INTERIOR ALTERATION PLANS FOR:
CJO, INC.
AT
GATEWAY PLAZA
SPACE N0. A-2 AND A-3
SANFORD, FLORIDA
VICINITY MAP
LAKE000rMONROE
46
,--SITE LOCATION
GATEWAY PLAZA
NORTH
INDEX OF DRAWINGS
CS COVER SHEET /GEN. NOTES
EXISTING SITE PLAN
A-1 OVERALL FLOOR PLAN —PHASE 2 & 3
A-2 SUITE FLOOR PLAN —PHASE 3
A-3 ENLARGED FLOOR PLAN —PHASE 3
A-4 OVERALL REFLECTED CEILING PLAN —
PHASE 2 & 3
A-5 WALL SECTIONS /FIRE RATING
DETAILS & MISC. DETAILS
A-6 AIR CONDITIONING PIAN
A-7 ELECTRICAL FLOOR PLAN
PROJECT DATA
AREA OF IMPROVEMENT:
PUBLIC TOILET FIXTURE COUNT:
WATER CLOSETS
URINAL
LAVATORIES
BUILDING CODE
MECHANICAL CODE
PLUMBING CODE
ELECTRICAL CODE
UFE SAFETY CODE
FIRE CODE
FLORIDA ACCESSIBILITY CODE
ENERGY EFFICIENCY CODE
CONSTRUCTION TYPE:
AUTOMATIC FIRE SPRINKLERS
OCCUPANCY TYPE:
PREVIOUS USE:
5,573 SQ. FT.
MEN
WOMEN
EXIST,
NEW
TOTAL
EXIST.
NEW
TOTAL
1
0
1
1
1
2
0
0
0
0
0
0
1
0
1
1
1
2
2001 FLORIDA
BUILDING CODE
2001 FLORIDA
MECHANICAL CODE
2001 FLORIDA
PLUMBING CODE
1999 NEC
---
2000 NFPA 101
2001 FLORIDA
FIRE PREVENTION CODE
2001 FLORIDA
BUILDING CODE (CHAPTER 11)
2001 FLORIDA
BUILDING CODE (CHAPTER 13
IV UNPROTECTED
YES
---
GROUP B
- BUSINESS
RETAIL
ARCHITECTURAL SYMBOLS
DETAIL
SECTION
INTERIOR
ELEVATION
COLUMN
NUMBER
DOOR
NUMBER
ELEVATION
(7#1� DETAIL LETTER OR NUMBER
00 SHEET WHERE DETAIL IS DROWN
SECTION LETTER OR NUMBER
DIRECTION OF SECTION CUT
SHEET WHERE SECTION IS DRAWN
ELEVATION LETTER OR NUMBER
N#N SHEET WHERE ELEVATION IS DR4WP
QCOLUMN CENTER LINE
i
O
HEIGHT ABOVE FINISHED FLOOR (A.F.F.
LEGAL DESCRIPTION
By:
Sanford Fire
Date: Z-)
tioi DiY*
INTERIOR FINISH FIRE CHARACTERISTICS
FLAME SPREAD
RATINGS
CLASS
FLAME
SPREAD
FUEL
CONTRIBUTION
SMOKE
DENSITY
PLASTIC LAMINATES
---
165
---
135
EPDXY PAINT FINISH
A / 1
10
0
0
ACOUSTICAL TILE
---
25
---
50
Z
PROJECT GENERAL NOTES
THE CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND DIMENSIONS PRIOR
TO ANY WORK AND SHALL BE RESPONSIBLE FOR ALL WORK AND MATERIALS
INCLUDING THAT FURNISHED BY SUBCONTRACTORS.
2. DIMENSIONS TAKE PRECEDENCE OVER DRAWINGS; DO NOT SCALE DRAWINGS TO
DETERMINE ANY LOCATION. THE OWNER SHALL BE NOTIFIED IF ANY DISCREPANCY
OCCURS PRIOR TO CONTINUING WITH WORK.
3. DISCREPANCIES BETWEEN PORTIONS OF THE CONTRACT DOCUMENTS ARE
NOT INTENDED. THE CONTRACTOR IS TO CLARIFY WITH THE ARCHITECT AND
OWNER ANY SUCH DISCREPANCIES PRIOR TO COMMENCING WORK.
4. THE CONTRACTOR SHALL REPORT TO THE ARCHITECT ANY ERRORS,
INCONSISTENCIES, OR OMISSIONS HE MAY DISCOVER. THE
CONTRACTOR IS RESPONSIBLE FOR CORRECTING ANY ERRORS AFTER THE
START OF CONSTRUCTION WHICH HAVE NOT BEEN BROUGHT TO THE
ATTENTION OF THE ARCHITECT. THE MEANS OF CORRECTING ANY ERROR
SHALL FIRST BE APPROVED BY THE ARCHITECT AND OWNER,
5. ALL PLAN DIMENSIONS ARE FROM FACE OF STUD OR FACE OF FINISH OR
FACE OF CMU UNLESS OTHERWISE NOTED.
6. ALL WORK AND MATERIALS SHALL CONFORM TO THE REQUIREMENTS OF ALL
FEDERAL, STATE, LOCAL AND OSHA CODES AND LOCAL RESTRICTIONS,
7. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO LOCATE
ALL EXISTING MECHANICAL AND ELECTRICAL SERVICES AND DISTRIBUTION
SYSTEMS WHETHER SHOWN OR NOT, AND TO PROTECT THEM FROM
DAMAGE, THE CONTRACTOR SHALL BEAR ALL EXPENSE OR REPAIR OR
REPLACEMENT OF UTILITIES OR OTHER PROPERTY DAMAGED BY
OPERATIONS IN CONJUNCTION WITH THE PERFORMANCE OF THE WORK.
8. FIRE EXTINGUISHERS - SIZE,TYPE,NUMBER AND LOCATION IS TO BE
COORDINATED WITH THE BUILDING AND FIRE DEPARTMENTS.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPLACEMENT OR
REMEDY OF ANY FAULTY, IMPROPER OR INTERIOR MATERIALS OR
WORKMANSHIP WHICH SHALL APPEAR WITHIN ONE (1) YEAR OR AS
OTHERWISE SPECIFIED FOR A SPECIFIC COMPONENT AFTER THE COMPLETION
AND ACCEPTANCE OF THE WORK UNDER THIS CONTRACT.
10. THE CONTRACTOR SHALL PROVIDE BACKING/BLOCKING AS REQUIRED FOR
MOUNTING OF WALL MOUNTED SHELVES AND CABINETS, ALL WOOD BLOCKING,
PLYWOOD SHEATHING, SUB -FLOORING AND WOOD FRAMING CONCEALED
WITHIN WALL, FLOOR OR CEILING SPACES SHALL BE PRESSURE TREATED
WHEN INSTALLED AGAINST CONCRETE BLOCK.
11, SILICONE CAULK SHALL BE USED AT THE FOLLOWING LOCATIONS
INCLUDING, BUT NOT LIMITED TO:
1. METAL DOOR AND WALL CONNECTION
2. CONDUIT AND PIPE PENETRATIONS AT WALLS AND CEILING.
3. JUNCTION OF MILLWORK (CABINETS, SHELVES, ETC.),
12, CONTRACTOR IS TO CLEAN WORK AREAS ON A DAILY BASIS SO AS NOT TO
ACCUMULATE DEBRIS.
13. UPON PROJECT COMPLETION CONTRACTOR IS TO CLEAN WORK AREAS AND
JOB SITE THOROUGHLY SO AS TO REMOVE ALL ONSTRUCTION DUST,
RESIDUE, AND DEBRIS.
1 14. DO NOT OBSTRUCT STREETS, SIDEWALKS, ALLEYS OR OTHER
I RIGHT-OF-WAY WITHOUT FIRST OBTAINING PROPER PERMITS.
15. ALL WORK SHALL BE ACCOMPLISHED WITH QUALITY WORKMANSHIP OF THE
HIGHEST INDUSTRY STANDARDS. ALL MATERIALS SHALL BE INSTALLED IN
STRICT ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS AND
RECOMMENDATIONS. MATERIALS AND METHODS SHALL CONFORM TO THE
APPROPRIATE NATIONAL TRADE BOOK; I.E. TILE COUNCIL OF AMLRICA
HANDBOOK FOR CERAMIC TILE INSTALLATION, ARCHITECTURAL WOODWORK
I INSTITUTE, "QUALITY STANDARDS," ETC.
16, THE OWNER MAY PERFORM ADDITIONAL WORK THAT IS NOT PART OF THIS
CONTACT WITH HIS OWN FORCES, UNDER SEPARATE CONTRACTS
AND/OR WITH OTHER CONTRACTORS. THE CONTRACTOR SHALL COOPERATE
WITH THE OWNER AND OTHER CONTRACTORS AND COORDINATE HIS WORK
WITH THE OWNER SO THAT THE WORK BY OTHERS CAN BE
INCORPORATED IN A TIMELY MANNER.
17, THE CONTRACTOR SHALL BE RESPONSIBLE FOR JOB SAFETY, AND SHALL
TAKE ALL NECESSARY PRECAUTIONS TO ENSURE SAFETY OF WORKS AND
OCCUPANTS AT ALL TIMES.
18. ALL ELECTRICAL, MECHANICAL, AND PLUMBING WORK SHALL
CONFORM TO STATE AND LOCAL REQUIREMENTS,
19. REMODEL WORK SHALL NOT OBSTRUCT, OR CAUSE TO BE INOPERATIVE, EXISTING
FIRE ALARM SYSTEMS. MODIFICATION TO FIRE ALARM SYSTEMS SHALL BE
PERFORMED BY A FIRE ALARM CONTRACTOR, WHO SHALL OBTAIN A PERMIT FROM
THE BUILDING DEPT. PRIOR TO WORK.
20. THE CONTRACTOR SHALL MAINTAIN, IN GOOD CONDITION, ONE COMPLETE SET OF
CONSTRUCTION DOCUMENTS WITH ALL REVISIONS, ADDENDUMS AND CHANGE
ORDERS ON THE PREMISES AT ALL TIMES. THE DOCUMENTS ARE TO BE KEPT
UNDER THE CARE OF THE JOB SUPERINTENDENT.
I21. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL MINOR ITEMS WHICH ARE
OBVIOUSLY AND REASONABLE NECESSARY TO COMPLETE ANY INSTALLATION.
22. IT SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO ISOLATE
ALL WORK AREAS IN SUCH A WAY AS TO PROTECT THE ADJACENT BUILDING
SPACES AND STRUCTURE.
