HomeMy WebLinkAbout1401 W Seminole Blvd (a)Central Florida Regional Hospita
1st Floor L
U
& D
Nu rse's Station Renovat
at
401 West Seminole Boulevard
Sanford, Florida 32771
N
= WORK
I
on
SYMBOL LEGEND
SYMBOL
DESCRIPTION
ROOM NAME 1
ROOM TAG - INDICATES ROOM NAME, ROOM
ROOM NAME 2
NUMBER (FIRST DIGIT INDICATES FLOOR LEVEL.
000)
REMAINING DIGITS INDICATE ROOM NUMBER 01
N.S.F.
THRU 99) AND NET SQUARE FOOTAGE (N.S.F.)
AD2.2
DOOR NUMBER TAG - FIRST DIGIT INDICATES
0000
FLOOR LEVEL. MIDDLE DIGITS INDICATE ROOM
2ND FLOOR DEMOLITION FLOOR PLANS & DEMO NOTES
NUMBER 01 THRU 999. LAST DIGIT INDICATES
A1.1
NUMBER OF DOORS IN THE ROOM A, B, C, etc...
0
EXTERIOR ELEVATION TAG - TOP NUMBER
IST FLOOR DIMENSION / REFERENCE PLAN, LEGEND & SECTIONS
INDICATES DETAIL LOCATION AND BOTTOM
A4.1
NUMBER INDICATES PAGE NUMBER
INDICATES DETAIL NUMBER AND NAME, SCALE OF
INTERIOR ELEVATIONS & MILLWORK SECTIONS
DETAIL & XREF USED IN DETAIL
ID2.1
COLUMN GRID LINE TAG - A, B, C, ETC. IN ONE
XX
DIRECTION & 1,2,3 ETC. IN THE OPPOSITE
INTERIOR CODE SCHEDULE
LOCATION OF GRID NOTED A2,47, ETC.
X
INTERIOR ELEVATION TAG - TOP NUMBER
X 0 X
INDICATES DETAIL NUMBER, BOTTOM NUMBER
.
VINDICATES
PAGE NUMBER AND A,B,C,D INDICATE
M0.2
DIRECTION OF ELEVATION
X
M2.1
0
REFERENCE TAG INDICATES LOCATION OF
Sim .
ENLARGED PLANS, ELEVATIONS, AND DETAILS -
TOP NUMBER INDICATES DETAIL NUMBER AND
ELECTRICAL
BOTTOM NUMBER INDICATES PAGE DETAIL IS
E0.1
FOUND ON
WALL TAG INDICATES WALL TYPE - REFER TO
LOCATION PLAN FIRST FLOOR
WALL LEGEND FOR DETAILS OF WALL
E2.1
COMPONENTS
o' -a°
AFF
HEIGHT TAG INDICATES ELEVATION HEIGHTS
0
SECTION MARK - TOP NUMBER INDICATES
E3.1
SECTION NUMBER AND BOTTOM NUMBER
INDICATES PAGE SECTION IS FOUND ON
OWINDOW
TAG INDICATES WINDOW TYPE
QO
REVISION TAG INDICATES REVISION NUMBER
PHOTO TAG - TOP NUMBER INDICATES SECTION
RISER DIAGRAM - ELECTRICAL
NUMBER AND BOTTOM NUMBER INDICATES PAGE
SECTION IS FOUND ON
VICINITY MAP
INDEX OF DRAWINGS
0
SHEET
ARCHITECTURAL
A0.0
COVER SHEET, INDEX, LEGENDS & SITE MAP
AD2.1
1ST FLOOR DEMOLITION PHASES
AD2.2
1ST FLOOR DEMOLITION FLOOR PLANS & DEMO NOTES
AD2.3
2ND FLOOR DEMOLITION FLOOR PLANS & DEMO NOTES
A1.1
1ST FLOOR LIFE SAFETY PLAN, BUILDING STATISTICS & UL DETAIL
A2.1
IST FLOOR DIMENSION / REFERENCE PLAN, LEGEND & SECTIONS
A4.1
1ST FLOOR REFLECTED CEILING PLAN, DETAILS & LEGEND
A9.1
INTERIOR ELEVATIONS & MILLWORK SECTIONS
ID2.1
1ST FLOOR WALL FINISH PLAN & FLOORING PLAN
ID8.1
INTERIOR CODE SCHEDULE
MECHANICAL
M0.1
LEGEND, SYMBOLS AND GENERAL NOTES
M0.2
MECHANICAL SPECIFICATIONS
M2.1
DEMO/RENO MECHANICAL
M3.1
DETAILS AND SCHEDULES
ELECTRICAL
E0.1
SYMOBOL LEGEND GENERAL NOTES SPECIFICATION AND DETAILS
E1.1
LOCATION PLAN FIRST FLOOR
E2.1
DEMO/RENO FIRST FLOOR POWER & SYSTEMS
E2.2
DEMO/RENO FIRST FLOOR NURSECALL
E3.1
DEMO/RENO FIRST FLOOR LIGHTING
E6.1
PANEL SCHEDULES
E6.2
PANEL SCHEDULES
E7.1
RISER DIAGRAM - ELECTRICAL
PLUMBING
P0.1
SPECIFICATIONS, SCHEDULES, NOTES & LEGEND - PLUMBING
P2.1
DEMOLITION PLAN PLUMBING
P3.1
RENOVATION PLAN PLUMBING
FIRE PROTECTION
FP1.1
RENOVATION PLAN FIRE PROTECTION
go
pFFICE
C F RM m L & -D
Sanford, , Florida
PERMIT SET
201 OmO38
10-25-10 KAG LLR
issue date drawn by aDDroved by Droiect number
REVISION SCHEDULE
0 DATE DESCRIPTION
COVER SHEET, INDEX AOM0
LEGENDS & SITE MAP
sheet number
THESE DOCUMENTS AND THEP CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY FOR THE SPECIFIC PROJECT
NOTED ON THESE DRAWINGS. ANY REPRODUCTION ANDIOR REDISTRIBUTION WITHOUT THE EXPRESSED WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES,
INC. Is PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING
CODES AND THE APPLICABLE FIRE SAFETY STANDARDS.
BURKE HOGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL 32746
407.333.2005 AACOM233 Camala McCaft Hogw
AR•OOOD533
WWW.BHM.US.COM
PHASE II
PHASE III
Scale: 3116" =1'-0"
Scale:3/8" = V-0"
: 318" =1'-0"
Ru
N
REMOVE UP TO ALIGN
i EXIST(NG SOFFIT.
D VERIFY HEIGHT.
N
GENERAL DEMOLITION NOTES:
DEMOLITION KEYNOTES— REFER TO DEMOLITION KEYNOTES FOR SPECIFIC DEMOLITION REQUIREMENTS. SPECIFIC DEMOLITION ITEMS ARE NOT TO BE CONSIDERED ALL INCLUSIVE OR COMPLETE IN
THEMSELVES. PERFORM ADDITIONAL DEMOLITION THAT MIGHT BE REASONABLY REQUIRED IN THE PREPARATION FOR AND INSTALLATION OF NEW CONSTRUCTION OR SPECIFIED FINISHES. DEMOLITION
WORK SHALL BE PERFORMED IN A MANNER THAT WILL NOT DAMAGE ADJOINING SURFACES INDICATED TO REMAIN. SURFACES SHALL BE PATCHED TO PROVIDE AN ACCEPTABLE SUBSTRATE FOR NEW
FINISHES.
DEMOLITION WORK— PERFORM DEMOLITION ACTIVITIES IN ACCORDANCE WITH APPLICABLE AUTHORITIES HAVING JURISDICTION. DEMOLISH INA METHODICAL AND CAREFUL MANNER AS REQUIRED TO
ACCOMMODATE NEW WORK SPECIFIED. PERFORM DEMOLITION WORK IN A MANNER AS TO MINIMIZE DAMAGE, EXCESSIVE NOISE OR VIBRATION, AND DISTURBANCE TO ADJACENT OCCUPIED BUILDING
AREAS AND OPERATIONS AS POSSIBLE. ANY OPERATION THAT IS ANTICIPATED TO CAUSE DISTURBANCE TO THE OWNER OR TENANT, SHALL BE COORDINATED WITH THE FACILITY ADMINISTRATION A
MINIMUM OF ONE (1) WEEK PRIOR TO EXECUTION OF WORK.
"REMOVE" SHALL MEAN TO DETACH ITEMS FROM EXISTING CONSTRUCTION AND LEGALLY DISPOSE OF THEM OFFSITE IN AN EPA APPROVED LANDFILL. DO NOT BURN DEMOLISHED MATERIALS.
"REMOVE AND SALVAGE": DETACH ITEMS FROM EXISTING CONSTRUCTION AND DELIVER THEM TO OWNER.
"REMOVE AND REINSTALL": DETACH ITEMS FROM EXISTING CONSTRUCCTION, PREPARE THEM FOR REUSE, AND REINSTALL THEM WHERE INDICATED.
"EXISTING TO REMAIN": EXISTING ITEMS OF CONSTRUCTION THAT ARE NOT TO BE REMOVED AND THAT ARE NOT OTHERWISE INDICATED TO BE REMOVED, REMOVED AND SALVAGED, OR REMOVED AND
REINSTALLED.
OWNER RESERVES THE FIREST RIGHT OF REFUSAL FOR ALL ITEMS REMOVED. COORDINATE WITH OWNER'S REPRESENTATIVE BEFORE DEMOLITION BEGINS.
NEATLY CUT OPENINGS AND HOLES PLUMB, SQUARE, AND TRUE TO DIMENSIONS REQUIRED. USE CUTTING METHODS LEAST LIKELY TO DAMAGE CONSTRUCTION TO REMAIN OR ADJOINING
CONSTRUCTION. USE HAND TOOLS OR SMALL POWER TOOLS DESIGNED FOR SAWING OR GRINDING, NOT HAMMERING AND CHOPPING, TO MINIMIZE DISTURBANCE OF ADJACENT SURFACES.
TEMPORARILY COVER OPENINGS TO REMAIN.
DO NOT USE CUTTING TORCHES OR OPEN FLAME CUTTING TOOLS
SEE GENERAL NOTES ON THE MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR ADDITIONALDEMOLITION NOTES.
LOCATE SELECTIVE DEMOLITION EQUIPMENT DEBRIS AND MATERIALS SO AS NOT TO IMPOSE EXCESSIVE LOADS ON SUPPORTING WALLS, FLOORS, OR FRAMING.
CLEAN AREAS OF DEMOLITION DAILY, INCLUDING ADJACENT AREAS OF SITE OF DUST, DIRT, AND DEBRIS CAUSED BY SELECTIVE DEMOLITION OPERATIONS.
PROTECTION EXERCISE CARE DURING WORK TO PROTECT EXISTING INTERIOR AND EXTERIOR CONSTRUCTION TO REMAIN. REPAIR TO, OR REPLACEMENT OF, EXISTING CONSTRUCTION DUE TO
DAMAGE BY DEMOLITION ACTIVITIES SHALL BE PERFORMED AT NO COST TO THE OWNER.
HAZARDOUS MATERIALS - THE CONTRACTOR SHALL IMMEDIATELY REPORT ANY HAZARDOUS OR TOXIC MATERIALS ENCOUNTERED TO ARCHITECT AND OWNER.
OPENINGS - WHERE OPENINGS ARE CREATED IN EXISTING CONSTRUCTION TO REMAIN, SUCH AS REMOVAL OF EXISTING DOORS OR WINDOWS ON WALLS INDICATED TO REMAIN, PROVIDE NEW
CONSTRUCTION OF TYPE AND THICKNESS IS TO MATCH ADJACENT. MATERIALS USED TO FILL THOSE OPENINGS AND FINISHES INSTALLED SHALL MATCH EXISTING UNLESS NEW FINISHES ARE
SCHEDULED FOR THOSE SURFACES.
EXISTING SERVICES - WHERE EXISTING SERVICES SUCH AS PLUMBING, ELECTRICAL, GAS, ETC. ARE AFFECTED BY DEMOLITION WORK, SUCH AS REMOVAL OF AN EXISTING PARTITION, THE SERVICES
SHALL BE REMOVED TO A POINT WHERE THEY CAN BE CAPPED AND TERMINATED UNLESS OTHERWISE SHOWN ON THE DRAWINGS OF THE SPECIFIC DISCIPLINE AFFECTED.
FINISHES -CONTRACTOR SHALL REMOVE EXISTING FINISHES AND PREPARE SUBSTRATES TO RECEIVE NEW FINISHES. PREPARATION OF SUBSTRATES SHALL INCLUDE, BUT NOT BE LIMITED TO, THE
FOLLOWING IF DEEMED REQUIRED BY THE ARCHITECT:
• PATCHING AND/OR LEVELING OF FLOOR SLAB.
• RE -PRIMING OF STRUCTURAL COLUMNS, BEAMS, JOISTS, ETC. DAMAGED FROM DEMOLITION ACTIVITIES.
DEMOLITION NOTES:
1. REMOVE ALL FLOORING, WALL COVERINGS AND WALL BASE IN ITS ENTIRETY IN 'SCOPE OF WORK AREA. AREA OF WORK IS INDICATED ON
DEMOLITION PLAN WITH A BOLD DASHED LINE. PREPARE FLOORS AND WALLS TO RECEIVE NEW FINISHES.
2. REMOVE EXISTING PARTITION IN ITS ENTIRETY OR UP TO HEIGHT SPECIFIED ON PLAN. PARTITIONS TO BE REMOVED ARE INDICATED AS DASHED
LINES.
3. REMOVE EXISTING DOOR AND DOOR FRAME. DOOR TO BE REMOVED IS INDICATED AS A DASHED LINE. RE -USE DOOR AND FRAME AS NEEDED.
4. REMOVE EXISTING SUSPENDED ACOUSTIC CEILING SYSTEM INCLUDING GRID AND ALL ATTACHMENTS. RE -USE CEILING TILES, REPLACE ALL
DAMAGED OR DISCOLORED TILES.
5. REMOVE EXISTING LIGHT FIXTURES. LIGHT FIXTURE ARE TO BE RE -USED, CLEANED, REPAIRED AND RE-LAMPED AS NECESSARY BEFORE
REINSTALLATION. COORDINATE WITH ELECTRICAL DRAWINGS FOR ADDITIONAL NOTES.
6. REMOVE EXISTING MILLWORK. MILLWORK TO BE REMOVED IS INDICATED AS A DASHED LINE.
7. REMOVE EXISTING PLUMBING. PLUMBING TO BE REMOVED IS INDICATED AS A DASHED LINE. COORDINATE WITH PLUMBING DRAWINGS FOR
ADDITIONAL NOTES.
8. EXISTING DOOR AND DOOR FRAME TO REMAIN.
9. EXISTING MILLWORK TO REMAIN.
10. EXISTING PLUMBING TO REMAIN.
11. EXISTING SOFFIT TO REMAIN.
12. EXISTING PARTITION TO REMAIN.
13. TEMPORARY WALLNISQUEEN DIVIDER DURING DEMOLITION PHASE II & III.
14. EXISTING SUSPENDED ACOUSTIC CEILING SYSTEM INCLUDING GRID TO REMAIN.
15. EXISTING LIGHT FIXTURES TO REMAIN.
16. REMOVE EXISTING CRASH GUARDS. PATCH AND REPAIR WALLS AS NEEDED.
17. REMOVE EXISTING SHOWER CURTAIN ROD AND SHOWER CURTAIN.
18. REMOVE EXISTING MEDICAL GAS MOULDING IN PATIENT ROOMS. PATCH AND REPAIR WALLS AS NEEDED.
19. REMOVE WINDOW TREATMENTS. PATCH AND REPAIR WALLS AS NEEDED.
G F. R L A
Sanford, Florida
PERMIT SET
2010.038
10-25-10 KAG LLR
issue date drawn by approved by project number
REVISION SCHEDULE
A01 DATE DESCRIPTION
DEMOLITION FLOOR
PLANS & DEMO NOTES A D 2 m 1
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE 6 MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY FOR THE SPECIFIC PROJECT
NOTED ON THESE DRAWINGS. ANY REPRODUCTION ANDIOR REDISTRIBUTION WITHOUT THE EXPRESSED WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES,
INC. S PROHIBITED BYLAW. TO THE BEST OF THE ARCHITECTS KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING
CODES AND THE APPLICABLE FIRE SAFETY STANDARDS.
BURKE HOGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL 32746
407.333.2005 AAC000233 Camala McCarter Hogue
AR•0009533
.BHM.US.COM
SMnKF CnMPARTMFNT CHART
T
Scale: 1/8" =1'-0"
BUILDING STATISTICS & CODE ANALYSIS
APPLICABLE CODES
A. FLORIDA FIRE PREVENTION CODE, 2007 NFPA 1 -UNIFORM FIRE CODE, 2006
B. FLORIDA FIRE PREVENTION CODE, 2007 NFPA 101 -LIFE SAFETY CODE, FLORIDA EDITION, 2006
C. NFPA 220- STANDARD ON TYPES OF BUILDING CONSTRUCTION
D. FLORIDA BUILDING CODE, 2007 WITH 2009 SUPPLEMENTS
CONSTRUCTION TYPE PER FBC 2007- CHAPTER 6 & TABLE 601
OCCUPANCY CLASSIFICATION PER FBC & FFPC- 2007
TYPE II -B (SPRINKLERED) (PER FBC 903.6)
FBC 308 -GROUP 1-2 AND (FBC 3401.1 ALTERNATION)
FFPC-NFPA 101-19: HEATH CARE (EXISTING)
FFPC-NFPA 101-43: BUILDING REHABILITATION (43.5 MODIFICATION)
AREA CALCULATION
FBC TABLE 1004. 1.1 -AREA ALLOWANCES PER OCCUPANT
GROSS AREA AS DEFINED BY FBC 502.1(S.F.)
TENANT: 4,360/100=44 OCCUPANTS
AREA OF WORK 1ST FLOOR: 4,360 SQ.FT.
OCCUPANCY LOAD: 44 - SEE LIFE SAFETY PLAN
FBC TABLES 715.4- FIRE PROTECTION RATINGS
FBC TABLE 1005.1 -EGRESS WIDTH
TYPE OF ASSEMBLY REQUIRED ASSEMBLY OPENING PROTECTION
ELEMENT REQUIRED PROVIDED
DISTRIB.
REQUIRED PROVIDED REQUIRED PROVIDED
STAIRWAYWIDTH: 0.4x44= 17.6" 58"
58"
OCCUPANCY- (302.1) 1 1 3/4 HR 3/4 HR
EXISTING
FIRE WALLS/ BARRIERS- 4 X 3 X
GREATER THAN 1 HOUR 3 X 3 X
OTHER EGRESS WIDTH: 02 x 44 = 8:8"' ' ' ' ' ' 128"
East
SHAFT, EXIT WALLS 2 X 11/2 X
11/2 X 11/2 X
FIRE WALLS/ BARRIERS -
1 HR. -SHAFT, EXITWALLS 1 1 1 X
128".....
OTHER FIRE BARRIERS 1 X 3/4 x
FBC TABLE 1016.1- EXIT ACCESS TRAVEL DISTANCE
CORRIDOR WALLS 1 1 1/3 1/3
REQUIRED
PROVIDED
0.5 X 1/3 X
OTHER FIRE PARTITIONS 1 X 3/4 X
MAXIMUM TRAVEL DISTANCE 200'-0"
88'-9"
NFPA 101 A10.2.2- INTERIOR FINISH CLASIFICATION LIMITATIONS
COMMON PATH of TRAVEL -(1014.3) 25'-0"
NA
FBC TABLE 1017.1- CORRIDOR FIRE RESISTANCE RATING
VERITCAL EXITS & EXIT EXIT ACCESS CORRIDORS OTHER SPACES
PASSAGEWAYS
REQUIRED
PROVIDED
A OR B - EXISTING A OR B- EXISTING A, B OR C
CORRIDOR FIRE RESISTANCE RATING 0 HOUR
0 HOUR
FBC TABLES 1015.1 & 1019.2- SINGLE MEANS OF EGRESS
MININUM CLEARING OPENING41008.1.1) 32"
32"
APPLIES
MIN INUM STAIR WIDTH -(1009.1) 44"
58"
SPACE WITH ONE MEANS OF EGRESS PER 1015.1 NA
MIN INUM CORRIDOR WIDTH- (1017.2) 96"
96"
BUILDING WITH ONE EXIT -(1019.2) NA
MAXIMUM DEAD END CORRIDOR -(1017.3) 20'
16'-2"
EXIT ARRANGEMENT PER 1015.2
FBC TABLE 1019.1- MINIMUM NUMBER OF EXITS
DIAGONAL DISTANCE: 1/3 DISTANCE DISTANCE BETWEEN EXITS
REQUIRED
PROVIDED
AREA OF WORK: 119'-3" 39'-9" 76'-T
OCCUPANT LOAD= 44 2
3
LIFE SAFETY LEGEND
FIRE RATED WALL LEGEND
r--4'=9 1 HOUR RATED WALL - UL U465
LIFE SAFETY SYMBOLS
MAXIMUM TRAVEL DISTANCE TO NEAREST EXIT.
DIAGONAL DISTANCE OF BUILDING
<_ - DISTANCE BETWEEN TWO MOST REMOTE EXITS
A LOIST�� TRAVEL DISTANCE TO THE EXTERIOR
•
===x -
THE TRAVEL DISTANCE TO THE FIRE EXTINGUISHERS IS
DENOTED BY THE RADIUS, WITH THE RADIUS INDICATING
THE ACTUAL TRAVEL DISTANCE
WAYFINDING DEVICES
® EXIT LIGHT - CEILING MOUNTED
EXIT LIGHT - WALL MOUNTED
FIRE EXTINGUISHERS
® TYPE I EXTINGUISHER W/ BRACKET - 4A-60B:C
SPECIALTY SIGNALING DEVICES
FIRE SPRINKLER HEADS ARE INDICATED ON FIRE PROTECTION DRAWINGS.
DUCT SYSTEM FIRE DAMPERS ARE INDICATE ON MECHANICAL DRAWINGS.
EMERGENCY LIGHTING IS INDICATED ON ELECTRICAL DRAWINGS.
FIRE ALARM SYSTEM DETAILS ARE INDICATED ON ELECTRICAL DRAWINGS.
Design No. U465
Nonbearing Wall Rating -1 HR.
D D O
1. Floor and Ceiling Runners - (not shown) - Channel shaped runners,
3-5/8 in. wide (mm), 1-1/4 in. legs, formed from min No. 25 MSG (min No.
20 MSG when Item 4C is used) gals steel, attached to floor and ceiling with
fasteners spaced 24 in OC max
2. Steel Studs - Channel shaped, 3.5/8 in. wide (min),1-1 /4 in WIW=
folded back returns, formed from min No. 25 MSG (min No.20
Item 4C is used) galy steel spaced 24 in OC max..
3. Batts and Blankets* - (Optional) - Mineral wool or glass fiber batts par-
tiallg or com letely filling stud cavity.
See Batts and Blankets (B4Z) category for names of Classified• companies.
4 Wallboard, Gypsum*- 5/8 in. thief 4 ft wide, attached to steel studs and
floor and ceiling track with 1 in Ions, Type S steel screws spaced 8 in OC.
along edges of board and 12 in OC m tl�e field of the board joints oriented
verticallq and staggered on opposite sides of the assembly. When attached to
item 6 (furring channels), wallboard is screw attached to furring channels
with 1 in loug, 'fie S steel screws spaced 12 in OC
AMERICAN GYPSUM CO Type AG -C.
CANADIAN GYPSUM COMPANY. -Types AR, C, IP -X2,. SCX,
SHX, WRC or WRX.
CELOTEX CORP Type 1.
CONTINENTAL GYPSUM COMPANY Types CG -C, CG5-5,
CG6-6, CG9-9, CGTC-C.
G -P GYPSUM CORP, SUB OF
GEORGIA -PACIFIC CORP -Types 5, .9, C, GPFS6.
LAFARS6E GDYPSUM, DIV OF IE GYPSUM INC -Type BGC.
LAFARGE CORP Types LGFCZ LGFC2A, LGFC6, LGFC6A,
LGFC-C.
NATIONAL GYPSUM CO T FSK -G, FSW-G.
NATIONAL GYPSUM CO-'I�ype FR or WR.
PABCO GYPSUM, DIV OF
PACIFIC COAST BUILDING PRODUCTS INC Type PGC
REPUBLIC GYPSUM CO T RG-C.
STANDARD GYPSUM L L C -Type SG -C.
TEMPLE-INLAND FOREST PRODUCTS CORP - TGC
UNITED STATES GYPSUM CO Type AR, C, FRXIP-X2,
SCX, SHX, WRC or WRX.
YESO PANAMERICANO S A DE C V Type AR, C, IP -X2,
SCX, SHX, WRC or WRX.
WESTROC INC -Type Westroc Fireboard.
4A. Wallboard, Gypsum* - (As an alternate to Item 4) - Nom 3/4 in. thick, 4
ft wide, installed as described in Item 4 with screw length increased to 1-1 /4
in
CANADIAN GYPSUM COMPANY Type AR.
UNITED STATES GYPSUM CO -Type AR.
- PESO PANAMERICANO S A DE C V --Type AR.
4C. Wallboard, Gypsum* - (As an alternate to Item 4, 4A and 4B) - 5/8 in.
thickyps panels, installed as described in Item 4 with Type S-12 steel
screws. T'he liength and spacing of the screws as specified under Item 4.
CANADIAN GYPSUM COMPANY - FRX.
UNITED STATES GYPSUM CO Type
5. Joint Tape and Compound - Vmyl, dry or premixed joint compound,
applied in two coats to joints and screw heads; paper tape, 2 in wide,
embedded in first layer of compound over all joints. As an alternate, nomi-
nal 3/32 in. thick gypsum veneer pplaster mai► be applied to the entire sur-
face of Classified veneer baseboard. joints reinforced.
6. Furring Channel - (Optional -Not Shown) - Resilient 25 MSG galy steel
furring channels spaced vertically max 24 in. OC, flange portion attached to
each intersecting stud with 1/2 in. long type 5-12 panhead steel screws. Not
fat use with Type FRX gym ?awls -
'Bearing the UL Classification Marking
G 4 F, R4 Hir n L , & I D
Sanford, Florida
PERMIT SET
2010.038
10-05-10 KAG LLR
issue date drawn by approved by project number
REVISION SCHEDULE
An I DATE I DESCRIPTION
LIFE SAFETY PLAN,1
BLDG STATS. & UL DETAILS A `
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY FOR THE SPECIFIC PROJECT
NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED WRITTEN CONSENT OF BURKE, HOGUE NL MILLS ASSOCIATES,
INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPUCABLE MINIMUM BUILDING
CODES AND THE APPLICABLE FIRE SAFETY STANDARDS.
BURKE HOGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL 32746
407.333.2005 AAC000233
WWW.BHM.US.COM
CemMe McCarter Hogue
AR -0009533
PHASE II
Scale: 3/16"= 1'-0"
PHASE I - MOVE NOURISHMENT STATION TEMPORARILY TO NURSE'S LOUNGE.
Scale: 318" =1'-0"
NOURISHMENT 3
jli!121 A9.1
II
L
C=1 W
J
U
'HASE II
ALIGN
ti L -
A9.1'
NURSE
(_1 22
6'-0"
CLEAR
I.
N
r
O
M
INN
2'-0"
A �
A9.1
iii
A
n
1 HOUR RATED WALL PARTITION UL -0465
5 Scale: 3/4" =1'-0"
03001.C3
EXISTING
TYPICAL INTERIOR WALL PARTITION
4 Scale: 3/4" =1'-0"
SELECTIVE KEYNOTES 0
03001 CONCRETE WORK
03001.C3 CONCRETE FLOOR SLAB
03001.C4 CONCRETE SLAB ON GRADE
03001.C5 CONCRETE SLAB ON METAL DECK
07842 FIRE -RESISTIVE JOINT SYSTEMS
07842.C1 FIRESAFING
07842.C3 FIRE-RESISTANT RATED SEALANT
09111 NON-STRUCTURAL METAL FRAMING
09111.61 STEEL STUD RUNNER TRACK
09111.67 FIRE RATED SLIP -JOINT
09111.C1 STEEL STUD
09111.C3 STEEL STUD BRACE
09250 GYPSUM BOARD
09250.A1 GYPSUM WALL BOARD
09250.62 TYPE X GYPSUM BOARD
09511 ACOUSTICAL PANEL CEILINGS
09511.A1 EXPOSED -GRID ACOUSTICAL PANEL CEILING SYSTEM
09511.D3 HANGER WIRE
09912 INTERIOR PAINTING
09912.A1 PAINTED FINISH
DIMENSION NOTES
1. GENERALLY PLAN DIMENSIONS ARE FROM FACE OF CMU WALL TO
CENTER OF STUD WALLS EXCEPT AT CORRIDORS & CRITICAL CLEAR
DIMENSIONS WHERE DIMENSION IS FROM FACE OF FINISHED GYPSUM
BOARD ON SIDE WHERE CLEAR DIMENSION MUST BE HELD.
