTACH TRACK WITH #10-16 SKEWS
48" O.C.
(4) #10-16 @ 12" O.C. EACH FLANGE. SUPPORT
(4) #10--16
SCREWS, TYP. BOX BEAMS Hrm ONE FULL HT.
SCREWS, TYP.
STUD 6005162-33 AND ONE BEDDING
STUD 6005162-33 TYP. EACH END
(.O. STOREFRONT SYSTEM
F, .,
w. ;,
----
B.O. ENTRY _
_
--
----
----
I.
a
EL - 11'-0"
EL = 11'-0"
5/8" GYP. BD. OVER
ROLLING GRILLE
t
..,.=� .
i7 T-
_
HITH 600T125-33 TRACKS TSB,
5/8'l GYP. BD.
OVER
-:
FRAMING ' PAINT
BEYOND
ATTACH TRACK WITH #10-16 SCREWS
3 5/8" METAL
STUD
PT -5
1
@ 12" O.C. EACH FLANGE. SUPPORT
FRAMING, PAINT
PT -5
BOX BEAMS WITH ONE FULL HT.
WALL TILE (OJT -1) AND MA5TIC ON
STUD 6005162-33 AND ONE BEARING
1/2" CEMENT E30ARD. OVER 2 1/2"
STUD 6005162-33 TYP. EACH END.
METAL STUD FRAMING
ROLLING GRILLE
WALL TILE (WT
-1) ON MASTIC OVER 1/2"
COIL
CEMENT 50ARD.
FRANCESCA'5 WILL
COVE LIGHTING,
PROVIDE TILES
INSTALL 45
AND SNIP TO SITE.
DIRECT BY OWNER d
SPECIFIED BY WB
�I
MANUFACTURES
RECOMMENDATIONS.
�+
EDGE MOUNTED
n
SIGN BY SIGN
VENDOR
6"
O
I I
ALUM. STOREFRONT
SYSTEM WITH 1/2"
I I
,
TEMPERED GLAZING
I I
r
I I
_ B.O. ENTRY
--------
_ B.O. ENTRY
EL = 8'-0"
EL = 8'-0"
1'—ill
(oil
TJ
2I -All
'f
BOX BEAM HEADER: (2)
5/6" GYP. BD. OVER 6005162--33 WITH 362T125-33
3 5/8" METAL STUD TRACKS TSB. ATTACH TRACK
LED CAN LIGHT
(E> MErAL DECKING.
ATTACH BUILT-UP SECTION TO
u
FRAMING @ 16 O.C., WITH #10--16 SCREWS @ 12 O.C.
(E) s rEEL JOIST TOP CHORD W/
LEASE LINE.-----------
TYP. EACH FLANGE. SUPPORT BOX
s,LT rOP CHORD.
(3)1k12-14 SCREWS, TYP. EA END. (E) r E E L JO
_
BEAMS WITH ONE FULL H �.
DO NOT PENETRATE ROOF DECK.
STUD 3625162-33 AND ONE
BEARING STUD 3625162--33
5/8" GYP. BD. OVER
TYP. EACH END.
3 5/8" METAL STUD
I
FRAMING
BUILT-UP HEADER:
LEASE LINE.
(N) 8003162-54 METAL STUD
INSIDE OF 8005200.54 METAL ✓ L2x2x68 MILSxO'-8" LONG METAL
(N)
TRACK. CONNEO'T TOGETHER
CLIP ONE SIDE OF DIAD. BRACE W/
USING Ik10.16SCREWS « 6" U.C., (3) #10-16 SCREWS EA LEG, rYP.
MAX., `L" FROM EA END.
MANUAL ROLL -UP DOOR.
SEE AI.I FOR MORE INFO.STEEL
TUBE SUPPORT
IN WALL - SHOWN DASH[``
POST ......
(N) NEW LIGHTGAGE DIAGONAL
(E) SFEEL JOIST BOTTOM CHORD. BRACES @ 48" O.C.
01
BEFORE INSTALLING ANCHORS,
CONTRACTOR SHALL VERIFY WITH
LANDLORD THAT ATTACHMENT
SHOWN IS ACCEPTABLE.
BRACING PARALLEL TO ROOF JOISTS.
WALL BEYOND
WALL BEYOND
STOREFRONT BRACING CONNECTION AT FRAMING ABOVE
3
PARTNERS
brand - operations: build
7007 DISCOVEF Y BLVD �1
DUBLIN, OH 4317 3;:;.
614.634.7000 T _:_01
WDPARTNERS'.COMc
1I
SEMINOLE T.C.
200 TOWNE CENTER CIRCLE_
SPACE #13110
SANFORD, FL 32771
DRAWN BY:
WD PROJECT NUMBER
FRCC00050
VAV BOX SCHEDULE
EXHAUST FAN SCHEDULE
TAG
MANUFACTURER
INLET
CFMSIZE
O.A.
"FAG
MAKE
MODEL NO.
NOTES
Sales
NOTES
DESCRIPTION
CFM
CFM
HP
187
NOTES
MANUFACTURER
EF -1
SEE ELEC.
SEE ELEC.
90
MAX
MIN
120/1/60
VAV-1
TRANE
VCCF12
12"
1000
300
1, 2
NOTES:
1. FACTORY PROVIDED DISCONNECT SWITCH, CONTROL
TRANSFORMER.
2. PROVIDE NEW THERMOSTAT. COORDINATE WITH
LANDLORD FOR THERMOSTAT MANUFACTURER AND MODEL
INFORMATION.
VENTILATION RATE SCHEDULE
Mechanical Ventilation Schedules
Based upon ASHRAE 62.1, 2007
EXHAUST FAN SCHEDULE
TAG
MANUFACTURER
MODEL
NOMINAL
O.A.
FAN
VOLTAGE
MCA/MOCP
NOTES
Sales
TAG
DESCRIPTION
CFM
CFM
HP
187
NOTES
MANUFACTURER
EF -1
SEE ELEC.
SEE ELEC.
90
-
130 WATTS
120/1/60
-
1
NOTES:
-
-
WATER CLOSET
1. CEILING EXHAUST FAN. 90 CFM a 0.375" ESP. FURNISHED WITH FACTORY MOUNTED DISCONNECT AND BACKDRAFT
DAMPER.
Total (square feet)
954
VALVE COEFFICIENT
VENTILATION RATE SCHEDULE
Mechanical Ventilation Schedules
Based upon ASHRAE 62.1, 2007
PLUMBING FIXTURE CH ®ULE
Room Name
Classification
Room Area
(sq.ft.)
Area OA Rate
(cfm/sq.ft.)
FIXTURE
VALVE/FAUCET
People OA Rate
(cfm/person)
CONNECTIONS
Sales Area
Sales
TAG
DESCRIPTION
15
12
7.5
187
NOTES
MANUFACTURER
MODEL
MANUFACTURER
MODEL
WASTE
VENT
CW
HW
Restroorn
64
-
-
-
WATER CLOSET
AMERICAN
CADET
Total (square feet)
954
VALVE COEFFICIENT
RA
197
CWR
CONDENSER WATER RETURN
RD
WC -1
ADA
STANDARD
#2467.016, WHITE
RESISTOR
DC
4"
2"
3/4"
-
1, 2, 3
RTU
LAV -1
LAVATORY
AMERICAN
LUCERNE
AMERICAN
RELIANT
2"
1-1/2"
1/2"
1/2"
4, 5, 10
SD
SUPPLY DIFFUSER
ADA
STANDARD
#0355.012, WHITE
STANDARD
#7385.050
FIRE ALARM CONTROL PANEL
SMD
SMOKE DETECTOR
FCU
FAN COIL UNIT
SR
FD -1
FLOOR DRAIN
JAY R. SMITH
2O05A-P050
TIME CLOCK
-
3"
1-1/2"
-
-
9
UH
UNIT HEATER
FLOOR CLEAN
FAN POWERED BOX
SERIES 4000 TO
VOLT
FSD
FIRE SMOKE DAMPER
VA
VOLT AMPERE
GND
GROUND
VAC
FCO
OUT
JAY R. SMITH
SUITE FLOOR FINISH
VARIABLE AIR VOLUME
HAC
HEATED AIR CURTAIN
VD
VOLUME DAMPER
HOA
7
E1N.H-1
POINT -OF. -USE
WATER HEATER
CI IRONOM,ITE
HEATING RELAY
WSHP
WATER SOURCE HEAT PUMP
L
LINE VOLTAGE
3/8, ,,:
-3/8 .,
„ 6.v.
EWC-1
WATER COOLER
ELKAY
EZTL8C
-
-
2"
1-1/2"
1/2"
-
11
NOTES:
1
1.
PROVIDE WITH BEMIS MANUFACTURING MODEL 1955SSC STANDARD WHITE OPEN FRONT SEAT.
SUPPLY DIFFUSERS ONLY.
4. EXTERNAL FOIL WRAP INSULATION IS DAO O ALL
2.
PRESSURE ASSISTED TANK TYPE.
REVISIONS
REVISION #1: 01-08-2014
3.
FURNISH RIGHT AND LEFT HAND MODELS AS REQUIRED PER ADA.
4.
PROVIDE WITH JAY R. SMITH #0700 FLOOR MOUNT CONCEALED -ARM LAVATORY CARRIER.
5.
PROVIDE WITH TRUEBRO LAV GUARD.
6.
20 AMPS, 208 VOLT SINGLE PHASE, 4160 WATTS, 57°F TEMPERATURE RISE @ 0.5 GPM.
7.
PROVIDE POLISHED NICKEL BRONZE COVER WITH ZARB-1470-A CLEANOUT PLUG.
8.