23. MINIMUM FLAME SPREAD CLASSIFICATION OF INTERIOR FINISH SHALL
CONFORM TO THE BUILDING CODE AND LOCAL GOVERNING BUILDING
CODES/ORDINANCES.
24. ACCEPT PREMISES AS FOUND. OWNER ASSUMES NO RESPONSIBILITY FOR THE
CONDITION OF THE EXISTING BUILDING SITE OR EXISTING STRUCTURES AT THE TIME
OF BIDDING OR THERE AFTER,
25. GYPSUM WALLBOARD AND SUSPENDED CEILING SYSTEMS SHALL CONFORM TO
REQUIREMENTS OF LOCAL BUILDING CODES AND ORDINANCES,
26. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO SECURE ALL
NECESSARY PERMITS AND APPLICATIONS,
27. ALL NEW DRYWALL AND ABUTTING SURFACES ARE TO BE FINISHED TO A
SMOOTH PAINTABLE SURFACE.
28. ALL EXISTING INTERIOR WALLS ARE TO BE PATCHED AND POINTED UP AS
REQUIRED TO PROVIDE A SMOOTH UNIFORM PAINTABLE SURFACE.
29. GYPSUM WALL BOARD SHALL BE INSTALLED WITH ALL CORNER BEADS, TRIM,
ACCESSORIES, MOULDINGS, ETC., AS REQUIRED FOR COMPLETION, TAPED AND
SANDED READY FOR PAINT BY DRYWALL CONTRACTOR, ALL WORK WILL BE
PERFORMED IN ACCORDANCE WITH U.S. GYPSUM STANDARDS.
30. UPON COMPLETION OF WORK THE GENERAL CONTRACTOR SHALL CLEAN ALL
WINDOWS (INTERIOR AND EXTERIOR), JAMBS, CLEAN, SEAL AND WAX ALL VINYL TILE
FLOORS, ALL TOILET ROOMS, SALES FLOOR CAREFULLY REMOVING THOROUGHLY ALL
I TAPE, LABELS, AND OTHER CONSTRUCTION DIRT AND DEBRIS.
RECEIVED
APR 0 o
3
F�;
V)
Z
0
0
�j
CLI
a
z
0
0
� A
W E-+
1--1 O
F+i w o0
O g L0 o
z
EU)00
�V woODoCD
H o :5
N Q
w
x
CONTRACTOR SHALL VERIFY
ALL CONDITIONS AND
DIMENSIONS AT THE JOB SITE
AND NOTIFY THE ARCHITECT
OF ANY DIMENSIONAL ERRORS,
OMISSIONS OR DISCREPANCIES
BEFORE BEGINING OR
FABRICATING ANY WORK.
DO NOT SCALE DRAWINGS.
O
Li
Ln
Z •
N
O p 0
za o
a
a "�
� �` a o
LTJ W
J O Q a can
a
I' wxi-w-jo
QIF- T-�ZW
Ozqp ti.tn..1tYU
_ �ww'
WO00}Zlt <zw
oz 'Q: Z
Lj `a Un a r`cwt1-"(
Ltl N H w U U W
O af_va'00L' u a
ZC9 O u1 W Z
pf�Lmh �QWGW jW
A",,pwZ1,i-O'w�eT
i; J J.aw .L Wa W I_
U w¢O,nu)T?IWTL.
W wF`t�W gr-
r.It.�fJl
O W s Q
CL p wc`ew0WUW00
WwmL saa
z
It rl (L
J
Qf''�q(AUFR'>
i n s i
r L ,�
W1 L O
wU(jCZG)
H rZt _ WO
E i
JRJJ
DATE
03/28/03
SCALE
AS NOTED
PROJECT NO.
C32479
FILE NAME
2479CSU
ti SHEET
d
s
W
r
r -
CAO),9
TOYS
R US
SERVICE
MERCHANDISE
KEY PLA
z N.T.S.
AM \
FLOOR PLAN LEGEND:
F777= EXIST, WALL TO REMAIN.
�l
IRETAIL
stiF� �'q NEW PHASE 3 WALL. SEE WALL
q, SECTIONS,
q, NEW PHASE 2 WALL, SEE WALL
i
Al
\\\
RETAIL A FUTURE
--o
i
A2
A3
i
A4
i
A4.8
OVERALL FLOOR PLAN - RETAIL 'A'
SCALE: 1/8" , l' -O"
0
.3
0
43
0
0
L
0
A
W E-4
o �
O
�u1
00
W
® ® g M O
Q V1 Z
-J C) cI
_ ►n ao
F -131 LL. . .
v)Lu �, o
p xx
`'p a
N
L W0
Q
a _
c w
0
0
c
�L
O
O
a�
a.
C
7
7
V
D
nc=)
o
...... ,ice z
-)
U
CONTRACTOR /SHALL VERIFY
ALL CONDITIONS :AND
DIMENSIONS AT THE JOB SITE
AND NOTIFY THE ARCHITECT
OF ANY DIMENSIONAL ERRORS,
OMISSIONS OR DISCREPANCIES
BEFORE BEGINING OR
FABRICATING ANY WORK.
DO NOT SCALE DRAWINGS.
o ..
o
Q
o
0
v
V
N
� N
N
o CL t�
a cao
o l
O
ami Q 3►N�
n a
o LLJ p
o (n
n
JQ can
a
N
t Q
Q cy-
o
V
O W
Q
CL
� U
a
C
0
0
r
M
V)
z
0
0
Q
0
0
Z
.3
0
M
0
0
N
z
t
0
U
DRAWN
BJ, PH
CHECKED
JRJJ
DATE
03/28/03
SCALE
AS NOTED
PROJECT NO.
C32479
FILE NAME
2479AIU
SHEET
lam. —
P
ROOM FINISH SCHEDULE
ROOM FLOOR BASE WALLS CEILING HEIGHT
ENTRY CARPET 4" VINYL PAINT ALL WALLS EXIST. ACOUST./GRID 10'-0"
SHOWROOM CARPET 4" VINYL PAINT ALL WALLS EXIST. ACOUST./GRID 10'-0"
SHOP CARPET 4" VINYL PAINT ALL WALLS EXIST. ACOUST./GRID 10'-0"
OFFICE #3 CARPET 4" VINYL . PAINT ALL WALLS EXIST. ACOUST./GRID 10'-0"
OFFICE #4 CARPET 4" VINYL PAINT ALL WALLS EXIST. ACOUST./GRID 10'-0"
HALL #2 CARPET 4" VINYL PAINT ALL WALLS EXIST. ACOUST./GRID 10'-0"
NEW RESTROOM VINYL 4" VINYL PAINT ALL WALLS EXIST. ACOUST./GRID 10'-0"
BREAK ROOM VINYL 4" VINYL PAINT ALL WALLS EXIST, ACOUST./GRID 10'-0"
OFFICE #2 CARPET 4" VINYL PAINT ALL WALLS NEW ACOUST,/GRID 10'-0"
HALL #1 VINYL 4" VINYL PAINT ALL WALLS EXIST. ACOUST./GRID 10'-0"
OFFICE # 1 CARPET 4" VINYL PAINT ALL WALLS NEW ACOUIST./GRID 10'-0"
ELEC. ROOM VINYL 4" VINYL PAINT ALL WALLS NEW ACOUIST./GRID 10'-0"
EXIST, MEN EXIST. EXIST, PAINT ALL WALLS EXIST. ACOUST./GRID 10'-0"
EXIST. WOMEN EXIST. EXIST. PAINT ALL WALLS EXIST. ACOUST./GRID 10'-0"
EXIST. VEST, EXIST. EXIST. PAINT ALL WALLS EXIST. ACOUST./GRID 10'-0"
DOOR SCHEDULE
# SIZE THK. MATERIAL FRAME TYPE REMARKS HARDWARE
1. PR. 3'-0"x7'-0" 1-3/4" WD/GLASS METAL FRENCH STEEL REINF.
2, 3'-0" X 7'-0" 1-3/4" WD/GLASS METAL FRENCH STEEL REINF,
3. 3'-0" X 6'-8" 1-3/4" WD/GLASS WOOD FRENCH INTERIOR DOOR 1
4. 3'-0" X 6'-8" 1-3/4" WD/GLASS WOOD FRENCH INTERIOR DOOR 2
5. 3'-0" X 6'-8" 1-3/4" WOOD METAL FLUSH SOLID CORE
6. 3'-0" X 6'-8" 1-3/4" WOOD METAL FLUSH SOLID CORE
7. 2'-0" X 6'-8" 1-3/4" WOOD METAL FLUSH SOLID CORE
E1. 3'-0" x 7'-0" 1-3/4" EXIST, METAL EXIST. FLUSH EXIST, EXTERIOR EXIST.
^ E2. 3'-0" x 6'-8" 1-3/4" EXIST, WOOD EXIST. FLUSH EXIST, EXTERIOR EXIST,
GROUP 1
1-1/2 PR. BUTTS SELF CLOSING SPRING HINGES 4-1/2 X 4-1/2
1 LOCKSET SCHLAGE 2-3/4" BSXASA
1 WALL MOUNTED DOOR STOP IVEY
GROUP 2
1-1/2 PR. BUTTS SELF CLOSING SPRING HINGES 4-1/2 X 4-1/2
1 PASSAGE SET SCHLAGE 2-3/4" BSXASA
1 WALL MOUNTED DOOR STOP IVEY
WALL MOUNTED
TRANSPARENCY
BY OTHERS
DISPLAY CASES
BY OTHERS —r
0
LF .,
\ s�o:j" qfs�
�, �, y ;
1
� e
r A Y e
ID
P
N
Ln
U o ® EXISTIf�C�
QRINRNG '`
' i' L
FO NTAI�I ' h -
2
A-5 A-5
I U
El-
6,-� 5-+ 91-011 E_
0
E2
' i' il) E
(FE2
m
V)
z
0
V)
a
0
Uz-
DOOR SCHEDULE
# SIZE THK. MATERIAL FRAME TYPE REMARKS HARDWARE
1. PR. 3'-0"x7'-0" 1-3/4" WD/GLASS METAL FRENCH STEEL REINF.
2, 3'-0" X 7'-0" 1-3/4" WD/GLASS METAL FRENCH STEEL REINF,
3. 3'-0" X 6'-8" 1-3/4" WD/GLASS WOOD FRENCH INTERIOR DOOR 1
4. 3'-0" X 6'-8" 1-3/4" WD/GLASS WOOD FRENCH INTERIOR DOOR 2
5. 3'-0" X 6'-8" 1-3/4" WOOD METAL FLUSH SOLID CORE
6. 3'-0" X 6'-8" 1-3/4" WOOD METAL FLUSH SOLID CORE
7. 2'-0" X 6'-8" 1-3/4" WOOD METAL FLUSH SOLID CORE
E1. 3'-0" x 7'-0" 1-3/4" EXIST, METAL EXIST. FLUSH EXIST, EXTERIOR EXIST.