2. ALL INTERIOR FRAME WALLS ARE 3- %" METAL STUD U.N.O.
3. WINDOW & DOOR OPENINGS ARE GENERALLY DIMENSIONED TO THE
EDGE OF ROUGH OPENINGS FOR EXTERIOR CMU WALLS & TO
CENTERLINE OF INTERIOR OPENINGS.
4. TYPICALLY EDGE OF DOOR IS LOCATED 4" OFF OF ADJACENT WALL
EXCLUSIVE OF FRAME U.N.O. ALL OTHER DOOR OPENINGS ARE
LOCATED TO ONE SIDE OF ROUGH OPENING, FRAME EXCLUSIVE.
5. DO NOT SCALE THIS DRAWING.
WALL LEGEND
Q-�
WLegend
NO.
DESCRIPTION
PLAN VIEW
1
3 518" x 20 GA. METAL STUDS 24" O.C. MAX., WITH 5/8"
GYPSUM BOARD BOTH FACES 6" ABOVE CEILING.
DIAGONAL BRACING EVERY 4' O.C. SEE DETAIL 4/A2.1.
2
3 5/8" x 25 GA. METAL STUDS AT 24" O.C. MAX., WITH
SOUND BATT INSULATION IN CAVITY WITH 5/8" TYPE'X'
GYPSUM WALLBOARD BOTH FACES TO UNDERSIDE OF
DECK. ONE HOUR RATED PER UL- U465. SEE DETAIL
5/A2.1.
3
EXISTING WALLS TO REMAIN
1 HOUR RATED WALL PARTITION DETAIL
6 Scale: 3/4" =1'-0"
,: F RL,�.
&D
Sanford, Florida
PERMIT SET
10-25-10 KAG LLR
issue date drawn by approved by
201 0.038
project number
REVISION SCHEDULE
0 DATE DESCRIPTION
IST FLOOR DIM. / REF. PLANS A 1
LEGENDS & SECTION
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY FOR THE SPECIFIC PROJECT
NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED WRITTEN CONSENT OF BURKE, HOGUE d MILLS ASSOCIATES,
INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING
CODES AND THE APPLICABLE FIRE SAFETY STANDARDS.
BURKE HOGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL 32746
407.333.2005 AAC000233 C -1a
AR=bpm Hogue
*NOTE: ALL EXISTING ACOUSTICAL CEILING
SYSTEM AND LIGHT FIXTURES TO REMAIN U.N.O.
Scale: 3116" =1'-0"
/-- EXISTING SOFFIT
=XI TIN
NK
NEW SOFFIT
ALIGN WITH EXISTING SOFFIT
.100.
SELECTIVE KEYNOTES D
09111
i
0911121
STEEL STUD RUNNER TRACK
09111.C1
STEEL STUD
09250
GYPSUM BOARD
09250.A1
GYPSUM WALL BOARD
09250.E2
CORNER BEAD
09511
ACOUSTICAL PANEL CEILINGS
09511.61
ACOUSTICAL CEILING UNIT
0
/-- EXISTING SOFFIT
=XI TIN
NK
NEW SOFFIT
ALIGN WITH EXISTING SOFFIT
.100.
SELECTIVE KEYNOTES D
09111
NON-STRUCTURAL METAL FRAMING
0911121
STEEL STUD RUNNER TRACK
09111.C1
STEEL STUD
09250
GYPSUM BOARD
09250.A1
GYPSUM WALL BOARD
09250.E2
CORNER BEAD
09511
ACOUSTICAL PANEL CEILINGS
09511.61
ACOUSTICAL CEILING UNIT
CEILING LEGEND
48" x 24" SUSPENDED ACOUSTICAL CEILING SYSTEM. CEILING
HEIGHT AT 8'-0" IN CORRIDORS AND 8'-10" AFF THROUGHOUT
U.N.O.
MOISTURE RESISTANT GYPSUM BOARD CEILING OR SOFFIT
® 2'x4' FLUORESCENT FIXTURE
® EXIT LIGHT
CSF Rv . L & D
Safford, Florida
PERMIT SET
10-25-10 KAG LLR
issue date drawn by approved by
201 0.038
project number
REVISION SCHEDULE
0 DATE DESCRIPTION
REFLECTED CEILING PLANS A4 1
DETAILS &LEGENDS ■
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE d MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY FOR THE SPECIFIC PROJECT
NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES,
INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPUCABLE MINIMUM BUILDING
CODES AND THE APPLICABLE FIRE SAFETY STANDARDS.
66 Chi �
AV
1�
BURKE HOGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL 32746
407.333.2005 AAC000233 CemWoMcCaEn Hoary
AR -0009533
WWW.BHM.US.COM
PATIENT i _/
TRACKING
MONITOR I
-----J
11 12 12 11--� F--�
A9.1 A9.1 06402.R1 A9.1 A9.1 FETAL SECURITY
06402.N1 I MONITOR I I MONITOR
sk-
', 06402.M7
. r
`q 06402.C9 ..
M
........ ... . ....... ......
N
06402.N7
5'-5" 3'-6" T-01 /2" 48" O.C. MAX 4'-0" 3'-61 /2" 4'-0"
700 12'-41/2" 11'-61/2'
A B
NURSE STATION - FRONT COUNTER
Scale: 3/8" =1'-0"
E
06402.132
FULL HEIGHT
- VERIFY MOUNTING
HEIGHT WITH OWNER
REPRESENTATIVE.
06402.111
06402.N1
Z4
M
06402.62 I VERIFY MOUNTING
HEIGHT WITH OWNER
IN
M I I REPRESENTATIVE.
I I 10 --_1
A9.1 AL
BASE I MONITOR I
06402.M7 �
CV
06402.81 I
o I
N
06402.N7
_� %48" O.C. MAX
1'-6" V-6" V-6" 2'_6" 2'-6" 2'-6" 2'-6" 2'-6" 2'-6" 2'-2" 06402.1`1 `-6'~ 3'-11" 4'-0"
4 Ow A 10
41-71/2" 17'-2" 0,
9'-11"
A B
NURSE STATION -
Scale: 3/8" =1'-0"
0
N
IIE
4
ch
0
CV
TOP CABIN
6 Scale: 11/2" =1'-0"
r
o
CN
BASE CABINET TOP/BASE CABINET
7 Scale: 1 1/2" =1'-0"
0
CV
VE
114" 4'-0" " 4'-0"
91-gor
A
1DICTATION STATIONS
Scale: 3/8" =1'-0"
;�it1YAl
06402.R1
064
9
c`Q c� M is
N 06402.N7 N
48" O.C. MAX
TOP/BASE W/OUT DRAWER
Scale: 11/2" =1'-0"
IE
N
CD
COLUMN � 2'-91/2 L
B
C
D
O
ch
FULL HEIGHT CABINET
Scale: 1 1/2" =1'-0"
IE
Cr7
SELECTIVE KEYNOTES O
I
k .NSACTION WORK SUURFA(
1 Scale: 1 1/2„ =1'-0"
2'-5 3/4
WORK SURFACE WI TOP CABINETADA WORK SURF
GFRH-L&
Sanford, Florida
PERMIT SET
2010.038
REVISION SCHEDULE
0 DATE DESCRIPTION
INTERIOR ELEVATIONS & A9 m 1
MILLWORK SECTIONS
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY FOR THE SPECIFIC PROJECT
NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES,
INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPUCABLE MINIMUM BUILDING
CODES AND THE APPUCABLE FIRE SAFETY STANDARDS.
•
BURKE HOGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL 32746
407.333.2005 AACOM233 Cemal"McC"rWHogue
AR -0009533
WWW.BHM.US.COM
06100
ROUGH CARPENTRY
0610011
WOOD BLOCKING
6 7
06402
INTERIOR ARCHITECTURAL WOODWORK
A9.1 A9.1
06402.61
BASE CABINET
06402.62
WALL CABINET
06402.C1
PLYWOOD
06402.C9
PLYWOOD - PLASTIC LAMINATE FINISH
06402.J2
CABINET DOOR
06402.62
06402.J3
CABINET DRAWER
-1
7
<7
=4
06402.J6
ADJUSTABLE SHELF
1-
9
06402.M2
PLASTIC LAMINATE FINISH
I
-
-
0640215
06402.M6
PLASTIC LAMINATE BACKSPLASH
I I
4
06402.M7
PLASTIC LAMINATE COUNTERTOP
I NOURISH. I
15001.G4
06402.N1
TRANSACTION TOP
I STATION I
e
06402.N7
PLASTIC LAMINATE SUPPORT PANEL
I I
N
06402.M7
06402.P1
PLASTIC LAMINATE PANEL
I I
06402.R1
SOLID POLYMER MATERIAL
I
06402.W2
ADJUSTABLE SHELF STANDARD
I
0640215
06402.X3
PLASTIC GROMMET
I I
REFRIG.
0
06402.X4
CASEWORK PULL
I
N
0640261
0640215
CASEWORK CYLINDER LOCK
L - - _1
09111
NON-STRUCTURAL METAL FRAMING
2'-8"
2'-1"
2'-6"
1'-3°
09111.G2
STEEL BACKING PLATE
CLEAR
6'-0"
09841
FIXED SOUND -ABSORPTIVE PANELS
09841.A1
ACOUSTICAL WALL PANEL
15001
PLUMBING & MECHANICAL EQUIPMENT AND SYSTEMS
15001.G4
HAND SINK
NOURISHMENT STATION
Scale: 3/8" =1'-0"
I
k .NSACTION WORK SUURFA(
1 Scale: 1 1/2„ =1'-0"
2'-5 3/4
WORK SURFACE WI TOP CABINETADA WORK SURF
GFRH-L&
Sanford, Florida
PERMIT SET
2010.038
REVISION SCHEDULE
0 DATE DESCRIPTION
INTERIOR ELEVATIONS & A9 m 1
MILLWORK SECTIONS
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY FOR THE SPECIFIC PROJECT
NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES,
INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPUCABLE MINIMUM BUILDING
CODES AND THE APPUCABLE FIRE SAFETY STANDARDS.
•
BURKE HOGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL 32746
407.333.2005 AACOM233 Cemal"McC"rWHogue
AR -0009533
WWW.BHM.US.COM
I
t
JScale: 3l8" =1'-0"
N
INTERIOR
CODE
SCHEDULE
BASE CODE SCHEDULE
TYPE
COLOR
CODE
MANUFACTURER
MANUFACTURER #
TYPE
COLOR
GILDED MESH
SIZE
CLASS 1
GAUGE
FLAME
SPREAD
RATING
REMARKS
B-3
JOHNSONITE
GROUNDED 264
VINYL BASE
GROUNDED
4"
COLOR
.08"
CLASS 1
VIEWING ROOM, NURSE LOUNGE
RESILIENT CODE SCHEDULE
CODE
MANUFACTURER
MANUFACTURER #
TYPE
COLOR
FINISH/SHEEN
FLAME
SPREAD
RATING
FLAME
P-1
NOT USED
GILDED MESH
CLASS 1
VERTICAL SURFACES
PL -2
PIONITE
SPREAD
SHERWIN WILLIAMS
CODE
MANUFACTURER
MANUFACTURER #
TYPE
COLOR
SIZE
GAUGE
RATING
REMARKS
R-1
NOT USED
R-2
ARMSTRONG
LP 092
MARMORETTE SHEET
SAND
12'
CLASS 1
LINOLEUM
.08"
R-3
ARMSTRONG
LP 476
LINORETTE SHEETLINOLEUM
YUKON DESERT
12'
CLASS 1
.08"
PAINT CODE SCHEDULE
CODE
MANUFACTURER
MANUFACTURER #
TYPE
COLOR
FINISH/SHEEN
FLAME
SPREAD
RATING
REMARKS
P-1
NOT USED
GILDED MESH
CLASS 1
VERTICAL SURFACES
PL -2
PIONITE
P-2
SHERWIN WILLIAMS
SW 6121
ACRYLIC LATEX
WHOLE WHEAT
SEMI -GLOSS
CLASS 1
LOW VOC. TYPICAL WALL COLOR
PLASTIC LAMINATE CODE SCHEDULE
CODE
MANUFACTURER
MANUFACTURER #
COLOR
FINISH
FLAME
SPREAD
RATING
REMARKS
PLA
WILSONART
4912-38
GILDED MESH
CLASS 1
VERTICAL SURFACES
PL -2
PIONITE
AT371
CRESSIDA
CONTENT
CLASS 1
HORIZONTAL SURFACES
SOLID SURFACE CODE SCHEDULE
CODE
MANUFACTURER
MANUFACTURER #
COLOR
FINISH
FLAME
SPREAD
RATING
REMARKS
SS -1
NOT USED
SPREAD
SS -2
IN PRO
P9064
SNAKE SKIN
CONTENT
CLASS 1
NURSE'S STATION TRANSACTION LEDGE
FABRIC CODE SCHEDULE
FLAME
SPREAD
CODE
MANUFACTURER
MANUFACTURER #
COLOR
CONTENT
RATING
REMARKS
F-3
MAHARAM
SEASON 901040
002 CREEK
POLYESTER
I CLASS 1
1 DICTATION STATION FABRIC WRAPPED PANELS.
FINISH NOTES:
ALL FINISHES ARE TO MEET ALL FIRE AND BUILDING CODE ORDINANCES. INTERIOR FINISHES SHALL BE IN ACCORDANCE WITH NFPA 101:10.2,2006 EDITION.
SELECTIVE KEYNOTES
C FkvmmL&
Sanford, Florida
PERMIT SET
2010,.038
REVISION SCHEDULE
0 DATE DESCRIPTION
INTERIOR CODE SCHEDULE ' DS .1
&FINISH PLAN
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE 3 MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY FOR THE SPECIFIC PROJECT
NOTED ON THESE DRAWINGS. ANY REPRODUCTION ANDIOR REDISTRIBUTION WITHOUT THE EXPRESSED WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES,
INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING
CODES AND THE APPLICABLE FIRE SAFETY STANDARDS.
BURKE HOGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL 32746
407.333.2005 AAC000233 CwWaMcCarter Hoab
AR•0009533
FIRE PROTECTION SPECIFICATIONS
GENERAL:
DRAWINGS AND GENERAL PROVISIONS OF CONTRACT, INCLUDING GENERAL AND
SUPPLEMENTAL CONDITIONS AND DIVISION I SPECIFICATIONS, APPLY TO WORK SPECIFIED
IN THIS SECTION.
SCOPE OF WORK:
WORK REQUIRED UNDER THIS SECTION INCLUDES PROVIDING ALL LABOR, MATERIALS,
EQUIPMENT, FEES AND SERVICES FOR, AND REASONABLY INCIDENTAL TO, PROPER
COMPLETION OF ALL FIRE PROTECTION WORK HEREIN SPECIFIED, EXCEPTING ONLY WORK
OR MATERIALS SPECIFIED OR NOTED AS BEING FURNISHED AND/OR INSTALLED BY
OTHERS.
1. ALL WORK SHALL COMPLY WITH NFPA REQUIREMENTS, 2007 FLORIDA BUILDING CODE
(WITH 2009 SUPPLEMENTS), CITY OF ORLANDO FIRE CODE, FLORIDA FIRE PREVENTION
CODE (2007 EDITION), LIFE SAFETY CODE - NFPA 101 (2006 EDITION), AUTOMATIC
SPRINKLER SYSTEMS - NFPA 13 (2002 EDITION) AND THE NATIONAL FIRE ALARM
CODE - NFPA 72 (2002 EDITION).
2. ALL WORK SHALL BE PERFORMED BY COMPETENT WORKMEN SKILLED AND LICENSED
IN THIS PARTICULAR TRADE.
3. PROVIDE SPRINKLER SYSTEM TO NFPA 13 SPECIFIC HAZARD OCCUPANCY
REQUIREMENTS. ANY DEVIATIONS THEREFROM MAY BE MADE AS REQUIRED BY
INSPECTION AGENCIES, INSURING AGENCIES OR AS REQUIRED DUE TO INTERFERENCE
WITH OTHER EQUIPMENT, STRUCTURAL MEMBERS, DUCTS, ETC. PROVIDE ADDITIONAL
HEADS AS MAY BE REQUIRED FOR AN APPROVED SYSTEM.
4. RESPONSIBILITY FOR ELEVATIONS OF PIPING:
A. CAREFULLY FIELD CHECK THE ELEVATIONS OF EXISTING GRADES AND BURIED
SERVICE LINES AND MAKE A CAREFUL LAYOUT OF THE PROPOSED NEW
SERVICES BEFORE STARTING WITH THE WORK, MAKING EVERY ATTEMPT TO AVOID
INTERFERENCES.
B. ATTEN11ON IS CALLED TO DUCTWORK, HEATING AND COOLING PIPING, WATER
AND DRAIN PIPING, AND TO THE ELECTRICAL INSTALLATION, WHICH WILL BE
INSTALLED . BY OTHERS.
C. ANY DISCREPANCIES OR CONFLICTS DISCOVERED SHOULD BE REPORTED TO THE
ARCHITECT/ENGINEER, AND WORK SHALL NOT PROCEED UNTIL A SATISFACTORY
RESOLUTION IS FOUND. NO ADDITIONAL COMPENSATION WILL SUBSEQUENTLY BE
MADE TO THE CONTRACTOR BY THE OWNER TO COVER THE COST OF ANY SUCH
INTERFERENCES, WHETHER DUE TO NEGLIGENCE, ERROR, OVERSIGHT OR OTHER
CAUSE IN NOT HAVING PROPERLY ESTABLISHED THE ELEVATIONS OF ALL NEW
OR EXISTING PIPING, ETC.
5. PIPING SHALL BE CONCEALED IN AREAS WITH CEILINGS AND EXPOSED IN AREAS
WITHOUT CEILINGS.
6. PIPING SHALL BE INSTALLED AND SUPPORTED PER NFPA 13.
7. SLOPE PIPING IN ACCORDANCE WITH NFPA REQUIREMENTS.
8. PROVIDE DRAINS AT RISERS, ON VALVED SECTIONS, AT SIAMESE CONNECTIONS AND
AT OTHER LOCA11ONS REQUIRING SAME FOR COMPLETE DRAINAGE OF SYSTEMS.
PIPE DRAINS TO OUTSIDE OF BUILDING OR AS APPROVED.
9. WALL PENETRATIONS THROUGH FIRE RATED PARTITIONS SHALL BE SEALED WITH
PRO -SET "FIRE STOP COUPLING" SYSTEM OR WITH GEDNEY TYPE CFS1 FIRE SEAL OR
EQUAL. SPACE BETWEEN SLEEVE AND WALL TO BE COMPLETELY SEALED WITH
CAULKING. VOID BETWEEN SLEEVE PLUGS TO BE FILLED WITH INSULATION.
CODES AND STANDARDS:
ALL FIRE PROTECTION WORK SHALL BE IN STRICT COMPLIANCE WITH THE 2007 FLORIDA
BUILDING CODE, 2007 FLORIDA FIRE PREVENTION CODE AND NFPA 13 (2002 EDITION).
THE CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS, INSPECTIONS AND PAY ALL
FEES.
SYSTEM DESCRIPTION:
CONTRACTOR SHALL REVISE EXISTING SPRINKLER SYSTEM AS REQUIRED FOR THE NEW
LAYOUT INCLUDING NEW PIPING FOR NEW OR RELOCATED SPRINKLER HEADS TO PROVIDE
FOR PROPER COVERAGE. ALL HEADS ARE TO BE CENTERED IN THE CEILING TILES.
DRAWINGS FOR APPROVALS:
BEFORE PROCEEDING WITH WORK, THE CONTRACTOR IS TO PERFORM SYSTEM HYDRAULIC
CALCULATION, SYSTEM LAYOUTS AND SUBMIT SHOP DRAWINGS FIRST TO THE AUTHORITY
HAVING JURISDICTION, AND THEN TO THE ARCHITECT/ENGINEER FOR REVIEW.
SUBMITTALS SHALL SHOW LOCATIONS OF PIPING, SPRINKLER HEADS, ETC., AND SHALL
INCLUDE INFORMATION ON VALVES, SPRINKLER HEADS, ALARM VALVES, ETC. AT
LEAST TWO (2) SETS OF THE SHOP DRAWINGS SHALL BEAR THE APPROVAL STAMP OF
THE LOCAL FIRE MARSHALL.
EQUIPMENT AND MATERIALS:
ALL DEVICES, EQUIPMENT AND MATERIALS SHALL BE NEW, SHALL BE IN ACCORDANCE
WITH NFPA REQUIREMENTS AND SHALL BEAR FACTORY MUTUAL AND THE
UNDERWRITER'S LABEL OF APPROVAL.
ABOVE GROUND PIPE AND FITTINGS: PIPE ABOVE GROUND AND WITHIN THE BUILDING
SHALL BE STANDARD WEIGHT, SCHEDULE 40 BLACK STEEL PIPE OR APPROVED
SEAMLESS THIN WALL BLACK STEEL PIPE CONFORMING TO ASTM A53. PIPE FITTINGS
SHALL BE OF A TYPE APPROVED FOR SPRINKLER SYSTEMS AND DESIGNED FOR 175 PSI
WORKING PRESSURE. MALLEABLE IRON STANDARD WEIGHT FITTINGS WILL BE
ACCEPTABLE IN SIZES UP TO 6". MECHANICAL PIPE COUPLINGS (ROLLED OR CUT
GROOVED) MAY BE USED WHERE ALLOWED BY AUTHORITY HAVING JURISDICTION.
UNDERGROUND PIPE AND FITTINGS: UNDERGROUND PIPE SHALL BE CLASS 150 PVC
TYPE "BLUE BRUTE" AWWA C-900, UL AND FM LISTED WITH M.J. FITTINGS. FLUSH
UNDERGROUND PIPE PRIOR TO CONNECTION TO INSIDE PIPING.
SECTIONS OF CROSS MAINS, RISERS AND FEED MAINS MAY BE SHOP WELDED. WELDED
FITTINGS SHALL COMPLY WITH ANSI STANDARD #B-16.9-1971. WELDING SHALL BE
DONE IN ACCORDANCE WITH METHODS SET FORTH IN THE ANSI STANDARD B31.10-1067
AND APPLICABLE ADDENDA.
INTERIOR VALVES: 2-1/2" AND LARGER SHALL BE OS AND Y, FLANGED, IBBM GATE
VALVES. 2" AND SMALLER SHALL BE THREADED, BRONZE GATE VALVES. ALL VALVES
DESIGNED FOR 175 PSI WWP. LISTED GROOVED OR BUTTERFLY VALVES ARE
ACCEPTABLE.
SPRINKLER HEADS: NEW SPRINKLER HEADS SHALL MATCH BUILDING STANDARDS. IF
BUILDING STANDARD SPRINKLER HEADS ARE NO LONGER AVAILABLE, REPLACE ALL
EXISTING HEADS AS FOLLOWS; FOR FINISHED AREAS SPRINKLER HEAD SHALL BE A
VIKING MICROFAST MODEL M QUICK RESPONSE PENDENT, 1/2" ORIFICE, CHROME FINISH,
WITH VIKING MICROMATIC MODEL E-1 RECESSED ESCUTCHEON. FOR ALL EXPOSED
UNFINISHED AREAS SPRINKLER HEAD SHALL BE A VIKING MICROFAST MODEL M QUICK
RESPONSE UPRIGHT, 1/2" ORIFICE, BRASS FINISH. CONCEALED SPRINKER HEADS SHALL
BE VIKING, 5.6K, 1/2" ORIFICE, COLOR BY ARCHITECT. PROVIDE CONCEALED HEAD WITH
PLATE.
PROVIDE BUILDING MANAGEMENT WITH EXTRA STOCK OF NEW SPRINKLER HEADS AS
REQUIRED BY NFPA 13 (2002 ED.). RELIABLE AND TYCO ARE EQUAL
GENERAL SHEET NOTES
1. BUILDING IS EXISTING AND FULLY SPRINKLERED.
2. FIRE PROTECTION CONTRACTOR SHALL ACCOUNT FOR ANY CROSSMAINS OR BRANCH LINES
THAT NEED TO BE MODIFIED, RELOCATED OR ADJUSTED FOR ELEVATIONS DUE TO NEW
CEILING LAYOUT.
3. CONTRACTOR SHALL VISIT THE SITE AND SHALL BE FAMILIAR WITH THE COMPLETE SCOPE
OF WORK PRIOR TO BIDDING ON THIS PROJECT.
4. WHERE CEILING ELEVATION CHANGES OCCUR, CONTRACTOR SHALL SPACE SPRINKLER
HEADS FOLLOWING OBSTRUCTION RULES PER NFPA 13.
5. CONTRACTOR SHALL EXTEND A SWING JOINT OR ARM -OVER TO NEW PENDENT SPRINKLER
HEADS' LOCATION FROM EXISTING "TEES" FEEDING SPRIGS OR DROPS OF EXISTING
UPRIGHT/PENDENT HEADS. IF THESE METHODS ARE NOT FEASIBLE, CONTRACTOR SHALL
CAP THE TEE, ABANDON THE SUPPLY ABOVE THE CEILING SPACE AND PROVIDE A NEW
TAP INTO THE EXISTING BRANCH LINE AS REQUIRED.
6. IF NEW BRANCHLINES ARE REQUIRED, CONTRACTOR SHALL BASE SIZING OF NEW PIPING
ON EXISTING BRANCHLINE SIZES AND THE NUMBER OF SPRINKLER HEADS THEY FEED.
7. ALL SPRINKLER HEADS SHALL BE CENTERED IN THE MIDDLE OF CEILING TILES.
8. CONTRACTOR SHALL COORDINATE FINAL COLOR SELEC11ON OF SPRINKLER HEADS WITH
ARCHITECT PRIOR TO BUYING ITEMS.
PAINTING AND STENCILING:
PROVIDE PAINTING AND STENCILING OF ALL EXPOSED PIPING, EQUIPMENT, ETC.
INSTALLED AS PART OF THIS CONTRACT.
TEST OF COMPLETED SYSTEM:
ABOVE GROUND PIPING: PERFORM A HYDROSTATIC TEST OF THE PIPING SYSTEM IN
ACCORDANCE WITH THE REQUIREMENTS OF NFPA 13 (2002 ED.).
NOTIFY THE ARCHITECT/ENGINEER/OWNER/ UNDERWRITER PRIOR TO PERFORMING THE
TEST WHO, AT THEIR OPTION, MAY DESIRE TO WITNESS THE TEST. TEST SHALL BE
SATISFACTORY TO THE ARCHITECT, ENGINEER, OWNER, UNDERWRITER OR AUTHORITIES
HAVING JURISDICTION.
IF TEST PROVES UNSATISFACTORY, LEAKS SHALL BE REPAIRED AND A NEW TEST SHALL
BE PERFORMED. NO BACK FILLING SHALL BE DONE OVER BURIED JOINTS UNTIL PIPE
HAS BEEN PROVEN WATER TIGHT. SECURE PIPING IN PLACE PRIOR TO TESTING.
AFTER TESTING HAS BEEN COMPLETED, ALL VALVES SHALL BE LEFT IN THEIR
RESPECTIVE NORMAL POSITIONS, AND THE OWNER AND HIS DULY APPOINTED
REPRESENTATIVE SHALL BE INSTRUCTED IN THE CARE, OPERATION AND MAINTENANCE
OF THE ENTIRE SYSTEM.
MATERIAL AND TEST CERTIFICATE SHALL BE COMPLETED AND TURNED OVER TO THE
OWNER'S REPRESENTATIVE UPON COMPLETING THE TEST.
CHLORINATION:
ARRANGE FOR CHLORINATION OF THE SERVICE ENTRANCE PIPING FROM POINT OF
CONNECTION TO THE MUNICIPAL WATER MAIN UP TO AND INCLUDING THE FLANGE AND
SPIGOT INSIDE THE BUILDING.
PAY FOR ALL COSTS ASSOCIATED WITH CHLORINATING THE PIPING SYSTEM.