CAST IRON CLEANOUT "IEE WITH STAINLESS STEEL ROUND COVER. PLUG TO BE GAS AND WATER TIGHT.
- IN CLOSED CEILING AREAS AND NOT
9.
PROVIDE FLOOR DRAIN WITH '1/2" TRAP PRIMER AND ACCESS DOOR IN WALL FOR ACCESS.
10.
PROVIDE LEONARD 270 THERMOSTATIC MIXING VALVE, ASSE 1017 AND ASSE 1070 RATED.
"0 MP
11.
PROVIDE WITH DEARBORN 17 GA. TRAP, TRAP ADAPTER, AND ANGLE STOP. WATER COOLER IS 325 WATTS AT 120V, 1 PH, 60HZ.
VENTILATION RATE SCHEDULE
Mechanical Ventilation Schedules
Based upon ASHRAE 62.1, 2007
TAG
Room Name
Classification
Room Area
(sq.ft.)
Area OA Rate
(cfm/sq.ft.)
Default Occupancy
(4/1000 sq.ft.)
Occupancy
(#)
People OA Rate
(cfm/person)
Total OA
(cfm)
Sales Area
Sales
804
0.12
15
12
7.5
187
Storage
Storage Room
86
0.12
NEW
2424
1
RG -1
room (If ixture)
Restroorn
64
-
-
-
-
-
P�Lt
Total (square feet)
954
VALVE COEFFICIENT
RA
197
DRAWING LEGEND
TAG
SUPPLY DIFFUSER
DESCRIPTION
RETURN GRILLE/ REGISTER
TAG
MODEL
SD -1
AIR DEVICE DESIGNATION
150
CFM
TYPE
NORMALLY CLOSED
EXHAUST FAN / LIGHT COMBO
T
THERMOSTAT
®
SPRINKLER HEAD
(E)
EXISTING TO REMAIN
(R)
EXISTING TO BE RELOCATED
(N)
NEW
D
AIR DEVICE SCHEDULE
TAG
MOUNTING
DESCRIPTION
FINISH
MANUFACTURER
MODEL
SIZE
NOTES
ANALOG OUTPUT
TYPE
NORMALLY CLOSED
AUX
AUXILLIARY
NO.
NORMALLY OPEN
AWG
SD -1
LAY -IN
SUPPLY
WHITE
TITUS
OMNI
2424
1
RG -1
LAY -IN
RETURN
WHITE
TITUS
50F
2424
2
NOTES:
1. PROVIDE AG -75 DAMPER.
2. 1/2" X 1/2" X 1/2" EGGCRATE RETURN AIR GRILLE.
EA10 x1l, A ` =
AHU
AIR HANDLING UNIT
MOD
MODULATING
Al
ANALOG INPUT
N
NEUTRAL
AO
ANALOG OUTPUT
NC
NORMALLY CLOSED
AUX
AUXILLIARY
NO
NORMALLY OPEN
AWG
AMERICAN WIRE GAUGE
OA
OUTDOOR AIR
CD
CONTROLDAMPER
OL
OVERLOAD
COM
COMMON
OVR
OVERRIDE
CU
CONDENSING UNIT
PC
PHOTOCELL
CV
CONTROL VALVE
PT
PROGRAMMABLE THERMOSTAT
CV
VALVE COEFFICIENT
RA
RETURN AIR
CWR
CONDENSER WATER RETURN
RD
RETURN DIFFUSER
CWS
CONDENSER WATER SUPPLY
RES
RESISTOR
DC
DIRECT CURRENT
RG
RETURN GRILLE
DI
DIGITAL INPUT
RTU
ROOFTOP UNIT
DO
DIGITAL OUTPUT
RVR
REVERSING VALVE RELAY
EA
EXHAUST AIR
S
TEMPERATURE SENSOR
EF
EXHAUST FAN
SD
SUPPLY DIFFUSER
EOL
END OF LINE
SEF
SMOKE EXHAUST FAN
FACP
FIRE ALARM CONTROL PANEL
SMD
SMOKE DETECTOR
FCU
FAN COIL UNIT
SR
SUPPLY REGISTER
FD
FIRE DAMPER
TC
TIME CLOCK
FDM
FLOW DISPLAY MODULE
TDM
TEMPERATURE DISPLAY MODULE
FM
FLOWMETER
UH
UNIT HEATER
FPB
FAN POWERED BOX
V
VOLT
FSD
FIRE SMOKE DAMPER
VA
VOLT AMPERE
GND
GROUND
VAC
VOLT ALTERNATING CURRENT
H
HOT
VAV
VARIABLE AIR VOLUME
HAC
HEATED AIR CURTAIN
VD
VOLUME DAMPER
HOA
HAND OFF AUTO
WAP
WIRELESS ACCESS POINT
HR
HEATING RELAY
WSHP
WATER SOURCE HEAT PUMP
L
LINE VOLTAGE
WUH
WALL UNIT HEATER
LS
LIQUID SENSOR
X
TRANSFORMED
MD
MINIMUM OR MODULATING DAMPER
XMFR
TRANSFORMER
MIN
MINIMUM
WMS
WIRE MESH SCREEN
GENERAL NOTES:
1.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTING CONDITIONS PRIOR TO
250
SUBMITTING A BID. SUBMISSION OF A BID SERVES AS EVIDENCE THAT THE CONTRACTOR HAS
VISITED THE SITE AND HAS ACCOUNTED FOR ALL EXISTING CONDITIONS IN THE BID.
2.
BEFORE COMMENCING ANY WORK, CONTRACTOR SHALL REVIEW THE MOST RECENT NATIONAL,
2.
STATE, AND LOCAL CODE REQUIREMENTS, AND PERFORM THE WORK IN STRICT ACCORDANCE WITH
THESE.
3.
CONTRACTOR IS REQUIRED TO READ THE SPECIFICATIONS AND REVIEW THE DRAWINGS FOR ALL
DIVISIONS OF WORK AND IS RESPONSIBLE FOR THE COORDINATION OF THIS WORK AND THE WORK
OF ALL SUBCON"TRAC"TORS WITH ALL DIVISIONS OF WORK.
4.
CONTRACTOR SHALL ADHERE TO LANDLORD SPECIFICATIONS AND TENANT DESIGN CRITERIA.
5.
CONTRACTOR SHALL PROVIDE ALL EQUIPMENT, MATERIAL, LABOR, AND SUPERVISION NECESSARY
TO COMPLETE THE WORK IN ACCORDANCE WITH THE SPECIFICATIONS AND STANDARDS AS
OPROVIDE
OUTLINED HEREIN.
6.
UPON COMPLETION OF THE WORK, CONTRACTOR SHALL VERIFY THE PROPER WORKING ORDER OF
THE SYSTEM(S) AND MAKE ANY ADJUSTMENTS AS REQUIRED.
7.
PROVIDE ALL LOW VOLTAGE CONTROL WIRING FOR THE TEMPERATURE CONTROL SYSTEM.
I
COORDINATE WITH THE ELECTRICAL CONTRACTOR FOR CONTROL SYSTEM CONDUIT AND POWER
0
REQUIREMENTS. COORDINATE EXACT LOCATIONS WITH THE GC FOR ALL TEMPERATURE CONTROL
LANDLORD NOTES:
COMPONENTS.
8.
THE CONTRACTOR SHALL ENSURE THAT ALL EQUIPMENT, PIPING, AND DUCTWORK, NOT BEING USED
\a
OR SHOWN TO REMAIN, IS FULLY REMOVED AND NOT ABANDONED. COORDINATE REQUIREMENTS
WITH GC AND LANDLORD, VERIFY SCOPE OF WORK WITH GC PRIOR TO BID AND INCLUDE ALL COSTS
IN BID.
9.
PROVIDE IDENTIFICATION FOR EQUIPMENT LOCATED ON THE ROOF OR OUTSIDE OF THE DEMISED
PREMISES. PROVIDE STENCIL WITH A MINIMUM OF 4" HIGH BLACK SPRAY PAINTED LETTERS,
INDICATING TENANT'S NAME, HVAC UNIT NUMBER AND SPACE NUMBER. VERIFY ADDITIONAL
0
REQUIREMENTS WITH LANDLORD.
10.
ALL RETURN GRILLES IN CONSTRUCTION AREAS MUST BE COVERED WITH FILTER MEDIA WHILE
HVAC SYSTEM IS RUNNING. REPLACE FILTER MEDIA WHEN IT GETS DIRTY.
11.
CERTIFIED TAB CONTRACTOR TO REBALANCE NEW AND EXISTING AIR DEVICES TO CFM AS
DESIGNATED ON PLAN.
SPRINKLER N NOTES:
1.
FIRE PROTECTION PLANS, SPRINKLER DRAWINGS, MUST BE ENGINEERED AND WET SIGNED BY A
250
LANDLORD APPROVED, LICENSED REGISTERED FIRE PROTECTION CONTRACTOR IN THE LOCAL
JURISDICTION. FINAL INSTALLATION MUST COMPLY WITH NFPA 13 AND STATE AND LOCAL
AUTHORITIES HAVING JURISDICTION.
2.
INS -FALL SPRINKLER HEADS ABOVE AND BELOW DUCTWORK AND OTHER OBSTRUCTIONS AS
REQUIRED BY NFPA 13. COORDINATE INSTALLATION OF HEADS WITH HVAC CONTRACTOR AND GC.
3.
SPRINKLER HEAD LAYOUT IS A SUGGESTED LAYOUT AND/OR A REPRESENTATION OF THE
APPROXIMATE LOCATIONS OF EXISTING HEADS. COORDINATE SPRINKLER HEAD LAYOUT AND PIPE
ROUTING WITH ARCHITECTURAL PLANS, STRUCTURAL PLANS, HVAC CONTRACTOR, ELECTRICAL
CONTRACTOR, AND GC. THE FIRE SPRINKLER CONTRACTOR SHALL INCLUDE IN THE BID AND BE
RESPONSIBLE FOR THE EXACT QUANTITY OF SPRINKLER HEADS REQUIRED FOR COVERAGE AND
FINAL APPROVAL.