^ E2. 3'-0" x 6'-8" 1-3/4" EXIST, WOOD EXIST. FLUSH EXIST, EXTERIOR EXIST,
GROUP 1
1-1/2 PR. BUTTS SELF CLOSING SPRING HINGES 4-1/2 X 4-1/2
1 LOCKSET SCHLAGE 2-3/4" BSXASA
1 WALL MOUNTED DOOR STOP IVEY
GROUP 2
1-1/2 PR. BUTTS SELF CLOSING SPRING HINGES 4-1/2 X 4-1/2
1 PASSAGE SET SCHLAGE 2-3/4" BSXASA
1 WALL MOUNTED DOOR STOP IVEY
WALL MOUNTED
TRANSPARENCY
BY OTHERS
DISPLAY CASES
BY OTHERS —r
0
LF .,
\ s�o:j" qfs�
�, �, y ;
1
� e
r A Y e
ID
P
N
Ln
U o ® EXISTIf�C�
QRINRNG '`
' i' L
FO NTAI�I ' h -
2
A-5 A-5
I U
El-
6,-� 5-+ 91-011 E_
0
E2
' i' il) E
(FE2
m
V)
z
0
V)
a
0
Uz-
WALL MOUNTED
TRANSPARENCY
BY OTHERS
DISPLAY CASES
BY OTHERS —r
0
LF .,
\ s�o:j" qfs�
�, �, y ;
1
� e
r A Y e
ID
P
N
Ln
U o ® EXISTIf�C�
QRINRNG '`
' i' L
FO NTAI�I ' h -
2
A-5 A-5
I U
El-
6,-� 5-+ 91-011 E_
0
E2
' i' il) E
(FE2
m
V)
z
0
V)
a
0
Uz-
oo
(
Ln
-0 5 3,, .4. E-.+
M-�-1
:0 �� E+
Ln 2
-5 O,' I w
\I o
0 Z r\ o
�, I g M M
5 5 Z Q�_ I n
1'� _ � U 00
A-5 A-5 p' r 3 o 0
5 fL � ZD CD
V)
O3 i/1 0
3 3 N Q
O �
`b 11 A-5 0
WALL MOUNTED ~
TRANSPARENCY �• a
BY OTHERS ��• �'
5 2
A-5
�A-5
r. 3 5 n I c
A-5
0
WALL MOUNTED ��'• A-5 �, o
TRANSPARENCY
BY OTHERS PGj
V l
C)
P
D N
�\� .2
FliL
CONTRACTOR�SHALL VERIFY
9'-0" 3'-0" ALL CONDITIONS, --AND
6 o DIMENSIONS AT THE JOB SITE
I AND NOTIFY THE ARCHITECT
EXISTING '' 1 OF ANY DIMENSIONAL ERRORS,
STEEL W s OMISSIONS OR DISCREPANCIES
U Q BEFORE BEGINING OR
COLUMN EXISTING — D FABRICATING ANY WORK,
GQ� STEEL 0 00 NOT SCALE DRAWINGS.
COLUMN �W x
C3 � WALL MOUNTED
LAS TRANSPARENCY '
BY OTHERS Q
O 0 0
SHOW CASES
(BY OTHERS)
oy��, O tic DISPLAY CASES
�p'L�� ��ppo \ BY OTHERS V N
4
A-5
{
Q 6
Q
N
o
�b I oCLM
a. ¢I ¢o
� Z
o�
's- > 0
a o
N
O \ O
4 `� W w z
o ® va
A-5 WALL MOUNTED
TRANSPARENCY v •7
SHOW CASES SHOW CASES BY OTHERS Q
(BY OTHERS) (BY OTHERS)
� o O
4 a LLJ
A-5 Z
TRANSPARENCY DISPLAY TRANSPARENCY DISPLAY �s
`o BY OTHERS BY OTHERS
4 Q
L
CL
\ \ \ \ _ _ _ _._._.—._a.---------- _ _ _ _ _ _ ----- _A wl- _ _ _ _ _ _ _ _ _ ----------------- -----------
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ .........
EXISTING STOREFRONT �{ REMOVE EXISTING DOOR
TRANSOM AND SIDE LIGHT.
FILL IN WITH NEW
11 -7------ ; ;------ STOREFRONT FRAMING AND
GLAZING TO MATCH EXISTING o
STOREFRONT.
0
0
N
Q
0
U
FLOOR PLAN
SCALE: 3/16" = 1'-0"
DRAWN
BJ, PH
CHECKED
JRJJ
DATE
03/28/03
SCALE
AS NOTED
PROJECT NO.
C32479
FILE NAME
2479A2U
SHEET
A-2
NEW 3"
V.T.R. -
EXIST, 4"
WASTE
NEW 2" \ I
VENT -� \
I I
I
I
--f -- NEW LAV.
NEW 4"
WASTE --NEW 2"
EXIST. 4 VENT
WASTE
,A.- NEW W.C.
NEW LAV. — NEW 2" -NEW WALL
WASTE CLEANOUT
� SANITARY RISER DIAGRAM
SCALE; N.T.S.
NEW GRAB BARS PROVIDE
BLOCKING AS REQUIRED
FOR SUPPORT
3'-6" 1
d-
r�
NEW SURFACE MOUNTED- L NEW WATER
TOILET TISSUE HOLDER CLOSET
RESTROOM
B SCALE 112 " = 1'-0"
NEW GRAB BARS PROVIDE MIRROR
BLOCKING AS REQUIRED
---FOR SUPPORT
NEW SURFACE
MOUNTED
TOILET TISSUE
HOLDER
x
CO
rn I
1'-6" NEW WATER
CLEAR CLOSET
RESTROOM
A SCALE 1/2" = 1'-0"
NEW SINK
WRAP DRAIN
PIPE WITH
INSULATION
-p
43
0
C�m_
Z
v
L
NV
T
�
C
O
d.
Q
7
`
�
V)
0
N
V)
C-
M
Z
I
dao
Z
o�
>-:z
I_'
Q N
O
Q
I o
I..1..1
o
W
N
J
0Q
Q a (n
V
V
I-
Q
O
o
V
O
Q
W
O
z
-: i
H_
N V 1
N L
C
O
L
V
C
O J
V
7 /Mq
O u
O O o Z N In M
o g M S O
°�' �✓
O
Q V 1 0 IQ u,
r -
Ln 00
3 v` N Iw- c:) 0
W
r�N C) p
VJ O z _t
V �T O x
3 V N Q Li
o F+1
Q)
0 0-4
0
r?
L l
n u
o w
V)
0
c
`L
O
O
-F�
O
E
O �
O
c
`L
rn
CONTRACTOR SHALL VERIFY
ALL CONDITIONS -AND
DIMENSIONS AT THE JOB SITE
AND NOTIFY THE ARCHITECT
OF ANY DIMENSIONAL ERRORS,
OMISSIONS OR DISCREPANCIES
BEFORE BEGINING OR
FABRICATING ANY WORK.
DO NOT SCALE DRAWINGS.
U)
z
V
Z
v
L
NV
T
�
C
O
d.
Q
7
`
�
V)
0
N
o
C-
M
Z
I
dao
o�
>-:z
I_'
Q N
Q
I o
I..1..1
o
W
S
J
0Q
Q a (n
V
V
I-
Q
O
o
V
O
W
ENLARGED FLOOR PLAN
DRAWN
BJ, PH
CHECKED
JRJJ
DATE
03/28/03
SCALE
AS NOTED
PROJECT NO.
C32479
FILE NAME
2479A3U
w
SHEET
h
41.54 '{ .vp
tEF i f i
Z
v
o
D
T
�
C
O
d.
CL
0
a
ENLARGED FLOOR PLAN
DRAWN
BJ, PH
CHECKED
JRJJ
DATE
03/28/03
SCALE
AS NOTED
PROJECT NO.
C32479
FILE NAME
2479A3U
w
SHEET
h
41.54 '{ .vp
tEF i f i
LEGEND:
EXISTING SUSPENDED
= ACOUSTICAL CEILING
SYSTEM
i s
D
NEW SUSPENDED
ACOUSTICAL CEILING
SYSTEM, MATCH
EXISTING,
NEW (N), EXISTING (E) OR RELOCATED (R),
2'x4', 4 TUBE RECESSED FLUORESCENT LIGHT
FIXTURE WITH PARABOLIC LENS, NEW FIXTURES
TO MATCH EXISTING,
NEW (N), EXISTING (E) OR RELOCATED (R),
2'x4', 4 TUBE RECESSED FLUORESCENT LIGHT
FIXTURE WITH PRISMATIC LENS, NEW FIXTURES
TO MATCH EXISTING,
NEW (N), EXISTING (E) OR RELOCATED (R),
2'x4', 4 TUBE RECESSED FLUORESCENT LIGHT
FIXTURE WITH PARABOLIC LENS, WIRED TO
FUNCTION AS A NIGHT LIGHT, NEW FIXTURES
TO MATCH EXISTING.
NEW (N), EXISTING (E) OR RELOCATED (R),
2'x2', 4 TUBE RECESSED FLUORESCENT LIGHT
FIXTURE WITH PARABOLIC LENS, NEW FIXTURES
TO MATCH EXISTING,
REMOVE EXISTING LIGHT FIXTURE OR
RELOCATE EXISTING LIGHT FIXTURE AS SHOWN,
RECESSED MR16, 50 WATT, INCANDESCENT
LIGHT FIXTURE.
NEW RECESSED EMERGENCY LIGHT WITH
BATTERY BACK—UP,
NEW, EXISTING OR RELOCATED CEILING
MOUNTED EXHAUST FAN,
SUPPLY AIR DIFFUSER, SEE SHEET A-6,
RETURN AIR GRILLE, SEE SHEET A-6,
MANUrAU I UKtK JUJrtwutU D«vn LniJuw
CEILING 0 8'-0" A.F.F. TO BOTTOM OF SOFFIT,
TYPICAL.
J........................... .
........ ........... ....... ... ...... .... .
.... .............. .....