THE SYSTEM SHALL BE TESTED IN ACCORDANCE WITH AWWA C-651 OR C-652
STANDARD PROCEDURE FOR DISINFECTING WATER MAINS AND LOCAL CODES AND
ORDINANCES AND SHALL NOT BE CONNECTED TO THE MUNICIPAL WATER SYSTEM UNTIL
PROVEN SAFE. DELIVER CHLORINATION CERTIFICATION TO THE OWNER AND OR THE
MUNICIPAL WATER DEPARTMENT THAT THE SYSTEM HAS BEEN PROVEN SAFE.
WATER SUPPLY TREATMENT:
WATER SUPPLIES AND ENVIRONMENTAL CONDITIONS SHALL BE EVALUATED BY
OWNER FOR THE EXISTENCE OF MICROBES AND CONDITIONS THAT CONTRIBUTE TO
MICROBIOLOGICALLY INFLUENCED CORROSION (MIC). WHERE CONDITIONS ARE FOUND
THAT CONTRIBUTE TO MIC, THE OWNER SHALL NOTIFY THE SPRINKLER CONTRACTOR
AND A PLAN SHALL BE DEVELOPED TO TREAT THE SYSTEM USING ONE OF THE
METHODS AS ESTABLISHED UNDER NFPA 13 (2002 ED.).
FIRE PROTECTION GENERAL NOTES
ALL PIPING TO BE TESTED AT 200 PSI FOR A MINIMUM OF 2 HOURS.
HYDRAULIC CALCULATIONS DESIGN CRITERIA:
SUPPORT AREAS:
A. ORDINARY HAZARD GROUP I
B. SYSTEM TYPE: WET SYSTEM
C. DENSITY: 0.15 GPM/SQ. FT FOR 1500 SQ. FT.
D. COVERAGE PER SPRINKLER: 130 SQ. FT. MAXIMUM
E. TEMPERATURE RATING: ORDINARY TEMPERATURE
F. MAXIMUM SPRINKLER SPACING: 15-0"
RETAIL / OFFICES / HALLWAYS:
A. LIGHT HAZARD OCCUPANCY
B. SYSTEM TYPE: WET SYSTEM
C. DENSITY: 0.10 GPM/SQ. FT. FOR 1500 SQ. FT.
D. COVERAGE PER SPRINKLER: 225 SQ. FT. MAXIMUM
E. TEMPERATURE RATING: ORDINARY TEMPERATURE
F. MAXIMUM SPRINKLER SPACING: 15 -0 -
SPRINKLER INSTALLATIONS SHALL BE IN STRICT ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA) 13 SPRINKLER SYSTEMS, FIRE MARSHALS OFFICE,
OWNERS INSURANCE CARRIER, ALL LOCAL, STATE, FEDERAL CODES AND REGULATIONS AND
ANY OTHER AUTHORITIES HAVING JURISDICTION OVER THIS PROJECT.
ALL PERMITS REQUIRED IN CONNECTION WITH THIS SPRINKLER SYSTEM SHALL BE
OBTAINED AND PAID FOR BY THE SPRINKLER CONTRACTOR.
COORDINATE ALL PIPE ROUTING WITH ALL OTHER TRADES TO AVOID DUCTWORK, LIGHTING,
PIPING AND ANY BUILDING STRUCTURE. ROUTE ALL PIPING CONCEALED ABOVE CEILING,
WITHIN CHASES OR CONCEALED WITHIN WALLS.
FIRE PROTECTION CONTRACTOR SHALL THOROUGHLY INVESTIGATE THE SITE BEFORE
BIDDING. NO CHANGES SHALL BE ALLOWED IN CONTRACT PRICE FOR WORK REQUIRED TO
COMPLY WITH EXISTING CONDITIONS.
ALL EQUIPMENT SHALL BE UL AND FM LISTED AND LABELED. MANUFACTURER SHALL BE
EQUAL TO GRINNEL, VIKING.
BRANCH LINES PIPING TO BE SCHEDULE 40 BLACK STEEL PIPE JOINED WITH THREADED
OUTLET FITTINGS.
ALL SPRINKLER DROPS TO BE 1" SCHEDULE 40 WITH 1" X 1/2- THREADED REDUCER.
HANGERS TO BE SIZED AND SPACED IN ACCORDANCE WITH NFPA 13.
PROJECT SPECIFICATIONS TAKE PRECEDENCE OVER PLANS.
APPROVAL FROM OWNER'S INSURANCE CARRIER IS CONTRACTOR'S RESPONSIBILITY.
CONTRACTOR TO BASE ALL CALCULATIONS UPON CURRENT FLOW TEST SUPPLIED BY FIRE
SPRINKLER CONTRACTOR.
ALL SPRINKLER HEADS TO BE OF THE QUICK RESPONSE TYPE IN LIGHT HAZARD
OCCUPANCIES INSTALLED IN FULL ACCORDANCE WITH MANUFACTURER'S GUIDELINES (REFER
TO FIRE SPRINKLER LEGEND).
ALL SPRINKLER HEADS IN MECHANICAL/ELECTRICAL ROOMS TO BE STANDARD RESPONSE,
212'F.
THESE PLANS ARE CONCEPTUAL IN NATURE PER FLORIDA STATUTE 61G15-30.
SELECTIVE KEYNOTES D
L�
CFRH m L & D
Sanford, Florida
PENINSULA ENGINEERING INC.
CONSULTING ENGINEERS
ESTABLISHED IN 1977 eight
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 • 407.246.1688 • EB 3089
Copyright — All ideas, designs, methods on4 plans Indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and JOB#:
developed for use on and in connection with the specified project. None of the ideas, designs,
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
PERMIT SET
2010m038
09-10-2010 GJG JAM
issue date drawn by approved by project number
REVISION SCHEDULE
a DATE DESCRIPTION
RENOVATION PLAN F P 1
FIRE PROTECTION
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
``t%jiIIIIIII,/
OEfkT O A4 ��i
�ti. •'�G E N SF'• • Gtr`
13
No
-o
5T OF =
2�
1:101i is r E,
13 BURKE HQGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL
32746
407.333.2005 AAC000233
W
B H M U 5
LJJ
U
FIRE SPRINKLER LEGEND
SYMBOL
DESCRIPTION
EXISTING SPRINKLER HEAD LOCATION (WET SYSTEM) TO BE RELOCATED.
R
EXTEND NEW 1"0 SUPPLY TO NEW QUICK RESPONSE SPRINKLER HEAD
LOCATION.
EXISTING SEMI -RECESSED PENDENT SPRINKLER HEAD TO REMAIN.
EXISTING SPRINKLER HEAD TO BE REMOVED. CAP AND ABANDON SUPPLY
ABOVE CEILING.
NOTE:
FIRE SPRINKLER
CONTRACTOR SHALL PROVIDE TEMPORARY QUICK
RESPONSE
SPRINKLER HEADS FOR AREAS THAT MAY BE LEFT WITHOUT
ADEQUATE
PROTECTION DUE TO PHASING OF CONSTRUCTION OR DUE TO
THE LOCATION OF TEMPORARY WALLS.
SELECTIVE KEYNOTES D
L�
CFRH m L & D
Sanford, Florida
PENINSULA ENGINEERING INC.
CONSULTING ENGINEERS
ESTABLISHED IN 1977 eight
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 • 407.246.1688 • EB 3089
Copyright — All ideas, designs, methods on4 plans Indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and JOB#:
developed for use on and in connection with the specified project. None of the ideas, designs,
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
PERMIT SET
2010m038
09-10-2010 GJG JAM
issue date drawn by approved by project number
REVISION SCHEDULE
a DATE DESCRIPTION
RENOVATION PLAN F P 1
FIRE PROTECTION
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
``t%jiIIIIIII,/
OEfkT O A4 ��i
�ti. •'�G E N SF'• • Gtr`
13
No
-o
5T OF =
2�
1:101i is r E,
13 BURKE HQGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL
32746
407.333.2005 AAC000233
W
B H M U 5
LJJ
U
PLUMBING SPECIFICATIONS
SCOPE OF WORK
WORK SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING:
PROVIDE ALL LABOR, MATERIALS, SERVICES, EQUIPMENT AND APPLIANCES
REQUIRED FOR THE FABRICATION AND INSTALLATION OF THE PLUMBING SYSTEM,
AS INDICATED ON THE DESIGN DRAWINGS AND AS OUTLINED IN THESE
SPECIFICATIONS.
RELATED WORK SPECIFIED ELSEWHERE
REFER TO ELECTRICAL SPECIFICATION (DIV. 16) FOR ELECTRICAL WORK TO BE
DONE IN CONJUNCTION WITH THE PLUMBING WORK. THIS CONTRACTOR IS
RESPONSIBLE FOR ALL CONDUIT, WIRING, JUNCTION BOXES, ETC.
SUBSTITUTIONS
EQUIPMENT AND DESIGN OF SYSTEMS INDICATED ON THE DESIGN DRAWINGS
AND WITHIN THESE SPECIFICATIONS SHALL BE CONSIDERED AS "SPECIFIED
STANDARD" OF QUALITY. NO SUBSTITUTIONS SHALL BE MADE WITHOUT PRIOR
WRITTEN APPROVAL OF THE ENGINEER.
CODES AND STANDARDS
THE ENTIRE SYSTEM AND ALL COMPONENTS LISTED HEREIN SHALL MEET ALL
STATE, COUNTY, AND LOCAL CODES AND ORDINANCES IN EVERY RESPECT.
THE CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS, INSPECTIONS AND
PAY ALL FEES.
PRODUCTS
ALL EQUIPMENT, ETC., SHALL BE NEW UNLESS OTHERWISE NOTED, AND AS
SPECIFIED FREE OF DEFECTS AS SHOWN ON THE DRAWINGS AND AS INDICATED
IN THESE SPECIFICATIONS. ALL ELECTRICAL POWERED EQUIPMENT SHALL BE
U.L. OR E.T.L. LISTED.
WORKMANSHIP
ALL MATERIALS SHALL BE FABRICATED AND INSTALLED IN A NEAT AND
PROFESSIONAL MANNER WITH THE COORDINATION OF ALL INVOLVED TRADES TO
AVOID INTERFERENCES AND DELAY DUE TO LACK OF COORDINATION. NO
ALLOWANCES WILL BE MADE FOR REWORK DUE TO COORDINATION DIFFICULTIES
OR INTERFERENCES BETWEEN INVOLVED TRADES.
SHOP DRAWINGS AND SUBMITTALS
SUBMIT FOR ENGINEER'S APPROVAL, SHOP DRAWINGS, AND MANUFACTURER'S
DATA FOR ALL NEW EQUIPMENT AND FIXTURES PRIOR TO PURCHASE AND OR
FABRICATION. SHOP DRAWINGS FOR EQUIPMENT REQUIRING ELECTRIC POWER OR
CONTROL WIRING CONNECTIONS SHALL INCLUDE COMPLETE WIRING DIAGRAMS
AS-BUILTS CONTRACTOR SHALL PROVIDE THE ENGINEER TWO (2) SETS OF
COMPLETE PLUMBING AS -BUILT DRAWINGS AT THE TIME OF SUBSTANTIAL
COMPLETION. AS BUILTS SHALL BE PROVIDED ON REPRODUCIBLE VELLUM AND
AUTOCAD DRAWING FILES [RELEASE 2007 OR LATER]. AS -BUILT DRAWINGS
SHALL CONSIST OF AN ACCURATE "AS -BUILT" RECORD OF THE INSTALLED
WORK. PROJECT WILL NOT BE COMPLETE UNTIL ACCURATE AS-BUILTS ARE
DELIVERED.
ACCESS PANELS
CONTRACTOR SHALL PROVIDE HINGED ACCESS DOORS (MIN. 12"X12") FOR
VALVES, ETC. WHERE FLOORS, WALLS, AND CEILINGS MUST BE
PENETRATED TO ACCESS MECHANICAL SYSTEMS. FINISH SHALL BE
COORDINATED THROUGH ARCHITECT TO MATCH SURROUNDING FINISHES.
EXECUTION
ALL LOCATIONS OF EQUIPMENT, PIPING, ETC., INDICATED ON THE DRAWINGS IS
DIAGRAMMATIC AND SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE TO THE
PLANS SUBJECT TO BUILDING CONSTRUCTION AND INTERFERENCES WITH OTHER
TRADES. ALL WORK SHALL BE INSTALLED TO INSURE MAXIMUM HEADROOM,
BALANCED OPERATION AND SUITABLE AESTHETIC APPEARANCE. CONTRACTOR
IS RESPONSIBLE FOR ANY FIELD MEASUREMENTS REQUIRED TO PROVIDE AN
APPROVED AND FUNCTIONAL INSTALLATION.
NOT ALL COMPONENTS REQUIRED FOR A COMPLETE INSTALLATION ARE SHOWN
ON THESE DRAWINGS. REFER TO EQUIPMENT INSTALLATION INSTRUCTION,
SCHEDULES AND APPLICABLE CODES FOR ADDITIONAL INFORMATION, INCLUDING
REQUIRED CONNECTION LOCATIONS, TYPES AND SIZES.
PROVIDE ISOLATION VALVES AND UNIONS AT ALL EQUIPMENT AND AS
INDICATED ON DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING AND INSTALLING
ADEQUATE AND PROPER INSULATION AND MOISTURE -SEAL IN A MANNER THAT
WILL PERMANENTLY PREVENT THE ACCUMULATION OF ANY OBJECTIONABLE
MOISTURE ON THE EXTERIOR OF CONDENSATE DRAIN PIPING, OR OTHER PARTS
OF THE SYSTEM. HE SHALL CORRECT THE CAUSE OF ANY CONDENSATION AND
FULLY REPAIR, WITHOUT COST TO THE OWNER, ANY DAMAGES TO BUILDING
SURFACES, FURNISHINGS OR EQUIPMENT CAUSED BY CONDENSATION FROM
THIS SYSTEM, FOR THE FULL PERIOD OF THE GUARANTEE.
PERFORM ALL WORK NECESSARY TO PREPARE THE STRUCTURE FOR THE
INSTALLATION OF THE WORK.
ALL HOLES, OPENINGS AND DAMAGED MATERIALS CREATED DURING
CONSTRUCTION SHALL BE REPAIRED AND FINISHED BY EXPERIENCED WORKMEN.
PROVIDE ALL ROOF, WALL AND FLOOR PENETRATIONS REQUIRED TO COMPLETE
INSTALLATION OF WORK (MAINTAIN FIRE RATING OF EXISTING STRUCTURE). ALL
PENETRATIONS SHALL BE PATCHED AND FINISHED TO MATCH SURROUNDING
SURFACES AND FINISHES. ALL EQUIPMENT OR PIPE PENETRATIONS THROUGH
WALL, ROOF AND FLOORS SHALL BE SLEEVED AND SEALED SO AS TO BE
WATER AND AIR TIGHT.
ALL ROOF CUTS AND REPAIRS SHALL BE PERFORMED BY AN APPROVED
ROOFING CONTRACTOR IN ORDER TO MAINTAIN ROOF WARRANTY.
CLEANING, TESTING AND ADJUSTING:
THE CONTRACTOR, AT HIS EXPENSE, SHALL CLEAN, REPAIR, ADJUST, CHECK,
BALANCE, AND PLACE IN SERVICE THE VARIOUS SYSTEMS
HEREIN SPECIFIED WITH THEIR RESPECTIVE EQUIPMENT, ACCESSORIES AND
PIPING. HE SHALL FURNISH ALL LABOR, MATERIALS, EQUIPMENT, AND TOOLS
REQUIRED TO PERFORM TESTS REQUIRED BY THESE SPECIFICATIONS AND BY
THE GOVERNING AUTHORITIES.
NO WORK SHALL BE COVERED OR CONCEALED UNTIL PROPERLY INSPECTED
AND TESTED.
EXCAVATION AND BACKFILL:
PROVIDE ALL EXCAVATION AND TRENCHING TO THE CORRECT ELEVATIONS, FOR
THE INSTALLATION OF ALL PIPING. PROVIDE ALL BACKFILL IN STRICT
ACCORDANCE WITH THE EXCAVATION AND
BACKFILL SECTION OF DIVISION 1 SPECIFICATIONS.
TESTING:
ALL DOMESTIC WATER PIPING SYSTEMS SHALL BE TESTED FOR ABSOLUTE
TIGHTNESS BY SUBJECTING THE SYSTEM TO A HYDROSTATIC PRESSURE OF 150
PSI GAUGE OR 50 PSI OVER WORKING PRESSURE, WHICHEVER IS GREATER FOR A
PERIOD OF NOT LESS THAN EIGHT (8) HOURS. ALL LEAKS SHALL BE REPAIRED
AND THE HYDROSTATIC TEST REAPPLIED UNTIL, FOR AN EIGHT (8) HOUR PERIOD,
NO LEAKS CAN BE FOUND WHILE THE SYSTEM IS SUBJECT TO THE TEST
PRESSURE.
SOIL PIPE AND CONDENSATE DRAINS SHALL BE TESTED BY TEMPORARILY
PLUGGING ALL OUTLETS AND FILLING THE SYSTEM WITH WATER TO THE LEVEL OF
THE HIGHEST VENT STACK. THE SYSTEM MUST BE INSPECTED AND ALL LEAKS
REPAIRED AND THE TEST REPEATED UN11L THE WATER LEVEL DOES NOT
DECREASE FOR A PERIOD OF 24 HOURS.
MAINTENANCE MANUALS
PROVIDE COMPLETE MAINTENANCE MANUALS (3 REQUIRED) ON ALL NEW
EQUIPMENT. ORGANIZE OPERATING AND MAINTENANCE DATA INTO SUITABLE
SETS OF MANAGEABLE SIZE. BIND PROPERLY INDEXED DATA IN INDIVIDUAL,
HEAVY-DUTY, 2 -INCH, 3 -RING VINYL -COVERED BINDERS WITH POCKET FOLDERS
FOR FOLDED SHEET INFORMATION. MARK APPROPRIATE IDENTIFICATION ON
FRONT AND SPINE OF EACH BINDER. INCLUDE THE FOLLOWING TYPE OF
INFORMATION. THE INFORMATION WILL BE TURNED OVER TO THE OWNER AT TIME
OF SUBSTANTIAL COMPLETION:
- OPERATING AND MAINTENANCE INSTRUCTIONS
- SPARE PARTS LIST
- COPIES OF WARRANTIES
- WIRING DIAGRAMS
- INSPECTION REPORTS & APPROVALS
- SHOP DRAWINGS AND PRODUCT DATA
TRAINING SERVICES
THOROUGHLY INSTRUCT THE OWNER'S REPRESENTATIVE IN THE OPERATION OF
ALL EQUIPMENT FURNISHED AND LOCATION OF ALL VALVES AND CONTROL
DEVICES.
TRAIN BUILDING OWNER'S PERSONNEL DURING NORMAL WORKING HOURS ON
START-UP AND SHUT -DOWN PROCEDURES, TROUBLESHOOTING PROCEDURES,
SERVICING AND PREVENTATIVE MAINTENANCE SCHEDULE AND PROCEDURES.
REVIEW WITH THE OWNER'S PERSONNEL, THE DATA CONTAINED IN THE
OPERATING AND MAINTENANCE MANUALS. SCHEDULE TRAINING WITH OWNER,
PROVIDE AT LEAST 7 -DAYS PRIOR NOTICE TO ARCHITECT/ENGINEER.
SYSTEM IDENTIFICATION
PROVIDE IDENTIFICATION LABELS ON OR NEAR EACH PIECE OF MAJOR
EQUIPMENT AND EACH OPERATIONAL DEVICE AND DISCONNECT. THE LABELS
SHALL BE CONSTRUCTED OF ENGRAVED PLASTIC LAMINATE SIGN OR PLASTIC
EQUIPMENT MARKER PERMANENTLY SECURED TO EQUIPMENT. THE LETTERING
SHALL BE A MINIMUM OF 1/2 INCH HIGH FOR EQUIPMENT NAME AND 3/8 INCH
FOR EQUIPMENT INFORMATION.
HANGERS AND SUPPORTS
PROVIDE ALL NECESSARY, PIPE SUPPORTS, HANGER, RODS, CLAMPS AND
ATTACHMENTS TO PROPERLY INSTALL AND SUPPORT PIPING AND EQUIPMENT
FROM THE BUILDING STRUCTURE.
PROVIDE ANY ANGLE IRON OR UNISTRUT AND SUSPENSION RODS REQUIRED TO
INSTALL EQUIPMENT, PIPING AND DUCTWORK.
ALL SUPPORTS EXPOSED TO OUTDOORS SHALL BE CLEANED, PRIMED AND
PAINTED TO PREVENT RUSTING. FINISH COLOR AS SELECTED BY OWNER.
THE USE OF BALING WIRE OR PERFORATED METAL STRAPPING IS NOT
ACCEPTABLE FOR SUPPORTS.
WARRANTY/GUARANTEE:
THE CONTRACTOR SHALL WARRANTY/GUARANTEE AND MAINTAIN THE
STABILITY OF WORK AND MATERIALS AND KEEP SAME IN PERFECT REPAIR AND
CONDITION OF THE PERIOD OF ONE (1) YEAR. DEFECTS OF ANY KIND DUE TO
FAULTY WORK OR MATERIALS APPEARING DURING THE ABOVE MENTIONED PERIOD
MUST BE IMMEDIATELY MADE GOOD BY THE CONTRACTOR AT HIS OWN EXPENSE
TO THE ENTIRE SATISFAC11ON OF THE OWNER AND ARCHITECT AND ENGINEER.
SUCH RECONSTRUCTION AND REPAIRS SHALL INCLUDE ALL DAMAGE TO THE
FINISH OR FURNISHING OF THE BUILDING RESULTING FROM THE ORIGINAL
DEFECT OR REPAIRS THERETO.
WATER SUPPLY SYSTEM:
EXTEND WATER SERVICE AS INDICATED ON DESIGN DRAWINGS.
PROVIDE SHOCK ABSORBERS AND VACUUM BREAKERS WHERE REQUIRED.
PIPE AND FITTINGS ABOVE GROUND - TYPE L HARD COPPER AND WROUGHT
COPPER FITTINGS.
PIPE AND FITTINGS BELOW GROUND - TYPE "K" SOFT COPPER.
VALVES - BALL VALVES - ALL BRONZE, RISING STEM, DOUBLE WEDGE TAPER
SEAT, 125 PSI STEAM PRESSURE.
CHLORINATION - BEFORE BEING PLACED IN SERVICE ALL WATER DISTRIBUTION
SYSTEMS SHALL BE STERILIZED WITH CHLORINE IN ACCORDANCE WITH AWWA
C-601-54 STANDARD PROCEDURE FOR DISINFECTING WATER MAINS.
INSULATE HOT WATER LINES WITH 1" RUBATEX INSULATION OR EQUAL.
INSULATION TO BE FIRE RATED FOR USE IN RETURN AIR PLENUM.
CONNECTIONS TO MISCELLANEOUS EQUIPMENT -
ROUGH -IN AND CONNECT WATER, WASTE, AND VENT TO COMPLETE THE
INSTALLATION OF EQUIPMENT LISTED ON THE DRAWINGS.
PLUMBING FIXTURES SHALL BE PROVIDED COMPLETE AS SHOWN ON THE
DRAWINGS WITH ALL REQUIRED SUPPLY, WASTE, SOIL, AND VENT
CONNECTIONS, TOGETHER WITH ALL FITTINGS, SUPPORTS, FASTENING DEVICES,
COCKS, VALVES, AND TRAPS.
ALL FIXTURES SHALL HAVE STOP VALVES ON ALL WATER CONNECTIONS.
ALL EXPOSED METAL TRIM ON ALL FIXTURES SHALL BE POLISHED CHROMIUM
PLATED. ALL EXPOSED PIPES EXTENDING FROM WALL SHALL HAVE CHROMIUM
PLATED BRASS ESCUTCHEON MOUNTED AGAINST WALL. EXPOSED PVC PIPING
AND P -TRAPS ARE UNACCEPTABLE.
THE PLUMBING FIXTURES SHALL BE ROUGHED -IN ACCORDANCE WITH
MANUFACTURER'S "ROUGH -IN INFORMATION". PROVISIONS FOR MOUNTING WALL
FIXTURES SHALL BE MADE WHILE THE WALL IS BEING BUILT.
DRAINAGE SYSTEM:
EXTEND PIPING AS INDICATED ON THE DRAWINGS.
PIPE SLOPE:
2-1/2 INCH DIAMETER AND LESS SHALL BE INSTALLED WITH A FALL OF NOT
LESS THAN 1/4 INCH PER FOOT.
3 INCH DIAMETER OR LARGER SHALL BE INSTALLED WITH A FALL NOT LESS
THAN 1/8 INCH PER FOOT.
PIPE AND FITTINGS:
CAST IRON PIPE: ASTMa74 SERVICE WEIGHT HUB -AND -SPIGOT OR CISPI 301
SERVICE WEIGHT NO -HUB.
DRAIN, WASTE AND VENT PIPING LOCATED IN FIRE RATED WALL
ASSEMBLIES AND RETURN AIR PLENUMS SHALL BE SERVICE -WEIGHT CAST IRON
WITH NO/HUB OR BELL AND SPIGOT FITTINGS.
ALL CAST IRON SOIL PIPE AND FITTINGS SHALL BE MARKED WITH THE
COLLECTIVE TRADEMARK OF THE CAST IRON SOIL PIPE INSTITUTE (CISPI) AND
BE LISTED BY NSF INTERNATIONAL.
CONDENSATE DRAIN PIPING LOCATED ON THE EXTERIOR SHALL BE TYPE L HARD
COPPER AND WROUGHT COPPER FITTINGS, WITH SOLDERED JOINTS (USE ONLY
"LEAD FREE").
PROVIDE CLEANOUTS EVERY 75 FEET, AT CHANGES IN DIRECTION, AT BASE OF
DOWNSPOUTS AND AT BASE OF SOIL AND WASTE STACKS.
SHOCK ARRESTOR: SIOUX CHIEF PER DRAWINGS
WALL CLEANOUT: ZURN, JONESPEC, JOSAM OR EQUAL.
FLOOR CLEANOUT: ZURN, JONESPEC, JOSAM OR EQUAL.
PLUMBING FIXTURE SCHEDULE
PLAN DESCRIPTION MANUF. / MODEL No.
MARK
S-1 SINK: (SINGLE COMPARTMENT)
1. TYPE 302, 18-8 STAINLESS STEEL, SELF RIMMING SINGLE DAYTON D-11719
COMPARTMENT, 17x19x6 1/8 DEEP, PUNCHED FOR 3 HOLES,
TAILPIECE AND STAINLESS CUP STRAINER.
2. FITTING: CONCEALED BODY, ADJUSTABLE 8" CENTERS, SWIVEL CHICAGO FAUCET
GOOSENECK SPOUT, 4" WRIST BLADE HANDLES. ALL EXPOSED 786-GN2A-317,
PARTS POLISHED CHROMIUM PLATED FINISH. 1.6 G.P.M. INTEGRAL
FLOW CONTROL
3. TRAP: CAST BRASS ADJUSTABLE "P" TRAP WITH CLEANOUT. McGUIRE
4. SUPPLY. 3/8" ANGLE SUPPLY WITH PLASTIC VERTICAL TUBE, McGUIRE
WHEEL HANDLE STOPS AND ESCUTCHEON.
IM -1 ICE MAKER OUTLET BOX:
1 • RECESSED UNIT WITH ONE 1/2- VALVE (TOP SUPPLY) COLD OATEY 38681
WATER.
FD -1 FLOOR DRAIN WITH AUTOMATIC TRAP PRIMER:
1. DRAIN: CAST IRON BODY WITH BOTTOM OUTLET COMBINATION ZURN ZN-415-P
INVERTIBLE MEMBRANE CLAMP AND DEEP SEAL TRAP ADJUSTABLE
TYPE NICKEL CAST BRONZE STRAINER, TRAP PRIMER CONNECTION.
2. PRIMER: ALL BRONZE BODY WITH INTEGRAL OPERATION ASSEMBLY ZURN Z-1022
WITH GASKETED BRONZE COVER.
PLUMBING LEGEND
SYMBOL
ABBRV.
DESCRIPTION
SAN
SAN
SANITARY WASTE
GL
GL
GREASE LINE
SD
SD
STORM DRAIN
RWL
RWL
RAIN WATER LEADER
COND
COND
CONDENSATE DRAIN
-
CW
COLD WATER
- -
HW
HOT WATER
DIRECTION OF FLOW
----- V -----
V
VENT LINE
SII_
VTR
VENT THRU ROOF
oc
P -TRAP
®c
FD
FLOOR DRAIN
BALL VALVE (FULL PORT)
E
CAPPED PIPE
G
RISER DOWN (ELBOW)
0+--
RISER UP (ELBOW)
+
BRANCH - TOP CONNEC11ON
BRANCH - BOTTOM CONNEC11ON
.+.