KEYED NOTES:
0
CONNECT NEW SANITARY LINE INTO THE EXIS"f ING SANITARY SERVICE, PROVIDE ADDITIONAL
250
CLEANOUTS AS REQUIRED. FIELD VERIFY EXACT LOCATION AND SIZE OF SANITARY LINE AND
INVERT PRIOR TO BID. THIS CONTRACTOR IS RESPONSIBLE FOR ANY CUTTING AND PATCHING OF
THE FLOOR THAT MAY BE REQUIRED AS IT RELATES TO THE PLUMBING SCOPE OF WORK. REFER
TO WASTE AND VENT RISER DIAGRAM AND PLUMBING SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS.
CCONNECT
NEW COLD WATER LINE INTO THE EXISTING COLD WATER TAP. NOTIFY G.C. IF TAP IS
SMALLER THAN SHOWN. REFER TO WATER RISER DIAGRAM AND PLUMBING SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS. COORDINATE BACKFLOW PREVENTER REQUIREMENTS WITH
LANDLORD AND LOCAL AUTHORITY HAVING JURISDICTION. CONTRACTOR SHALL PURCHASE
WATER METER AND REMOTE READER FROM LANDLORD'S TENANT COORDINATOR. INSTALL PER
LANDLORD AND LOCAL AUTHORITY'S REQUIREMENTS.
OPROVIDE
NEW THERMOSTAT FOR VAV-1. COORDINATE MAKE AND MODEL NUMBER WITH
PRELIM SET 10 16 2013
LANDLORD TO TIE INTO EXISTING MALL DDC SYSTEM.
DEMOLISH EXISTING VAV BOX, VERIFY EXACT LOCATION IN THE FIELD. NEW VAV BOX TO BE
INSTALLED IN LOCATION SHOWN. INSTALL VAV BOX IN ACCORDANCE WITH THE MANUFACTURER'S
I
GUIDELINES AND MAINTAIN ALL REQUIRED SERVICE CLEARANCES.
0
CONNECT NEW MEDIUM PRESSURE DUCT TO EXISTING LANDLORD SUPPLY DUCT SYSTEM. VERIFY
LANDLORD NOTES:
EXACT LOCATION IN THE FIELD PRIOR TO VAV BOX INSTALLATION.
PRIOR TO BID, CONTRACTOR SHALL VISIT THE SITE AND FIELD VERIFY THE EXISTING CONDITIONS
\a
OF THE SPRINKLER SYSTEM AND DETERMINE EXACT SCOPE/EXTENT OF SPRINKLER
MODIFICATIONS WITH LANDLORD AND LOCAL FIRE MARSHAL. INCLUDE ALL COSTS IN BID FOR
REQUIRED SPRINKLER MODIFICATIONS. EXISTING SPRINKLER HEADS IN EXISTING CEILINGS CAN
BE REUSED WHERE APPROPRIATE. NEW SPRINKLER HEADS SHALL BE INSTALLED IN NEW CEILING
OR IN OPEN STRUCTURE AREAS (STOCKROOM) AS REQUIRED. PROVIDE NEW SPRINKLER PIPE AS
NEEDED. ENSURE PROPER COVERAGE PER NFPA 13.
0
EXISTING RETURN AIR TRANSFER GRILLE THRU DEMISING WALL SHALL BE REUSED. VERIFY EXACT
LOCATION IN THE FIELD. VERIFY EXISTING FIRE DAMPER IS IN COMPLETE WORKING ORDER.
REPAIR OR REPLACE AS REQUIRED.
PROVIDE NEW POINT OF USE ELECTRIC WATER HEATER. INSTALL AND MAKE PIPING CONNECTIONS
PER DETAIL M2-01 ON SHEET M2 AND MANUFACTURER INSTALLATION INSTRUCTIONS,
9L
NEW CEILING EXHAUST FAN/LIGHT COMBO BY ELECTRICAL CONTRACTOR. FAN CONTROL SHALL
BE WIRED THROUGH THE LIGHT SWITCH SERVING THE RESTROOM. COORDINATE INSTALLATION
WITH ELECTRICAL CONTRACTOR. EXTEND 6"0 DUCT FROM THE NEW EXHAUST FAN AND CONNECT
TO EXISTING MALL EXHAUST SYSTEM. VERIFY EXACT LOCATION IN THE FIELD.
10
EXTEND NEW VENT PIPING TO MALL VENT SYSTEM. VERIFY MALL VENT SYSTEM LOCATION IN THE
FIELD PRIOR TO WORK. REFER TO WASTE AND VENT RISER DIAGRAM AND PLUMBING
SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
I M l
H a
U
d
250
ISSUE DATES
4,
I�
PRELIM SET 10 16 2013
n j
I
LANDLORD NOTES:
\a
FINAL SET: 11-6-2013
REST�'
�E�
���
3
>
1. G.C. SHALL VERIFY TRANSFER AIR OPENINGS EXIST AND MEET
PE : 11-20-2013
PERMIT SET
I•.•
MALL CRITERIA FOR VAV/HVAC COMPLIANCE .
3
L. GC SHALL UTILIZE A LL APPROVED CONTRACTOR FOR ALL
SD 1
INTERFACE CONNECTIONS TO CURRENT MALL JOHNSON EMS
r
RU -1=;
6 10':,x';
SYSTEM. CONTACT MALL OPERATIONS TO VERIFY.
--
150
3. EXTERNALLY INSULATED FLEXIBLE DUCT, NOT TO EXCEED 5'-0"
IN LENGTH, MAY BE USED FOR VERT"TICAL CONNECTIONS TO
5
1
_
t 8
SUPPLY DIFFUSERS ONLY.
4. EXTERNAL FOIL WRAP INSULATION IS DAO O ALL
�]
REVISIONS
REVISION #1: 01-08-2014
.......... ...-- VD
- IN CLOSED CEILING AREAS AND NOT
"0 MP
14x12
IN LIEU OF INTERNAL DUCT LINER.
'
>
s
3 . 3
VAV=1 <UD VD Vp
.r.,v
. .,
,r..
SurnmerDaily Range...............................................................................................
WinterDesign Dry-Bulb........................................................................................... 37.0 IF
WinterDesign Wet-Bulb.......................................................................................... 31.1 IF
Atmospheric Clearness Number.............................................................................. 0.90
Average Ground Reflectance................................................................................. 0.20
SoilConductivity.................................................................................................... 0.800 BTU/(hr-ft-°F)
50 h
WEATHER DATA
Design
HVAC LOAD CALCULATIONS
Time
Maximum
Zone
VAV
Air System Information
Cooling
Design aar% meters:
i
Air
of
Air System Narne................................ BLOCK LOAD Number of zones.........................................................
. 1
Stock Room
1
Sensible
Equipment Class ............................................ UNDEF Floor Area ............................................
............ 1003.0 ft2
CityName..........................................................................................................
Orlando
Area
Air System Type .................................................. VAV Location ....................................
Orlando, Florida
Location..............................................................................................................
Florlda
(CFM)
Sizing Calculation Information
(MBH)
Latitude....................................................................................................................
28.4
Deg.
Zone and space: Sizing Method:
944
Longitude
81.3
Deg.
Zone CFM .......................... Peak zone sensible load Calculation Months .......................................
Jan to Dec
.................................................................................................................
Elevation................................................................................................................
105.0
ft
Space CFM .................. Individual peak space loads Sizing Data .............................................
User -Modified
SummerDesign Dry-Bulb........................................................................................
94.0
IF
IF
Zane Sizing Data
23.3
Summer Coincident Wet-Bulb..................................................................................
76.0
79.1: / 67.6
IF
Sensible coil load .................................................
19.8
166
OF
74.5/62.5
`F
SurnmerDaily Range...............................................................................................
WinterDesign Dry-Bulb........................................................................................... 37.0 IF
WinterDesign Wet-Bulb.......................................................................................... 31.1 IF
Atmospheric Clearness Number.............................................................................. 0.90
Average Ground Reflectance................................................................................. 0.20
SoilConductivity.................................................................................................... 0.800 BTU/(hr-ft-°F)
50 h
Local Time Zone (GMT +/- N hours).......................................................................... . ours
Consider Daylight SavingsTime ................................................................................. No
Zone Terminal Sizing Data
Simulation Weather Data
.............................................. .................. noneN/A y ..1.. ,, Y i , I t�.._ ; , . €.. .at"<. =Jr�. a �• :,;� f:,. 'his � y�c�tt�•r
Current Data is...................................................................... 2001 ASHRAE Handbook N:.1or?¢:, r€,€ na ,_,r t,c} =.fs. r ; �,s, .€ s,y .>f .., €.
Design Cooling Months............................................................... January to December Space Loads and Airflows
Zone Name /
Space Name
Maximum
Design
Minimum
Time
Maximum
Zone
VAV
HEATING DATA AT DES HTG
HEATING OA DB / WB 37.0 IF / 31.1 IF
Cooling
Air
Air
of
Heating
Floor
Stock Room
1
Sensible
Flow
Flow
Peak
Load
Area
Zone
Zone Name
(MBH)
(CFM)
(CFM)
Load
(MBH)
(ft2)
CFM/ft2
Zone 1
17.3
944
213
Jan 1900
0.0
1003.0
0.94
Local Time Zone (GMT +/- N hours).......................................................................... . ours
Consider Daylight SavingsTime ................................................................................. No
Zone Terminal Sizing Data
Simulation Weather Data
.............................................. .................. noneN/A y ..1.. ,, Y i , I t�.._ ; , . €.. .at"<. =Jr�. a �• :,;� f:,. 'his � y�c�tt�•r
Current Data is...................................................................... 2001 ASHRAE Handbook N:.1or?¢:, r€,€ na ,_,r t,c} =.fs. r ; �,s, .€ s,y .>f .., €.