REFLECTED CEILING PLAN
J
_T
>-
11
m
V)
z
0
a
0
0
z
W E4
E 4
- Q'
F--1 O
�w
O O Z M Lo O
T� U �oo I uj
V 1 Z = E uo 00
Lu O c)
�No r
T� o g:
r`r/,, N Q
�
CPQ
N
c�
CONTRACTOR, SHALL -VERIFY
ALL CONDITIONS AND
DIMENSIONS AT THE JOB SITE
AND NOTIFY THE ARCHITECT
OF ANY DIMENSIONAL ERRORS,
OMISSIONS OR DISCREPANCIES
BEFORE BEGINING OR
FABRICATING ANY WORK.
DO NOT SCALE DRAWINGS.
cyO
u -
t)
Z •
N
c M
dao
i
O Q 3
Q QNB
�'�
a�
cy—
w z
can
N
C Q
u O
N
n
W
C
� Z
U
T O
U �
1
7
2
DRAWN
BJ, PH
CHECKED
JRJJ
DATE
03/28/03
SCALE
AS NOTED
PROJECT N0,
C32479
FILE NAME
2479A4U
SHEET
A-4
I
t,
SYSTEM NO. WL1006
(FORMERLY SYSTEM NO. 187)
F RATING - 2 HR
TRATING -0HR
�g
SECTION g—g 1'
1. WALL ASSEMBLY -THE FIRE -RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CIONSTRUCTED OF
THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL AND
PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING
CONSTRUCTON FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS.
WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED 16 IN. O.C. STEEL STUDS
TO BE MIN 2-1/2 IN. WIDE AND SPACED MAX 24 IN. O.C.
B. WALLBOARD, GYPSUM* - TWO LAYERS OF NOM 5/8 IN. THICK GYPSUM WALLBOARD, AS
SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION DESIGN, MAX. DIAM OF OPENING IS 2 IN.
2. THROUGH PENETRANTS - ONE METLIC PIPE, CONDUIT OR TUBING TO BE CENTERED WITHIN THE FIRESTOP 2.
SYSTEM. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY, THE
FOLLOWING TYPES AND SIZES OF METALLIC PIPE, CONDUIT OR TUBING MAY BE USED;
A. STEEL PIPE - NOM 1 IN. DIAM (OR SMALLER) SCHEDULE 5 (OR HEAVIER) STEEL PIPE. A NOM
ANNULAR SPACE OF 5/16 IN. IS REQUIRED WITHIN THE FIRESTOP SYSTEM.
B. CONDUIT - NOM 1 IN. DIAM (OR SMALLER) ELECTRICAL METALLIC TUBING OR RIGID STEEL
CONDUIT. A NOM ANNULAR SPACE OF 5/16 IN. IS REQUIRED WITHIN THE FIRESTOP SYSTEM.
C. COPPER TUBING - NOM 1 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
A NOM ANNULAR SPACE OF 5/16 IN. IS REQUIRED WITHIN THE FIRESTOP SYSTEM.
D. COPPER PIPE - NOM 1 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
A NOM ANNULAR SPACE OF 5/16 IN. IS REQUIRED WITHIN THE FIRESTOP SYSTEM.
3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. FILL, VOID OR CAVITY MATERIAL* - PUTTY - MIN 1-1/2 IN. THICKNESS OF FILL MATERIAL
APPLIED WITHIN THE ANNULS, ON BOTH SURFACES OF WALL. ADDITIONAL FILL MATERIAL TO
BE INSTALLED SUCH THAT A MIN 1/8 IN. CROWN IS FORMED AROUND THE PENETRATING ITEM,
HEVI-DUTY/NELSON UNIT OF GENERAL SIGNAL CORP, - TYPE FSP PUTTY
*BEARING THE UL CLASSIFICATION MARKING
D�IPEPENETRATION DETAIL
T TO SCALE
DESIGN N0. U465
NONBEARING WALL RATING -1 HR.
2 3 4 5
2 4
1. FLOOR AND CEILING RUNNERS - (NOT SHOWN) CHANNEL SHAPED RUNNERS, 3-5/8 IN. WIDE (MIN),
1-1/4 IN. LEGS, FORMED FROM N0, 25 MSG (MIN. NO. 20 MSG WHEN ITEM 4C IS USED) GLAV STEEL,
ATTACHED TO FLOOR AND CEILING WITH FASTENERS SPACED 24 IN. OC MAX. 3,
2, STEEL STUDS - CHANNEL SHAPED, 3-5/8 IN. WIDE (MIN), 1-1/4 IN. LEGS 3/8 IN, FOLDED BACK
RETURNS, FORMED FROM NO. 25 MSG (MIN NO. 20 MSG WHEN ITEM 4C IS USED) GALV STEEL
SPACED 24 IN, OC MAX.
3. BATTS AND BLANKETS*- (OPTIONAL) - MINERAL WOOL OR GLASS FIBER BATTS PARTIALLY OR
COMPLETELY FILLING STUD CAVITY.
SEE BATTS AND BLANKETS (BZJZ) CATEGORY FOR NAMES OF CLASSIFIED COMPANIES.
3A. FIBER SPRAYED* - AS AN ALTERNATE TO BATTS AND BLANKETS (ITEM #3) SPRAY APPLIED CELLULOSE
INSULATION MATERIAL. THE FIBER IS APPLIED WITH WATER TO COMPLETELY FILL THE ENCLOSED CAVITY
IN ACCORDANCE WITH THE APPLICATION INSTRUCTIONS SUPPLIED WITH THE PRODUCT. NOMINAL DRY
DENSITY OF 3.0 LB/CU.FT.
U S GREENFIBER L L C- COCOON STABILIZED CELLULOSE INSULATION.
*
SYSTEM NO. W—L-2088
F RATINGS - 1 AND 2 HR (SEE ITEM 1)
T RATINGS - 0, 1 AND 2 HR (SEE ITEM 2)
SECTION A—A
WALL ASSEMBLY - THE 1 OR 2 HR FIRE RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE
CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400
SERIES WALL AND PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE
FOLLOWING CONSTRUCTON FEATURES:
A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS.
WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED 16 IN. O.C. STEEL STUDS
TO BE MIN 3-1/2 IN, WIDE AND SPACED MAX 24 IN. O.C.
B. WALLBOARD, GYPSUM* - THICKNESS, TYPE, NUMBER OF LAYERS AND FASTENERS AS REQUIRED IN THE
INDIVIDUAL WALL AND PARTITION DESIGN, DIAM OF OPENING SHALL BE 7/8 IN, LARGER THAN THE
OUTSIDE DIAM OF NONMETALLIC PIPE OR CONDUIT (ITEN 2)
THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE
WALL ASSEMBLY IN WHICH IT IS INSTALLED.
THROUGH PENETRANTS - ONE NONMETALLIC PIPE OR CONDUIT TO BE INSTALLED EITHER CONCENTRICALLY
OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE FOR NOM 1-1/4 IN, DIAM AND
SMALLER BETWEEN THE PIPE OR CONDUIT AND PERIPHERY OF OPENING SHALL BE MIN 0 IN. (POINT CONTACT)
TO MAX 7/8 IN. THE ANNULAR SPACE FOR PIPE OR CONDUIT GREATER THAN NOM 1-1/4 IN. DIAM BETWEEN
THE PIPE OR CONDUIT AND PERIPHERY OF OPENING SHALL BE MIN 1/2 IN. TO MAX. 1 IN. PIPE OR CONDUIT
TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.
THE FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES OR CONDUITS MAY BE USED:
A. POLYVINYL CHLORIDE (PVC) PIPE - NOM 2 IN. DIAM (OR SMALLER) SCHEDULE 40 SOLID CORE OR
CELLULAR CORE PVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE
OR VENT) PIPING SYSTEM.
B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE - NOM 2 IN. DIAM (OR SMALLER) SDR17 CPVC
PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT)
PIPING SYSTEMS.
C. POLYVINYL CHLORIDE (PVC) PIPE - NOM 3 IN. DIAMOR SMALLER) SCHEDULE 40 SOLID CORE
PVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY PIPING SYSTEM.
D. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE - NOM 3 IN. DIAM (OR SMALLER) SDR17 CPVC
PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS.
E. RIGID NONMETALLIC CONDUIT++ - NOM 3 IN. DIAM (OR SMALLER) SCHEDULE 40 PVC CONDUIT
INSTALLED IN ACCORDANCE WITH ARTICLE 347 OF THE NATIONAL ELECTRICAL CODE (NFPA NO. 70).
F. ELECTRICAL NONMETALLIC TUBING (ENT)++ - NOM 1 IN. DIAM (OR SMALLER) ENT FORMED OF PVC,
INSTALLED IN ACCORDANCE WITH ARTICLE 331 OF THE NATIONAL ELECTRICAL CODE (NFPA NO. 70).
SEE RIGID NONMETALLIC CONDUIT (DZKT) AND ELECTRICAL NONMETALLIC TUBING (FKHU) IN UL
CONSTRUCTION MATERIALS DIRECTORY OR NAMES OF MANUFACTURERS.
G. ACRYLONITRILE BUTADIENE STYRENE (ABS) PIPE - NOM 2 IN. DIAM (OR SMALLER) SCHEDULE 40
SOLID CORE OR CELLULAR CORE ABS PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED
(DRAIN, WASTE OR VENT) PIPING SYSTEMS.
THE HOURLY T RATING IS DEPENDENT ON THE HOURLY RATING OF THE WALL ASSEMBLY, THE PIIPE
OR CONDUIT SIZE AND WHETHER THE PIPE IS INTENDED FOR USE AS A CLOSED OR VENTED
SYSTEM, AS SHOWN IN THE FOLLOWING TABLE:
NOM PIPE WALL ASSEMBLY CLOSED (C) OR T RATING
DIAM IN. RATING HR VENTED (V) HR
1/2 TO 3 1 C 1
1/2 TO 1-1/4 1 V 1
1/2 TO 1-1/4 2 C 2
1/2 TO 1-1/4 2 V 1
2 1 V 0
2 2 V 0
FILL, VOID OR CAVITY MATERIALS* - CAULK OR PUTTY - MIN THICKNESS OF 5/8 IN, AND 1-1/4 INI.
OF CAULK OR PUTTY FOR 1 OR 2 HR RATED WALL ASSEMBLIES, RESPECTIBLY, APPLIED WITHIN ANNULUS
BETWEEN PIPE OR CONDUIT AND PERIPHERY OF THE OPENING, FLUSH WITH BOTH SURFACES OF WALL
ASSEMBLY. AT THE POINT CONTACT LOCATION BETWEEN PIPE OR CONDUIT AND GYPSUM WALLBOARD, A MIN
1/2 IN, DIAM BEAD OF CAULK OR PUTTY SHALL BE APPIED AT THE PIPE OR CONDUIT/WALLBOARD
INTERFACE ON BOTH SURFACES OF WALL ASSEMBLY.