BRANCH - SIDE CONNECTION
POINT OF CONNECTION
PLUMBING GENERAL NOTES
1. ALL PLUMBING INSTALLA11ONS AND MATERIALS SHALL BE IN STRICT
ACCORDANCE WITH ALL LOCAL, STATE AND FEDERAL CODES, LAWS,
ORDINANCES AND REGULATIONS OF ALL AUTHORITIES HAVING JURISDICTION
OVER THIS PROJECT.
2. PIPE ROUTING SHOWN ON THESE DRAWINGS IS SCHEMATIC AND IS NOT
INTENDED TO INDICATE EXACT ROUTING. PLUMBING CONTRACTOR SHALL
PROVIDE ANY ADDITIONAL OFFSETS AND FITTINGS REQUIRED FOR PROPER
INSTALLATION AND TO MAINTAIN PROPER CLEARANCES.
3. COORDINATE ALL PIPE ROUTING WITH ALL OTHER TRADES PRIOR TO
INSTALLATION. ROUTE ALL PIPING TO AVOID DUCTWORK, PIPING AND BUILDING
STRUCTURE.
4. SEE ARCHITECTURAL DRAWINGS FOR EXACT PLUMBING FIXTURE LOCATIONS AND
MOUNTING HEIGHTS FOR COMPLIANCE WITH FLORIDA BUILDING CODE
ACCESSIBILITY REQUIREMENTS. SINKS REQUIRED TO BE ACCESSIBLE SHALL BE
MOUNTED WITH COUNTER RIM NO HIGHER THAN 34 INCHES ABOVE FINISH
FLOOR. CONTROLS FOR FLUSH VALVES SHALL BE MOUNTED ON THE WIDE SIDE
OF THE TOILET AREAS NO MORE THAN 44 INCHES ABOVE THE FLOOR. FOR ALL
OTHER FIXTURE MOUNTING HEIGHTS SEE PLUMBING FIXTURE SCHEDULE.
5. ROUTE ALL PIPING CONCEALED ABOVE CEILING, WITHIN CHASES OR ABOVE
NON -ACCESSIBLE CEILINGS, REFER TO ARCHITECTURAL DRAWINGS FOR CEILING
TYPES.
6. ALL VALVES, WATER HAMMER ARRESTORS, CONTROLS AND CLEANOUTS
CONCEALED WITHIN CHASES OR ABOVE NON -ACCESSIBLE CEILINGS SHALL HAVE
24 in. X 24 in. METAL ACCESS PANELS UNLESS INDICATED OTHERWISE ON
DRAWINGS. PROVIDE UL 1 1/2 HOUR LABEL ACCESS PANELS IN 1 AND 2 HOUR
CONSTRUCTION.
7. INSTALL SHUTOFF VALVES ON ALL WATER LINES IN THE FOLLOWING LOCATIONS:
• ALL MAJOR BRANCH RUNS SUCH AS BRANCHES SERVING A FLOOR, WING,
OR A MAJOR SECTION OF BUILDING.
• ALL EQUIPMENT CONNECTIONS.
• OTHER LOCATIONS AS MAY BE INDICATED ON DRAWINGS.
8. INSTALL BALANCING VALVES AS INDICATED ON THE DRAWINGS AND AS
REQUIRED FOR PROPER BALANCING OF THE VARIOUS SYSTEM.
9. PLUMBING CONTRACTOR SHALL PROVIDE VALVE DIRECTORY WITH A TAG
SCHEDULE SHOWING LOCATION OF EACH VALVE, TYPE, NUMBER,
MANUFACTURER, FUNCTION AND ALL OPERATING POSITIONS.
10. PLUMBING CONTRACTOR SHALL PROVIDE SLEEVES FOR ALL PIPES PASSING
THROUGH FLOORS, WALLS AND CEILINGS. EXTEND SLEEVES 2" in. ABOVE
FLOORS. MAKE ALL SLEEVES FLUSH WITH WALLS AND CEILINGS. CONTRACTOR
SHALL FIRE STOP ALL PENETRATIONS OF RATED WALLS, CEILINGS, ETC.,
INCLUDING ROOF. FLASH AND COUNTER FLASH ALL ROOF PENETRATIONS.
11. PLUMBING CONTRACTOR SHALL PROVIDE CHROME PLATED HINGED ESCUTCHEON
WITH SET SCREWS AT EACH EXPOSED PIPE PASSING THROUGH A WALL, FLOOR
OR CEILING IN FINISHED PORTIONS OF THE BUILDINGS.
12. PLUMBING CONTRACTOR SHALL PROVIDE BELLOW TYPE WATER HAMMER
ARRESTORS ON ALL HOT AND COLD WATER LINES. INSTALL IN UPRIGHT
POSITION AT ALL QUICK CLOSING VALVES, SOLENOIDS, ISOLATED PLUMBING
FIXTURES AND SUPPLY HEADERS AT PLUMBING FIXTURE GROUPS. LOCATE AND
SIZE AS SPECIFIED OR AS SHOWN ON THE DRAWINGS AND WHERE NOT SHOWN,
LOCATE IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND
COMPLY WITH THE PLUMBING AND DRAINAGE INSTITUTE STANDARDS WH 201.
13. AT ADA FIXTURES WHERE SHOWN ON THE DRAWINGS, OR WHERE REQUIRED BY
GOVERNMENTAL AGENCIES HAVING JURISDICTIONS, PROVIDE
PER -MANUFACTURED INSULATION KITS ON THE SUPPLIES, TRAP AND DRAIN AT
LAVATORIES AND SINKS FOR HANDICAPPED PERSONS.
14. ALL VENTS THRU ROOF SHALL BE A MINIMUM OF TEN FEET (10'-0") FROM
ANY AIR INTAKE.
15. PLUMBING CONTRACTOR SHALL INSTALL DIELECTRIC UNIONS AT ALL
CONNECTIONS OF DISSIMILAR METALS.
16. ALL HOT WATER AND HOT WATER RETURN LINES SHALL BE INSULATED WITH 1"
WALL THICKNESS, PRE -SLIT, FLEXIBLE UNICELLULAR POLYOLEFIN FOAM PLENUM
RATED ARMAFLEX INSULATION.
17. PLUMBING CONTRACTOR SHALL THOROUGHLY INVESTIGATE THE SITE, CAREFULLY
STUDY THE PLUMBING DRAWINGS, AND BECOME THOROUGHLY FAMILIAR WITH
THE EXISTING CONDITIONS BEFORE BIDDING, NO CHANGES WILL BE ALLOWED IN
CONTRACT PRICE FOR EXTRA WORK CLAIMS BECAUSE CONTRACTOR FAILED TO
FOLLOW THESE DIRECTIONS.
18. EXISTING CONDITIONS AS SHOWN ON THESE DRAWINGS ARE TAKEN FROM
ORIGINAL AND AS-BUILTS DRAWINGS OF THE BUILDING. THESE DRAWINGS IN
PART ARE UNVERIFIED AND FIELD CONDITIONS SHALL GOVERN. FIELD VERIFY
EXISTING INSTALLATIONS OF ALL DESCRIPTION AND MODIFY EXISTING PLUMBING
SYSTEMS WHICH ARE TO REMAIN ACTIVE, TO FACILITATE RECONNECTION AND
EXTENSION UNDER NEW WORK. PROVIDE SHUT-OFF VALVES ON ALL PIPES AT
THE POINT OF TIE-IN TO EXISTING SYSTEM.
19. INTERRUPTION OF EXISTING SERVICES SHALL BE MINIMAL AND SHALL BE FULLY
COORDINATED WITH OWNER IN ADVANCE. PLUMBING CONTRACTOR SHALL SUBMIT
TIME THAT SERVICE WILL BE DOWN, AREA OF PIPING AND ANY EQUIPMENT
THAT WILL BE AFFECTED. SCHEDULE ANY INTERRUPTION DURING NON-CRITICAL
HOURS OR NOTIFY OWNER AT LEAST TWENTY-FOUR (24) HOURS PRIOR TO
INTERRUPTION. PUT INTERRUPTED SERVICES BACK INTO OPERATION AS SOON
AS IS PRACTICAL. NO SHUT DOWN CAN BE DONE WITHOUT THE OWNER'S
APPROVAL.
20. DURING THE PROGRESS OF WORK THE PLUMBING CONTRACTOR SHALL MAINTAIN
AN ACCURATE RECORD OF ALL CHANGES MADE TO THE PLUMBING SYSTEM.
THE RECORD DRAWINGS SHALL SHOW, CHANGES, DIMENSIONS AND LOCATIONS
OF ALL PIPING. CHANGES SHALL BE DONE IN AUTOCAD RELEASE 2007 OR
ABOVE AND SUBMITTED TO THE OWNER AND GENERAL CONTRACTOR AT FINAL
COMPLETION.
SELECTIVE KEYNOTES O
PENINSULA ENGINEERING INC"
CONSULTING ENGINEERS
ESTABLISHED IN 1977 0. 09ht
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 - 407.246.1688 • EB 3089 0.09
0
Copyright - All ideas, designs, methods and plans indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and
developed for use on and in connection with the specified project. None of the ideas, designs, JOB#:
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
GJG JHM
issue date drawn by approved by project number
REVISION SCHEDULE
DATE I DESCRIPTION
SPECIFICATIONS, SCHEDULES, P O .
NOTES REGEND • PLUMBING shee1
t number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
1111111t���,`
0ERTO
•��r✓ENSF•;pG
o.37313 •i �'
AT OF : or
FL d�q��� �� BURKE HOGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL
32746
407.333.2005 MC000233
.. r n RA
vv •r T v I . ... ...
PHASE 1 WORK NOTES N
NURSES'
NOURISH
DIR.
OFFICE
CO
Tt
fk
PLUMBING DEMOLITION NOTES
1. THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION OF
EXISTING PLUMBING SYSTEMS AS REQUIRED TO PERFORM NEW WORK. ALL
FIXTURES, PIPING TRIM AND MISCELLANEOUS DEBRIS SHALL BE TURNED OVER TO
OWNERS REPRESENTATIVE OR REMOVED FROM SITE AND PROPERLY DISPOSED OF
AT THE DIRECTION OF THE OWNER'S REPRESENTATIVE.
2. ALL PIPING FOR ITEMS TO BE REMOVED SHALL BE CAPPED IN A CONCEALED
LOCATION SUCH AS ABOVE CEILING AND BELOW FINISH FLOOR. PIPING SHALL BE
CAPPED IN APPROVED CAPPING METHODS UTILIZING PIPE CAPS INTENDED FOR
SUCH USE. ALL CAPS SHALL BE AIRTIGHT AND WATERTIGHT. EXISTING SANITARY
WASTE PIPING CAPPED BELOW SLAB SHALL NOT CREATE DEADENDS IN THIS
BUILDING DRAINAGE SYSTEM.
3. PLUMBING CONTRACTOR SHALL PROTECT THE STRUCTURE, FURNISHING, FINISHES
AND ADJACENT MATERIALS NOT INDICATED OR SCHEDULED TO BE REMOVED.
4. PIPING WHICH IS TO REMAIN IN SERVICE SHALL NOT BE DISTURBED. EXISTING
PIPING BROKEN DURING CONSTRUCTION SHALL BE REPLACED WITH NEW PIPING OF
THE SAME SIZE AND MATERIAL.
PLUMBING DEMOLITION NOTES
1Q EXISTING SINK TO BE REMOVED AND TURNED OVER TO OWNER'S
REPRESENTATIVE.
O2 EXISTING WATER CLOSET TO BE REMOVED AND TURNED OVER TO
OWNER'S REPRESENTATIVE,
O3 EXISTING LAVATORY TO BE REMOVED AND TURNED OVER TO OWNER'S
REPRESENTATIVE.
® EXISTING FLOOR DRAIN TO BE REMOVED AND TURNED OVER TO OWNER'S
REPRESENTATIVE.
5O EXISTING DOMESTIC WATER FILTER FOR ICE MACHINE SUPPLY TO BE REMOVED
AND RELOCATED.
© EXISTING RAIN WATER LEADER FROM ABOVE TO BE RELOCATED.
70 EXISTING MEDICAL GAS PRESSURE ALARM PANELS SERVING "LABOR AND DELIVERY"
AND DELIVERY ROOM/OPERATING TO REMAIN. (OXYGEN, VACUUM AND MEDICAL AIR)
® EXISTING ZONE VALVE BOX SERVING "LABOR AND DELIVERY" TO REMAIN.
(OXYGEN, VACUUM AND MEDICAL AIR)
NOTE:
PLUMBING CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS
TO PROTECT EXISTING MEDICAL GAS OUTLETS, EQUIPMENT AND ALARM
PANELS FROM CONSTRUCTION DUST AND DEBRIS DURING DEMOLITION
AND RENOVATION PHASES OF PROJECT.
SELECTIVE KEYNOTES Q
CFRH m L & D
Sanford, Florida
PENINSULA ENGINEERING INC.
CONSULTING ENGINEERS
ESTABLISHED IN 1977 �pyright
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 - 407.246.1688 - EB 3089 2009
0
Copyright — All ideas, designs, methods and plans indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and
developed for use on and in connection with the specified project. None of the ideas, designs, JOB#:
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
PERMIT SET
09-10-2010 GJG JAM
issue date drawn by approved by
2010.038
REVISION SCHEDULE
Al DATE I DESCRIPTION
project number
DEMOLITION PLAN P21
PLUMBING ■
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION ANDIOR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
``,t%IIIIfill, i'
P�gERT0 M 0�
mak. ENS
R
No 313
T
�.�� � IDT•ice
S -'M due " `.F
FL''�i�1�1p.�`�< BURKE HOGUE MILLS, INC.
32746
407.333.2005 AAC000233
W W W B H M U
S
0 M
t
T,
COR
T 15'
N
RELOCATED 4" RAIN
WATER LEADER DOMI
WITH CLEANOUT
I
-NEW 4" STOR o i
BELOW SLAB
o
- -niniiiiiiiiiiiiii- - -
i
EXISTING STORM
BELOW S
i
NURSE'S -
STATION
U
��R CEILING
I
ABpi
/
N5A G
pN� GE1�
GI�I� pl��
10 Bp G
tIIN� A6
GEII.IN
E I I I
91 OpAR. f
p
CoPUE�SA
o 8
RAID
NSAf oT o�
CON,G 000 51 NG
EtJ
6IN G 115� NK
S�J6 10QP 5I
NK
SANITARY WASTE RISER DIAGRAM
NURSE LOUNGE 97
SCALE: NONE
NOTE:
IN PHASE 2 OF PROJECT PLUMBING
CONTRACTOR SHALL RELOCATE EXISTING
ICE MACHINE, WATER FILTRATION SYSTEM
AND DUAL CHECK VALVE FROM
TEMPORARY LOCATION IN NURSE LOUNGE
97 TO NEW NOURISHMENT ROOM. CAP
TEMPORARY ICE MACHINE SUPPLY UNE
ABOVE CEILING USING APPROVED
CAPPING METHODS.
�A00ER GGA> Lo�R
A1ERTpR R�'.�R �
ARRES U WA f f
5
Y
ELG CH GA�IGJE`�
�A� I Y I
I , I
LOLOG �.
9
DOMESTIC WATER RISER DIAGRAM
SCALE: NONE
I 3
I
1
G
RY
ANI
TA
P3 3� 5 5VNG
1
1 P.p•C• 1 1I E
1 2 SAS
I
�/L I
E�15 tARY
AR(S�
��I4, 5AN
NOROO�
SANITARY WASTE RISER DIAGRAM
NOURISHMENT ROOM
SCALE: NONE
L
LOCAF �o�R
2,H
F 1�
�` I ,.004
I L
I ,
E�
T �
CORR. URI
T1 312 ROOM
DOMESTIC WATER RISER DIAGRAM
NOURISHMENT
SCALE: NONE
N
['Ll
0
NURSES
STATION
J?
CORR,
T1 312
N
SELECTIVE KEYNOTES p
PLUMBING RENOVATION PLAN NOTES
Q1 PLUMBING CONTRACTOR SHALL TIE NEW 3" SANITARY WASTE LINE BELOW
SLAB INTO NEAREST EXISTING SANITARY WASTE LINE OF PROPER SIZE.
CUT AND PATCH SLAB AS REQUIRED.
Q2 PLUMBING CONTRACTOR SHALL TIE NEW 1 1/2" WASTE LINE AND NEW
2" VENT LINE INTO EXISTING VENTED SANITARY LINE OF PROPER SIZE.
O3 PLUMBING CONTRACTOR TO RELOCATE EXISTING 4" RAIN WATER LEADER
FROM ABOVE CEILING TO BELOW SLAB, PROVIDE CLEANOUT AT BASE.
® POINT OF CONNECTION (P.O.C.) PLUMBING CONTRACTOR TO PROVIDE AND
INSTALL NEW 4" STORM LINE BELOW SLAB. CONNECT NEW 4" STORM TO
EXISTING 4" STORM LINE BELOW SLAB, CUT AND PATCH SLAB AS REQUIRED.
05 PLUMBING CONTRACTOR SHALL PROVIDE AND INSTALL NEW 4" RAIN WATER
LEADER (RWL) ABOVE CEILING. TIE NEW RWL INTO EXISTING RWL ABOVE CEILING.
© PLUMBING CONTRACTOR SHALL PROVIDE AND INSTALL A TEMPORARY 3/8" ID
CONDENSATE TUBING LINE ABOVE CEILING. PROVIDE A INVERTED "U" AT HIGHEST
POINT OF THE DISCHARGE LINE. DISCHARGE UNE TO BE ROUTED ABOVE CEILING,
MAINTAINING A CONTINUOUS DOWNWARD SLOPE. TUBE IS TO BE SUPPORTED IN SUCH
A WAY AS TO AVOID KINKING OR PINCHING LINE AND BLOCKING THE FLOW.
Q7 RELOCATED ICE MACHINE, REFER TO ARCHITECTURAL PLANS FOR ADDITIONAL
INFORMATION.
® TEMPORARY CONDENSATE PUMP FOR ICE MACHINE. CONDENSATE PUMP TO BE
ZOELLER PUMP CO. MODEL NO. 520 (OR EQUAL).
Q PLUMBING CONTRACTOR TO TIE NEW 1/2" DOMESTIC COLD WATER LINE INTO
NEAREST EXISTING DOMESTIC COLD WATER LINE OF PROPER SIZE. PROVIDE
AND INSTALL DOUBLE CHECK VALVE ASSEMBLY ON DOMESTIC COLD WATER ICE
MACHINE SUPPLY LINE. WATTS MODEL NO. 719 (OR EQUAL).
10 EXISTING WATER FILTRATION SYSTEM. PLUMBING CONTRACTOR SHALL RELOCATE
EXISTING WATER FILTER SERVING RELOCATED EXISTING ICE MACHINE. PLUMBING
CONTRACTOR SHALL REFURBISH IF NECESSARY, IF REPLACEMENT IS REQUIRED, NEW
WATER FILTRATION SYSTEM SHALL MATCH EXISTING OR HOSPITAL STANDARD.
11 PLUMBING CONTRACTOR SHALL TIE NEW 1/2" DOMESTIC HOT AND COLD WATER
LINES INTO NEAREST EXISTING DOMESTIC HOT AND COLD WATER LINES OF PROPER
SIZE.
12 PLUMBING CONTRACTOR SHALL TIE NEW DOMESTIC 1/2" COLD AND 1/2" HOT
WATER LINES INTO NEAREST EXISTING DOMESTIC WATER LINE OF PROPER SIZE.
13 PLUMBING CONTRACTOR TO TIE NEW 1/2" DOMESTIC COLD WATER LINE INTO
NEAREST EXISTING DOMESTIC COLD WATER LINE OF PROPER SIZE. RELOCATE
EXISTING DOUBLE CHECK VALVE ASSEMBLY AND EXISTING WATER FILTRATION
SYSTEM FROM TEMPORARY LOCATION IN NURSE LOUNGE 97.
NOTE:
PLUMBING CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS
TO PROTECT EXISTING MEDICAL GAS OUTLETS, EQUIPMENT AND ALARM
PANELS FROM CONSTRUCTION DUST AND DEBRIS DURING DEMOLITION
AND RENOVATION PHASES OF PROJECT.
CFRH m L & D
Sanford, Florida
PENINSULA ENGINEERING INC.
CONSULTING ENGINEERS
ESTABLISHED IN 1977 pyright
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 - 407.246.1688 • EB 3089 2009
0
Copyright — All ideas, designs, methods and plans Indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and JOB
developed for use on and in connection with the specified project. None of the ideas, designs, #-
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
PERMIT SET 201 OmO38
09-10-2010 GJG JAM
issue date drawn by approved by project number
REVISION SCHEDULE
DATE DESCRIPTION
RENOVATION PLAN P3N1
PLUMBING sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATION COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
�%%11111f1j/0I
P�0ERTO
No 313
P
.� to .
', •A/��..� la, BURKE HOGUE MILLS, INC.
""fill 11� �,,``�� 1130 Business Center Drive, Lake Mary, FL
32746
407.333.2005 AAC000233
W W W B H M U S C 0 M
FH_1
ABBREVIATIONS
HB
FAI
SUPPLY DUCT UP
V
o
HC
HANDICAPPED
A
AIR
HE
ID
INSIDE DIAMETER, INDIRECT DRAIN
VD
AAV
AUTOMATIC AIR VENT
HAND -OFF -AUTOMATIC
IN
INCH
VERTICAL
AC
AIR CONDITIONER
VTR
VENT THROUGH ROOF
HR
HOUR
AIR CONDITIONING UNIT
X-1ACU
HVAC
HEATING/VENTILATING/AIR CONDITIONING
AD
ACCESS DOOR, AIR DRYER
RHC
KW
KILOWATT
AFF
ABOVE FINISHED FLOOR
HWR
HOT WATER RETURN
WC
AFG
ABOVE FINISHED GRADE
HEAT EXCHANGER
WCO
WALL CLEAN OUT
AHU
AIR HANDLING UNIT
LAV
LAVATORY
ALUM
ALUMINUM
WPD
LOR
LIMIT OF REMOVAL
AP
ACCESS PANEL
LWT
LEAVING WATER TEMPERATURE
APD
AIR PRESSURE DROP
ATC
AUTOMATIC TEMPERATURE CONTROL
M
AV
AIR VENT
MAX
MAXIMUM
MBH
THOUSAND BTU PER HOUR
101
MD
MANUAL DAMPER
BDD
BACK DRAFT DAMPER
MIN
MINIMUM
BOT
BOTTOM
M/S
METERS PER SECOND
BP
BACKFLOW PREVENTER
BTU
BRITISH THERMAL UNIT
FNW
N
NORTH
FC -1
NA
NOT APPLICABLE/NOT AVAILABLE
C
CELCIUS, DEGREE CELCIUS
NO OR #
NUMBER, NORMALLY OPEN
CD
CONDENSATE DRAIN
NTS
NOT TO SCALE
CENT
CENTRIFUGALNG
NATURAL GAS
CFM
CUBIC FEET PER MINUTE
1-01
CH
CHILLED WATER
OA
OUTSIDE AIR
CLG
CEILING
OBD
OPPOSED BLADE DAMPER
CO
CLEAN OUT
OD
OUTSIDE DIAMETER
COND
CONDENSATE
OPER
OPERATING
COTG
CLEAN OUT TO GRADE
CW
COLD WATER
[P]
P
PUMP
D
PRS
PRESSURE REDUCING STATION
DB
DRY BULB
PRV
PRESSURE REDUCING VALVE
DCW
DOMESTIC COLD WATER
PSI
POUNDS PER SQUARE INCH
DEG
DEGREE
PSIG
POUNDS PER SQUARE INCH GAUGE
DELIV
DELIVERY
DF
DRINKING FOUNTAIN
FR_1
DG
DOOR GRILLE
RA
RETURN AIR
DHW
DOMESTIC HOT WATER
RD
ROOF DRAIN
DISC
DISCONNECT
REG
REGISTER
DN
DOWN
REF
REFRIGERANT, REFERENCE
DWV
DRAIN, WASTE AND VENT PIPING
RF
RETURN FAN
RH
REHEAT, RELATIVE HUMIDITY
RHC
REHEAT COIL
EA
EXHAUST AIR, EACH
RM
ROOM
EAT
ENTERING AIR TEMPERATURE
RPM
REVOLUTION PER MINUTE
ED
EQUIPMENT DRAIN
RTU
ROOF TOP UNIT
EDH
ELECTRICAL DUCT HEATER
RWL
RAIN WATER LEADER
EF
EXHAUST FAN
-1
EFF
EFFICIENCY
Fs
ELEV
ELEVATION
S
SINK
ENT
ENTERING
SA
SUPPLY AIR
EWC
ELECTRIC WATER COOLER
SAN
SANITARY
EM
ELECTRIC WATER HEATER
SF
SUPPLY FAN
EWT
ENTERING WATER TEMPERATRE
S/FD
SMOKE/FIRE DAMPER
ST
STEAM
F-1
F
FAHRENHEIT, DEGREE FAHRENHEITFT
FCO
FLOOR CLEAN OUT
T
THERMOSTAT
FCU
FAN COIL UNIT
TEMP
TEMPERATURE
FD
FIRE DAMPER, FLOOR DRAIN
TG
TRANSFER GRILLE
FPB
FAN POWERED BOX
TH
THERMOMETER
FPM
FEET PER MINUTE
TP
TRAP PRIMER
FPS
FEET PER SECOND
TMV
THERMOSTATIC MIXING VALVE
F/SD
FIRE/SMOKE DAMPER
TYP
TYPICAL
FT
FEET
101
[G7
UC
UNDER CUT
GPH
GALLONS PER HOUR
UH
UNIT HEATER
GPM
GALLONS PER MINUTE
UR
URINAL
FH_1
a
HB
HOSE BIBB
SUPPLY DUCT UP
V
VENT, VOLT
HC
HANDICAPPED
VAV
VARIABLE AIR VOLUME
HE
HEAT EXCHANGER
VD
VOLUME DAMPER
HOA
HAND -OFF -AUTOMATIC
VERT
VERTICAL
HP
HORSEPOWER
VTR
VENT THROUGH ROOF
HR
HOUR
EXHAUST DUCT DOWN
HVAC
HEATING/VENTILATING/AIR CONDITIONING
W
EXHAUST FAN ON ROOF
RHC
HWS
HOT WATER SUPPLY
WB
WET BULB
HWR
HOT WATER RETURN
WC
WATER CLOSET
HX
HEAT EXCHANGER
WCO
WALL CLEAN OUT
HZ
HERTZ (CYCLES PER SECOND)
WH
WALL HYDRANT
WPD
WATER PRESSURE DROP
0_1 SUPPLY DIFFUSER
Fr EXISTING SUPPLY DIFFUSER
LJ
01 RETURN GRILLE
Fr-- ;_511 EXISTING RETURN GRILLE
F -I M.A.C. LEGEND
r _ J EXISTING DUCTWORK
i/�Z1� DEMO EXISTING DUCTWORK
(HATCH DENOTES REMOVAL)
NEW DUCTWORK
LJ
EXHAUST GRILLE
SUPPLY DUCT UP
FR
LA
EXISTING EXHAUST GRILLE
SUPPLY DUCT DOWN
RETURN DUCT UP
SIDEWALL GRILLE OR LOUVER
RETURN DUCT DOWN
(AZ—EM
DIFFUSER DESIGNATION
EXHAUST DUCT UP
TYPE
CFM
EQUIPMENT TAG
EXHAUST DUCT DOWN
QH
HUMIDISTAT
®i
EXHAUST FAN ON ROOF
RHC
REHEAT COIL
-�—
NEW THERMOSTAT BUTTERFLY VALVE
QT
—D�— GATE VALVE
<Tl EXIST. THERMOSTAT
--� rl— B
POINT OF CONNECTION ALL OR GLOBE VALVE
(EXISTING TO NEW)— CHECK VALVE
SD DUCT SMOKE DETECTOR —SII— UNION
FO FIRESTAT Q PRESSURE GAGE AND COCK
�j MOTOR OPERATOR STRAINER — Y PATTERN
W/ VALVE AND HOSE END CONN.