Design Cooling Months............................................................... January to December Space Loads and Airflows
Zone Name /
Space Name
Mult.
Cooling Time
Sensible of
(MBH) Load
Air Heating
Flow Load
(CFM) (MBH)
Floor
Area Space
(ft2) CFM/ft2
Zone '1
AirSystem Type ..................................................
VAV
HEATING DATA AT DES HTG
HEATING OA DB / WB 37.0 IF / 31.1 IF
Location ...............................................
Sales
1
13.0 Jan 1900
709 0.0
799.0 0.89
Stock Room
1
3.91 Jan 21001
211 0.0
144.01 1.46
Restroom
1
0.51 Jan 21001
25 0.0
60.01 0.42
HVAC LOAD CALCULATIONS
Air System Information
• � N -bee of zone 1
Air�,ystern Narne................................
Equipment Class ............................................
BLOCK LOAD
UNDEF
um ............................................
Floor Area............................................................
I.............
1003.0
ft2
AirSystem Type ..................................................
VAV
HEATING DATA AT DES HTG
HEATING OA DB / WB 37.0 IF / 31.1 IF
Location ...............................................
Orlando, Florida
Sensible Latent
Details (BTU/hr) (BTU/hr)
Sizing Calculation Information
Window & Skylight Solar Loads
0 ft2 0
0 ft2
Zone and Space Sizing Method;
0 ft2 0
0 ft2 0
Roof Transmission
Zone CFM .......................... Peak zone
sensible load
0 ft2 0
Calculation Months .......................................
Jan to Dec
0 ft2 0
Space CFM .................. Individual peak
space loads
Sizing Data ..............................................
User -Modified
Central Cooling Coil Sizing Data
Door Loads
0 ft2 0
0 ft2 0
Total coil load .........................................................
1.9
Tons
Load occurs at .................................................
Jan 1300
Totalcoil load .......................................................
23.3
MBH
OA DB / WB ...................................................
79.1: / 67.6
IF
Sensible coil load .................................................
19.8
MBH
Entering DB / WB ...........................................
74.5/62.5
`F
Coil CFM at Jan 1300 ............................................
944
CFM
Leaving DB ! WB ...........................................
55.0/53.9
IF
Maxblock CFM .....................................................
944
CFM
Coil ADP..................................................................
52.8
IF
Sum of peak zone CFM .........................................
944
CFM
Bypass Factor........................................................
0.100
0
Sensible heat ratio ..............................................
0.851
0
Resulting RH..............................................................
52
%
ft2/Ton.................................................................
516.9
- 0
Design supply ternp.................................................
55.0
IF
BTU/(hr-ft2)...........................................................
23.2
0
Zone T -stat Check .................................................
0 of 1
OK
Water flow @ 10.0 IF rise .....................................
4.66
gpin
Max zone temperature deviation ................................
0.7
IF
Supply Fan Sizing Data
Plenum Wall Load
0% 0
-
0 0
Actual max CFM ....................................................
944
CFM
Fan motor BFIP........................................................
0.10
BHP
StandardCFM .......................................................
940
CFM
Fan motor kW ..........................................................
0.08
I<W
Actual max CFM/ft2...............................................
0.94
CFM/ft2
Fan static.................................................................
0.75
in wg
Outdoor Ventilation Air Data
0
Supply Fan Load
944 CFM 283
213 CFM -99
Design airflow CFM ..................................................
0
CFM
CFM/person.............................................................
0.00
CFM/person
CFM/ft2.................................................................0.00
0% 0
CFM/ft2
01/. 0
-
>> Total System Loads
DESIGN COOLING
DESIGN HEA11N01
COOLING DATA AT Jan 1300
COOLING OA DB / WB 79.6'F/67.6'F
HEATING DATA AT DES HTG
HEATING OA DB / WB 37.0 IF / 31.1 IF
ZONE LOADS
Sensible Latent
Details (BTU/hr) (BTU/hr)
Sensible Latent
Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads
0 ft2 0
0 ft2
Wall Transmission
0 ft2 0
0 ft2 0
Roof Transmission
0 ft2 0
0 ft2 0
Window Transmission
0 ft2 0
0 ft2 0
Skylight Transmission
0 ft2 0
0 ft2 0
Door Loads
0 ft2 0
0 ft2 0
Floor Transmission
1003 ft2 0
1003 11:2 0 -
partitions
0 ft2 0
0 ft2 0 -
Ceiling
0 f 0
0 ft2 0
Overhead Lighting
1059 W 2925
0 0
Task Lighting
1598 W 4341
0 0
Electric Equipment
1250 W 4197
-
00
People
15 2498
3007
0 0
0
Infiltration
- 0
0
0
0
Miscellaneous
0
0
- 0
0
Safety Factor
15% /15% 2094
451
10% 0
0
.,> Total Zone Loads
16055
3458
0
0
Zone Conditioning
19544
3458
- -1709
0
Plenum Wall Load
0% 0
-
0 0
Plenum Roof Load
01/. 0
0 0
Plenum Lighting Load
0°/ 0
00
Return Fan Load
944 CFM 0
213 CFM 0
Ventilation Load
0 CFM 0
0
0 CFM 0
0
Supply Fan Load
944 CFM 283
213 CFM -99
-
Space Fan Coil Fans
- 0
0
Duct Heat Gain / Loss
0% 0
01/. 0
-
>> Total System Loads
19827
3458
-1808
0
Central Cooling Coil
19827
3458
-1808
0
, Total Conditioning
19827
3458
-1808
0
Key:
Positive values are clg loads
Negative values are htg loads
Positive values are htg loads
Negative values are clg loads
ELECTRICAL COMMENTS:
• ABSOLUTELY NO FLEXIBLE CONDUIT IS PERMITTED IN DEMISING WALLS. FLEXIBLE CONDUIT IS PERMITTED FOR SHORT, FINAL CONNECTIONS ONLY
(6'-0" OR LESS).
• EXPOSED CONDUIT SHALL BE INSTALLED IN STRAIHGT LINES, PARALLEL OR IN RIGHT ANGLES TO THE BUILDING STRUCTURE. DO NOT LOOP EXCESS
FLEXIBLE CONDUIT IN CEILING SPACE OR WALL CAVITY.
• CABLE TYPES AC OR NM CABLES ARE NOT ACCEPTABLE. TYPE MC CABLE, ELECTRIC METALLIC TUBING (EMT), AND RIGID GALVANIZED CONDUIT ARE
PERMITTED.
• ALL EQUPMENT, DEVICES, AND FIXTURES SHALL BE GROUNDED IN COMPLIANCE WITH NEC AND UL REQUIREMENTS.
• ALL PANELS TO BE UI. LABELED WITH BOLT -ON TYPE CIRCUIT BREAKERS.
• 7 -DAY, 24-HOUR TIME CLOCK IS REQUIRED TO CONTROL STOREFRONT ENRTY LIGHTS, SHOW WINDOW, SHOW WINDOW LIGHTS, SHOW WINDOW
RECEPTACLES, AND STOREFRONT SIGNAGE. ILLUMINATED STOREFRONT SIGNS MUST REMAIN LIT DURING ALL MALL BUSINESS HOURS.
• TENANT IS REQUIRED TO MAKE A FIELD SURVEY OF THE EXISTING ELECTRICAL SERVICE TO ENSURE THAT THE TOTAL CONNECTED LOAD DOES NT
EXCEED THE ELECTRICAL SERVICE. ANY/ALL MODIFICATIONS OR UPGRADES NEEDED ARE SUBJECT TO LANDLORD'S PRIOR APPROVAL, AND WILL
BE COMPLETED BY TENANT/TENANT'S G.C., AT TENANT'S SOLE EXPENSE.
• ALL ELECTRICAL PANELS TO BE MOUNTED ON PLYWOOD BACKER BOARD.
• PANEL PHASE LOADS TO BE BALANCED WITHIN 10%.
• ELECTRICAL PANELS MAY NOT BE RECESSED IN DEMISING PARTITIONS, SURFACE MOUNT OR FUR OUT WALL TO ACHIEVE FLUSH APPEARANCE.
• ONLY 30KVA AND SMALLER TRANSFORMERS MAY BE SUSPENDED FROM BUILDING STRUCTURE, ALL OTHER TRANSFORMERS NUST BE FLOOR
MOUNTED.
• FLOOR PENETRATIONS
TENANT'S G.C. MUST ADVISE THE PROPERTY'S OPERATIONS DIRECTOR PRIOR TO ANY SLAB CUTTING OR REMOVAL. ALL FLOOR PENETRATIONS
MUST BE CORE -BORED OR SAW -CUT (NO JACK-HAMMERIN(3 PERMITTED). PRIOR TO WORK, TENANT'S G.C. MUST VERIFY THAT TENANT'S WORK WILL
NOT CONFLICT WITH EXISTING, STRUCTURAL, UTILITY, OR OTHER UNDER SLAB CONDITIONS. TENANT'S WORK MUST NOT COMPROMISE OR DAMAGE
THE EXISTING STRUCTURE. ANY DAMAGE CAUSED BY TENANT'S WORK IS TO BE REPAIRED AT TENANT'S EXPENSE.