MINESOTA MINING & MFG CO - CP 25WB+, MPS -2+
++BEARING THE UL LISTING MARK.
*BEARING THE UL CLASSIFICATION MARKING
PIPE PENETRATION _D1TAIL
8 NOT TO SCALE
4. WALLBOARD, GYPSUM -5/8 IN. THICK, 4 FT. WIDE, ATTACHED TO STEEL STUDS AND FLOOR AND
CEILING TRACK WITH 1 IN. LONG, TYPE S SELF -TAPPING STEEL SCREWS SPACED 8 IN. OC. ALONG 3-5/8" METAL STUDS
EDGES OF BOARD AND 12 IN. OC. IN THE FIELD OF THE BOARD. JOINTS ORIENTED VERTICALLY AND @ 48" O.C. BRACE
STAGGERED ON OPPOSITE SIDES OF THE ASSEMBLY. WHEN ATTACHED TO ITEM 6 (FURRING CHANNELS), WALL TO BAR JOIST
WALLBOARD IS SCREW ATTACHED TO FURRING CHANNELS WITH 1 IN. LONG, TYPE S STEEL SCREWS
SPACED 12 IN. OC.
BORAL GYPSUM INC. -TYPE BG -C. EXISTING SUSPENDED
CANADIAN GYPSUM COMPANY - TYPES AR, C, IP -X2, SCX, SHX, WRC OR WRX. ACOUSTICAL CEILING
CONTINENTAL GYPSUM COMPANY - TYPE CG -C. SYSTEM
EAGLE -GYPSUM PRODUCTS - TYPE EG -C.
G -P GYPSUM CORP. - TYPES 5, 9, C, GPFS6, GPFS-C.
NATIONAL GYPSUM CO., CHARLOTTE, NC - TYPES FSK -G, FSW-G.
NATIONAL GYPSUM CO., RIYADH, SAUDIA ARABIA - TYPE FR OR WR. R-19 BATT INSULATION
PABCO GYPSUM CO. - TYPE PG -C.
REPUBLIC GYPSUM CO. - TYPE RG -C,
STANDARD GYPSUM CORP. - TYPE SG -C.
TEMPLE-INLAND FORREST PRODUCTS CORP. - TYPE TP -5.
UNITED STATES GYPSUM CO. - TYPE AR, C, IP -X2, SCX, SHX, WRC OR WRX
YESO PANAMERICANO SA de CV - TYPE AR, C, IP -X2, SCX, SHX, WRC OR WRX,
WESTROC INDUSTRIES LTD. - TYPE WESTROC FIREBOARD.
4A. WALLBOARD, GYPSUM* - (AS AN ALTERNATE TO ITEM 4) - NOM 3/4 IN. THICK, 4 FT WIDE,
INSTALLED AS DESCRIBED IN ITEM 4 WITH SCREW LENGTH INCREASED TO 1-1/4 IN.
CANADIAN GYPSUM COMPANY - TYPE AR. i
UNITED STATES GYPSUM CO. - TYPE AR. STORE FRONT FRAMING
YESO PANAMERICANO SA de CV - TYPE AR. AND GLAZING - KAWNEER
4B. WALLBOARD GYPSUM - (AS AN ALTERNATE TO ITEMS 4 AND 4A) - 5/8 IN. THICK INSTALED TRI -FAB 450 OR EQUAL
AS DESCRIBED IN ITEM 4, JOINT COVERING (ITEM 5) NOT REQUIRED.WITH CLEAR FINISH
CANADIAN GYPSUM COMPANY - TYPE WSX. o
UNITED STATES GYPSUM CO. - TYPE WSX.
YESO PANAMERICANO SA de CV - TYPE WSX, o
5. JOINT TAPE AND COMPOUND - VINYL, DRY OR PREMIXED JOINT COMPOUND, APPLIED IN TWO COATS 1/2' GYP. BD. BOTH
TO JOINTS AND SCREW HEADS; PAPER TAPE, 2 IN. WIDE, EMBEDDED IN FIRST LAYER OF COMPOUND SIDES OF 3 5/8" (25
OVER ALL JOINTS, AS AN ALTERNATE, NOMINAL 3/32 IN. THICK GYPSUM VENEER PLASTER MAY BIE GA.) METAL STUDS ® 24"
APPLIED TO THE ENTIRE SURFACE OF CLASSIFIED VENEER BASEBOARD. JOINTS REINFORCED, O.C. BRACE STUDS AS
6, FURRING CHANNEL - (OPTIONAL -NOT SHOWN) - RESILIENT 25 MSG GALV. STEEL FURRING CHANNELS i REQUIRED BY CODE
SPACED VERTICALLY MAX 24 IN. OC, FLANGE PORTION ATTACHED TO EACH INTERSECTING STUD WITH EW CARPET ON
1/2 IN. LONG TYPE S-12 PANHEAD STEEL SCREWS.
*BEARING THE UL CLASSIFICATION MARKING. SLAKING CONCRETE
TENANT f,.SEPERATION iWALL
6 DETAIL; k. ksPHASE}t y*2 5 WALL SECTION—PH. 3
NOT TO SCALE SCALE 1 /2
EXISTING SUSPENDED
ACOUSTICAL CEILING
SYSTEM,
SYSTEM
NO.
WL1001
N
(FORMERLY
SYSTEM NO. 147)
VARIES QZ
F RATINGS -1,2,3 AND
4 HR
(SEE ITEMS 2
AND 3)
T RATINGS -0,1,2,3
AND
4 HR (SEE ITEM 3)
L RATING AT AMBIENT -LESS
THAN
1 CFM/SQ. FT.
(SEE ITEM 3)
L RATING AT 400 F -LESS
THAN
1 CFM/SQ. FT.
(SEE ITEM3)
SYSTEM NO. WL1017
(FORMERLY
F RATING - 1,2 SYSTEM )
HR(SEES TEM3)
TRATING -0HR
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
I 4 v
0
Z
3 1C o
V)
2
1B
A - A
SECTION A—A
SECTION A—A
1. WALL ASSEMBLY -THE 1,2,3 OR 4 HOUR FIRE -RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE
CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SE- 1. WALL ASSEMBLY -THE 1 OR 2 HR FIRE RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CON -
RIES WALL OR PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLL- STRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR U400 SERIES z
OWING CONSTRUCTION FEATURES; WALL OR PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING
A. STUDS -WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 H FIRE RATED ASSEMBLIES) OR' CONSTRUCTON FEATURES; o
STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED 16 IN. O.C. A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS.
WITH NOM 2 BY 4 IN. LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN, 3-5/8 IN. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED 16 IN. O.C. WITH NOMST
Q
WIDE BY 1-3/8 IN. DEEP CHANNELS SPACED MAX 24 IN. O.C. 2 BY 4 IN. LUMBER END PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN, 3-5/8 IN.WIDE
B. WALLBOARD, GYPSUM* -NOM 1/2 OR 5/8 IN. THICK, 4 FT. WIDE WITH SQUARE OR TAPERED EDGES, BY 1-3/8 IN. DEEP CHANNELS SPACED MAX. 24 IN. O.C. W E-+
THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTA- B. WALLBOARD, GYPSUM* - NOM 5/8 IN. THICK, 4 FT, WIDE WITH SQUARE OR TAPERED EDGES. THE o E�
ATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RES- GYPSUM WALLBOARD TYPE, NUMBER OF LAYERS, AND SHEET ORIENTATION SHALL BE AS SPECIFIED �+
ISTANCE DIRECTORY, MAX DIAM OF OPENING IS 13-1/2 IN. IN THE INDIVIDUA-L WALL OR PARTITION DESIGN. DIAM OF CIRCULAR CUT THROUGH GYPSUM WALL- o F Io
2. PIPE OR CONDUIT -NOM 12 IN. DIAM (OR SMALLER) SCHEDULE 10 OR HEAVIER) STEEL PIPE, NOM 6 IN. BOARD ON EACH SIDE OF WALL ASSEMBLY TO BE MIN, 0 IN. (POINT CONTACT) TO MAX 1 IN. Q
DIAM (OR SMALLER) STEEL CONDUIT, NOM 4 IN. DIAM (OR SMALLER STEEL ELECTRICAL METALLIC TUBING OR LARGER THAN OUTSIDE DIAM OF FLEXIBLE METAL CONDUIT (ITEM 2) INSTALLED IN THROUGH OPEN-
TYPE L OR (OR HEAVIER) COPPER TUBING OR NOM 1 IN. DIAM (OR SMALLER) FLEXIBLE STEEL CONDUIT. ING. SIDE EDGE OF CIRCULAR OPENING TO BE MIN. 3 IN. FROM NEAREST STUD IN WALL CAVITY.Z N ® rCe))
WHEN COPPER PIPE OR FLEXIBLE STEEL CONDUIT IS USED, MAX F RATING OF FIRESTOP SYSTEM (ITEM3) _ 0
IS 2 H. STEEL PIPE OR CONDUITS LARGER THAN NOM 4 IN. DIAM MAY ONLY BE USED IN WALLS CONSTR- C. FASTENERS WHEN WOOD STUD FRAMING IS EMPLOYED, GYPSUM WALLBOARD ATTACHED TO STUDS Q U)o
J ao o
WITH CEMENT COATED NAILS AS SPECIFIED IN THE INDIVISUAL WALL OR PARTITION DESIGN. WHEN Z
UCTED USING STEEL CHANNEL STUDS. A MAX OF ONE PIPE OR CONDUIT IS PERMITTED IN THE FIRESTOP U� �-+= w o Lo °O
STEEL CHANNEL STUD FRAMING IS EMPLOYED, GYPSUM WALLBOARD ATTCHED TO STUDS WITH TYPE S
SYSTEM. PIPE OR CONDUIT TO BE INSTALLED NEAR CENTER OF STUD CAVITY WIDTH AND TO BE RIGIDLY SUP- n � °O
PORTED ON BOTH SIDES OF WALL ASSEMBLY. SELF -DRILLING, SELF -TAPPING BULGE -HEAD STEEL SCREWS AS SPECIFIED IN THE INDIVISUAL WALL Qlj 3 N o
3. FILL, VOID OR CAVITY MATERIAL* - CAULK -CAULK FILL MATERIAL INSTALLED TO COMPLETELY FILL ANNULAR OR PARTITION DESIGN. P -SMALLER)L o z - .1
SPACE BETWEEN PIPE OR CONDUIT AND GYPSUM WALLBOARD AND WITH A MIN 1/4 IN, DIAM. BEAD OF CAULK 2. THROUGH PENETRANTING PRODUCT* - FLEXIBLE METAL CONDUIT NOM 4 IN. DIAM (OR 3 � N
APPLIED TO PERIMETER OF PIPE OF CONDUIT AT ITS EGRESS FROM THE WALL. CAULK INSTALLED SYMETRICA- ALUMINUM OR STEEL FLEXIBLE METAL CONDUIT+. MAX ONE FLEXIBLE METAL CONDUIT TO BE INSTALLED
LLY ON BOTH SIDES OF WALL ASSEMBLY. THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT NEAR CENTER OF CIRCULAR OPENING IN GYPSUM WALLBOARD. FLEXIBLE METAL CONDUIT TO BE RIGIDLY W
UPON THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED. AS SHOWN IN THE SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY, o H
FOLLOWING TABLE. THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OR SIZE AFC CABLE SYSTEMS INC. Q la -z x
OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, 3. FILL, VOID OR CAVITY MATERIAL* - CAULK - CAULK FILL MATERIAL FORCED INTO ANNULAR SPACE AROUND ry u
AS TABULATED BELOW: ENTIRE CIRCUMFERENCE OF THROUGH PENETRATING PRODUCT TO COMPLETELY FILL OPENING IN GYPSUM
MAX PIP ANNULAR F T WALLBOARD LAYERS ON EACH SIDE OF THE WALL ASSSEMBLY, A MIN 5/8 IN. THICKNESS OF CAULK IS
OR CONDUIT SPACE, RATING RATING REQUIRED FOR THE 1 HR. F RATING, A MIN. 1-1/4 IN THICKNESS OF CAULK IS REQUIRED FOR 2 F o
DIAM, IN. IN. HR. HR. RATING,
1 0 TO 3/16 1 OR 2 0+, 1 OR 2 MINNESOTA MINING & MFG CO - CP 25WB+
1 1/4 TO 1/2 3 OR 4 3 OR 4 *BEARING THE UL CLASSIFICATION MARKING
4 0 TO 1/4 1 OR 2 0
6 1/4 TO 1/2 3 OR 4 0 PIPE PENETRATION DETAILcn
12 3/16 TO 3/8 1 OR 2 0 1 O NOT TO SCALE E
+WHEN COPPER PIPE IS USED, T RATING IS 0 H. -' o
MINNESOTA MINING & MFG. CO.- TYPES CP -25 S/L, CP -25 N/S, CP -25 WB, CP -25
WB+. (NOTE; L RATINGS APPLY ONLY WHEN TYPE CP -25 WB+ CAULK IS USED.) EXIST. 5/8" TYPE "X" CUT IN BOX - 2G �_ hj
*BEARING THE UL CLASSIFICATION MARKING GYP. BD. ® BOTH ® 24" A.F.F.