AIR FLOW
CD CONDENSATE DRAIN
ETR EXISTING TO REMAIN —CHWS— CHILLED WATER SUPPLY (CHWS)
I LOR LIMITS OF REMOVAL—CHWR-- CHILLED WATER RETURN (CHWR)
HWS— HEATING WATER SUPPLY (HWS)
EXISTING FIRE —HWR-- HEATING WATER RETURN (HWR)
SPRINKLER HEAD
FD
NEW FIRE DAMPER 0 ELBOW UP
1FD G ELBOW DOWN
EXIST. FIRE DAMPER
I PIPE OFF BOTTOM OF PIPE
F/SD
I PIPE OFF TOP OF PIPE
NEW FIRE/SMOKE DAMPER
F/SD
EXIST. FIRE/SMOKE DAMPER
I
SERVICES OUTAGE NOTES:
PLANNED DISRUPTION OR SERVICE OUTAGES
PART 1 - GENERAL
1.1 DESCRIPTION
A. WORK INCLUDED: THIS SECTION APPLIES TO SITUATIONS IN WHICH THE CONTRACTOR OR
THEIR REPRESENTATIVES, INCLUDING, BUT NOT NECESSARILY LIMITED TO SUPPLIERS,
SUBCONTRACTORS EMPLOYEES AND FIELD ENGINEERS ENTER, HAVE ACCESS TO AND
CONDUCT THEMSELVES ON THE OWNER'S PROPERTY.
B. RELATED WORK: WORK AFFECTING THIS SECTION INCLUDES, BUT ARE NOT NECESSARILY
LIMITED TO GENERAL CONDITIONS, SUPPLEMENTARY CONDITIONS AND SECTIONS 1 OF THESE
SPECIFICATIONS.
1.2 PLANNED DISRUPTIONS OR SERVICE OUTAGES
A. PRIOR TO THE SHUTTING OFF, DISRUPTION, OR OTHERWISE MODIFYING THE FOLLOWING
EXISTING SERVICES, THE CONTRACTOR MUST REQUEST AUTHORIZATION FROM THE OWNER'S
AGENT, AT LEAST 72 HOURS PRIOR TO THE PLANNED OUTAGE OR DISRUPTION OF SERVICE.
IF THE SHUT -DOWN IS ANTICIPATED TO BE A SHUT -DOWN OF MAJOR CONSEQUENCE OR
AFFECT LARGE AREAS OF THE FACILITY, THE NOTICE MUST BE GIVEN ONE WEEK IN ADVANCE
TO ALLOW FOR ADEQUATE PLANNING.
ELECTRIC POWER (SERVICE) TO A BUILDING
ELECTRIC CIRCUITS AND SUBFEEDERS
WATER
SEWER - SANITARY
MEDICAL GASES: OXYGEN, NITROGEN, ANESTHESIA GASES, COMPRESSED
AIR AND VACUUM.
FIRE WATER
FIRE ALARM OR SMOKE DETECTION
TELEPHONE
OTHER SERVICES NOT NOTED, ETC.
B. THE SHUTDOWN REQUEST MUST BE IN WRITING. IT MUST INDICATE THE FOLLOWING:
1. BUILDING SERVICES TO BE AFFECTED.
2. SPECIFIC AREAS OF THE FACILITY TO BE AFFECTED.
3. DURATION OF THE DISRUPTION OF SERVICES
4. DESCRIPTION OF WORK TO BE PERFORMED.
5. NAME OF THE PERSON WHO, WILL SUPERVISE AND IS RESPONSIBLE FOR THE PROJECT.
C. THE SHUT -DOWN REQUEST FORM MUST BE SIGNED AND ACCEPTED BY THE TWO PARTIES;
HOSPITAL ENGINEERING AND THE CONTRACTOR'S SUPERVISOR. IF ALL PARTIES HAVE NOT
SIGNED OFF, THERE WILL BE NO SHUT -DOWN.
D. MEDICAL GAS SHUT -DOWN: WHEN MEDICAL GAS SHUT -DOWNS AFFECT OCCUPIED PATIENT
CARE AREAS OF THE HOSPITAL, THE CONTRACTOR SHALL NOTIFY THE HOSPITAL'S PROJECT
MANAGER OF THE
ANTICIPATED DISRUPTION IN AMPLE TIME TO SCHEDULE A PROJECT PLANNING MEETING PRIOR
TO THE SHUT -DOWN. THE PROJECT MANAGER WILL INVITE THE UNIT MANAGERS,
RESPIRATORY SERVICES
STAFF, ENGINEERING, SAFETY AND OTHERS TO ATTEND THE PLANNING MEETING.
1. THE SCOPE AND DURATION OF THE MEDICAL GAS SHUT -DOWN WILL BE ADDRESSED AT THE
MEETING. CONTRACTOR WILL BE REQUIRED TO HAVE ADEQUATE INFORMATION INCLUDING
DRAWINGS IF NECESSARY TO FULLY DESCRIBE THE SCOPE OF WORK.
2. RESPIRATORY SERVICES WILL DETERMINE IF THEY HAVE THE NECESSARY MATERIALS,
EQUIPMENT AND STAFF ON HAND TO ADEQUATELY HANDLE THE DURATION OF THE
SHUT -DOWN OR OTHERWISE
INDICATE HOW MUCH TIME THEY WILL NEED TO PREPARE.
3. PRIOR TO THE SHUT -DOWN, ALL PARTIES MUST MEET AT A PRESCRIBED TIME AND PLACE
TO CONFIRM ALL PREPARATIONS ARE IN PLACE TO BEGIN THE SHUT -DOWN. NO MEDICAL
GAS SHUT -DOWN WILL
PROCEED WITHOUT THE MED GAS CERTIFIER BEING ON SITE.
4. AS THE COMPLETION OF THE WORK, MED GAS CERTIFIER SHALL TEST AND PROVIDE WRITTEN
REPORT AS TO THE SUCCESSFUL COMPLETION OF THE MODIFICATION TO THE MEDICAL GAS
SYSTEMS.
5. WHEN RESPIRATORY SERVICES ASSESSES ALL AREAS AND DETERMINE THE SYSTEM IS
FUNCTIONAL, PATIENT CARE STAFF MAY RETURN PATIENTS TO NORMAL OPERATIONAL
SYSTEMS.
DEMOLITION GENERAL NOTES
1. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE DEMOLITION
OF EXISTING MECHANICAL SYSTEMS AS REQUIRED TO PERFORM NEW MECHANICAL
WORK. ALL DIFFUSERS, PIPING AND MISCELLANEOUS DEBRIS SHALL BE
TURNED OVER TO OWNERS REPRESENTATIVE OR REMOVED FROM SITE AND
PROPERLY DISPOSED OF AT THE DIRECTION OF THE OWNERS REPRESENTATIVE.
2. DEMOLITION SHALL INCLUDE REMOVAL OF PIPING, DUCTWORK, CONTROLS, ETC.
3. EXISTING EQUIPMENT PROPOSED FOR RE -USE SHALL BE CLEANED, TESTED AND
CALIBRATED BY THE HVAC CONTRACTOR. ANY DEFECTIVE PARTS SHALL BE
REPLACED TO BRING UNITS UP TO GOOD OPERATING CONDITIONS.
4. EXISTING INSULATION THAT IS DAMAGED SHALL BE REPAIRED/REPLACED WHERE
NECESSARY TO ENSURE CONTINUOUS INSULATION OVER ENTIRE SYSTEM.
5. COORDINATE WITH DIVISION 16 TO PERFORM ALL ELECTRICAL WORK NECESSARY
TO REMOVE, RELOCATE OR INSTALL ANY EQUIPMENT OR SYSTEMS THAT HAVE
ELECTRICAL POWER CONNECTIONS.
HVAC GENERAL NOTES
FURNISH ALL LABOR, MATERIALS, SERVICES, EQUIPMENT AND APPLIANCES
REQUIRED FOR THE RENOVATION OF EXISTING MECHANICAL SYSTEMS INCLUDING
HEATING, VENTILATION, AIR CONDITIONING, AND MISCELLANEOUS SYSTEMS AS
INDICATED ON THE DESIGN DRAWINGS AND AS OUTLINED IN THE SPECIFICATIONS.
THE ENTIRE SYSTEM AND ALL COMPONENTS SHALL HEREIN MEET ALL STATE,
COUNTY, AND LOCAL CODES AND ORDINANCES IN EVERY RESPECT.
MECHANICAL CONTRACTOR SHALL OBTAIN ALL PERMITS AND PAY ALL FEES
REQUIRED FOR HIS PORTION OF THE WORK.
CODES, STANDARDS AND DESIGN MATERIALS:
- FLORIDA BUILDING CODE, 2007 (WITH 2009 SUPPLEMENTS)
- FLORIDA BUILDING MECHANICAL CODE, 2007 (WITH 2009 SUPPLEMENTS)
- FLORIDA BUILDING PLUMBING CODE, 2007 (WITH 2009 SUPPLEMENTS)
FLORIDA BUILDING FIRE PREVENTION CODE, 2005
NATIONAL FIRE CODES, NFPA 2005 (CHAPTER 13)
ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
(STATE OF FLORIDA LATEST EDITION)
NEPA 101 - (2005)
- LOW PRESSURE DUCT CONSTRUCTION STANDARDS SMACNA 1996
REFER TO DRAWINGS FOR NEW AND REUSED EXISTING EQUIPMENT. ALL NEW
EQUIPMENT, ETC. SHALL BE OF THE BEST QUALITY, FREE OF DEFECTS, AS SHOWN
ON THE DRAWINGS, AND AS INDICATED IN THE SPECIFICATIONS.
ALL SYSTEMS SHALL BE FABRICATED AND INSTALLED IN A NEAT AND
PROFESSIONAL MANNER WITH THE COORDINATION OF ALL INVOLVED TRADES TO
AVOID INTERFERENCE AND DELAY DUE TO LACK OF COORDINATION. NO
ALLOWANCES WILL BE MADE FOR REWORK DUE TO COORDINATION DIFFICULTIES OR
INTERFERENCE BETWEEN INVOLVED TRADES.
EXISTING SYSTEMS SHOWN ON THIS PLAN ARE BASED ON FIELD OBSERVATIONS
AND AVAILABLE RECORD DRAWINGS. THIS INFORMATION IS PARTIALLY UNVERIFIED.
CONTRACTOR ASSUMES RESPONSIBILITY FOR FIELD VERIFICATION AND INVESTIGATION
PRIOR TO SUBMITTING BID. DO NOT SCALE THESE PLANS. NOT ALL NEW OR EXISTING
UTILITIES, PIPE, CONDUITS ETC, ARE NOT NECESSARILY SHOWN. WHERE EXISTING IS IN
THE WAY OF NEW WORK PROVIDE RELOCATION OF UTILITY.
PROVIDE NEBB OR AABC INDEPENDENT TEST AND BALANCE CONTRACTOR. EXISTING AIR
AND WATER QUANTITY SHALL BE RE -BALANCED TO QUANTITIES INDICATED ON PLAN.
MANUFACTURER'S RECOMMENDED SERVICE CLEARANCE FOR ALL EQUIPMENT SHALL
BE MAINTAINED.
CONTRACTOR SHALL INSPECT ALL SYSTEMS AND EQUIPMENT WITHIN THE AREA OF
WORK TO DETERMINE FITNESS FOR OPERATION. CONTRACTOR SHALL PROVIDE A
FULLY OPERATIONAL FINISHED SYSTEM AS DESCRIBED. PATCH AND MAKE GOOD
ALL LEAKS IN EXISTING PIPING. REPAIR AS REQUIRED TO RESTORE VAPOR BARRIER
AND INSULATION SYSTEM.
MECHANICAL CONTRACTOR SHALL EXAMINE ARCHITECTURAL, STRUCTURAL,
ELECTRICAL, PLUMBING AND FIRE PROTECTION DRAWINGS FOR ESTIMATING AND
CONSTRUCTION OF THIS PROJECT. SUBMISSION OF A PROPOSAL SHALL BE
CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER
CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED FOR ANY CORRECTIONS
REQUIRED DUE TO CONFLICTS WITH OTHER TRADES WILL NOT BE RECOGNIZED.
REFER TO ARCHITECTURAL PLANS FOR ADDITIONAL ICRA PLANS AND REQUIREMENTS.
DUCTWORK SHALL BE GALVANIZED STEEL OF GAUGES CONFORMING TO LATEST
EDITION OF SMACNA STANDARDS.
ALL DIMENSIONS ARE INSIDE NET FREE AREA.
NEW AND RELOCATED THERMOSTATS SHALL BE INSTALLED 48" ABOVE FINISHED
FLOOR.
DIFFUSER, REGISTER AND GRILLE INSTALLATIONS SHALL BE COORDINATED WITH
OTHER TRADES.
EXISTING DUCTWORK SHOWN IS FOR REFERENCE ONLY. VERIFY EXISTING LOCATIONS
AND DUCT SIZES.
ALL DUCT INSULATION SHALL COMPLY WITH FLORIDA MODEL ENERGY EFFICIENCY
CODE. SHEETMETAL DUCT WILL INCLUDE 2" DUCT WRAP.
ALL DUCTWORK SHALL BE SUPPORTED IN STRICT COMPLIANCE WITH SMACNA OR
FLORIDA MODEL EFFICIENCY CODES WHICHEVER IS STRICTER.
ALL DUCTWORK AND PIPING NOT OPERATIONAL DURING CONSTRUCTION SHALL BE
CAPPED UNTIL FINAL CONNECTIONS ARE MADE.
ALL RETURN GRILLES ON ALL HVAC SYSTEMS BEING OPERATED DURING
CONSTRUCTION SHALL HAVE FILTER MEDIA COVERING RETURN AIR OPENINGS TO
PRE -FILTER AIR. FILTER MEDIA TO BE REMOVED AT THE COMPLETION OF
CONSTRUCTION.
INSULATION USED WITHIN THIS PROJECT DESIGN MEETS THE CRITERIA AS PRESCRIBED
IN 2007 FMC SECTIONS 604.1 THROUGH 604.13.
ldlm� � ■ � w � rr 1k ff tri ■ / 1-00 IL / IL I O\ T r r\
5C1LCC; I IVC Kt Y IVU I CZ) U
PENINSULA ENGINEERING INC.
CONSULTING ENGINEERS
ESTAELISI•IED IN 1977 QC -yri ht
009
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 • 407.246.1688 • EB 3089 D
Copyright — All ideas, designs, methods and plans indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and
developed for use on and In connection with the specified project. None of the Ideas, designs, JOB#:
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
DHM JHM
issue date drawn by approved by project number
REVISION SCHEDULE
DATE I DESCRIPTION
LEGEND, SYMBOLS AND momi
GENERAL NOTES
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURL, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
`,��11111/111��
�����BERTO 41
o�,`�': •��s✓ E NSF •..pGtn
0.3 13 i u'
it * -
AT OF i'r
��� •. fgd'e ���
FL P�lAlAB ` BURKE HOGUE MILLS, INC.
1111111110 1130 Business Center Drive, Lake Mary, FL
32746
407.333.2005 AAC000233
W w w B----- –H- —M -- . - - U__ _ - S~ - -0 M
.MECHANICAL SPECIFICATIONS
GENERAL MECHANICAL REQUIREMENTS
DIVISION 15
.el:11.1:11:M_
DRAWINGS AND GENERAL CONDITIONS OF CONTRACT, INCLUDING GENERAL AND
SUPPLEMENTAL CONDITIONS AND DIVISION 1 SPECIFICATIONS APPLY TO WORK SPECIFIED
IN THIS SECTION.
SCOPE OF WORK
WORK SHALL INCLUDE BUT NOT BE LIMITED TO THE FOLLOWING:
PROVIDE ALL LABOR, MATERIALS, SERVICES, EQUIPMENT AND APPLIANCES REQUIRED
FOR THE FABRICATION, INSTALLATION, AND/OR RENOVATION OF MECHANICAL SYSTEMS
INCLUDING HEATING, VENTILATING, AIR CONDITIONING AND MISCELLANEOUS SYSTEMS AS
INDICATED ON THE DESIGN DRAWINGS AND AS OUTLINED IN THESE SPECIFICATIONS.
RELATED WORK SPECIFIED ELSEWHERE
REFER TO ELECTRICAL SPECIFICATION (DIV. 16) FOR ELECTRICAL WORK TO BE DONE IN
CONJUNCTION WITH THE MECHANICAL WORK. THIS CONTRACTOR IS RESPONSIBLE FOR
ALL CONDUIT, WIRING, JUNCTION BOXES, ETC., REQUIRED FOR HVAC CONTROLS.
INSTALL DUCT SMOKE DETECTOR FURNISHED BY DIVISION 16 IN SUPPLY AIR DUCTS OF
AIR HANDLING UNITS EXCEEDING 20GOCFM AND WHERE INDICATED ON DRAWINGS.
DETECTOR TO SHUT UNIT DOWN WHEN ACTIVATED.
SUBSTITUTIONS
EQUIPMENT AND DESIGN OF SYSTEMS INDICATED ON THE DESIGN DRAWINGS AND WITHIN
THESE SPECIFICATIONS SHALL BE CONSIDERED AS SPECIFIED STANDARD OF QUALITY.
NO SUBSTITUTIONS SHALL BE MADE WITHOUT PRIOR WRITTEN APPROVAL OF THE
ENGINEER.
ANY DEVIATION FROM SPECIFIED EQUIPMENT THAT AFFECTS THE ELECTRICAL
REQUIREMENTS SHALL BE COORDINATED BY THE MECHANICAL CONTRACTOR AND
EQUIPMENT VENDOR WITH THE ELECTRICAL CONTRACTOR PRIOR TO SUBMITTING BIDS.
FAILURE OF MECHANICAL CONTRACTOR AND VENDOR TO DO SO WILL NOT BE CAUSE
FOR CHANGE OF BID AT A LATER TIME. IT WILL NOT BE THE RESPONSIBILITY OF THE
ELECTRICIAN TO COORDINATE REVISED ELECTRICAL REQUIREMENTS DUE TO EQUIPMENT
CHANGES INITIATED BY THE MECHANICAL CONTRACTOR AND VENDOR. IN ADDITION, THE
MECHANICAL CONTRACTOR SHALL BE FINANCIALLY RESPONSIBLE FOR ANY AND ALL
CHANGES TO ENGINEERING PLANS REQUIRED BY AUTHORITY HAVING JURISDICTION.
CODES AND STANDARDS
APPLICABLE CODES:
— 2007 FLORIDA BUILDING CODE — MECHANICAL (WITH 2009 SUPPLEMENT)
— 2007 FLORIDA BUILDING CODE — EXISTING BUILDING
— NFPA 90A, 2002 EDITION
— NFPA 72, 2002 EDITION (TO COVER THE AIR DUCT DETECTORS)
— NFPA 101, 2006 EDITION
THE CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS, INSPECTIONS AND PAY ALL
FEES.
PRODUCTS
REFER TO PLANS FOR NEW AND REUSED EXISTING EQUIPMENT. ALL NEW EQUIPMENT,
ETC., SHALL BE AS SPECIFIED, FREE OF DEFECTS, AS SHOWN ON THE DRAWINGS, AND
AS INDICATED IN THESE SPECIFICATIONS. ALL ELECTRICALLY POWERED EQUIPMENT
SHALL BE U.L. OR E.T.L. LISTED.
WORKMANSHIP
ALL MATERIALS SHALL BE FABRICATED AND INSTALLED IN A NEAT AND WORKMANLIKE
MANNER WITH THE COORDINATION OF ALL INVOLVED TRADES TO AVOID INTERFERENCES
AND DELAY DUE TO LACK OF COORDINATION. NO ALLOWANCES WILL BE MADE FOR
REWORK DUE TO COORDINATION DIFFICULTIES OR INTERFERENCES BETWEEN INVOLVED
TRADES.
MECHANICAL CONTRACTOR SHALL DAILY REMOVE REFUSE AND DEBRIS ACCUMULATING
FROM MECHANICAL CONSTRUCTION AND PRIOR TO ACCEPTANCE OF THIS WORK. LEAVE
THE PREMISES BROOM CLEAN INSOFAR AS AFFECTED BY MECHANICAL WORK.
ALL DUCTWORK AND PIPING NOT OPERATIONAL DURING CONSTRUCTION SHALL BE
CAPPED UNTIL FINAL CONNECTIONS ARE MADE.
ALL RETURN GRILLES ON ALL HVAC SYSTEMS BEING OPERATED DURING CONSTRUCTION
SHALL HAVE FILTER MEDIA COVERING RETURN AIR OPENINGS TO PRE—FILTER AIR.
FILTER MEDIA TO BE REMOVED AT THE COMPLETION OF CONSTRUCTION.
SHOP DRAWINGS AND SUBMITTALS
SUBMIT FOR ENGINEER'S APPROVAL, A MINIMUM OF 2 PRINTED COPIES OF SHOP
DRAWINGS AND MANUFACTURER'S DATA FOR ALL NEW EQUIPMENT AND ACCESSORIES
PRIOR TO PURCHASE AND/OR FABRICATION. ELECTRONIC VERSIONS ARE NOT
ACCEPTABLE AND WILL BE RETURNED REJECTED. UN—REVIEWED.
SHOP DRAWINGS FOR EQUIPMENT REQUIRING ELECTRIC POWER OR CONTROL WIRING
CONNECTIONS SHALL INCLUDE COMPLETE WIRING DIAGRAMS
WHEN PROVIDED, THE DUCTWORK SHOP DRAWINGS WILL ONLY BE REVIEWED FOR
COMPLIANCE WITH THE DRAWINGS AND SPECIFICATIONS. THE DUCTWORK SHOP
DRAWINGS WILL NOT BE CHECKED FOR COORDINATION WITH OTHER TRADES OR
BUILDINGS STRUCTURE. IT IS THE RESPONSIBILITY OF THE CONTRACTORS TO
COORDINATE AND VERIFY ROUTING AND EXACT LOCATION OF SYSTEM COMPONENTS.
RECORD DRAWINGS
CONTRACTOR SHALL PROVIDE THE ENGINEER TWO (2) SETS OF COMPLETE HVAC
RECORD DRAWINGS AT THE TIME OF SUBSTANTIAL COMPLETION. RECORD DRAWINGS
SHALL BE PROVIDED ON REPRODUCIBLE VELLUM AND AUTOCADD DRAWING FILES
[RELEASE 2004 OR NEWER]. RECORD DRAWINGS SHALL CONSIST OF AN ACCURATE
AS—BUILT RECORD OF THE INSTALLED WORK. PROJECT WILL NOT BE COMPLETE UNTIL
ACCURATE RECORD DRAWINGS ARE DELIVERED.
ACCESS DOORS
CONTRACTOR SHALL PROVIDE HINGED ACCESS DOORS (MIN. 12 IN.X12 IN.) FOR
DAMPERS, VALVES, ETC. WHERE FLOORS, WALLS, AND CEILINGS MUST BE PENETRATED
TO ACCESS MECHANICAL SYSTEMS. FINISH SHALL BE COORDINATED THROUGH
ARCHITECT TO MATCH SURROUNDING FINISHES. FIRE RATED ACCESS DOORS IN FIRE
RATED WALLS OR CEILINGS SHALL BEAR A U.L. LABEL FOR FIRE RATING REQUIRED.
1. WALL: ACORN NO. 8211—H3, DRYWALL TYPE, PRIME COATED STEEL, CONCEALED
HINGE TYPE WITH ALLEN KEY LOCK ON REMOVABLE DOOR FOR PAINTED SURFACES.
FOR 11LE USE ACORN NO. 8212—H1, SATIN FINISH 18-8 STAINLESS STEEL. FOR
PLASTER WALLS, USE ACORN NO. 8212—H3 PRIME—COATED STEEL.
2. EXTERIOR AREAS: SMITH 4261, ZURN NO. Z-1460-15 CAST IRON SURFACE LEVEL
ACCESS COVER ASSEMBLY WITH LIFTING DEVICE WITH Z-1450-8 FOR CONCRETE
SURFACE. FOR ASPHALT CONCRETE OR EARTH SURFACE, USE ZURN NO.
Z-1460-15 WITH Z1450-8.
3. FLOORS: SMITH 4930, ZURN NO. Z-1460-10 NICKEL BRONZE SCORIATED SECURED
TOP ACCESS COVER WITH LIFTING DEVICE AND PERFORATED CONCRETE FLANGE.
SIZE AS INDICATED ON DRAWINGS. USE ZURN NO. ZANB-1460-12 OR SMITH 4940
FOR HINGED NON—REMOVABLE SECURED COVER.
EXECUTION
COORDINATE AND SCHEDULE THE WORK WITH THE OWNER TO MINIMIZE DISRUPTIONS TO
THE NORMAL OPERATIONS AT THE BUILDING.
ALL LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC., INDICATED ON THE DRAWINGS
IS DIAGRAMMATIC AND SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE TO THE PLANS
SUBJECT TO BUILDING CONSTRUCTION AND INTERFERENCES WITH OTHER TRADES. ALL
WORK SHALL BE INSTALLED TO ENSURE MAXIMUM HEADROOM, BALANCED OPERATION
AND SUITABLE AESTHETIC APPEARANCE. CONTRACTOR IS RESPONSIBLE FOR ANY FIELD
MEASUREMENTS REQUIRED TO PROVIDE AN APPROVED AND FUNCTIONAL INSTALLATION.
COORDINATE WITH OTHER TRADES AND FIELD—VERIFY EXISTING CONDITIONS FOR EXACT
LOCATION AND ROUTING OF SYSTEMS. PROVIDE OFFSETS, TRANSITIONS AND ADAPTORS
AS REQUIRED.
NOT ALL COMPONENTS REQUIRED FOR A COMPLETE INSTALLATION ARE SHOWN ON
THESE DRAWINGS. REFER TO EQUIPMENT INSTALLATION INSTRUCTION, SCHEDULES AND
APPLICABLE CODES FOR ADDITIONAL INFORMATION, INCLUDING REQUIRED CONNECTION
LOCATIONS, TYPES AND SIZES.
PERFORM ALL WORK NECESSARY TO PREPARE THE STRUCTURE FOR THE INSTALLATION
OF THE WORK. ALL HOLES, OPENINGS AND DAMAGED MATERIALS CREATED DURING
CONSTRUCTION SHALL BE REPAIRED AND FINISHED BY EXPERIENCED WORKMEN.
PROVIDE ALL PENETRATIONS REQUIRED TO COMPLETE INSTALLATION AND REMOVAL OF
WORK (MAINTAIN FIRE RATING OF EXISTING STRUCTURE). ALL PENETRATIONS SHALL BE
PATCHED AND FINISHED TO MATCH SURROUNDING SURFACES AND FINISHES. ALL
PENETRATIONS SHALL BE SLEEVED AND SEALED SO AS TO BE WATER AND AIR TIGHT.
CLEANING, TESTING AND ADJUSTING:
TEST AND BALANCE SHALL BE PERFORMED BY TEST AND BALANCE CONTRACTOR.
TESTING:
ADJUST THE AIR CONDITIONING SYSTEMS, VENTILATING SYSTEMS, FANS, ETC., TO
DELIVER NOT LESS THAN THE REQUIRED AIR QUANTITY WITH QUANTITIES IN EXCESS TO
BE SUBJECT TO THE APPROVAL OF THE ENGINEER IF FOUND TO NOT HAVE
OBJECTIONABLE EFFECTS SUCH AS NOISE, DRAFTS, OR MOTOR OVERLOAD.
THE TEST AND BALANCE CONTRACTOR SHALL PROVIDE A MINIMUM OF THREE (3)
COPIES OF A TEST AND BALANCE REPORT TO THE ENGINEER AT TIME OF FINAL AHCA
INSPECTION.
THE TEST AND BALANCE REPORT SHALL BE TYPEWRITTEN AND CONTAIN THE FOLLOWING
DATA:
1. DATE, TIME, WEATHER, WHEN TEST TAKEN.
2. AIR CAPACITIES AT EACH UNIT INCLUDING OUTSIDE AIR. (ENTERING AND LEAVING
DB/WB)
3. STATIC PRESSURE THROUGH UNITS AND UNIT COMPONENTS.
4. MOTOR OPERATING VOLTAGE AND AMPERAGE.
5. DRIVE TYPES, SIZES AND SPEED RANGE.
6. IDENTIFICATION OF ALL AIR TERMINAL DEVICES WITH DESIGN CFM AND ACTUAL CFM.
ADDITIONALLY, SYSTEMS DRAWINGS CLEARLY MARKED TO IDENTIFY LOCATION OF
EQUIPMENT AND AIR DEVICES TESTED SHALL BE PROVIDED ALONG WITH THE WRITTEN
TEST AND BALANCE REPORT.