E
r....A 20,22 1
y; # ...w..,.... , WH -1 .. 1
A 10
i
...... .,
3�
t9
,
w 1 _
t A-8 I
1r?(_),!AT "B.,
1 6+
Ll A-1 5 ) A 12
+1 1
13 I
J
A-4,6
...... ....z@
;1
,., g {.„......a 60A DISC 3SV1
= 1 ` 30KVA XFMR
1
POINT "A”
I A2
....... ... t...r.......... ..... .
A-10
E
OEM 1 POWER PLAN
mm SCALE: 1/4"=V-0"
.0
3 :
ADJACENT TENANT
t
" .... _ ..... .
13 t
.-
1 I 10
1
C�11
+14"
° A-18 A-17 u'
-12 VIA SW. 'T'
� E
t
E #
I �..
S. ...........
..y..... � . „ .........E ,ntS .... e.�
........ ;:
..nc
3
A-17
A-24' _, POINT "C"
#i �} t4
PANEL A t 13
!�I
VIA=eSW f"
A 1zdb+14" j IIA 18((1
1::..
ADJACENT TENANT
A-14,16
0VIA SW. '1'
11 A 18
}
1�
3
A -1l
A-12kh+14"
ELECTRICAL SYMBOLS LIST_
STANDARD 20A, 120/277V-10 SPST TOGGLE SWITCH MOUNTED AT +48" A.F.F.
$OS WALL MOUNTED INFRA -RED OCCUPANCY SENSOR.
OS CEILING MOUNTED ULTRASONIC OCCUPANCY SENSOR.
W STANDARD 20A, 120V-10 GROUNDING TYPE SIMPLEX RECEPTACLE MOUNTED AT
+18" A.F.F.
STANDARD 20A, 120V-16 GROUNDING TYPE DUPLEX RECEPTACLE MOUNTED AT
+18" A.F.F.
&.P STANDARD 20A, 120V-10 GROUNDING TYPE WEATHER PROOF (NEMA 3R) DUPLEX
RECEPTACLE MOUNTED AT +18" A.F.F.
STANDARD 20A, 120V-10 GROUNDING TYPE DUPLEX RECEPTACLE CEILING
MOUNTED AT STORE FRONT
STANDARD 20A, 120V-10 GROUNDING TYPE FOUR-PLEX RECEPTACLE MOUNTED AT
+18" A.F.F.
STANDARD 20A, 120V-10 GROUNDING TYPE "GROUND FAULT INTERRUPTER" (G.F.I.)
RECEPTACLE MOUNTED AT +18" A.F.F.
STANDARD 20A, 120V-10 ISOLATED GROUND TYPE DUPLEX RECEPTACLE,MOUNTED
AT +18" A.F.F.
STANDARD 20A, 120V-10 ISOLATED GROUND TYPE QUADRAPLEX
RECEPTACLE,MOUNTED AT+18" A.F.F.
STANDARD 15A, 120V-10 SIMPLEX CLOCK RECEPTACLE.
Ke
LM FUSED DISCONNECT SWITCH. AMPS, POLES AND FUSE SIZE AS INDICATED.
OPEN- INDICATES NON-FUSED
W.P. - INDICATES NEMA 3R ENCLOSURE
L® COMBINATION DISCONNECT SWITCH/MAGNETIC MOTOR STARTER. AMPS, POLES,
FUSE SIZE, AND NEMA SIZE AS INDICATED. PROVIDE COMPLETE WITH THERMAL
OVERLOAD PROTECTION PER MOTOR NAMEPLATE DATA, 120V CONTROL COIL -
U.O.N., AND H.O.A. (HAND -OFF -AUTO) SWITCH. W.P. - INDICATES NEMA 3R
ENCLOSURE.
® MAGNETIC MOTOR STARTER. POLES AND NEMA SIZE AS INDICATED, PROVIDE
COMPLETE WITH THERMAL OVERLOAD PROTECTION PER MOTOR NAMEPLATE
DATA, 120V CONTROL COIL - U.O.N., AND H.O.A. (HAND -OFF -AUTO) SWITCH.
W.P. - INDICATES NEMA 3R ENCLOSURE
MANUAL MOTOR STARTER SWITCH. HORSEPOWER RATED -120V - 10 -U.O.N.
M PROVIDE COMPLETE WITH THERMAL OVERLOAD PROTECTION.
O JUNCTION BOX. SIZED BY THE CONTRACTOR PER ACTUAL NUMBER OF CONDUITS
AND/OR CONDUCTORS PASSING THRU.
MOTOR OUTLET. H.P. OR F.L.A. - VOLTS & PHASE AS INDICATED.
TRANSFORMER AS SPECIFIED.
© TIME CLOCK.
DELIVERY BUZZER.
DELIVERY BUZZER PUSH BUTTON MOUNTED AT 54" A.F.F.
TELEPHONE PLYWOOD BACKBOARD.
Q THERMOSTAT FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR.
PROVIDE J -BOX AT +48" A.F.F.
(� VOLUME CONTROL MOUNTED AT +48" AFF.
Y® TELEPHONE OUTLET WITH (1) RJ11 PORT. JACK COLOR - GRAY.
XV DATA OUTLET WITH RJ45 PORTS (X) AMOUNT OF DATA PORTS. JACK COLOR -
ORANGE.
® COMBINATION TELE/DATA OUTLET WITH (1) RJ11 AND AND (2) RJ45 PORTS. JACK
COLOR - GRAY AND ORANGE.
® TELEPHONE OUTLET WITH (1) RJ11 PORT WITH TWO TELEPHONE LINES. JACK
COLOR - BLUE.
CONDUIT CONCEALED WITHIN BUILDING WALLS OR CEILING SPACE.
CONDUIT ROUTED BELOW FINISHED GRADE AND / OR CONCRETE SLAB.
HOMERUN TO DESTINATION AS INDICATED. REFER TO CONDUIT SYMBOL ABOVE.
FLEXIBLE CONDUIT CONNECTION FROM JUNCTION BOX.
GENERAL ELECTRICAL SAFETY REQUIREMENTS:
A. ALL ELECTRICAL WORK PRACTICES MUST COMPLY WITH APPLICABLE
SECTIONS OF THE OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION (OSHA), NATIONAL FIRE PROTECTION ASSOCIATION
(NFPA), NATIONAL ELECTRICAL CODE (NFPA 70 & 70E), NATIONAL
ELECTRICAL SAFETY CODE (NESC) AND STATE AND LOCAL ADOPTED
ELECTRICAL CODES.
B. THE GENERAL CONTRACTOR, ELECTRICAL CONTRACTOR AND ALL
APPLICABLE TRADES ARE RESPONSIBLE STRICT TRICT ADHERENCE TO
ALL ELECTRICAL SAFETY REQUIREMENTS. -
LANDLORD REQUIREMENTS:
• ALL HOME RUNS TO TENANT'S PANELS SHALL BE IN RIGID STEEL
CONDUIT OR EMT.
• ALL EXPOSED WIRING IN CEILINGS OR INTERIOR WALLS MUST BE IN
RIGID STEEL CONDUIT OR EMT.
• ALL WIRING IN LANDLORD DEMISING WALLS MUST BE IN RIGID STEEL
CONDUIT OR EMT.
• COORDINATE ALL FLOOR CUT MEANS AND METHODS OF ROUTING
CONDUIT THROUGH THE FLOOR WITH MALL OPERATIONS.
• NO CONDUIT TO BE SUPPORTED FROM THE ROOF DECK.
FIRE ALARMSYSTEM YM L
r "•
d��i,�S/U•• ir� %
FRCP I
FIRE CONTROL PANEL +72" A.F.F. TO TOP OF DEVICE
RPS
REMOTE POWER SUPPLY +72" A.F.F. TO TOP OF DEVICE
F-F—TC-1
FIRE TERMINAL CABINET
FSA
FIRE SYSTEM ANUNCIATOR +48" A.F.F. TO TOP OF DEVICE
Zc
CONTROL MODULE
Zr
RELAY MODULE CONTROL RELAY, SPDT, W/ LED
�j
MONITOR MODULE
a
PULL STATION +48" A.F.F. TO TOP OF DEVICE
QTS
WATER FLOW SWITCH
40
TAMPER SWITCH
DH
DOOR HOLD OPEN DEVICE
B. CIRCUITING INDICATED ON PLAN IS PARTIALLY DIAGRAMMATIC FOR
"THRU-WIRING"
24VDC HORN +90" A.F.F. TO TOP OF DEVICE
R1
SUPERVISION RELAY
O L
DETECTOR 120 VAC W/9VDC BATTERY
O
PHOTOELECTRIC SENSOR
3 :
ADJACENT TENANT
t
" .... _ ..... .
13 t
.-
1 I 10
1
C�11
+14"
° A-18 A-17 u'
-12 VIA SW. 'T'
� E
t
E #
I �..
S. ...........
..y..... � . „ .........E ,ntS .... e.�
........ ;:
..nc
3
A-17
A-24' _, POINT "C"
#i �} t4
PANEL A t 13
!�I
VIA=eSW f"
A 1zdb+14" j IIA 18((1
1::..
ADJACENT TENANT
A-14,16
0VIA SW. '1'
11 A 18
}
1�
3
A -1l
A-12kh+14"
ELECTRICAL SYMBOLS LIST_
STANDARD 20A, 120/277V-10 SPST TOGGLE SWITCH MOUNTED AT +48" A.F.F.
$OS WALL MOUNTED INFRA -RED OCCUPANCY SENSOR.
OS CEILING MOUNTED ULTRASONIC OCCUPANCY SENSOR.
W STANDARD 20A, 120V-10 GROUNDING TYPE SIMPLEX RECEPTACLE MOUNTED AT
+18" A.F.F.