SIDES OF STUDS
CONDUIT PENETRATION DETAIL y `�
AVT_TO SCALE
U
EXIST, 6" L 4" SQ. BOX CONTRACTOR SHALL VERIFY
META'_ STUDS ® 18" A.F,F. ALL CONDITIONS --ANDY
DIMENSIONS AT THE JOB SITE
AND NOTIFY THE ARCHITECT
OF ANY DIMENSIONAL ERRORS,
WRAP BOTH BOXES INSIDE THE EXIST. FIRE WALL ( 1 HR, RATED) W/ OMISSIONS OR DISCREPANCIES
FIRE RETARDANT PUTTY PADS COMPLETELY COVERING BOXES AND 3" OF Q BEFORE BEGINING OR
FABRICATING ANY WORK.
CONDUIT. SEE UL DESIGN (CLIV) WALL OPENING PROTECTIVE MATERIALS, o DO NOT SCALE DRAWINGS.
cnz
ELECTRICAL BOX PENETRATION DETAIL Q
11
SCALE; 1 = 1 -0 ELEC-PENETRATION o
U
LL_
EXISTING METAL BUILDING
3-5/8" METAL STUDS
® 48" O.C. BRACE
WALL TO BAR JOIST 8d Z a o
EXISTING SUSPENDED NEW R-19 BATT INSULATION FULL O
HEIGHT AT WAREHOUSE ONLY.
ACOUSTICAL CEILING NEW R-19 BATT NEW R-19 BATT � p__Q N
SYSTEM INSULATION INSULATION NEW R-19 CEILING BATT, Q i d
INSULATION '` W a o
0
, rnr000000000 F00000000 00000000100000010000 00000000000 o LLJ
® �--- w z
C � N
fn Q
EXIST. 2' X 4' SUSPENDED
ACOUSTICAL TILE LAY -IN SYSTEM iE <
a � Q
-19 BATF ,,, EXIST. OR NEW 2' X 4' w O
INSULATION EXIST. 2' X 4' SUSPENDED � J
ACOUSTICAL TILE LAY -IN SUSPENDED ACOUSTICAL TILELij
SYSTEM
o LAY -IN SYSTEM z 5/8" TYPE "X" GYP. BD. z a
Z
W w BOTH SIDES OF EXISTING w Z
FULL BATT INSULATION IN FULL BATT INSULATION IN 6" METAL STUDS ® 24"
RESTROOM PARTITIONS ONLY o RESTROOM PARTITIONS ONLY o O.C. - 1 HR. TENANT o o
FOR SOUND CONTROL o FOR SOUND CONTROL o SEPARATION WALL. PROVIDE o o
C) BRACING AND BLOCKING
C) m AS REQUIRED BY CODE. m
1/2" GYP. BD. BOTH SIDES o 1 /2" GYP. BD. BOTH SIDES OF o 0
STORE FRONT FRAMING OF 6 METAL STUDS 0 24
AND GLAZING - KAWNEER " '� 0 3 5/8" METAL STUDS 0 24" o
OOF STRUCTURE HEIGHT E
N
O.C. BRACING AND BLOCKING
VARIES QZ
•
Q
SEAL WALL TO ROOF DECK WITH o
N
FIRE RATED CAULK (PROVIDE FIRE
RATED BACKING AS REQUIRED) Q
a-
a
WALL TO BAR JOIST 8d Z a o
EXISTING SUSPENDED NEW R-19 BATT INSULATION FULL O
HEIGHT AT WAREHOUSE ONLY.
ACOUSTICAL CEILING NEW R-19 BATT NEW R-19 BATT � p__Q N
SYSTEM INSULATION INSULATION NEW R-19 CEILING BATT, Q i d
INSULATION '` W a o
0
, rnr000000000 F00000000 00000000100000010000 00000000000 o LLJ
® �--- w z
C � N
fn Q
EXIST. 2' X 4' SUSPENDED
ACOUSTICAL TILE LAY -IN SYSTEM iE <
a � Q
-19 BATF ,,, EXIST. OR NEW 2' X 4' w O
INSULATION EXIST. 2' X 4' SUSPENDED � J
ACOUSTICAL TILE LAY -IN SUSPENDED ACOUSTICAL TILELij
SYSTEM
o LAY -IN SYSTEM z 5/8" TYPE "X" GYP. BD. z a
Z
W w BOTH SIDES OF EXISTING w Z
FULL BATT INSULATION IN FULL BATT INSULATION IN 6" METAL STUDS ® 24"
RESTROOM PARTITIONS ONLY o RESTROOM PARTITIONS ONLY o O.C. - 1 HR. TENANT o o
FOR SOUND CONTROL o FOR SOUND CONTROL o SEPARATION WALL. PROVIDE o o
C) BRACING AND BLOCKING
C) m AS REQUIRED BY CODE. m
1/2" GYP. BD. BOTH SIDES o 1 /2" GYP. BD. BOTH SIDES OF o 0
STORE FRONT FRAMING OF 6 METAL STUDS 0 24
AND GLAZING - KAWNEER " '� 0 3 5/8" METAL STUDS 0 24" o
WALL SECTION— PH. 3
SCALE 1/2" = 1'-0"
z
t -A 1/2" = 1-0"
r=
t
OtS
LELE 1L/2"
.PHAS_E 221
11STENANT.T,SE
SCALE 1/2" = V-0"
DRAWN
BJ, PH
CHECKED
JRJJ
DATE
03/28/03
SCALE
AS NOTED
PROJECT NO.
C32479
FILE NAME
2479A-5
SHEET
A-5
TRI -FAB 450 OR EQUAL
O.C. BRACING AND BLOCKING
O.C. BRACING AND BLOCKING
o
0
WITH CLEAR FINISH
AS REQUIRED BY CODE.
CD
AS REQUIRED BY CODE.
o
NEW R-19 BATT INSULATION -
TO 10'-0" HIGH 0 OFFICES,
a
Q)
VINYL WALL BASE -
BOTH SIDES OF WALL
o
em
EW CARPET ON EXISTING
VINYL WALL BASE
VINYL WALL BASE
XISTING CONCRETE
0
N
i
CONCRETE SLAB
EXISTING CONCRETE SLAB
EXISTING CONCRETE SLAB
SLAB
O
FINISH PER SCHEDULE
FINISH PER SCHEDULE
0
UL DESIGNk; N0. U465 - 1 HOUR RATED
WALL SECTION— PH. 3
SCALE 1/2" = 1'-0"
z
t -A 1/2" = 1-0"
r=
t
OtS
LELE 1L/2"
.PHAS_E 221
11STENANT.T,SE
SCALE 1/2" = V-0"
DRAWN
BJ, PH
CHECKED
JRJJ
DATE
03/28/03
SCALE
AS NOTED
PROJECT NO.
C32479
FILE NAME
2479A-5
SHEET
A-5
EXIST.
EXHAUST FAN
EF -1
(RESTROOMS)
100 CFM (2
CFM/S.F.)
2.5 SONES
NOTES
.25 STATIC
BACKDRAFT
DAMPER
BROAN
5C189
MECHANICAL NOTES:
1. FLEXIBLE DUCTS OF NOT MORE THAN 10 FEET IN LENGTH MAY BE USED TO
CONNECT SUPPLY, RETURN OR EXHAUST AIR TERMINAL DEVICES TO RIGID DUCT
SYSTEMS.