MAINTENANCE MANUALS
• OPERATING AND MAINTENANCE INSTRUCTIONS
• SPARE PARTS LIST
• COPIES OF WARRANTIES
• WIRING DIAGRAMS
• INSPECTION REPORTS & APPROVALS
• SHOP DRAWINGS AND PRODUCT DATA
• TEST AND BALANCE INFORMATION
TRAINING SERVICES
THOROUGHLY INSTRUCT THE OWNER'S REPRESENTATIVE IN THE OPERATION OF ALL
EQUIPMENT FURNISHED AND LOCATION OF ALL VALVES AND CONTROL DEVICES.
TRAIN BUILDING OWNER'S PERSONNEL DURING NORMAL WORKING HOURS ON START—UP
AND SHUTDOWN PROCEDURES, TROUBLESHOOTING PROCEDURES, SERVICING AND
PREVENTATIVE MAINTENANCE SCHEDULE AND PROCEDURES. REVIEW WITH THE OWNER'S
PERSONNEL, THE DATA CONTAINED IN THE OPERATING AND MAINTENANCE MANUALS.
SCHEDULE TRAINING WITH OWNER, PROVIDE AT LEAST 7—DAYS PRIOR NOTICE TO
ARCHITECT/ENGINEER.
SYSTEM IDENTIFICATION
PROVIDE IDENTIFICATION LABELS ON OR NEAR EACH PIECE OF MAJOR EQUIPMENT AND
EACH OPERATIONAL DEVICE AND DISCONNECT. THE LABELS SHALL BE CONSTRUCTED
OF ENGRAVED PLASTIC LAMINATE SIGN OR PLASTIC EQUIPMENT MARKER PERMANENTLY
SECURED TO EQUIPMENT. THE LETTERING SHALL BE A MINIMUM OF 1/2 INCH HIGH FOR
EQUIPMENT NAME AND %" FOR EQUIPMENT INFORMATION.
HANGERS AND SUPPORTS
PROVIDE ALL NECESSARY DUCTWORK AND PIPE SUPPORTS, HANGERS, RODS, CLAMPS
AND ATTACHMENTS TO PROPERLY INSTALL AND SUPPORT DUCTWORK, PIPING AND
EQUIPMENT FROM THE BUILDING STRUCTURE. PROVIDE ANY ANGLE IRON OR UNISTRUT
AND SUSPENSION RODS REQUIRED TO INSTALL EQUIPMENT, PIPING AND DUCTWORK.
ALL SUPPORTS EXPOSED TO OUTDOORS SHALL BE CLEANED, PRIMED AND PAINTED TO
PREVENT RUSTING. FINISH COLOR AS SELECTED BY OWNER.
THE USE OF BALING WIRE, CLOTH WEBBING OR PERFORATED METAL STRAPPING IS NOT
ACCEPTABLE FOR SUPPORTS.
WARRANTY/GUARANTEE:
THE CONTRACTOR SHALL WARRANTY/GUARANTEE AND MAINTAIN THE STABILITY OF
WORK AND MATERIALS AND KEEP SAME IN PERFECT REPAIR AND CONDITION OF THE
PERIOD OF ONE (1) YEAR. DEFECTS OF ANY KIND DUE TO FAULTY WORK OR
MATERIALS APPEARING DURING THE ABOVE MENTIONED PERIOD MUST BE IMMEDIATELY
MADE GOOD BY THE CONTRACTOR AT HIS OWN EXPENSE TO THE ENTIRE SATISFACTION
OF THE OWNER AND ARCHITECT AND ENGINEER. SUCH RECONSTRUCTION AND REPAIRS
SHALL INCLUDE ALL DAMAGE TO THE FINISH OR FURNISHING OF THE BUILDING
RESULTING FROM THE ORIGINAL DEFECT OR REPAIRS THERETO.
HEATING JVENTILATINGJAIR CONDITIONING SPECIFICATIONS
SCOPE OF WORK
FURNISH AND INSTALL COMPLETE AIR CONDITIONING SYSTEMS AS INDICATED ON THE
DESIGN DRAWINGS AND AS OUTLINED WITHIN THESE SPECIFICATIONS. WORK SHALL
INCLUDE BUT NOT BE LIMITED TO THE FABRICATION AND/OR INSTALLATION OF THE
SCHEDULED CONSTANT VOLUME BOXES, AIR DISTRIBUTION AND DUCTWORK.
EQUIPMENT:
CONTROLS — CALIBRATE EXISTING CONTROLS
ALL NEW CONTROLS SHALL BE PNEUMATIC TYPE CONTROLS TO MATCH CONTROLS IN
THE AREA. COORDINATE MODIFICATIONS TO OWNER'S GRAPHICAL INTERFACE TO REFLECT
SYSTEM MODIFICATIONS.
AIR DISTRIBUTION EQUIPMENT:
FURNISH SUPPLY AIR GRILLES AND RETURN AIR REGISTERS AS SCHEDULED ON THE
DESIGN DRAWINGS. PRICE MAY BE SUBSTITUTED AS AN EQUAL
GRILLES, REGISTERS, AND CEILING DIFFUSERS SHALL BE FURNISHED AS SCHEDULED ON
THE DESIGN DRAWINGS AND SHALL BE ALL STEEL CONSTRUCTION. AIR DISTRIBUTION
SHALL NOT EXCEED NC -30 NOISE CRITERIA AS DEFINED IN THE LATEST ASHRAE GUIDE.
flivid CLilcT.l
MATERIALS: GALVANIZED STEEL (G-90) OF GAUGES CONFORMING TO LATEST EDITION
OF SMACNA STANDARDS BASED ON THE FOLLOWING PRESSURE UNLESS SPECIFICALLY
NOTED OTHERWISE ON THE DRAWINGS.
1. SUPPLY AIR: 2 IN. W.G. POSITIVE PRESSURE
2. RETURN AIR: 1 IN. W.G. NEGATIVE PRESSURE
3. EXHAUST AIR: 1 IN. W.G. POSITIVE/NEGATIVE PRESSURE
ALL DIMENSIONS ARE INSIDE NET FREE AREA.
ADJUSTABLE SPLITTERS AND DAMPERS SHALL BE INSTALLED IN EVERY SPLIT AND
BRANCH DUCT AND SHALL BE PROVIDED WITH LOCKING QUADRANTS ON EXPOSED OR IN
ACCESSIBLE AREAS OF THE DUCT FOR EASE OF OPERATION.
ELBOWS OR CHANGES IN DUCT DIRECTION GREATER THAN 45 DEGREES SHALL BE
FITTED WITH AIR TURNS CONSISTING OF CURVED AIRFOIL BLADES OR VANES WHICH WILL
PERMIT THE AIR TO MAKE ABRUPT TURNS WITHOUT APPRECIABLE TURBULENCE.
PROVIDE REMOTE CABLE DAMPER OPERATORS FOR DAMPERS INSTALLED IN HARD
CELINGS WHEN ACCESS TO DAMPERS IS NOT AVAILABLE. THE CABLE OPERATORS
SHALL INCLUDE CABLE AND WIRE, SOCKET WRENCH OPERATOR WITH MOUNTING
BRACKETS AND CABLE CLAMP AND ALL NECESSARY MOUNTING HARDWARE TO ATTACH
TO DAMPER SHAFTS AND DUCTWORK. THE OPERATOR SHALL BE INSTALL IN AN
ACCESSIBLE LOCATION OR PROVIDED WITH AN ACCESS PANEL. THE REMOTE CABLE
DAMPER OPERATORS SHALL BE AS MANUFACTURED BY YOUNG REGULATOR COMPANY
OR EQUAL FROM VENTLOCK.
FIRE DAMPERS:
FIRE DAMPERS SHALL BE TYPE B CURTAIN TYPE, SUITABLE FOR EITHER VERTICAL OR
HORIZONTAL INSTALLATION, WITH 20 GAUGE STEEL CHANNEL FRAMES, 24 GAUGE STEEL
BLADES, AND 18 GAUGE STEEL ENCLOSURE WITH DUCT COLLARS. ALL PARTS
GALVANIZED MILL FINISH.
FIRE DAMPERS SHALL BE EQUAL TO RUSKIN TYPE IBD2 FOR WALLS UP TO 2 HOURS.
INSTALL IN ACCORDANCE WITH NFPA-90A, TESTED IN ACCORDANCE WITH UL SAFETY
STANDARD 555, % HOUR AND 4 HOUR PROTECTION, 1657 FUSIBLE LINK. FURNISH
FIRE DAMPERS AND ACCESS DOORS THERETO IN ALL DUCTS PENETRATING ANY RATED
CONSTRUCTION AND WHERE INDICATED ON DRAWINGS. USE FOLDING BLADE TYPE C IN
HIGH VELOCITY ROUND DUCTS. USE FOLDING BLADE TYPE FOR SQUARE AND
RECTANGULAR DUCTS, AS DETAILED. FIRE DAMPERS SHALL BEAR THE ONE—HOUR
UNDERWRITER'S LABORATORY UL SAFETY STANDARD 555, % HOUR PROTECTION, 1657
FUSIBLE LINK.
COMBINATION SMOKE/FIRE DAMPER:
DAMPERS SHALL BE CLASS II FOR ALL LOCATIONS, WITH ACCESS DOORS. INSTALL IN
ACCORDANCE WITH NFPA-90A TEST PROCEDURES. ALL SHALL HAVE UL LABEL FOR A
COMPLETE ASSEMBLY. DAMPERS RATED FOR 1-1/2 HOUR PROTECTION WITH 165•F
FUSIBLE LINK, EQUAL TO RUSKIN FSD60-2 WITH DSDN NO FLOW DUCT SMOKE
DETECTOR. MOTOR OPERATOR VOLTAGE SHALL BE 120 VOLT UNLESS INDICATED ON
PLANS. COORDINATE WITH FIRE ALARM AND ELECTRICAL CONTRACTORS. DESIGNER:
NOTE TO VERIFY VOLTAGE WITH ELECTRICAL
ACCESS DOORS
FURNISH IN DUCTWORK AS INDICATED AND WHEREVER NECESSARY FOR PROPER ACCESS
TO ALL INSTRUMENTS, CONTROLS, FIRE DAMPERS, MOTORIZED DAMPERS AND EQUIPMENT
AND FOR CONVENIENT INSPECTION, MAINTENANCE AND REPLACEMENT OF SAME. SIZE
SHALL BE AMPLE FOR USAGE. OPENINGS SHALL BE REINFORCED ON ALL SIDES WITH
MATERIAL OR DUCTWORK IN WHICH DOORS ARE INSTALLED.
HARDWARE — USE VENT LOK HARDWARE THROUGHOUT. ALL DOORS TO BE HINGED
WITH BRASS PIN HINGES AND WITH QUICK OPENING LATCHES AS FOLLOWS:
1. REACH—IN DOORS TO 18 IN. HIGH.
2. TWO (2) #150 HINGES W/ONE #90 LATCH.
HIGH VELOCITY FIRE DAMPER DOORS — DOORS SHALL OPEN TO INSIDE OF DUCT; BE
HELD IN PLACE BY PRESSURE—SENSITIVE LATCHES FOR MANUAL OR VACUUM RELEASE;
FURNISHED WITH CHAIN RETAINER AND HANDLE; SUCH AS UNITED TYPE AR -2. DOORS
SHALL BE INSTALLED DOWNSTREAM OF DAMPERS WHEREVER POSSIBLE.
1IIRI11W:1111140
SHALL BE AS MANUFACTURED BY CERTAINTEED, OWENS—CORNING, MANVILLE,
PITTSBURGH CORNING, ARMSTRONG, OR APPROVED EQUAL. INSULATION SUNDRIES AND
ADHESIVES SHALL BE AS MANUFACTURED BY BENJAMIN FOSTER, CHILDERS, VIMASCO,
OR APPROVED EQUAL. ALL INSULATION SHALL BE SUITABLE FOR INSTALLATION IN A
RETURN AIR PLENUM.
INSULATE ALL SHEETMETAL DUCTWORK EXCEPT EXHAUST DUCTWORK EXTERNALLY WITH
MANVILLE R SERIES MICROLITE TYPE 75 OR 100 INSULATION OR APPROVED EQUAL.
INSULATION TO HAVE TYPE II FSK FACING AND UL FIRE HAZARD CLASSIFICATION OF:
FLAME SPREAD 25, SMOKE DEVELOPED 50, FUEL CONTRIBUTED 50. INSTALL
INSULATION PER SMACNA, FLORIDA MODEL ENERGY EFFICIENCY CODE AND
MANUFACTURER'S RECOMMENDATIONS. ALL INSULATION JOINTS SHALL BE SEALED WITH
GLASS FABRIC AND MASTIC.
MINIMUM INSULATION THICKNESSES ARE AS FOLLOWS:
• SUPPLY AND RETURN AIR IN UNCONDITIONED SPACE: 1.5" (R-6.5 MIN.)
• SUPPLY AND RETURN AIR IN CONDITIONED INTERIOR SPACE: 1.0" (R-4.3 MIN.)
CONTRACTOR SHALL BE RESPONSIBLE FOR FURNISHING AND INSTALLING ADEQUATE AND
PROPER INSULATION AND MOISTURE—SEAL IN A MANNER THAT WILL PERMANENTLY
PREVENT THE ACCUMULATION OF ANY OBJECTIONABLE MOISTURE ON THE EXTERIOR OF
AIR CONDITIONING UNITS, REFRIGERANT PIPING, CONDENSATE DRAIN PIPING, AIR DUCTS
OR OTHER PARTS OF THE SYSTEM. CONTRACTOR SHALL CORRECT THE CAUSE OF ANY
CONDENSATION AND FULLY REPAIR, WITHOUT COST TO THE OWNER, ANY DAMAGES TO
BUILDING SURFACES, FURNISHINGS OR EQUIPMENT CAUSED BY CONDENSATION FROM
THIS SYSTEM, FOR THE FULL PERIOD OF THE GUARANTEE.
HEATING HOT WATER PIPING SPECIFICATION
PIPING
HEATING HOT WATER PIPING BETWEEN J" AND 2" IS TO BE CONSTRUCTED FROM TYPE
1" COPPER WATER TUBE (HARD TEMPER) (ASTOR B-88). PIPING BETWEEN 3" AND 12"
IS TO BE CONSTRUCTED FROM SCHEDULE 40, BLACK STEEL PER ASTM A120 OR ASTM
A53, A OR B, SEAMLESS.
FITTINGS
FITTINGS UP TO 2" ARE TO BE 150 LB., MALLEABLE IRON PER ASTM A197 SCREWED.
OR WROUGHT COPPER FITTINGS WITH SOLDERED JOINTS. FITTINGS BETWEEN 2—J" TO 8•
ARE TO BE SCHEDULE 40, BLACK SEAMLESS WELDING PER ASTM A234.
UNIONS FOR PIPE SIZES UP TO 2" ARE TO BE 300 LB. W.S.P. BRASS GROUND JOINT
TYPE, SCREWED, MALLEABLE IRON.
BALL VALVES UP TO 2" ARE TO BE APOLLO FULL PORT, TWO PIECE 600 PSI BRONZE
BODY STAINLESS STEEL BALL, WITH HANDLE EXTENSION AS REQUIRED TO CLEAR
INSULATION, TEFLON SEATS AND STUFFING BOX RING, LEVER HANDLE, SCREWED ENDS.
2—� VALVES ARE TO BE AMERICAN VALVE 4000 FULL PORT.
INSULATION
SHALL BE AS MANUFACTURED BY OWENS—CORNING, MANVILLE, SCHULLER, KNAUF,
CERTAINTEED, PITTSBURGH CORNING, RDC, AND RUBATEX OR APPROVED EQUAL.
INSULATION SUNDRIES AND ADHESIVES SHALL BE AS MANUFACTURED BY BENJAMIN
FOSTER, CHILDERS, VIMASCO, OR APPROVED EQUAL. ALL INSULATION SHALL BE
SUITABLE FOR INSTALLATION IN A RETURN AIR PLENUM.
INSULATION SHALL BE 1%' THICK PREFORMED SECTIONAL HEAVY DUTY DENSITY
FIBERGLASS INSULATION AND FACTORY APPLIED VAPOR BARRIER, ALL SERVICE JACKET
WITH PRESSURE SENSITIVITY SELF SEALING LONGITUDINAL LAP BUTT STRIPS.
SELECTIVE KEYNOTES O
PENINSULA ENGINEERING INC.
CONSULTING ENGINEERS
ESTABLISHED IN 1977 & � t
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 - 407.246.1688 • EB 3089 D
Copyright — All ideas, designs, methods and plans indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and
developed for use on and in connection with the specified project. None of the Ideas, designs, JOBI:
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
DHM JHM
issue date drawn by approved by
REVISION SCHEDULE
DATE I DESCRIPTION
project number
MECHANICAL MOm2
SPECIFICATIONSsheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
`tt%►tlII#I,,
0ERTO p,4 foo
���` P�, .....• � 'ice
0
o, : �• ENSF••..
.3 313 u'
• J/ � it
ST E OF
. to
FL'.g�e�yfo:' 37Sjav�BURKE HOGUE MILLS, INC.
�1p►i',�` 1130 Business Center Drive, Lake Mary, FL
32746
407.333.2005 AAC000233
W W W B H M U S
I&
1 I I
EXIST. CA
I 1
I I I
I I
+-29x16
J Fr
�'-18x10 — — —�- I
11
I
10 25 C L_-'1
u I '
1 I i 18x12—� 38x16 —
I i�ffffi ��ff�ff 77771 ffx 21x161 1 I °
I -
II All
�� EXIST. CAV ---
I
1
I
" 190 J
\-/2 WAY i —
1
I I I
1 I I= 10x8110x8----�
J° 4-t _TI I------ '
-J L — -� I' I — -L `_- I i 38x16
,-(2 I 118x8 �?
x-21 x12
10x6 -I ------i-----
1 8
_ rl-�--
--- T I +0-16}c8 �—
III \ 1
I II I 11 - I i 38x16'
II I
8x41 k
/ IL ff I�f�fffff off I
°
1 I
— — — — — — —
I
I I I
DEMOLITION PLAN MECHANICAL
SCALE: 1 /4" = 1'-0"
GENERAL NOTES:
1. THE CONTRACTOR SHALL CONFIRM THE EXACT LOCATION AND SIZE OF
EXISTING DUCTWORK. ANY DISCREPANCY THAT MAY ADVERSELY AFFECT
THE PROJECT DESIGN SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT OR ENGINEER FOR RESOLUTION. DO NOT PRICE UNTIL
RESOLUTION IS PROVIDED.
KEYED NOTES:
O1 REMOVE EXISTING RETURN DUCTWORK AT MAIN, AND PREPARE FOR NEW
DUCTWORK. REMOVE EXISTING REGISTERS AND VOLUME DAMPERS. CAP AT LIMIT OF
REMOVAL SYMBOL WERE NEW DUCTWORK WILL NOT BE CONNECTING. INSULATE PER
SPECIFICATIONS.
O2 REMOVE EXISTING SUPPLY DUCTWORK BACK TO LIMIT OF REMOVAL AND CAP
AIRTIGHT TO MATCH EXISTING DUCT CONSTRUCTION WERE NEW DUCTWORK IS NOT
CONNECTING IN NEW WORK. INSULATE PER SPECIFICATIONS.
O3 EXISTING EXHAUST DUCTWORK TO BE REMOVED BACK TO LIMIT OF REMOVAL AND
PATCHED TO MATCH EXISTING DUCT CONSTRUCTION.
O4 EXISTING CONSTANT VOLUME CONTROL BOX (CAV) TO BE INSPECTED, CLEANED AND
RETURNED CONDITION WHERE SCHEDULE AIRFLOWS CAN BE DELIVERED.
An
FAI
I I I
I
1 46x16 —q' i
4
I I
4, '
60 80 I 1
120
J -- - EXIST. CAV29x161 1
— _ 940 CFM 1 6
18x10 — — — i ' — 18x12 38x16 —9-
1 0
-150 LJ 5 1 I I
— — — ISR: _ _ —
I —
STAT ` -1 I x
( I D 360 1 4 1 1 4
1110
1 iGO
g.
_ I EXIST. CAV 10"o' J
LOU LIrm
VNI
----- --I --I-- J'+_ FETA
__X I' I
F.
' I i'
10)
1 190
STATI WAY �
FI
00
I I
LLL
1_ 1ox8 _ �oXB___-
X]
_ I I
L
' _ ' I i 38x16 -
[F/
oil
6 118x8 --,�
�R N 140 1 B 140 1
�-21x121 I
----
I x 10x6 I -- i -----�
I _I____0 OF
I I I
I I
I �
:I I 20
16x8 1
I I I I
1` 140 1 1 1 I i Kv
38x16
CE
ID T I
I I
I — — —7
UL U�
I
I I I; SII 1
I I I I
I I I
1
`---------I---I----I-- 11 _ 200
2 WAY
I I
RENOVATION PLAN MECHANICAL
SCALE:1 /4" = 1'-0"
GENERAL NOTES:
1. THE CONTRACTOR SHALL CONFIRM THE EXACT LOCATION AND SIZE OF
EXISTING DUCTWORK. ANY DISCREPANCY THAT MAY ADVERSELY AFFECT
THE PROJECT DESIGN SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT OR ENGINEER FOR RESOLUTION. DO NOT PRICE UNTIL
RESOLUTION IS PROVIDED.
2. FABRIC FLEXIBLE DUCTWORK IS PERMISSIBLE ONLY ON SUPPLY AIR
SYSTEMS. ALL RETURN AIR DUCTWORK SHALL BE RIGID GALVANIZED
STEEL OR APPROVED METAL FLEX DUCTWORK.
3. EQUIVALENT ROUND OR RECTANGULAR DUCTWORK MAY BE USED.
D
KEYED NOTES=
O1
CONNECT TO EXISTING SUPPLY AIR DUCTWORK WITH SPIN -IN FITTING WITH VOLUME
DAMPER AND EXTEND NEW SUPPLY AIR DUCT TO NEW AIR DIFFUSER IN CEILING GRID.
COORDINATE FINAL DIFFUSER LOCATION WITH CEILING OBSTRUCTIONS.
20
NEW RETURN AIR GRILLE LOCATED IN CEILING GRID. EXTEND NEW 10x6 DUCT TO
CONNECT TO EXISTING ABOVE CEILING. PROVIDE NEW VOLUME DAMPER FOR
0
BALANCING.
O3
EXTEND NEW 8"0 EXHAUST DUCT FROM EXISTING 10x8 EXHAUST MAIN TO
NOURISHMENT ROOM. TERMINATE AT NEW EXHAUST GRILLE. COORDINATE FINAL
GRILLE LOCATION WITH EXISTING AND/OR NEW OBSTRUCTIONS.
O4
CONNECT TO EXISTING RETURN AIR DUCTWORK IN CORRIDOR AND EXTEND NEW DUCT
INTO AREA OF WORK. PROVIDE OFFSETS AND RELOCATE EXISTING OBSTRUCTIONS TO
FACILITATE THE INSTALLATION OF THE NEW RETURN DUCT.
O5
FIELD LOCATE EXITING THERMOSTAT AND RELOCATE TO NEW LOCATION REFLECTED
ON CONSTRUCTION DOCUMENTS. EXTEND EXISTING CONTROLS AS REQUIRED TO
INSTALL IN NEW LOCATION. IF THERMOSTAT IS NOT IN OPERABLE CONDITION
REPLACE WITH NEW EQUIVALENT TO MATCH BUILDING STANDARD.
O
EXISTING CONSTANT VOLUME BOX AND ALL AIR DISTRIBUTION DOWNSTREAM OF BOX
TO BE BALANCED TO AIRFLOWS REFLECTED ON DESIGN DOCUMENTS.
SELECTIVE KEYNOTES D
PENINSULA ENGINEERING EERING I C.
CONSULTING ENGINEERS ^
ESTABLISHED IN 1977 &-yri ht
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 • 407.246.1688 • EB 3089 0
Copyright — All ideas, designs, methods and plans indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and
developed for use an and in connection with the speclfled project. None of the Ideas, designs, JOB#:
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
DHM JHM
issue date drawn by approved by project number
REVISION SCHEDULE
DATE DESCRIPTION
1 11-01-10 AHCA COMMENTS
DEMO/RENO M 2 1
MECHANICALsheet number
■
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
`���IIIIItf1!!!
ER -TO M 0
.•
ENS G �:
F
• r
-�13 cn0. :
�: /IUWAV, ���BURKE HOGUE MILLS, INC.
"'��i►111�1��� 1130 Business Center Drive, Lake Mary, FL
32746
407.333.2005 AAC000233
W W W B H M U S C 0 M
STRAP RM038 TRAPEZE HAN(`lS
1/2"MIN.
�- STRAP OF ROD
HANGER STRAPS —UNLESS FOOT OF STRAP I ANGLE
IS PLACED UNDER A
BOTTOM REINFORCEMENT
— 60" MAX i > 60"
12" MAX.
SPACING
< I.–L
2" MIN.
10 SHEETMETAL SCREWS _1 2"fes
MIN SIZE BOLT(S) L MAX. 10"-0"
BOTTOM SCREWS MAY BE FOR LOAD ON CENTER
OMITTED IF HANGER LOOPS
WIRE F
ROUND DUCT
1 1/2" STRAP WIRE STRAP
LOAD RATED HANGER
FASTENERS 1 1/2" STRAP
IANGER RODIr-ROUND DUCT HANGER 1]
ROUND DUCT
10" DIA. MAX 50" DIA. MAX 50" DIA. MAX
BAND OF SAME SIZE
AS HANGER STRAP
DUCT SUPPORT DETAILS
ROUND BRANCH
DUCT
VOLUME DAMPER
SPIN–IN BELLMOUTH
FITTING
ROUND BRANCH "A"
DUCT
VOLUME DAMPER
RECTANGULAR
TO ROUND TAP
FLOW
"B"
RETURI
DUCTW
SCALE: NONE
BRANCH DUCT DETAILS
SCALE: NONE
PAINT INTERIOR OF
DUCT BLACK. USE
NON–TOXIC PAINT
EQUAL TO NECK SIZE
RETURN/EXHAUST AIR LACOUSTiCAL
DEVICE (SEE SCHEDULE) CEILING TiLE
RETURN GRILLE DETAIL
NOT TO SCALE
SPIN–IN BELL MOUTH
SEAL AIRTIGHT WITH GLASS FAB AND MASTIC
SPIN–IN FITTING WITH
VOLUME DAMPER
DRAWBAND CLAMP
' INSULATED DUCT
SEAL PENETRATION
MAIN BRANCH
SPIN -IN COLLAR FITTING DETAIL
NOT TO SCALE
x
PIVOT DAMPER a L`'
(VD)0- w
BEARING
TRUNK
DUCT–\
BRANCH DUCT
QUADRANT
LOCKING LEVER
ANGULAR
TAP COLLAR
AIR FLOW(SUPPLY)
AIR FLOW RgVRN EXHAUST
SUPPLY RETURN AND EXHAUST
SCALE NOT TO SCALE
VOLUME DAMPER
RIGID DUCT
CEILING J
NEW DIFFUSER
NOTE:
DOES NOT PERMIT CONICAL FITTING.
VOLUME DAMPER
IANGER (TYP.)
SUPPORT
STRAP
HANGER (TYP.)
SUPPORT
STRAP
_: u
RIGID DUCT
CEILING
NEW DIFFUSER
CEILING DIFFUSER DETAIL
NOT TO SCALE
BAR JOISi
3–WAY MODULATING VALVE
HWS/HWR
we] w:PiN
INSULATION
SEAL AIRTIGHT
INSULATION
SEAL AIRTIGHT
EXISTING FRAME
NEW CONC. DECK
DROP–IN
ANCHOR
INC ATR
ZINC ATR
HANGER
EXISTING CONC. DECK
I,L•LIe1:1Z
ROD COUPLING POWDER DRIVEN STUD
ZINC ATR
PIPE HANGER
PIPE HANGER DETAIL
SCALE: NONE
TO SPACE
REHEAT COIL CONTROL vv...
SEQUENCE OF OPERATION
1. BMS TO MONITOR AND CONTROL REHEAT COIL.
2. ZONE THERMOSTAT TO MODULATE CONTROL VALVE TO MAINTAIN SPACE TEMPERATURE SET POINT
(ADJUSTABLE).
3. COIL DISCHARGE AIR TEMPERATURE TO BE MONITORED BY BMS.
4. BMS TO MONITOR SPACE TEMPERATURE.
SELECTIVE KEYNOTES O
MAIN DUCT
DIFFUSERS, REGISTERS
AND GRILLES
SCHEDULE
TRANSITION
TO SIZE
MAX.
MAX. NC
MAX. PD
(IN. WG.)