STANDARD 20A, 120V-16 GROUNDING TYPE DUPLEX RECEPTACLE MOUNTED AT
+18" A.F.F.
&.P STANDARD 20A, 120V-10 GROUNDING TYPE WEATHER PROOF (NEMA 3R) DUPLEX
RECEPTACLE MOUNTED AT +18" A.F.F.
STANDARD 20A, 120V-10 GROUNDING TYPE DUPLEX RECEPTACLE CEILING
MOUNTED AT STORE FRONT
STANDARD 20A, 120V-10 GROUNDING TYPE FOUR-PLEX RECEPTACLE MOUNTED AT
+18" A.F.F.
STANDARD 20A, 120V-10 GROUNDING TYPE "GROUND FAULT INTERRUPTER" (G.F.I.)
RECEPTACLE MOUNTED AT +18" A.F.F.
STANDARD 20A, 120V-10 ISOLATED GROUND TYPE DUPLEX RECEPTACLE,MOUNTED
AT +18" A.F.F.
STANDARD 20A, 120V-10 ISOLATED GROUND TYPE QUADRAPLEX
RECEPTACLE,MOUNTED AT+18" A.F.F.
STANDARD 15A, 120V-10 SIMPLEX CLOCK RECEPTACLE.
Ke
LM FUSED DISCONNECT SWITCH. AMPS, POLES AND FUSE SIZE AS INDICATED.
OPEN- INDICATES NON-FUSED
W.P. - INDICATES NEMA 3R ENCLOSURE
L® COMBINATION DISCONNECT SWITCH/MAGNETIC MOTOR STARTER. AMPS, POLES,
FUSE SIZE, AND NEMA SIZE AS INDICATED. PROVIDE COMPLETE WITH THERMAL
OVERLOAD PROTECTION PER MOTOR NAMEPLATE DATA, 120V CONTROL COIL -
U.O.N., AND H.O.A. (HAND -OFF -AUTO) SWITCH. W.P. - INDICATES NEMA 3R
ENCLOSURE.
® MAGNETIC MOTOR STARTER. POLES AND NEMA SIZE AS INDICATED, PROVIDE
COMPLETE WITH THERMAL OVERLOAD PROTECTION PER MOTOR NAMEPLATE
DATA, 120V CONTROL COIL - U.O.N., AND H.O.A. (HAND -OFF -AUTO) SWITCH.
W.P. - INDICATES NEMA 3R ENCLOSURE
MANUAL MOTOR STARTER SWITCH. HORSEPOWER RATED -120V - 10 -U.O.N.
M PROVIDE COMPLETE WITH THERMAL OVERLOAD PROTECTION.
O JUNCTION BOX. SIZED BY THE CONTRACTOR PER ACTUAL NUMBER OF CONDUITS
AND/OR CONDUCTORS PASSING THRU.
MOTOR OUTLET. H.P. OR F.L.A. - VOLTS & PHASE AS INDICATED.
TRANSFORMER AS SPECIFIED.
© TIME CLOCK.
DELIVERY BUZZER.
DELIVERY BUZZER PUSH BUTTON MOUNTED AT 54" A.F.F.
TELEPHONE PLYWOOD BACKBOARD.
Q THERMOSTAT FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR.
PROVIDE J -BOX AT +48" A.F.F.
(� VOLUME CONTROL MOUNTED AT +48" AFF.
Y® TELEPHONE OUTLET WITH (1) RJ11 PORT. JACK COLOR - GRAY.
XV DATA OUTLET WITH RJ45 PORTS (X) AMOUNT OF DATA PORTS. JACK COLOR -
ORANGE.
® COMBINATION TELE/DATA OUTLET WITH (1) RJ11 AND AND (2) RJ45 PORTS. JACK
COLOR - GRAY AND ORANGE.
® TELEPHONE OUTLET WITH (1) RJ11 PORT WITH TWO TELEPHONE LINES. JACK
COLOR - BLUE.
CONDUIT CONCEALED WITHIN BUILDING WALLS OR CEILING SPACE.
CONDUIT ROUTED BELOW FINISHED GRADE AND / OR CONCRETE SLAB.
HOMERUN TO DESTINATION AS INDICATED. REFER TO CONDUIT SYMBOL ABOVE.
FLEXIBLE CONDUIT CONNECTION FROM JUNCTION BOX.
GENERAL ELECTRICAL SAFETY REQUIREMENTS:
A. ALL ELECTRICAL WORK PRACTICES MUST COMPLY WITH APPLICABLE
SECTIONS OF THE OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION (OSHA), NATIONAL FIRE PROTECTION ASSOCIATION
(NFPA), NATIONAL ELECTRICAL CODE (NFPA 70 & 70E), NATIONAL
ELECTRICAL SAFETY CODE (NESC) AND STATE AND LOCAL ADOPTED
ELECTRICAL CODES.
B. THE GENERAL CONTRACTOR, ELECTRICAL CONTRACTOR AND ALL
APPLICABLE TRADES ARE RESPONSIBLE STRICT TRICT ADHERENCE TO
ALL ELECTRICAL SAFETY REQUIREMENTS. -
LANDLORD REQUIREMENTS:
• ALL HOME RUNS TO TENANT'S PANELS SHALL BE IN RIGID STEEL
CONDUIT OR EMT.
• ALL EXPOSED WIRING IN CEILINGS OR INTERIOR WALLS MUST BE IN
RIGID STEEL CONDUIT OR EMT.
• ALL WIRING IN LANDLORD DEMISING WALLS MUST BE IN RIGID STEEL
CONDUIT OR EMT.
• COORDINATE ALL FLOOR CUT MEANS AND METHODS OF ROUTING
CONDUIT THROUGH THE FLOOR WITH MALL OPERATIONS.
• NO CONDUIT TO BE SUPPORTED FROM THE ROOF DECK.
VERY EXACT LOCATION WITH OWNER. G.C. TO INSTALL STEREO AND RUN
SPEAKER WIRE, G.C. TO RUN WIRE BEHIND FURNITURE, SPEAKERS WD PROJECT NUMBER
INSTALLED ON FOP OF FURNITURE TO RIGHT AND LEFI OF BACK
CASHWRAP. SPEAKERS TO MUTE WHEN FIRE ALARM IS ACTIVATED. G.C. TO FRCC00050
VERIFY ALL REQUIREMENTS WITH LANDLORD AND TO COORDINATE WITH
FIRE ALARM CONTRACTOR AS REQUIRED.
DUPLEX RECEPTACLE WITH COVER PLATE MOUNTED IN SOFFIT ABOVE
WINDOW. CONTROL RECEPTACLE WITH TIME CLOCK AND SWITCHES AT
MANAGER'S DESK. RECEPTACLE AND COVER PLATE TO MATCH �����As{aaaaaae�®d
SURROUNDING WALL COLOR. .,��' 4.H�`�� o9d
cam.
4 NEW PANEL "A" 208Y/1 20V, 3PH, 4W WITH A 100A MAIN CIRCUIT BREAKER. �.,\\ G E N �� "•.,'y ����
REFER TO SHEET E-3 FOR MORE DETAIL.
_ No 6 '.
AN
5 NEW TIME CLOCK FOR LIGHTING AND RECEPTACLES. REFER TO SHEETE2
0 =_
FOR MODEL NUMBER. COORDINATE EXACT LOCATION PRIOR TO BID.
O2' X 4' X 3/4" TELECOMM. BOARD WITH DEDICATED QUADRAPLEX r'",~ %STATE OF r
RECEPTACLE AND CIRCUIT WITH ISOLATED GROUND. VERIFY SYSTEM
L AL TELEPHONE "o" OB �•••���"
GENERAL N
r "•
d��i,�S/U•• ir� %
COMPANY. EXTEND 1" TELEPHONE CONDUIT WITH PULL WIRE FROM
IN
A. THE CONTRACTOR FOR THIS WORK IS REQUIRED TO READ THE
PSB
u
SPECIFICATIONS REVIEW DRAWINGS OF ALL DIVISIONS OF WORK AND IS
RESPONSIBLE FOR THE COORDINATION OF THIS WORK AND THE WORK OF
PARTNERS
ALL SUBCONTRACTORS WITH ALL DIVISIONS OF WORK. IT IS THE
CONTRACTOR'S RESPONSIBILITY TO PROVIDE ALL SUBCONTRACTORS
ISSUE GATES
40
WITH A COMPLETE SET OF BID DOCUMENTS.
E PRELIM SET: 10-16-2013
B. CIRCUITING INDICATED ON PLAN IS PARTIALLY DIAGRAMMATIC FOR
"THRU-WIRING"
band op�r�tl®ns build
CLARITY. CIRCUITING SHALL BE WHERE AND WHENEVER
0 FINAL SET: 11-6-2013
POSSIBLE.
PERMIT SET: 11-20-2013
C. FIELD VERIFY EXACT LOCATION AND ELECTRICAL REQUIREMENTS OF ALL
HVAC EQUIPMENT WITH MECHANICAL CONTRACTOR PRIOR TO ORDERING
7007 DISCOVERY BLVD
ELECTRICAL EQUIPMENT.
DUBLIN, OH 43017
't
D. ALL RECEPTACLE CIRCUITS UP TO 100'-0" SHALL UTILIZE #12 CONDUCTORS
614.634.7000 T
I
10 D1 Ar GnnGnrr nP ni iAn PP:C'PPTA('.1 F ANn WIRF R0[ ITINCa WITH MILLWORK
MINIMUM. ALL RECEPTACLE CIRCUITS FROM 101'-0" TO 150'-0" IN LENGTH
SHALL UTILIZE #10 CONDUCTORS MINIMUM. CIRCUITS ABOVE 251'-0" SHALL
WDPARTNERS.CON
UTILIZE #6 CONDUCTORS MINIMUM.