2. THERMAL OR ACOUSTICAL LINING MATERIALS SHALL NOT BE INSTALLED WITHIN
DUCTS, TERMINAL BOXES, SOUND TRAPS AND OTHER IN -DUCT SYSTEMS SERVING
AREAS SUCH AS OPERATING, DELIVERY AND RECOVERY ROOMS, NURSERIES,
INTENSIVE CARE UNITS AND NEGATIVE PRESSURE ISOLATION ROOMS UNLESS
TERMINAL FILTERS WITH 90 PERCENT EFFICIENCY ARE INSTALLED DOWNSTREAM
OF THE DUCT LINING,
HVAC PLAN SYMBOLS LEGEND
SYMBOL
QTY
DESCRIPTION
MOUNTING
MANUFACTURER & CATALOG
REMARKS
NOTES
24 X24 FACE SIZE W/ 12 NOMINAL NECK SIZE
AIR SUPPLY GRILLE
RECESSED
TITUS MODEL TMS
CLEAN AND PAINT ALL EXIST, DIFFUSERS TO MATCH EXIST,
1,2
CEILING TILE. ADD INSULATION BLANKETS ABOVE DIFFUSER
24X48 OR 24 X 24 FACE SIZE
AIR RETURN GRILLE
RECESSED
TITUS MODEL 50-F
CLEAN AND PAINT ALL EXIST. DIFFUSERS TO MATCH EXIST.
1,2
CEILING TILE, ADD INSULATION BLANKETS ABOVE DIFFUSER
BUILDING STANDARD
RECESSED
IMATCH EXISTING
INSTALL NEW 6" DIA. GALV. METAL DUCT TO EXISTING
1,2
EXHAUST GRILLE/FAN
ROOF PENETRATION.
O
THERMOSTAT
WALL MOUNTED
REMOVE, CLEAN AND REMOUNT OVER NEW WALL FINISH
HVAC SYMBOLS LEGEND NOTES:
1. 'N' NOTATION NEXT TO AN HVAC FIXTURE INDICATES THAT CONITRACTOR IS TO
PROVIDE A NEW HVAC FIXTURE AS SPECIFIED IN THE HVAC SYMBOLS LEGEND,
2. 'R' NOTATION NEXT TO AN HVAC FIXTURE INDICATES THAT CONTRACTOR IS TO
RELOCATE AN HVAC FIXTURE AS SHOWN ON THE REFLECTED CEILING PLAN.
3. DIFFUSERS / GRILLES WITHOUT DESIGNATIONS INDICATES EXISTIING BUILDING
STANDARD DIFFUSER / GRILLE TO REMAIN IN EXISTING POSITION.
R-6 FILE)
DUCT W01
2" METAL
STRAPPIN,
2x2 "PER.
NECK ON ROOF
3"0 GALV. METAL
DUCT TO ROOF
BATHROOM EXHAUST FAN
CFM PER SQUARE FOOT
IrW/ "ZERO" BACK DRAFT
DAMPER
NOTE: MAKE UP AIR FOR NEW RESTROOM IS
BY UNDERCUT DOOR AND THE AC
SUPPLY. MAKE-UP AIR IS TO BE
EQUIVALENT TO AIR EXHAUSTED.
3EXHAUST DETAIL
NOT TO SCALE HVACD05H,DWG
NOTE: ALL DUCT WORK TO BE SUPPORTED
TO SMACNA AND TIMA STANDARDS
BEADED WIRE
OR 2" STRAPPING
® 48" O.C.
R-6 FLEXR 2" METAL
DUCT WORK STRAPPING
48 0. C.
2FLE�(QU CTDETAIL
NOT TO SCALE HVACD04H.DWG
NOTE: ALL DUCT WORK TO
BE _SUPPORTED TO
JA AN[
ARDS
WIRE
I
NOTE: PER 2001 FLORIDA
MECHANICAL CODE, SEAL
ALL SEAMS AND
CONNECTIONS WITH 181 UL
APPROVED ALUMINUM TAPE.
DUCT WORK
} 1 NOT TO SCALE HVACD01H.DWG
F
NEW 24x48 RETURN AIR DUCT TO BE '
CONNECTED TO EXISTING RETURN AIRji
PLENUM
/i ✓ ; ,
i/ ✓i' j
" /
/ 7 f
/
1xi To
i J R
FOR
6 ✓/rr / �� r /
♦/ � of ` ,yr ,' � : � #/ ,i � f'`"
f J ° fJ'"'p J ✓' i' ✓F\ —� j}J �J/ ,
/ / i / `` i Oma' ✓ ;, f -!:%' -'' J '`
// / ✓Tk .J.. O Jf O ✓ /ice r J ♦` :: I J`i'J' J ' r:
/%// •J'` / �F//i \\iiJ/ pi/ jr r/ O. Jj' J � ,:! ,O fr •/,. `'�.' /J J ,
� „ yr /" ,. J/ / • i' < J /i
/ lam.♦ ��� '� O+tp/ r ✓ ,/ / o J Jar,, O ` f r fir f ✓�;.
NEW 2448 RETURN AIR DUCT TO BE
CONNECTED TO EXISTING RETURN AIR
PLENUM
/
J
.:::...:::.::»»...».....:....:.:...................:..........:..........................»:.:.:..:....:.....�............:..........
........... ::..... :. o \ J
a
SCALE: 3/16" = 1'-0"
DRAWN
BJ, PH
CHECKED
JRJJ
DATE
03/28/03
SCALE
AS NOTED
PROJECT NO,
C32479
FILE NAME
2479A6U
SHEET
A-6
0
L
0
� V 1
r
V w
r
C `^'
O
U
0
'O
O 'u\
cl:� rl J1
O ® o J M Q
a
d J O Q c) U)
% ^Q Ln 00
w OJ r-
N �1 w
Q" �
cn o Z
( --4 o
o �
0
Q
CL
o �
22
0
j
0
c�J
v -
o
o � i
N............. j
U �
N
N
L
,r
N
CONTRACTQR SHALL -VERIFY
ALL CONDITIONS AND
DIMENSIONS AT THE JOB SITE
AND NOTIFY THE ARCHITECT
OF ANY DIMENSIONAL ERRORS,
OMISSIONS OR DISCREPANCIES
BEFORE BEGINING OR
FABRICATING ANY WORK.
DO NOT SCALE DRAWINGS.
L
L
I
o ..
o �
Q
C)
LjU
C
N
y�
V
O
S NU
Q Z •
0
N
�V
M
Z �¢M
�Q
i"Q�
Q
N
W
L ��a
® Q ¢ cn
N Q c� V
V
E
L j
a
o �
o
V
O
F
v
o ,0
T 0
V �
Q
O
L
Q *Q
SCALE: 3/16" = V-0"
DRAWN
BJ, PH
CHECKED
JRJJ
DATE
03/28/03
SCALE
AS NOTED
PROJECT NO.
C32479
FILE NAME
2479A7U
SHEET
- 7
m
N
Z
O
_N
LLJ
a
0
d
1
Z
�
L
I
Li
0
L
0
� V 1
r
V w
r
C `^'
O
U
0
'O
O 'u\
cl:� rl J1
O ® o J M Q
a
d J O Q c) U)
% ^Q Ln 00
w OJ r-
N �1 w
Q" �
cn o Z
( --4 o
o �
0
Q
CL
o �
22
0
j
0
c�J
v -
o
o � i
N............. j
U �
N
N
L
,r
N
CONTRACTQR SHALL -VERIFY
ALL CONDITIONS AND
DIMENSIONS AT THE JOB SITE
AND NOTIFY THE ARCHITECT
OF ANY DIMENSIONAL ERRORS,
OMISSIONS OR DISCREPANCIES
BEFORE BEGINING OR
FABRICATING ANY WORK.
DO NOT SCALE DRAWINGS.
L
L
I
o ..
o �
Q
C)
LjU
C
N
y�
V
O
S NU
Q Z •
0
N
�V
M
Z �¢M
�Q
i"Q�
Q
N
W
L ��a
® Q ¢ cn
N Q c� V
V
E
L j
a
o �
o
V
O
F
v
o ,0
T 0
V �
Q
O
L
Q *Q
SCALE: 3/16" = V-0"
DRAWN
BJ, PH
CHECKED
JRJJ
DATE
03/28/03
SCALE
AS NOTED
PROJECT NO.
C32479
FILE NAME
2479A7U
SHEET
- 7
ROOM FINISH SCHEDULE
ROOM FLOOR BASE WALLS CEILING HEIGHT
ENTRY
CARPET
WOOD
PAINT ALL
WALLS
EXIST.
ACOUST./GRID
10'-0"
SHOWROOM
CARPET
WOOD
PAINT ALL
WALLS
EXIST.
ACOUST./GRID
10'-0"
SHOP
CARPET
4" VINYL
PAINT ALL
WALLS
EXIST.
ACOUST./GRID
10'-0"
OFFICE #3
CARPET
WOOD
PAINT ALL
WALLS
EXIST.
ACOUST./GRID
10'-0"
OFFICE #4
CARPET
WOOD
PAINT ALL
WALLS
EXIST.
ACOUST./GRID
10'-0"
HALL #2
CARPET
WOOD
PAINT ALL
WALLS
EXIST.
ACOUST./GRID
10'-0"
NEW RESTROOM
EXIST.
EXIST,
EXIST.
ONE (1)
EXIST.
ACOUST./GRID
10'-0"
BREAK ROOM
VINYL
4" VINYL
PAINT ALL
WALLS
EXIST.
ACOUST./GRID
10'-0"
OFFICE #2
CARPET
4" VINYL
PAINT ALL
WALLS
NEW ACOUST./GRID
10'-0"
HALL #1
VINYL
4" VINYL
PAINT ALL
WALLS
EXIST.
ACOUST./GRID
10'-0"
OFFICE #1
CARPET
4" VINYL
PAINT ALL
WALLS
NEW ACOUST./GRID
1 O'-0"
ELEC, ROOM
VINYL
4" VINYL
PAINT ALL
WALLS
NEW ACOUST./GRID
10'-0"
EXIST. MEN
EXIST.
EXIST.
PAINT ALL
WALLS
EXIST.
ACOUST./GRID
10'-0"
EXIST. WOMEN
EXIST,
EXIST.
PAINT ALL
WALLS
EXIST.
ACOUST./GRID
10'-0"
EXIST. VEST,
EXIST.
EXIST.
PAINT ALL
WALLS
EXIST.
ACOUST./GRID
10'-0"
FINISH NOTES
VINYL AND CARPET FLOORING VINYL OR CARPET FLOORING IS TO BE SELECTED BY OWNER OR TENANT,
INTERIOR FINISH REQUIREMENTS:
MINIMUM FLAMESPREAD CLASSIFICATIONS:
EXITS - CLASS B. - FLAMESPREAD 26-75, SMOKE DEVELOPED 0-450.