EQUAL TO
DEPTH AND
FINISH
MANUFACTURER
MODEL NUMBER
WIDTH OF
BRANCH DUCTS
LOUVERED FACE SUPPLY DIFFUSER17
0.04
_
REFER TO PLANS
WHITE
TITUS
TMS
FOR BRANCH
DUCT
LOUVERED FACE SUPPLY DIFFUSER
17
0.04
12"x12"/8"0
STEEL
SIZES
11TUS
FLOW
i
1
©
RETURN/EXHAUST/TRANSFER GRILLE
I
0.073
12"x12"/10"x10"
STEEL
WHITE
TITUS
50F
1
VOLUME DAMPER
RETURN/EXHAUST/TRANSFER GRILLE
RECTANGULAR
0.095
24"x24"/14"x14"
STEEL JWHITE
BRANCH DUCT
TiTUS
50F
1
NOTES:
VOLUME DAMPER
1. USE TYPE "A" CONNECTION
ONLY FOR BRANCHES TO
–
SINGLE DIFFUSERS, OR
1. ALL HVAC DUCTWORK, UNITS, REGISTERS, AND GRILLES SHALL BE SECURELY SUPPORTED FROM THE
GRILLES FROM THE MAIN.
STRUCTURAL MEMBERS AND NOT FROM THE ACOUSTICAL TiLE CEILING.
2. USE TYPE "B" OR "C" BRANCH
FLOW
WHERE BRANCH FLOW IS 20%
OR LESS OF MAIN.
"C"
3. USE TEE SPLIT WHERE BRANCH FLOW
IS MORE THAN 20% OF MAIN.
BRANCH DUCT DETAILS
SCALE: NONE
PAINT INTERIOR OF
DUCT BLACK. USE
NON–TOXIC PAINT
EQUAL TO NECK SIZE
RETURN/EXHAUST AIR LACOUSTiCAL
DEVICE (SEE SCHEDULE) CEILING TiLE
RETURN GRILLE DETAIL
NOT TO SCALE
SPIN–IN BELL MOUTH
SEAL AIRTIGHT WITH GLASS FAB AND MASTIC
SPIN–IN FITTING WITH
VOLUME DAMPER
DRAWBAND CLAMP
' INSULATED DUCT
SEAL PENETRATION
MAIN BRANCH
SPIN -IN COLLAR FITTING DETAIL
NOT TO SCALE
x
PIVOT DAMPER a L`'
(VD)0- w
BEARING
TRUNK
DUCT–\
BRANCH DUCT
QUADRANT
LOCKING LEVER
ANGULAR
TAP COLLAR
AIR FLOW(SUPPLY)
AIR FLOW RgVRN EXHAUST
SUPPLY RETURN AND EXHAUST
SCALE NOT TO SCALE
VOLUME DAMPER
RIGID DUCT
CEILING J
NEW DIFFUSER
NOTE:
DOES NOT PERMIT CONICAL FITTING.
VOLUME DAMPER
IANGER (TYP.)
SUPPORT
STRAP
HANGER (TYP.)
SUPPORT
STRAP
_: u
RIGID DUCT
CEILING
NEW DIFFUSER
CEILING DIFFUSER DETAIL
NOT TO SCALE
BAR JOISi
3–WAY MODULATING VALVE
HWS/HWR
we] w:PiN
INSULATION
SEAL AIRTIGHT
INSULATION
SEAL AIRTIGHT
EXISTING FRAME
NEW CONC. DECK
DROP–IN
ANCHOR
INC ATR
ZINC ATR
HANGER
EXISTING CONC. DECK
I,L•LIe1:1Z
ROD COUPLING POWDER DRIVEN STUD
ZINC ATR
PIPE HANGER
PIPE HANGER DETAIL
SCALE: NONE
TO SPACE
REHEAT COIL CONTROL vv...
SEQUENCE OF OPERATION
1. BMS TO MONITOR AND CONTROL REHEAT COIL.
2. ZONE THERMOSTAT TO MODULATE CONTROL VALVE TO MAINTAIN SPACE TEMPERATURE SET POINT
(ADJUSTABLE).
3. COIL DISCHARGE AIR TEMPERATURE TO BE MONITORED BY BMS.
4. BMS TO MONITOR SPACE TEMPERATURE.
SELECTIVE KEYNOTES O
ANCHOR TO
STRUCTURE
LJ LJ
HANGER RODS. LOCATED
MIN. 2'-0" TO CLEAR ALL VALVE
CONTROLS
FLEX DUCT
(TYPICAL)
CAV
/SUPPLY DUCT. SEE
SEE PLAN FOR SIZE SIZE DUCT PER DRAWINGS PLAN FOR SIZE
VPROVIDE TRANSITION
AS REQUIRED
CAV CONNECTION DETAIL
NO SCALE
CLOSE CEILING SR
SEAL ALL JOINTS
PERIMETER WiTH D
CLOSE OPEN DUCTS
POLY. SEAL WITH DU
SEAL AROUND ALL PIPE A'.
PENETRATIONS IN THE PAF
BARRIER WITH DUCT TAPE
CLOSE SPA
rl rfr -Mf-A Trr% 1AI^^r, \1 All rn
TYPICAL VISOUEEN DUST PROOF PARTITION
"A
SUPPORT STRAP. INSTALL A MINIMUM OF 6'-0"
ON CENTER. DO NOT "KINK" FLEX DUCT SAG MAX
AT 1' PER 10'-0"
CONNECT TO EXISTING
DUCTWORK
TAPE OR PANDUIT CONNECT10N TAPE OR PANDUIT CONNECTION
AT AIR DEVICE COLLAR AND AT AIR DEVICE COLLAR AND
SEAL AIR TiGHT SEAL AIR TIGHT
CEILING J
FLEXIBLE DUCT CONNECTION DETAIL
NO SCALE
3/8 " BALL VALVE AIR
VENT
T&P (3—WAY CONTROL VALVE
TAP
REFER TO
DRAWING
FOR RUNOUT
PIPE SIZES.
I �
UNIUN t I THUAL)yhl'Y
BALANCING VALVE (TYP)
WSBALL VALVE (TYPICAL)
TEMPORARY FLUSHING LOOP, CONNECTION, LINE
SIZE. REMOVE AND CAP WHEN SYSTEM IS PROVEN
CLEAN FROM FLUSHING.
NOTE:
TERMINAL BOXES
AND FOR DUCT
DIFFUSERS, REGISTERS
AND GRILLES
SCHEDULE
MARK
TYPE
MAX.
MAX. NC
MAX. PD
(IN. WG.)
SIZE INCHES
(Face/Neck)
MATERIAL
FINISH
MANUFACTURER
MODEL NUMBER
REMARKS
QA
LOUVERED FACE SUPPLY DIFFUSER17
0.04
24"x24"/10"0
STEEL
WHITE
TITUS
TMS
1
©
LOUVERED FACE SUPPLY DIFFUSER
17
0.04
12"x12"/8"0
STEEL
WHITE
11TUS
TMS
1
©
RETURN/EXHAUST/TRANSFER GRILLE
25
0.073
12"x12"/10"x10"
STEEL
WHITE
TITUS
50F
1
QD
RETURN/EXHAUST/TRANSFER GRILLE
25
0.095
24"x24"/14"x14"
STEEL JWHITE
TiTUS
50F
1
EXISTING DIFFUSER/GRILLE TO REMAIN
NOTES:
1. ALL HVAC DUCTWORK, UNITS, REGISTERS, AND GRILLES SHALL BE SECURELY SUPPORTED FROM THE
STRUCTURAL MEMBERS AND NOT FROM THE ACOUSTICAL TiLE CEILING.
ANCHOR TO
STRUCTURE
LJ LJ
HANGER RODS. LOCATED
MIN. 2'-0" TO CLEAR ALL VALVE
CONTROLS
FLEX DUCT
(TYPICAL)
CAV
/SUPPLY DUCT. SEE
SEE PLAN FOR SIZE SIZE DUCT PER DRAWINGS PLAN FOR SIZE
VPROVIDE TRANSITION
AS REQUIRED
CAV CONNECTION DETAIL
NO SCALE
CLOSE CEILING SR
SEAL ALL JOINTS
PERIMETER WiTH D
CLOSE OPEN DUCTS
POLY. SEAL WITH DU
SEAL AROUND ALL PIPE A'.
PENETRATIONS IN THE PAF
BARRIER WITH DUCT TAPE
CLOSE SPA
rl rfr -Mf-A Trr% 1AI^^r, \1 All rn
TYPICAL VISOUEEN DUST PROOF PARTITION
"A
SUPPORT STRAP. INSTALL A MINIMUM OF 6'-0"
ON CENTER. DO NOT "KINK" FLEX DUCT SAG MAX
AT 1' PER 10'-0"
CONNECT TO EXISTING
DUCTWORK
TAPE OR PANDUIT CONNECT10N TAPE OR PANDUIT CONNECTION
AT AIR DEVICE COLLAR AND AT AIR DEVICE COLLAR AND
SEAL AIR TiGHT SEAL AIR TIGHT
CEILING J
FLEXIBLE DUCT CONNECTION DETAIL
NO SCALE
3/8 " BALL VALVE AIR
VENT
T&P (3—WAY CONTROL VALVE
TAP
REFER TO
DRAWING
FOR RUNOUT
PIPE SIZES.
I �
UNIUN t I THUAL)yhl'Y
BALANCING VALVE (TYP)
WSBALL VALVE (TYPICAL)
TEMPORARY FLUSHING LOOP, CONNECTION, LINE
SIZE. REMOVE AND CAP WHEN SYSTEM IS PROVEN
CLEAN FROM FLUSHING.
NOTE:
TERMINAL BOXES
AND FOR DUCT
MOUNTED
HOT WATER HEATING
COILS.
PIPING AT
REHEAT
COIL
DETAIL
NOT TO SCALE
PENINSULA ENGINEEMNIG INC"
CONSULTING ENGINEERS
ESTABLISHED IN 1977 �2 09ht
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 - 407.246.1688 EB 3089 p
Copyright — All ideas, designs, methods and plans Indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and JOBS:
developed for use on and in connection with the specified project None of the ideas, designs.
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
DHM JHM
issue date drawn by approved by
REVISION SCHEDULE
DATE DESCRIPTION
1 11-01-10 AHCA COMMENTS
project number
DETAILS AND M3E1
SCHEDULES sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
`,�11111111//f
�'.•ENS��..Gt�`N
p 7313
OF UJ –
0.o, r.
19S®.cA•' �'' Pj�,
FL'�,ijSP�l�r�,I�`� BURKE HOGUE MILLS, INC.
if 1130 Business Center Drive, Lake Mary, FL
32746
407.333.2005 AAC000233
W W W B H M U S C O M
SYSTEM NO. W -L-1001
(FORMERLY SYSTEM NO. 147)
F RATINGS - 1, 2, 3 AND 4 HR (SEE ITEMS 2 AND 3)
T RATINGS - 0, 1, 2, 3 AND 4 HR (SEE ITEM 3)
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
SECTION A -A
t WALL ASSEMBLY - THE 1, 2, 3 OR 4 HR FIRE -RATED GYPSUM WALLBOARD/STUD WALL
ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED
IN THE INDIVIDUAL 0300 OR U400 SERIES WALL OR PARTITION DESIGNS IN THE UL FIRE
RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STWS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS (MAX 2 H FIRE
RATED ASSEMBLIES) OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF
NOM 2 BY 4 IN. LUMBER SPACED 16 IN. OC WITH NOM 2 BY 4 IN. LUMBER END
PLATES AND CROSS BRACES. STEEL STUDS TO BE MIN 3-5/8 IN WIDE BY 1-3/8 IN
DEEP CHANNELS SPACED MAX 24 IN. OC.
EL GYPSUM BOARD 0 - NOM 1/2 OR 5/8 IN. THICK, 4 FT. WIDE WITH SQUARE OR
TAPERED EDGES. THE GYPSUM WALLBOARD TYPE, THICKNESS, NUMBER OF
LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE
INDIVIDUAL 0300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY.
MAX DIAM OF OPENING IS 26 IN.
2. THROUGH PENETRANT - ONE METALLIC PIPE, CONDUIT OR TUBING INSTALLED
EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE
ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING
SHALL BE MIN OF 0 IN. (POINT CONTACT) TO MAX 2 IN. PIPE, CONDUIT OR
TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE
FOLLOWING TYPES AND SIZES OF METALUC PIPES, CONDUITS OR TUBING MAY BE
USED.
A. STEEL PPE - NOM 24 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. FiONI PPE - NOM 24 IN. DIAM (OR SMALLER) SERVICE WEIGHT (OR HEAVIER) CAST
IRON SOIL PIPE, NOM 12 IN. DIAM (OR SMALLER) OR CLASS 50 (OR
HEAVIER) DUCTILE IRON PRESSURE PIPE.
C. COMM - NOM 6 IN. DIAM (OR SMALLER) STEEL CONDUIT OR NOM 4 IN. DIAM
(OR SMALLER) STEEL ELECTRICAL METALLIC TUBING.
D. COPPER TUBM - NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
E. COPPER PPE - NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
F. THROUGH! PBNETRATNG PRODUCT* - THE FOLLOWING TYPES OF STEEL FLEXIBLE
METAL GAS PIPING MAY BE USED:
t NOM 2 IN. DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING
ON PIPING MAY OR MAY NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL
ASSEMBLY.
OMEGA FLEX NO.
2 NOM 1 IN. DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING
ON PIPING MAY OR MAY NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL
ASSEMBLY.
TITS( CORP.
A BUDDY CO.
3 NOM 1 IN. DIAM (OR SMALLER) STEEL FLEXIBLE METAL GAS PIPING. PLASTIC COVERING
ON PIPING MAY OR MAY NOT BE REMOVED ON BOTH SIDES OF FLOOR OR WALL
ASSEMBLY.
WARD MFG. INC.
& FLL VOD OR CAVITY MATERIAL* - CAULK OR SEALANT - MIN 5/8. 1-1 /4,1-7/8 AND 2-1 /2
IN. THICKNESS OF CAULK FOR 1, 2, 3 AND 4 HR RATED ASSEMBLIES, RESPECTIVELY, APPLIED
WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF THE WALL MIN 1/4 IN. DIAM BEAD OF CAULK
APPLIED TO GYPSUM BOARD/PENETRANT INTERFACE AT POINT CONTACT LOCATION ON BOTH
SIDES OF WALL. THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE
HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED, AS SHOWN IN THE
FOLLOWING TABLE. THE HOURLY T RATING OF THE FIRESTOP SYSTEM IS DEPENDENT UPON THE
TYPE OR SIZE OF THE PIPE OR CONDUIT AND THE HOURLY FIRE RATING OF THE WALL ASSEMBLY
IN WHICH IT IS INSTALLED, AS TABULATED BELOW:
MAX PPE OR CONDUIT
DIAM IK
F RATING
HR
T RATING
FIR
1
1 or 2
0+, 1 or 2
1
3 or 4
3 or 4
4
1 or 2 1
0
6
3 or 4 1
0
12
1 or 2 1
0
+ WHEN COPPER PIPE IS USED, T RATING IS 0 HR.
3M COMPANY - CP 25 WB+ CAULK OR FB -3000 WT SEALANT.
*BEARING THE UL CLASSIFICATION MARKING
NOTE: CONTRACTOR SHALL PROVIDE A UL LISTED 3M FIRE SEALANT OR APPROVED EQUAL.
ABOVE DRAWING REPRESENTS A 3M PRODUCT AND IT'S INSTALLATION. MATERIAL IS TYPICAL OF
ONE METHOD OF FIRE PROTECTION AND IT'S INSTALLATION. CONTRACTOR SHALL CONFIRM WITH
3M (MINNESOTA MINING & MFG. CO.) OR APPROVED EQUAL FOR THE EXACT MATERIAL,
REQUIREMENTS, AND INSTALLATION INSTRUCTIONS FOR THE SPECIFIC TYPE OF INSTALLATION. THE
CONTRACTOR SHALL PROVIDE A COPY OF THESE DOCUMENTS UPON REQUEST.
SYSTEM NO. CAJ1027
(FORMERLY SYSTEM NO. 202)
F RATINGS - 3 HR
T RATING - 0 HR
SECTION A -A
1 FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. THICK LIGHT WEIGHT OR NORMAL WEIGHT (100-
150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE
BLOCKS*. MAX DIAM OF THROUGH OPENING IS 12-1/4 IN.
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN FIRE RESISTANCE DIRECTORY FOR
NAMES OF MANUFACTURERS.
2 THROUGH P - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED
EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. MIN ANNULAR
SPACE BETWEEN PIPE, CONDUIT OR TUBING AND EDGE OF OPENING IS 0 IN. (POINT
CONTACT). MAX ANNULAR SPACE IS DEPENDENT ON PIPE, CONDUIT OR TUBING TYPE AND
SIZE AS WELL AS THE F RATING OF THE SYSTEM, AS SHOWN IN THE TABLE BELOW. PIPE,
CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE WALL ASSEMBLY.
THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - NOM 10 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. CONDUIT - NOM 6 IN. DIAM (OR SMALLER) RIGID STEEL CONDUIT.
C. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL
CONDUIT.
D. COPPER TUBING -NOM 3 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
E. COPPER PIPE - NOM 3 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
F. IRON PIPE - NOM 10 IN. DIAM (OR SMALLER) CAST OR DUCTILE PIPE.
PPE
CONDUIT OR
TUBING TYPE
MAX NOM PPE
CO DIRT OR TUBING
DIAM, N.
F
RATNG
HR
MAX ANNULAR
SPACE
N.
A or F
10
3
3/4
B
6
3
3/4
C
4
3
1-1/2
D AND E
3
3
3/4
D AND E
3
2
7/8
3. FILL, VOID, OR CAVITY MATERIALS* - PUTTY - MOLDABLE PUTTY MATERIAL KNEADED BY
HAND AND APPLIED TO FILL ANNULAR SPACE TO A MIN DEPTH OF 1 IN., FLUSH WITH TOP
SURFACE OF FLOOR. IN WALL ASSEMBLIES, REQUIRED PUTTY THICKNESS TO BE
INSTALLED SYMMETRICALLY ON BOTH SIDES OF WALL.
MINNESOTA MINING & MFG. CO. - MPS -2+.
*BEARING THE UL CLASSIFICATION MARKING
NOTE CONTRACTOR SHALL PROVIDE A UL LISTED 3M FIRE SEALANT OR APPROVED EQUAL.
ABOVE DRAWING REPRESENTS A 3M PRODUCT AND IT'S INSTALLATION. MATERIAL IS TYPICAL OF
ONE METHOD OF FIRE PROTECTION AND IT'S INSTALLATION. CONTRACTOR SHALL CONFIRM WITH
3M (MINNESOTA MINING & MFG. CO.) OR APPROVED EQUAL FOR THE EXACT MATERIAL,
REQUIREMENTS, AND INSTALLATION INSTRUCTIONS FOR THE SPECIFIC TYPE OF INSTALLATION. THE
CONTRACTOR SHALL PROVIDE A COPY OF THESE DOCUMENTS UPON REQUEST.
ELECTRICAL SPECIFICATIONS - DIVISION 16:
SECTION 16000- GENERAL PROVISIONS
A. PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT FOR A COMPLETE AND PROPERLY
OPERATING ELECTRICAL SYSTEM. INCLUDE NECESSARY FEES AND PERMITS WITHIN
BASE BID.
B. CODES AND STANDARDS
1. ALL WORK SHALL BE PROVIDED IN ACCORDANCE WITH ALL GOVERNING AUTHORITIES
LAWS, ORDINANCES, CODES, RULES AND REGULATIONS WHICH GOVERN THE WORK.
2. THE APPLICABLE GOVERNING AUTHORITIES LAWS, ORDINANCES, CODES, RULES AND
REGULATIONS SHALL CONSIST BASICALLY OF, BUT NOT LIMITED TO, THE FOLLOWING
(LATEST EDITIONS):
3. NFPA-70-2008, NATIONAL ELECTRICAL CODE.
4. NFPA-99-2005, STANDARD FOR HEALTH CARE FACILITIES
5. NFPA-101 (2006), LIFE SAFETY CODE.
6. NFPA-110 (2005), STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS.
7. NFPA 241 (2004), STANDARD FOR SAFEGUARDING BUILDING CONSTRUCTION AND
DEMOLITION OPERATIONS.
8. NFPA-1 UNIFORM FIRE CODE, 2006
9. CHAPTER 59A-3, 2007 FLORIDA ADMINISTRATIVE CODE
10. CHAPTER 395, FLORIDA STATUTES
11. CHAPTER 780, LIGHTNING PROTECTION CODE (2004).
12. 69A-53, F.A.C., STATE FIRE PREVENTION CODE (2007).
13. NFPA-72-2002, NATIONAL FIRE ALARM CODE.
14. 2007 FLORIDA FIRE PREVEN11ON CODE AND THE CURRENT ADOPTED CODES AND
STANDARDS BY iNE STATE OF FLORIDA.
15. 2006 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES.
16. FLORIDA BUILDING CODE 2007 CHAPTER 419.
17. FLORIDA AMERICANS WITH DISABILITIES, 2007 AS DESCRIBED IN ACCESSIBILITY
REQUIREMENTS MANUAL, DEPARTMENT OF COMMUNITY AFFAIRS.
18. LATEST EDITION OF ALL OTHER NFPA ARTICLES NOT LISTED, AS ADOPTED BY THE
STATE FIRE MARSHALL.
19. REQUIREMENTS OF THE FLORIDA BUILDING CODE 2007 WITH 2009
SUPPLEMENTS AND LOCAL AMMENDMENTS.
20. AMERICANS WITH DISABIUTY ACT, JANUARY 26, 1992.
21. ALL WORK SHALL BE PROVIDED IN ACCORDANCE WITH ALL ANSI STANDARDS
ADOPTED BY THE GOVERNING AUTHORITY. THIS INCLUDES BUT IS NOT LIMITED TO
SPECIAL REQUIREMENTS FOR FIRE ALARM, ELEVATORS AND HANDICAP PERSONS.
22. IT IS THE INTENT OF THE CONTRACT DOCUMENTS TO COMPLY WITH ALL
APPLICABLE GOVERNING AUTHORITIES, LAWS, ORDINANCES, CODES, RULES,
REGULA11ONS AND STANDARDS. WHERE DISCREPANCIES OCCUR, NOTIFY THE
ARCHITECT/ENGINEER, IN WRITING, AND ASK FOR INTERPRETATION A MINIMUM OF
TEN DAYS PRIOR TO THE BID OF THE CONTRACT DOCUMENTS. SUBMISSION OF A
PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT THE CONTRACTOR SHALL MEET
THIS INTENT. NO ADDITIONAL COMPENSATION SHALL BE PROVIDED FOR WORK
REQUIRED FROM INTERPRETATIONS OF DISCREPANCIES AFTER THE BID.
23. REQUIREMENT OF THE CITY OF ORLANDO
C. PERMITS AND INSPECTIONS: OBTAIN AND MAKE ALL PAYMENTS FOR PERMITS AND
INSPECTIONS REQUIRED. AT THE COMPLE11ON OF THE PROJECT AND BEFORE FINAL
ACCEPTANCE OF THE ELECTRICAL WORK, PROVIDE EVIDENCE OF FINAL INSPECTION
AND APPROVAL BY THE AUTHORITIES HAVING JURISDICTION.
D. CONTRACTOR SHALL THOROUGHLY INVESTIGATE SITE BEFORE BIDDING. NO CHANGES
WILL BE ALLOWED IN CONTRACT PRICE FOR WORK REQUIRED TO COMPLY WITH
EXISTING CONDITIONS.
E. ALL ELECTRICAL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER.
F. PROVIDE PHENOLIC NAMEPLATES ON ALL PANELBOARDS, SWITCHBOARDS,
DISCONNECTS, TRANSFORMERS, ETC, INDICATING DESIGNATION, CIRCUIT NUMBER(S),
VOLTAGE AND WHERE UNIT IS FED FROM. SECURE NAMEPLATES WITH AT LEAST
TWO SCREWS OR RIVETS. CEMENTING AND ADHESIVE INSTALLATION IS NOT
ACCEPTABLE.
G. ELECTRICAL CONTRACTOR SHALL EXAMINE ARCHITECTURAL, MECHANICAL, PLUMBING AND FIRE
PROTECTION DRAWINGS FOR ESTIMATING AND CONSTRUCTION OF THIS PROJECT. SUBMISSION
OF A PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN
MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED FOR CONNECTING
AND ENERGIZING EQUIPMENT SHOWN ON THOSE DRAWINGS WILL NOT BE RECOGNIZED.
ELECTRICAL CONTRACTOR SHALL COMMUNICATE DISCREPANCIES TO ENGINEER PRIOR
SUBMITTING A BID.
H. PROVIDE TEMPORARY POWER AND LIGHTING. INCLUDE PERMITS AND UTiUTY COMPANY
FEES FOR TEMPORARY SERVICES WITHIN BASE BID.
I. CONTRACTOR SHALL SCHEDULE ALL DOWN-TIME WITH THE OWNER PRIOR TO
BEGINNING THE WORK. PREMIUM/OVERTIME RATES MAY BE REQUIRED AND MUST BE
INCLUDED IN BASE BID.
J. CONTRACTOR SHALL THOROUGHLY REVIEW CONSTRUCTION DOCUMENTS. WHEN
CONFLICTS ARISE WITHIN CONSTRUCTION DOCUMENTS, CONTRACTOR SHALL NOTIFY
ENGINEER PRIOR TO SUBMITTING A BID. SUBMISSION OF A BID SHALL INDICATE
THAT CONTRACTOR THOROUGHLY REVIEWED CONSTRUCTION DOCUMENTS.
K. WHEN ENGINEER IS NOT AVAILABLE, OR TIME DOES NOT PERMIT, CONTRACTOR SHALL
INCLUDE THE MOST STRINGENT (COSTLY) REQUIREMENTS WITHIN BASE BID.
L. CONTRACTOR SHALL COORDINATE WITH UTILITY COMPANY AND TELECOMMUNICATION
COMPANY FOR LOCATIONS AND REQUIREMENTS PRIOR TO COMMENCEMENT OF WORK.
M. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING MANUFACTURERS,
SUB CONTRACTORS, VENDORS, AND SUPPLIERS, WITH A COPY OF THESE
SPECIFICATIONS.
N. GUARANTEE ALL ELECTRICAL SYSTEM MATERIALS AND WORKMANSHIP TO BE FREE FROM
DEFECTS FOR A PERIOD OF ONE (1) YEAR FROM THE DATE OF FINAL ACCEPTANCE AND
PROPERLY CORRECT LATENT DEFECTS ARISING WITHIN THIS PERIOD UPON NOTIFICATION BY
THE OWNER'S REPRESENTATIVE WITHOUT ADDITIONAL COMPENSATION.
0. DAILY REMOVE REFUSE AND DEBRIS ACCUMULATING FROM ELECTRICAL CONSTRUCTION AND
PRIOR TO ACCEPTANCE OF THIS WORK, LEAVE THE PREMISES "BROOM CLEAN" INSOFAR AS
AFFECTED BY ELECTRICAL WORK.
P. EQUIPMENT AND DESIGN OF SYSTEMS INDICATED ON THE DESIGN DRAWINGS AND WITHIN THESE
SPECIFICATIONS SHALL BE CONSIDERED AS "SPECIFIED STANDARD" OF QUALITY. NO
SUBSTITUTIONS SHALL BE MADE WITHOUT WRITTEN APPROVAL OF THE ENGINEER AT LEAST 10
DAYS PRIOR TO BID DATE.
ANY DEVIATION FROM SPECIFIED EQUIPMENT THAT AFFECT THE INSTALLATION, OPERATION,
PERFORMANCE, QUALITY OR LONGEVITY OF THE ELECTRICAL SYSTEMS AS DEFINED HEREIN,
SHALL BE REPLACED BY THE ELECTRICAL CONTRACTOR WITH NO ADDITIONAL COST TO THE
CLIENT, IN ADDITION, ELECTRICAL CONTRACTOR SHALL PROVIDE THE ENGINEERING WITH
PHOTOMETRIC FLOOR PLANS FOR ANY LIGHTING FIXTURES CHANGES FOR APPROVAL AT LEAST
10 DAYS PRIOR TO BID DATE.
SECTION 16050 - BASIC MATERIALS AND METHODS
A. RACEWAYS AND FITTINGS: ALL RACEWAYS AND FITTINGS SHALL BE GALVANIZED
RIGID STEEL OR INTERMEDIATE METAL CONDUIT WITH LOCKNUTS AND BUSHINGS, WITH
THE EXCEPTION THAT WHERE SPECIFICALLY ALLOWED BY THE NATIONAL ELECTRICAL
CODE AND APPLICABLE LOCAL CODES. ELECTRICAL METALLIC TUBING (E.M.T) MAY BE
USED FOR ALL INTERIOR EXPOSED AND CONCEALED WORK WHERE IT IS NOT SUBJECT
TO PHYSICAL DAMAGE OR CORROSION. FITTINGS SHALL BE STEEL SET SCREW TYPE.