I
E. PLACEMENT OF ALL RECEPTACLES IN THE "SALES" AREA SHALL BE
c�
INTENTIONAL (I.E. - CENTERED ON COLUMNS, WALL FEATURES OR TIGHT-
TO CORNERS AND AT 18" A.F.F UNLESS OTHER WISE NOTED). IF THE
I
RECEPTACLE IS NOT SHOWN IN A DESIRABLE LOCATION, FIELD VERIFY
EXACT PLACEMENT OF RECEPTACLE WITH TENANT'S PROJECT MANAGERiii
g 111 111glig 11 g! all ggw�g
PRIOR TO ROUGH -IN.
F. ELECTRICAL CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS AS
REQUIRED FOR A FULLY COMPLETE AND OPERABLE SYSTEM.
G. WHERE DRYWALL CEILINGS ARE USED IN THE "SALES" AREA, THE
SEMINOLE T.C.
ELECTRICAL CONTRACTOR SHALL ARRANGE CIRCUITS TO AVOID THE USE
OF JUNCTION BOXES IN INACCESSIBLE LOCATIONS. THE USE OF JUNCTION
200 TOWNS CENTER CIRCLE
BOXES ABOVE LAY -IN CEILINGS ARE ACCEPTABLE.
SPACE #1311C
H. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO INQUIRE WITH THE
LANDLORD'S REPRESENTATIVE ON ANY FIRE ALARM SYSTEMS IN USE AT
SANFORD, FL 32771
THE MALL AT THE TIME OF THE BID. IF THE FIRE ALARM SYSTEM IS NOT
ADEQUATELY DESCRIBED ON THE DRAWINGS, THE ELECTRICAL
CONTRACTOR IS RESPONSIBLE TO INFORM THE GENERAL CONTRACTOR
AND INCLUDE THE COST AS A SEPARATE LINE ITEM IN THE BID. NO
ADDITIONAL MONEY SHALL BE AWARDED FOR TIE-IN REQUIREMENTS TO A
LANDLORD'S FIRE ALARM SYSTEM THAT IS IN EXISTENCE AT THE TIME OF
THE BID, WITHOUT A SEPARATE LINE ITEM FOR THE FIRE ALARM SYSTEM
AT THE TIME OF THE BID.
I. INSTALL ENGRAVED BAKELITE NAMEPLATE ON SERVICE DISCONNECT"
SWITCH IN LANDLORD'S SWITCH GEAR WITH DEMISED PREMISES' SPACE
NUMBER.
IA
J. NO HANGERS, SUPPORTS, JUNCTION BOXES, ETC. SHALL BE ATTACHED TO
ROOF DECK..
K. COORDINATE ALL ROOF PENETRATIONS WITH THE LANDLORD. WRITTEN
PERMISSION FROM THE LANDLORD SHALL BE RECEIVED PRIOR TO ANY
WORK BEING PERFORMED. ALL ROOF PENETRATIONS TO BE BY
LANDLORD'S CONTRACTOR AT TENANT'S ELECTRICAL CONTRACTOR'S
EXPENSE.
L. ELECTRICAL CONTRACTOR IS TO CUT FLOOR (CORE DRILL ON ELEVATED
FLOORS) AS REQUIRED TO INSTALL CONDUITS TO CASHWRAP UNITS AND
PATCH FLOOR TO MATCH EXISTING. COORDINATE ALL WORK WITH
LANDLORD PRIOR TO STARTING WORK.
$>
M. ELECTRICAL CONTRACTOR IS TO FURNISH AND INSTALL TYPE WRITTEN
PANEL DIRECTORIES IN ALL PANEL BOARDS.
N. ALL RECEPTACLES TO BE MOUNTED VERTICALLY, NOT HORIZONTALLY.
O. RECEPTACLE COVER PLATES SHALL BE WHITE EXCEPT AT WAINSCOT,
WHERE THEY SHALL BE IVORY
P. "G.C. IS TO REVIEW STRUCTURE BELOW OUR SPACE PRIOR TO
CONSTRUCTION FOR CONDITIONS PREVENTING FLOOR PENETRATIONS AS
SHOWN. OBSTRUCTIONS THAT PREVENT LAYOUT AS SHOWN SHALL BE
BROUGHT TO THE ATTENTION OF THE ARCHITECT IMMEDIATELY AND
PRIOR TO FRAMING."
KEYED .
OCROSSCOM TO RUN TWO (2) CAT5E WIRES BETWEEN POINTS "A" & "B",
1
BETWEEN POINTS "B" AND "C", AND BETWEEN POINTS "C" AND "A'.
COORDINATE ALL ROUTING PRIOR TO ROUGH -IN.
2 PROVIDE RECEPTACLE AT BACK CASH WRAP FOR STEREO EQUIPMENT,
DRAWN BY:
VERY EXACT LOCATION WITH OWNER. G.C. TO INSTALL STEREO AND RUN
SPEAKER WIRE, G.C. TO RUN WIRE BEHIND FURNITURE, SPEAKERS WD PROJECT NUMBER
INSTALLED ON FOP OF FURNITURE TO RIGHT AND LEFI OF BACK
CASHWRAP. SPEAKERS TO MUTE WHEN FIRE ALARM IS ACTIVATED. G.C. TO FRCC00050
VERIFY ALL REQUIREMENTS WITH LANDLORD AND TO COORDINATE WITH
FIRE ALARM CONTRACTOR AS REQUIRED.
DUPLEX RECEPTACLE WITH COVER PLATE MOUNTED IN SOFFIT ABOVE
WINDOW. CONTROL RECEPTACLE WITH TIME CLOCK AND SWITCHES AT
MANAGER'S DESK. RECEPTACLE AND COVER PLATE TO MATCH �����As{aaaaaae�®d
SURROUNDING WALL COLOR. .,��' 4.H�`�� o9d
cam.
4 NEW PANEL "A" 208Y/1 20V, 3PH, 4W WITH A 100A MAIN CIRCUIT BREAKER. �.,\\ G E N �� "•.,'y ����
REFER TO SHEET E-3 FOR MORE DETAIL.
_ No 6 '.
AN
5 NEW TIME CLOCK FOR LIGHTING AND RECEPTACLES. REFER TO SHEETE2
0 =_
FOR MODEL NUMBER. COORDINATE EXACT LOCATION PRIOR TO BID.
O2' X 4' X 3/4" TELECOMM. BOARD WITH DEDICATED QUADRAPLEX r'",~ %STATE OF r
RECEPTACLE AND CIRCUIT WITH ISOLATED GROUND. VERIFY SYSTEM
L AL TELEPHONE "o" OB �•••���"
GROUNDING AND ALL OTHER REQUIREMENTS WITH OC
r "•
d��i,�S/U•• ir� %
COMPANY. EXTEND 1" TELEPHONE CONDUIT WITH PULL WIRE FROM
SERVICE ENTRANCE AT DEMISING WALL TO TELECOMM. BOARD. VERIFY
PSB
u
EXACT LOCATION IN FIELD. SEE SHEET E3 FOR FRANCESCA'S NOTES AND
DETAILS.
RECEPTACLE, DATA AND TELEPHONE OUTLET MOUNTED IN CASHWRAP
MILL WORK. COORDINATE EXACT PLACEMENT" OF DEVICE AND WIRE
ISSUE GATES
40
ROUTING IN CASHWRAP WITH MILLWORK DRAWINGS.
E PRELIM SET: 10-16-2013
(1) 1" CONDUIT FOR POWER AND (1) 1" CONDUITS FOR TELEPHONE/DATA
8
UNDERFLOOR FROM CASHWRAP TO NEARBY WALL OR COLUMN, UP TO
0 FINAL SET: 11-6-2013
ABOVE CEILING AND TO ELECTRICAL PANEL OR TELEPHONE BOARD AS
PERMIT SET: 11-20-2013
LABELED. STUB CONDUITS UP 16" ABOVE FINISHED FLOOR AT CASHWRAP.
SEE E3 FOR FRANCESCA'S NOTES AND DETAILS.
ELECTRIC WATER HEATER. CIRCUIT AS SHOWN.