EXITS ACCESS - CLASS B.- FLAMESPREAD 26-75, SMOKE DEVELOPED 0-450, WALL MOUNTED
OTHER SPACES - CLASS C,- FLAMESPREAD 76-200, SMOKE DEVELOPED 0-450. TRANSPARENCY
BY OTHERS—
WALL MOUNTED
TRANSPARENCY
BY OTHERS
DOOR SCHEDULE
GENERAL CONTRACTOR
TO PROVIDE AND INSTALL ALL FLOORING.
WOOD
BASE
SEE WALL SECTIONS 4
&.5/A-5 FOR SPECIFICATION. ONE (1) COAT
m
m
PRIMER
PLUS ONE (1)
COAT PAINT (SEMI -GLOSS FINISH).
AS NOTED
PROJECT NO.
WOOD
CHAIR RAIL
SEE WALL SECTIONS, 4
& 5/A-5 FOR SPECIFICATION. ONE (1) COAT
STILE 4
PRIMER
PLUS ONE (1)
COAT PAINT (SEMI -GLOSS FINISH).
VINYL
BASE
4" BASE
SELECTED BY
OWNER OR TENANT, GENERAL CONTRACTOR TO
STILE 4 °
PROVIDE
AND INSTALL VINYL BASE.
WALL
PAINT
ONE (1)
COAT PRIMER
PLUS ONE (1) COAT PAINT (SEMI -GLOSS
g
FINISH),
TRANSPARENCY
CEILING TILE & GRID
NEW 2'
x 4' BUILDNG
STANDARD SYSTEM.
NEW
WOOD DOORS
ONE (1)
COAT SANDING SEALER PLUS ONE (1) COAT SEMI -GLOSS URETHANE.
NEW
METAL DOORS &
FRAMES ONE (1)
COAT PRIMER
PLUS ONE (1) COAT SEMI -GLOSS.
INTERIOR FINISH REQUIREMENTS:
MINIMUM FLAMESPREAD CLASSIFICATIONS:
EXITS - CLASS B. - FLAMESPREAD 26-75, SMOKE DEVELOPED 0-450.
EXITS ACCESS - CLASS B.- FLAMESPREAD 26-75, SMOKE DEVELOPED 0-450, WALL MOUNTED
OTHER SPACES - CLASS C,- FLAMESPREAD 76-200, SMOKE DEVELOPED 0-450. TRANSPARENCY
BY OTHERS—
WALL MOUNTED
TRANSPARENCY
BY OTHERS
DOOR SCHEDULE
BJ, PH
CHECKED
JRJJ
m
m
# SIZE THK. MATERIAL FRAME TYPE
REMARKS
HARDWARE
AS NOTED
PROJECT NO.
00
3'-6" x 7'-0" 1-3/4" METAL/GLASS METAL STOREFRONT
AFn
KAWNEER 500 WIDE
STILE 4
SHEET
a
: 3'-6" X 7'-0" 1-3/4" METAL/GLASS METAL STOREFRONT
KAWNEER 500 WIDE
STILE 4 °
WALL MOUNTED
g
TRANSPARENCY
V)
3. 3'-0" X 6'-8" 1-3 4' WD GLASS WOOD FRENCH
/
INTERIOR DOOR
1
BY OTHERS
z
4. 3'-0" X 6'-8" 1-3/4" WD/GLASS WOOD FRENCH
INTERIOR DOOR
2
o
5. 3'-0" X 6'-8" 1-3/4" WOOD METAL FLUSH
SOLID CORE
Q 5
N
6. 3'-0" X 6'-8" 1-3/4" WOOD METAL FLUSH
SOLID CORE
1
7. 2'-0" X 6'-8" 1-3/4 WOOD METAL FLUSH
SOLID CORE
2
ee
Q 8, 3'-6" X''''6'1-3/4' WOOD METALFLUSH
SOLID CORE
1
EXISTING
Z
V)
STEEL
E1. 3'-0" x 7'-0" 1-3/4" EXIST. METAL EXIST. FLUSH
EXIST, EXTERIOR
3
DASHED LINE
COLUMN
f
a
,> " ��
E2. 3'- 0 x 6 -8 1-3/4 EXIST. WOOD EXIST. FLUSH
EXIST. INTERIOR
EXIST.
DISPLAY CASES
BY OTHERS
,.-'
,-Y'
REPRESENTS LIMITS
Z
U
LL_
o
OF WOOD CHAIR RAIL
o
DOOR NOTES: (PROVIDE HARDWARE AS SPECIFIED OR EQUAL TO)
,-'O
V)
SEE DETAIL 12/A-5
�y
''
0
�
�
1. ALL NEW WOOD DOORS ARE TO BE STAIN GRADE BIRCH,
CL-
o
Q
2. LOCKING DEVICES ON REQUIRED EXIT WAY DOORS SHALL NOT REQUIRE
THE USE OF
0
A KEY FOR OPERATION FROM INSIDE THE BUILDING,
0
3. DOOR LOCKSETS/PASSAGE SETS ARE TO BE RUSSWIN WITH LEVER ACTION HANDLES.
KEYED TO MASTER.
o
4. CONTRACTOR IS TO ADJUST ALL DOORS TO NORMAL WORKING OPERATION WHICH INCLUDES THE
\
' - '�
DISPLAY CASES
BY OTHERS
REPAIR OR REPLACEMENT OF HARDWARE AND WEATHER STRIPPING AS REQUIRED.
\
Z
FcV
5. UNDER CUT INTERIOR DOORS 1/2,"
\ `�
GROUP #1
1-1/2 PR. BUTTS FBB 179
4-1/2 X 4-1/2
\
A-5
DASHED LINE
1 LOCKSET RUSSWIN
2-3/4" BSXASA
\
\
'�'-
REPRESENTS LIMITS
1 WALL MOUNTED DOOR STOP IVEY
\
03
OF WOOD CHAIR RAIL.
GROUP 2
\
\
1
\\
SEE DETAIL 12/A-5
1-1/2 PR. BUTTS FBB 179
4-1/2 X 4-1/2
\
\
2 \\
4
1 PASSAGE SET RUSSWIN
2-3/4" BSXASA
\ \ \
1 WALL MOUNTED DOOR STOP IVEY
\ \
A-5
GROUP
1-1/2 PR. BUTTS EXISTING '"
\ \ �. �`�
SHOW CASES
1 LOCKSET EXISTING
\ \ �`� ,%
(BY OTHERS)
3 NEW SLIDE BOLTS FULL WIDTH OF DOOR
AUTOMATIC WITH TIME
DELAY
\
\
\\
GROUP #4
\ \
4
1-1/2 PR. BUTTS FBB 199
4-1/2 X 4-1/2
\ \
=
A-5
1 PANIC DEVICE DOR-O-MATIC 1590
"CO SIDE
\ \
��--
TRANSPARENCY DISPLAY
1 PULL HANDLE KAWNEER STYLE -12" @ EXTERIOR
\ \
tO
BY OTHERS
1 LATCH LOCK ADAMS RITE 4510
\ \
\
`Q---_—=---
1 ELECTRIC STRIKE ADAMS RITE 7130
------------
1 THRESHOLD KAWNEER BUTT HUNG
EXISTING STOREFRONT
1 CLOSER LCN 4041 SUPER SMOOTHEE
\
O (-
GROUP #5
\
\
11 -7 '
,
1-1/2 PR. BUTTS 21 FBB 199
4-1/2 X 4-1/2
\
\
1 PANIC DEVICE DOR-O-MATIC 1590 OR EQUAL
\
1 PULL HANDLE/LEVER RUSSWIN
1 LATCH LOCK RUSSWIN
1 ELECTRIC STRIKE RUSSWIN
----------------------
1 CLOSER LCN 4041 SUPER SMOOTHEE
0
0
w
wU
Qi
o �
U
CL
1--1
o ® 0 g C `n o
Q J O Q c) �
rwoJ 000
�I w = �` c)
3V)0
Q o
CJ p 'J v
N Q
0
W
EN -4
0-40 1
Q x
C
Q
U
o �
0
0
a
o
CONTRACTOR -SHALL VERIFY
ALL CONDITIONS AND
DIMENSIONS AT THE JOB SITE
AND NOTIFY THE ARCHITECT
OF ANY DIMENSIONAL ERRORS,
OMISSIONS OR DISCREPANCIES
BEFORE BEGINING OR
FABRICATING ANY WORK.
DO NOT SCALE DRAWINGS.
o ..
0
0
U IIS
V
� r ^
U v
Q Z
C,7
0
o Q Z
¢ CL a o
Q zq
N� C)
a o
W Q o M
CL
W ® I— w z
Q 0� Q
V
CQ CL
Q
O
U
W
Q �
� Z
U
o ,a�
o
CLCL0
RIM
� o
o
L
0
N
CD
0
U
FLOOR PLAN
SCALE: 3/16" = 1'-0"
DRAWN
BJ, PH
CHECKED
JRJJ
m
m
m
SCALE
AS NOTED
PROJECT NO.
00
FILE NAME
2479A2U
SHEET
a
g
V)
a
z
o
N
o
D_
ee
Z
V)
o
V„
a
Z
U
LL_
o
o
V)
�
�
o
CL-
o
Q
0
0
o
Lo-
Z
FcV
0
0
w
wU
Qi
o �
U
CL
1--1
o ® 0 g C `n o
Q J O Q c) �
rwoJ 000
�I w = �` c)
3V)0
Q o
CJ p 'J v
N Q
0
W
EN -4
0-40 1
Q x
C
Q
U
o �
0
0
a
o
CONTRACTOR -SHALL VERIFY
ALL CONDITIONS AND
DIMENSIONS AT THE JOB SITE
AND NOTIFY THE ARCHITECT
OF ANY DIMENSIONAL ERRORS,
OMISSIONS OR DISCREPANCIES
BEFORE BEGINING OR
FABRICATING ANY WORK.
DO NOT SCALE DRAWINGS.
o ..
0
0
U IIS
V
� r ^
U v
Q Z
C,7
0
o Q Z
¢ CL a o
Q zq
N� C)
a o
W Q o M
CL
W ® I— w z
Q 0� Q
V
CQ CL
Q
O
U
W
Q �
� Z
U
o ,a�
o
CLCL0
RIM
� o
o
L
0
N
CD
0
U
FLOOR PLAN
SCALE: 3/16" = 1'-0"
DRAWN
BJ, PH
CHECKED
JRJJ
DATE
04/01/03
SCALE
AS NOTED
PROJECT NO.
C32479
FILE NAME
2479A2U
SHEET
A-2