PROVIDE WHIP AT 8'-6" AFF FOR FURNITURE. COORDINATE EXACT
10 D1 Ar GnnGnrr nP ni iAn PP:C'PPTA('.1 F ANn WIRF R0[ ITINCa WITH MILLWORK
RF���S�C1NS
NEC ELECTRICAL LOAD SUMMARY
SIZE: 100 AMP MCB
ELECTRICAL LOAD
OPTIONS: NONE NEMA: 1
CONNECTED
NEC DEMAND
USE
NEC REFERENCE
LIGHTING ZONE -L1 VA/FT2
0.00
730
913
NEUTRAL: 100% TVSS: NO
220.12,42
LIGHTING ZONE -1_2 VA/FT2
0.00
_
0
0
w
220.12,42
LIGHTING ZONE13 VA/FT2
0.00
0
0
KW PER PHASE
220.12,42
TRACK - TL (FT)
96
952
6,840
Oc
220.43(6)
SIGNS - S (EA)
1
1,000
1,250
220.14(F)
SHOW WINDOW - SW (FT)
DESCRIPTION
0
0
220.14(G),43(A)
RATINGLU
DF = DIVERSITY FACTOR
RECEPTACLES - R
3,780
3,780
100%
220.14(H,I & K),44
KITCHEN RESISTIVE - KR
2,100
2,100
100%
220.56
KITCHEN MOTORS - KM
0
0
100%
220.56
COOLING MOTORS - C
�0
0
100%
220,40,50,60
HEATING - H
0
0
100%
100%
220.40,50,51,60
OTHER MOTORS - OM
MAX MOTOR HP 0
0
N/A
0
0
220.40,50
220.40,50
WATER HEATERS - WH
4,160
4,160
100%
220.40
OTHER - 0
100
100
100%
220.40
RECEPT. MGR'S DESK
R
3.0
1
TOTAL KW
12.8
19.1
POWER FACTOR: 99%
1
LIGHTING AREA - Al
TL
FT2 LIGHTING - L1
0.00
W/FT2
LIGHTING AREA - A2
FT2 LIGHTING - L2
0.00
WlFT2
LIGHTING AREA - A3
FT2 LIGHTING - L3
0.00
W/FT2 -
LIGHTING AREA
0
FT2 TOTAL LIGHTS:
0.00
W/FT2
COOLING AREA
0
FT2 COOLING - C
0.00
W/ T2
HEATING AREA
0
FT2 HEATING - H
0.00
W/FT2
MICROWAVE
CONNECTED:
0.00
W/FT2 NEC DEMAND:
0.00
W/FT2
SYSTEM VOLTAGE:
480
VOLTS
PHASES:
3
TL
CONNECTED:
15.6
AMPS j NEC DEMAND:
23.3
LAMPS
MOTOR CONTRIBUTION:
0.0
KW CONFIGURATION: 3 PHASE 4 WIRE
PANELBOARD: A
SIZE: 100 AMP MCB
FEEDER: # 3 W/#8 G IN 11/4" C CU SETS: 1
OPTIONS: NONE NEMA: 1
SERVICE ENTRANCE: NO
LENGTH: 50 FT CONDUIT TYPE: ST
TYPE: LIGHTING & APPLIANCE VOLTAGE DROP: 0.39%
FOR FAILURE TO COMPLY.
PARTNERS
B.
MOUNTING: SURFACE
VOLTAGE: 208Y/120V CONFIG: 3 PHASE 4 WIRE
NEUTRAL: 100% TVSS: NO
LOCATION: ELECTRIC ROOM
FED FROM: DP DIRECTION: TOP
BRANCH MOUNT: BOLT -ON BUS MATERIAL: CU
CIRCUIT
OC
w
Q,
Lu
a
w
�
EQUIPMENT PROVIDED BY OTHERS (INCLUDING HVAC EQUIPMENT) PRIOR TO ROUGH -IN AND
KW PER PHASE
KW PER PHASE
PROVIDE ALL REQUIRED FUSIBLE SWITCHES, TRANSFORMERS, STARTERS NECESSARY FOR
w
w
cn
cn
Oc
CIRCU IT
NO.
RATING
o
LIN, OH
DUBOH43Q17
o
DESCRIPTION
DESCRIPTION
o
;I c�j
0
RATINGLU
N0.
FIXTURES USED. PROVIDE SLOPE CEILING ADAPTERS WHERE REQUIRED.
f o
I
H.
_
ADDITIONAL EXIT SIGNS AND EMERGENCY LIGHTING MAY BE REQUIRED. ADDITIONAL
-A
FIXTURES SHALL BE LOCATED AS DIRECTED BY THE LOCAL BUILDING AUTHORITY.
A
B
C
A
g
C
1
20
1
2.1
L1
LTG - SALES
_
0.25
0.36
_
RECEPT. MGR'S DESK
R
3.0
1
20
2
3
20
1
3.8
TL
LTG - SALES TRACK
0.43
0.60
-_
REFRIGERATOR
KR`
5.0
1
20
4
5
20
1
1.9
L1
_
LTG DECORATIVE
0.21
_
f___
1.50
MICROWAVE
KR
12.5
1
20
6
7
-
20
1
4.5
TL
LTG SALES TRACK
_
0.52
-_
0,36
RECEPT. - PHONE BOARD
R
3.0
1
20
8
9
20
1
4.5
.0
WATER FOUNTAIN
/
0.54
!<�
0.54
''= '�
RECEPT. - BOH
R
4.5
1
20
10
11
20 ..
1
1.5
R
RECEPT. - BACKWRAP.
_
0.18
__
0.72
RECEPT. - SALES
R
6.0
1
20
12
13
20
1
8.8
S
STOREFRONT SIGN
1.00
,._
0.18
''
RECEPT. - CASHWRAP
R
1.5
1
20
14
15
20
1
2.0
L1
LTG - BOH
0.22
0.18
RECEPT. • CASHWRAP
R
1.5
1
20
16
_
17
20
1
4.5
R
RECEPT. - STOREFRONT
_
'_-
0.54
f--
0.72-
RECEPT. - FURNITURE
R
6.0
1
20
18
19
20
_
1
.4
l
L1
LTG - FITTING ROOM
0.05
�'
2.08
WATER HEATER
WH
20.0
2
30
20
21
SPARE _
''
2.08
_
WATER HEATER
WH
20.0
2
30
22
23
_
SPARE
-_
_ _
_
^ -
0.10
VAV-1
0
0.8
1
20
24
25
SPARE
�'
�'
��/�
SPARE
26
27
SPARE4KW-C;.__
SPARE
28
29SPARE
-`SPARE
30
GROUND: SOLID
DIVERSITY: 105% 4.8 KW -A 4.6 KW -B 4.0
SCCR: 42 kAIC
BALANCE: 89% CONNECTED: 13.4 KW 37.5 AMPS
SPEC. SECTION 262416
PF: 99% DEMAND: 14.1 KW 39.4 AMPS
I i rF-, n-nCr%i uvv, U-UUULINU, NNIM 1 UNLAN KtJIJ I IV t, r M -KI I UHLN MU I UK, WH -WA I EK HLA ILK, OM -OTHER MOTOR, L1,L2 OR 1 -3 -LIGHTING, TL -TRACK LIGHTING, S -SIGNS, SW -SHOW WINDOW,
R -RECEPTACLES, SF -SUB FEED, 0 -OTHER, E-EXISITNG SIZE: MLO -MAIN LUG ONLY, MOB -MAIN CIRCUIT BREAKER NOTE: GF -GROUND FAULT, AF -ARC FAULT, E -EXISTING
TC -VIA TIME CLOCK, ST -SHUNT TRIP, LC -LUCK ON, PC -PHOTO CELL CONTROLLED OPTIONS: SFL-SUB FEED LUGS, FTL-FEED THRU LUGS
(2) #1
A-24
""-'"' LEDER (3) #6 &
GND IN 1 "C BY E.C.
U15C;(JININLU 15W1 I (AFI
WITH 60A FUSES.
ONE -LINE DIAGRAM
EZ3�°wa
S� CALL: N.T.S. - -
NEW 60A, 3 -POLE
DISCONNECT SWITCH
WITH 60A FUSES.
I
I
- LANDLORD'S EXISTING
480Y/277V, 3 -PH, 4W
DISTRIBUTION PANEL
GENERAL NOTE:
A.
CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH THE EXISTING
CONDITIONS UNDER WHICH HE IS TO PERFORM HIS WORK. NO ALLOWANCE WILL BE MADE
FOR FAILURE TO COMPLY.
PARTNERS
B.
ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH THE 1993 (OR LATEST
ADOPTED) NATIONAL ELECTRICAL CODE AND ALL APPLICABLE FEDERAL, STATE AND LOCAL
CODES AND ORDINANCES.
C.
VERIFY EXACT LOCATION, MOUNTING HEIGHT AND ELECTRICAL REQUIREMENTS OF ALL
brand : operations: build
EQUIPMENT PROVIDED BY OTHERS (INCLUDING HVAC EQUIPMENT) PRIOR TO ROUGH -IN AND
PROVIDE ALL REQUIRED FUSIBLE SWITCHES, TRANSFORMERS, STARTERS NECESSARY FOR
PROPER OPERATION OF EQUIPMENT
E.
DUPLEX RECEPTACLES MOUNTED WITHIN 6FT. OF SINK TO BE A GFI RECEPTACLE.
7007 DISCOVERY BLVD
F.
ALL WIRING SHALL BE COPPER, THHN/THWN OR XHHW INSULATED IN CONDUIT. MINIMUM
LIN, OH
DUBOH43Q17
CONDUIT SIZE TO BE 1/2". PROVIDE INSULATED COPPER BOND WIRE ON ALL CIRCUITS.
614.634. T I!� A
G.
REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION OF LIGHT FIXTURES. VERIFY
;I c�j
CEILING TYPES AND PROVIDE NECESSARY MOUNTING HARDWARE TO ACCOMMODATE LIGHT
WDPARTNER[S.COM
FIXTURES USED. PROVIDE SLOPE CEILING ADAPTERS WHERE REQUIRED.
f o
I
H.
_
ADDITIONAL EXIT SIGNS AND EMERGENCY LIGHTING MAY BE REQUIRED. ADDITIONAL
-A
FIXTURES SHALL BE LOCATED AS DIRECTED BY THE LOCAL BUILDING AUTHORITY.
LANDLORD REQUIREMENTS:
• PRIOR TO BID, TENANT IS REQUIRED TO VERIFY THAT THE LANDLORD'S
EXISTING AVAILABLE ELECTRICAL SERVICE MEETS THE TENANTS TOTAL
CONNECTED LOAD.
• TGC TO SURVEY ALL EXISTING ELECTRICAL EQUIPMENT AND VERIFY
ANY ADDITIONAL LANDLORD WORK TO BE COMPLETED. VERIFY WITH
MALL OPERATIONS.
• COORDINATE ALL NEW ROUTING OF CONDUIT, FEEDER CABLES, AND
CONNECTIONS TO LANDLORD'S MAIN ELECTRICAL GEAR WITH MALL
OPERATIONS..
+ ANY AND ALL UPGRADES TO EXISTING EQUIPMENT SHALL BE AT TGC AT
TENANTS EXPENSE.