NO PVC, BX OR MC CABLE ALLOWED. INSTALL EXPANSION FITTINGS IN RACEWAYS
EVERY 200' LINEAR RUN OR WHEREVER STRUCTURAL EXPANSION JOINTS ARE
CROSSED.
B. CONDUCTORS: FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE (#12 UNLESS
OTHERWISE NOTED) THWN COPPER. NO ALUMINUM SHALL BE PERMITTED UNLESS
SPECIFICALLY NOTED OTHERWISE. INSTALL ALL WIRING IN CONDUIT OR APPROVED
RACEWAYS UNLESS OTHERWISE INDICATED. PROVIDE #1OAWG FOR BRANCH CIRCUITS
OVER 100 FEET IN LENGTH TO ACCOUNT FOR VOLTAGE DROP. PROVIDE #10 GROUND
TO CORRESPOND. ALL BRANCH CIRCUITS SHALL CARRY A GROUNDING EQUIPMENT
CONDUCTOR, AND BE WIRED WITH COLOR- CODED WIRE WITH THE SAME COLOR USED
FOR A PHASE THROUGHOUT. COLOR -CODE SHALL BE AS FOLLOWS:
120/240 VOLT 10: PHASE A - BLACK: PHASE B - RED
NEUTRAL - WHITE; GROUND - GREEN.
120/208 VOLT 30: PHASE A - BLACK: PHASE B - RED; PHASE C - BLUE;
NEUTRAL -WHITE; GROUND - GREEN.
277/480 VOLT 30: PHASE A -BROWN; PHASE B - ORANGE; PHASE C -
YELLOW; NEUTRAL - LIGHT GREY, GROUND -
GREEN.
A DEDICATED NEUTRAL CONDUCTOR SHALL BE INSTALLED FOR ALL CIRCUITS DEDICATED
OR NOT. NO SHARING OF THE NEUTRAL SHALL BE PERMITTED.
C. FINAL CONNECTIONS TO MOTORS
OR EQUIPMENT SUBJECT TO VIBRATION SHALL BE
MADE
UP WITH GREENFIELD IN DRY LOCATIONS AND WITH JACKETED, LIQUID- TIGHT,
FLEXIBLE, GALVANIZED STEEL CONDUIT IN WET OR DAMP LOCATIONS. LOCATE ALL
DEVICES
AND EQUIPMENT WHERE
SHOWN ON DRAWINGS. ALL DIMENSIONS SHOWN ON
THE
DRAWINGS ARE FROM FINISHED FLOOR TO THE CENTER OF THE DEVICE UNLESS
OTHERWISE INDICATED. STANDARD
MOUNTING HEIGHTS ARE AS FOLLOWS:
CONNECTED
DEVICES
HEIGHT AFF AT DEVICE CENTER
1.
ELECTRICAL OUTLETS
18"
2.
ELECTRICAL OUTLETS ABOVE
COUNTER 42"
3.
TELEPHONE
18"
4.
WALL TELEPHONE
54"
5.
LIGHT SWITCHES
46"
6.
THERMOSTATS
SEE MECH SPECS
7.
FIRE ALARM DEVICES - 80"
TO BOTTOM OF GLASS/& PER LATEST ADA REGULATIONS
8.
DISCONNECT SWITCHES
60" TO TOP
9.
PANELBOARDS
72" TO TOP
10.
EXIT SIGNS
AS NECESSARY
11.
SPECIAL DEVICES
AS NECESSARY
D. DISCONNECT SWITCHES: HEAVY DUTY, FUSED OR NON-FUSED AS CALLED FOR ON
PLAN DRAWINGS. PROVIDE SOLID NEUTRAL CONNECTION WHERE REQUIRED. USE
NEMA -1 INDOORS AND NEMA -3R OUTDOORS. ALL DISCONNECT SWITCHES SHALL BE
PROVIDED WITH GROUND KIT.
E. PROVIDE PANELBOARDS OF THE DEAD FRONT TYPE, NO LESS THAN 20 INCHES WIDE
AND 5 3/4 INCHES DEEP WITH QUANTITY OF BRANCH CIRCUITS/CIRCUIT BREAKERS
AS INDICATED ON THE PANELBOARD SCHEDULE WITH THE VOLTAGE. PHASE AND
AMPERE RATING AS REQUIRED. ALL PANELBOARDS SHALL HAVE PHASE SEQUENCE
CIRCUITS AND BOLT -ON CIRCUIT BREAKERS. MAIN BREAKERS SHALL BE MOLDED
CASE. CIRCUIT BREAKERS FEEDING HVAC LOADS SHALL BE HACR TYPE. TYPEWRITTEN
PANEL DIRECTORIES SHALL BE PROVIDED AT COMPLETION OF THE PROJECT.
F. ELECTRICAL CONTRACTOR SHALL REVIEW ONE LINE POWER RISER DIAGRAM IN
CONJUNCTION WITH SWITCHGEAR MANUFACTURER REPRESENTATIVE TO CROSS
REFERENCE POWER RISER WITH PANEL SCHEDULES AND VERIFY VOLTAGES, AMPS,
LUGS SIZES/ NUMBER AND CABINETS DIMENSIONS PRIOR TO SUBMITTING A BID.
G. EXERCISE CARE IN CONNECTING THE VARIOUS ELECTRICAL LOADS TO THE PANELS IN
ORDER TO ARRIVE AT A REASONABLE BALANCE BETWEEN LOADS IN EACH PHASE AT
EACH PANEL. MAKE TESTS AND ADJUST LOADS AT EACH PANEL TO RESULT IN
REASONABLY BALANCED LOAD CONDITION. SATISFACTORY TO THE UTILITY COMPANY. .
ENGINEER, OWNER AND INSPECTION AGENCIES DOCUMENT ALL SAID LOAD
ADJUSTMENTS.
H. MANUFACTURERS: BASE OF DESIGN IS SQUARE D.
I. MATERIALS SHALL BE NEW AND UNUSED AND THE CATALOGUED PRODUCTS OF
MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH MATERIALS.
THE MATERIALS SHALL BE OF THE MANUFACTURER'S LATEST STANDARD DESIGN
THAT COMPLIES WITH THE SPECIFICATION REQUIREMENTS.
J. LIGHTING FIXTURES SHALL BE AS SHOWN ON THE DRAWING AND SHALL BE
FURNISHED WITH LAMPS INSTALLED. CLEAN, RELAMP AND REFURBISH AS REQUIRED
FOR LIGHT FIXTURES THAT ARE ETR OR NL.
K. ALL GROUNDING SHALL CONFORM TO ARTICLE 250 OF THE NEC REQUIREMENTS. IN
ADDITION THERETO AS IMPOSED BY THE DRAWINGS AND THE LOCAL CODE
ENFORCEMENT AUTHORITIES HAVING JURISDICTION.
WHEN THE WATER MAIN METAL PIPE IS USED AS A SUPPLEMENTAL ELECTRODE,
CONNECTION SHALL BE MADE WITHIN 5 FT. OF POINT OF ENTRANCE OF PIPE INTO
THE BUILDING. CONNECTIONS OF CONDUCTORS TO GROUND RODS SHALL BE MADE
BY MEANS OF EXOTHERMIC WELD.
L. FIREPROOF ALL OPENINGS ON FIRE RATED WALLS BY AN UL APPROVED SYSTEM.
M. PROVIDE 4" SQUARE BOX AND 3/4" CONDUIT STUB -UP TO ACCESSIBLE CEILING
FOR TELEPHONE, TV AND DATA OUTLETS. PROVIDE INSULATING BUSHINGS AT
BOTH ENDS AND PULL STRING.
N. FURNISH FOR REVIEW AND APPROVAL FIVE (5) COPIES OF OR NUMBER REQUIRED BY
LOCAL JURISDICTION. CUT SHEETS AND SCHEDULES FOR ALL PANELBOARDS, LIGHT
FIXTURES, TRANSFORMERS AND ELECTRICAL EQUIPMENT IN A 3 -RING BINDER WITH A
FRONT PAGE FOR EACH CATEGORY WITH SPACE FOR ENGINEER'S STAMP AND
COMMENTS.
0. CONDUIT PENETRATIONS THROUGH FIRE RATED PARTITIONS SHALL BE SEALED
USING APPROVED FIRE SAFEING COMPOUND. REFER TO LIFE SAFETY FLOOR PLAN
FOR LOCATION OF FIRE RATED PARTITIONS.
P. CABLES NOT ENCLOSED IN CONDUITS WITHIN CEILING SPACES SHALL BE AIR
PLENUM RETURN FIRE RATED AND MEET THE REQUIREMENTS OF SECTION 602 OF
F.M.C.
Q. PROVIDE DISK FILE ON CAD 2000 RELEASE WITH "AS BUILT" ELECTRICAL
DRAWINGS AT THE COMPLETION OF THE PROJECT.
R. CONTRACTOR REPRESENTS THAT HIS BID IS BASED UPON THE MANUFACTURER'S
MATERIALS AND EQUIPMENT DESCRIBED IN THE CONTRACT DOCUMENTS.
S. ELECTRICAL CONTRACTOR SHALL REVIEW THE ARCHITECTURAL DRAWINGS FOR
DEVICES EXACT LOCATIONS, MOUNTING HEIGHTS AND QUANTITIES PRIOR TO BID AND
PRIOR TO ROUGH -IN. NOTIFY THE ENGINEER IMMEDIATELY IF ANY DISCREPANCIES
ARE FOUND.
T. FINAL QUANTITY OF EXIT AND EMERGENCY LIGHTS TO BE DETERMINED BY FIRE
MARSHALL. INCLUDE CONTINGENCY FOR 2 ADDITIONAL EXIT LIGHTS AND 2
ADDITIONAL EMERGENCY.
U. PROVIDE SWITCHBOARDS WITH THE VOLTAGE AND AMPERE RATINGS FOR THE MAIN
BREAKER, THE MAIN BUS AND THE FEEDER BREAKERS AS INDICATED ON THE ONE -LINE
POWER RISER DIAGRAM.
1. BUS BARS OF SILVER-PLATED COPPER OR TiN-PLATED ALUMINUM.
2. MOLDED CASE BREAKERS FOR THE MAIN AND FEEDERS.
3. BUS BARS OF SILVER-PLATED COPPER OR TiN-PLATED ALUMINUM.
4. PROVISIONS FOR PAD LOCKING THE CIRCUIT BREAKER HANDLES ON THE
"ON" AND "OFF" POSITION.
5. PROVIDE RUBBER INSULATION FLOOR MAT IN FRONT OF SWITCHBOARD FOR ENTIRE
LENGTH OF CENTER AND 4 FEET WIDE.
V. SWITCHBOARDS, MOTOR CONTROL CENTERS AND TRANSFORMERS SHALL BE MOUNTED
ON 4" THICK CONCRETE HOUSEKEEPING PADS. HOUSEKEEPING PADS SHALL EXTEND
AT LEAST 2" BEYOND ALL SIDES, FRONT AND BACK OF THE EQUIPMENT EXCEPT
WHERE EQUIP. EXTENDS TO WALLS. EXTENSIONS BEYOND SIDES OF THE EQUIPMENT
SHALL BE BEVELED.
W. ELECTRICAL CONTRACTOR MAY COMBINE CIRCUITS IN A COMMON RACEWAY AS LONG
AS CONDUCTORS ARE DERATED AS PER NEC. SHARED NEUTRAL SHALL NOT BE
ALLOWED UNLESS OTHERWISE INDICATED.
X. ELECTRICAL CONTRACTOR SHALL INCLUDE TRENCHING AND BACKFILLING, CORE
DRILLING, CUTTING AND PATCHING FOR THE INSTALLATION OF HIS/HER WORK WITHIN
BASE BID.
Y. CLEAN ALL LIGHT FIXTURES, LAMPS AND LENSES AND PANELBOARD INTERIORS PRIOR
TO FINAL ACCEPTANCE.
Z. SERVICE LATERALS THAT ARE NOT ENCASED IN CONCRETE AND THAT ARE BURIED 18 IN.
(457 MM) OR MORE BELOW GRADE SHALL HAVE THEIR LOCATION IDENTIFIED BY A WARNING
RIBBON THAT IS PLACED IN THE TRENCH AT LEAST 12 IN. (305 MM) ABOVE THE
UNDERGROUND INSTALLATION.
AA. REVIEW AND COORDINATE WITH DIV. 15 DRAWINGS FOR EQUIPMENT, CONDUIT, DEVICES, ETC.,
REQUIRED FOR A COMPLETE AND OPERATING HVAC SYSTEM.
BB. PROVIDE BACK BOXES AND RACEWAY FOR DOOR ACCESS CARD READERS AND ELECTRIC
STRIKES AS PER SECURITY CONTRACTOR DIRECTIONS. PROVIDE 120VAC TO EACH ELECTRIC
STRIKE DOOR LOCATION AND TO ACCESS CONTROL SYSTEM PANEL. ACCESS CONTROL
SYSTEM MUST DEACTIVATE OR OPEN ANY DOOR LOCKING MECHANISM AND REMAIN IN
FAIL SAFE POSITION WHENEVER FIRE ALARM SYSTEM IS ACTIVATED OR BUILDING POWER
FAILS. PROVIDE "PUSH -TO -EXIT" PUSHBUTTON AND MOTION DETECTOR AT EACH ACCESS
DOOR LOCATION. INTERLOCK WITH FIRE ALARM SYSTEM.
CC. CONTRACTOR REPRESENTS THAT HIS BID IS BASED UPON THE MANUFACTURER'S MATERIALS
AND EQUIPMENT DESCRIBED IN THE CONTRACT DOCUMENTS.
DD. ELECTRICAL CONTRACTOR SHALL FILL UTILITY SERVICE INFORMATION FORMS AND BUILDING
DEPARTMENT ELECTRICAL PERMIT FORMS.
EE. PROVIDE AND INSTALL PHASE LOSS PROTECTORS WITH AUTO RESET FOR ALL 10 AND 30
EQUIPMENT SHOWN ON MECHANICAL PLANS THAT HAVE AT LEAST 2 HOT CONDUCTORS. SEE
DIAGRAMS, THIS SHEET.
HOSPITAL SPECIAL REOUIREMENTS:
1. NOTIFY HOSPITAL PROJECT COORDINATOR WHEN PROJECT IS TO COMMENCE &
PROVIDE PROPOSED PROJECT SCHEDULE.
2. MEET WITH AND REVIEW PROGRESS OF CONSTRUCTION & AS -BUILT RECORD DRAWINGS
WITH (& AT A FREQUENCY SET BY) HOSPITAL PROJECT COORDINATOR.
3. PROVIDE WRITTEN NOTIFICATION TO HOSPITAL PROJECT COORDINATOR OF TiMES & DATES
FOR BUILDING INSPECTIONS OR REVIEW OF CONSTRUCTION BY AUTHORITIES HAVING
JURISDICTION.
4. PROVIDE COMPLETED HOSPITAL ENGINEERING DEPARTMENT EQUIPMENT REGISTRATION
FORMS FOR ADDITION, DELETION, RELOCATION OR PROVISION OF NEW ELECTRIC
CIRCUITS, ELECTRICAL PANELS, VALVES OR OTHER EQUIPMENT. BLANK FORMS ARE
AVAILABLE FROM HOSPITAL ENGINEERING DEPARTMENT.
5• COMPLY WITH HOSPITAL ENGINEERING DEPARTMENT STANDARDS FOR EQUIPMENT / POWER
PANEL / SYSTEM PANEL / DISCONNECT NAMEPLATiNG, PIPE LABELING, & VALVE TAGGING.
6. MAKE CONNECTIONS TO EXISTING SYSTEMS AT APPROVED TiMES MINIMIZING DURATION OF
INTERRUPTION TO EXISTING SERVICES. OBTAIN WRITTEN APPROVAL FOR 11ME & DURATION
OF A SCHEDULED SHUTDOWN FROM HOSPITAL ENGINEERING DEPARTMENT.
7. COMPLY WITH HOSPITAL POLICIES AND PROTOCOLS FOR CONSTRUCTION AND INFECTIOUS
CONTROL. COORDINATE WITH HOSPITAL.
8. HOSPITAL SHALL SUBMIT COPIES OF THEIR CONSTRUCTION STANDARDS AND INFECTIOUS
CONTROL RISK ASSESSMENT TO AHCA FOR REVIEW.
9. FIRE ALARM AND SMOKE DETECTION SYSTEMS SHALL ALWAYS BE ACTIVE. HEADS MAY BE
COVERED DURING HOURS OF CONSTRUCTION BUT THE COVERS SHALL BE REMOVED AT THE
END DAY. IF THIS IS IMPOSSIBLE, THEN INSTALL A FIRE WATCH TiLL THESE SYSTEMS ARE
ACTIVE.
10. IF THE FIRE ALARM OR SPRINKLER SYSTEMS IS OUT OF SERVICE FOR ANY EXTENDED
PERIOD OF TiME (I.E. GREATER THAN FOUR HOURS) THEN A FIRE WATCH SHALL BE
INSTALLED. SEE NFPA 101 ITEM 9.6.1.8 AND 9.7.6.
11. DOCUMENT THE TYPE OF FIREPROOFING METHOD BEING UTILIZED ON THE STRUCTURAL
FRAME FOR THESE AREAS UNDER RENOVATION, (I.E. SELF PROTECTING, SPRAY -ON FIRE
PROOFING, OR MEMBRANE).
A. SELECT THE FIRE RATING FOR THE SPRAY -ON FIREPROOFING FOR
TYPICAL UL ASSEMBLY (I.E. COLUMNS AND BEAMS) IN CASE PATCHING
IS REQUIRED.
B. IF A FIRE RATED MEMBRANE IS BEING EMPLOYED, DOCUMENT ITS
UL LISTED ASSEMBLY.
12. NO ITEMS OR MATERIALS SHALL BE STORED IN THE EXIT DISCHARGE OR PATH TO THE
PUBLIC WAY.
13. THE EXIT ACCESS CORRIDOR SHALL REMAIN OPEN AND ACCESSIBLE AT ALL TiMES.
14. ANY DAMAGE FOUND TO EXISTING WALLS, SHALL BE REPAIRED TO THEIR ORIGINAL FIRE
RESISTANT CONDITION.
EQUIPMENT NOTE=
PANELS, BREAKERS, FUSES, DISCONNECTS AND ALL ELECTRICAL DEVICES AND
EQUIPMENT SPECIFIED IN THESE PLANS ARE DESIGNED TO MEET THE FAULT
CURRENT AND COORDINATION STUDIES COMPLETED BY PEI. ANY CHANGES FROM
THE SPECIFIED EQUIPMENT COULD RESULT IN AN ELECTRICAL SYSTEM NOT
MEETING ALL REQUIREMENTS ENFORCED BY NEC, AHCA AND OTHER JURISDICTIONS.
CONTACT THE ENGINEER IF PROPOSED EQUIPMENT IS DIFFERENT THAN THAT
SPECIFIED AS THIS COULD WARRANT AN ADDITIONAL COST TO THE CONTRACTOR
FOR NEW FAULT CURRENT AND/OR COORDINATION STUDIES.
EXISTING SUBSCRIPT LEGEND:
ETR EXISTING DEVICE/LIGHT AND ASSOCIATED CIRCUIT WIRING TO REMAIN.
PROVIDE ALL NECESSARY EXTENSION OF CONDUIT AND WIRING AS
REQUIRED, IN ORDER TO MAINTAIN CIRCUIT CONTINUITY TO EXISTING
EQUIPMENT TO REMAIN.
ERL EXISTING DEVICE/LIGHT TO BE RELOCATED. JUNCTION AND EXTEND
EXISTING CONDUIT AND WIRING TO NEW LOCATION AS REQUIRED.
NL NEW LOCATION OF EXISTING DEVICE/LIGHT. PROVIDE EXTENSION OF
EXISTING CONDUIT AND WIRING AS REQUIRED. (PROVIDE NEW SWITCHING
AS INDICATED)
R EXISTING DEVICE/LIGHT TO BE REMOVED. WHERE EXISTING EQUIPMENT
TO REMAIN IS FED VIA EXISTING EQUIPMENT TO BE REMOVED, PROVIDE
ALL NECESSARY EXTENSION OF CONDUIT AND WIRING AS REQUIRED IN
ORDER TO MAINTAIN CIRCUIT CONTINUITY TO EXISTING EQUIPMENT.
RPL EXISTING DEVICE/LIGHT TO BE REPLACED. EXISTING CIRCUIT WIRING TO
REMAIN. REFER TO RENOVATION PLAN FOR MORE INFORMATION.
N NEW DEVICE/LIGHT TO MATCH EXISTING BUILDING STANDARDS
ELECTRICAL SYMBOL LEGEND=
NOTE: NOT ALL SYMBOLS USED IN THIS PROJECT
O ❑ T04 NORMAL CIRCUIT SED FLUORESCENT LIGHT FIXTURE
® ®
FLUORESCENT FIXTURE
CONNECTED
TO
CRITICAL CIRCUIT
® ®
FLUORESCENT FIXTURE
CONNECTED
TO
EMERGENCY CIRCUIT
= ■
FLUORESCENT FiXTURE
CONNECTED
TO
LIFE SAFETY CIRCUIT
N L "
FLUORESCENT FIXTURE
CONNECTED
TO
UNSWITCHED CIRCUIT
l-- - i -Q --I STRIP FLUORESCENT LIGHT FIXTURE - CEILING, WALL MOUNTED
0 n INCANDESCENT, HID OR COMPACT FLUORESCENT FIXTURE -
Y CEILING MOUNTED, WALL MOUNTED
® TEXIT SIGN FIXTURE, SHADED QUADRANT INDICATES FACE, WITH
ARROWS AS SHOWN ON PLAN - CEILING MOUNTED, WALL
MOUNTED
$ $2 $3$4 1 -POLE, 2 -POLE, 3 -WAY, 4 -WAY SWITCH
$K KEYSWITCH
0 03 04 INCANDESCENT DIMMER SWITCH,
1 -POLE, 3 -WAY, 4 -WAY SWITCH
$M $MP $WP MANUAL MOTOR STARTER TOGGLE SWITCH AS NOTED; "P"
INDICATES PILOT LIGHT, "WP" INDICATES WEATHERPROOF
GENERAL NOTES FOR RENOVATION:
1. EXISTING OUTLET BOXES AND CONDUIT WHICH ARE LOCATED
PROPERLY FOR NEW WORK MAY BE REUSED FOR NEW DEVICES
AND WIRE.
2. ALL CONDUIT AND WIRE REMOVED SHALL BE TAKEN BACK TO THE
SOURCE OF SUPPLY.
3. INSTALL A BLANK COVER PLATE WHERE REQUIRED.
4. VISIT THE JOB SITE PRIOR TO BIDDING TO VERIFY ALL ACTUAL
CONDITIONS.
5. REMOVE EXISTING POWER, LIGHTING, SYSTEMS, MATERIAL AND
EQUIPMENT WHICH ARE MADE OBSOLETE OR WHICH INTERFERE WITH
THE CONSTRUCTION OF THE PROJECT.
A. REINSTALL ANY SUCH POWER, LIGHTING, SYSTEMS, MATERIALS
AND EQUIPMENT WHICH ARE REQUIRED TO REMAIN ACTIVE FOR
THE FACILITY TO BE FULLY FUNCTIONAL.
6. WHERE EXISTING EQUIPMENT OR MATERIALS ARE REMOVED OR CHANGED,
ALL BRANCH CONDUITS, WHICH NO LONGER ARE IN SERVICE, SHALL BE
REMOVED. PENETRATIONS SHALL BE SEALED TO MEET WALL RATING. IF,
IN THE COURSE OF THE WORK, OUTLETS ARE COVERED UP TO OTHERWISE
RENDERED INACCESSIBLE, ALL WIRING TO SAME SHALL BE REMOVED TO
THE SOURCE. IF A CIRCUIT THAT MUST REMAIN IN SERVICE IS
INTERRUPTED THEREBY, IT SHALL BE RECONNECTED BY THE MOST
INCONSPICUOUS MEANS SO AS TO REMAIN IN OPERATION, WITH SAME
CAPACITY AS BEFORE. ALL BUILDING SURFACES DAMAGED, AND
OPENINGS LEFT BY REMOVAL OF BOXES, PIPING OR OTHER EQUIPMENT
SHALL BE REPAIRED BY THE CONTRACTOR. ALL HOLES LEFT IN JUNCTION
BOXES, SWITCHES, PANELS, ETC. SHALL BE CLOSED.
7. ALL REUSABLE DEVICES, FIXTURES AND EQUIPMENT SHALL BECOME
THE PROPERTY OF THE OWNER. ALL OTHER SALVAGE AND DEBRIS
SHALL BE REMOVED FROM THE PREMISES DAILY.
(( 8. VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND
C G DUPLEX RECEPTACLE AT 18"/AS NOTED, ABOVE COUNTER AT SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS
42 /AS NOTED, CEILING MOUNTED, GROUND FAULT TYPE, ISOLATED GROUND TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT
0(00 TYPE, WEATHERPROOF TYPE, SIMPLEX (AS NOTED) WILL AFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL
IG WP BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE
0 *
(2) DUPLEX RECEPTACLES IN SINGLE OUTLET BOX WITH
EO.1
SINGLE COVER PLATE AT 18"/AS NOTED, ABOVE COUNTER AT
E1.1
42"/AS NOTED
X
1 -POLE, 3 -WAY, 4 -WAY SWITCH, DIMMER CONNECTED TO
E2.1
CRITICAL CIRCUIT (RED DEVICE)
E2.2
DUPLEX RECEPTACLE (RED DEVICE) AT 18"/AS NOTED, ABOVE
E3.1
COUNTER AT 42"/AS NOTED CONNECTED TO CRITICAL CIRCUIT
E6.1
(2) DUPLEX RECEPTACLE (RED DEVICES) IN SINGLE OUTLET BOX WITH
E6.2
SINGLE COVER PLATE AT 18"/AS NOTED, ABOVE COUNTER AT 42"/AS
E7.2
NOTED CONNECTED TO CRITICAL CIRCUIT
® 0 [A
SPECIAL MOUNTED RECEPTACLE AS NOTED, PUSHBUTTON AS
NOTED, TELE -POWER POLE
-1� ©
FINAL CONNECTION TO EQUIPMENT
❑J OJ NCkT❑
JUNCTION BOXES, MOTOR, TRANSFORMER
I1�OT ®
FUSED DISCONNECT SWITCH, NON FUSED DISCONNECT, MOTOR STARTER
®1W
OR CONTACTOR, COMBINATION STARTER/DISCONNECT, ENCLOSED
CIRCUIT BREAKER
�
120/208 OR 120/240V PANELBOARD
lam
277/480V PANELBOARD
o
SYSTEMS CABINET- FLUSH MOUNTED, SURFACE MOUNTED (AS NOTED)
TELEPHONE TERMINAL BOARD, TELEPHONE SYSTEM
®
RACEWAY
-t
CONNECTION TO GROUND
W P
TELEPHONE OUTLET AT 18", WALL TELEPHONE OUTLET AT 54",
V V 3WV
ABOVE COUNTER, PAY TELEPHONE OUTLET. PROVIDE 4" SQ.
BOX AND 3/4" RACEWAY (WITH INSULATING BUSHING) TO
ACCESSIBLE CEILING
v v v
COMPUTER OUTLET, COiuPUTER OUTLET 48", PHONE/bATA PROVIDE
4 SQUARE BOX AND 3/4 CONDUIT (WITH INSULATING BUSHING)
TO ACCESSIBLE COLING
®
TELEVISION OUTLET AT 18" (UNLESS NOTED OTHERWISE)
8 f SMOKE DETECTOR, SMOKE DUCT DETECTOR
VOLUME CONTROL
OS SPEAKER
Q HEAT DETECTOR
DUCT/SMOKE DETECTOR REMOTE INDICATOR LIGHT
® SHUTDOWN RELAY, 24V DC
MANUAL PULL STATION, FLUSH
04 HORN AND STROBE LIGHT, FLUSH MOUNTED
V W WALL/CEILING MOUNT STROBE
® VOICE EVAC SPEAKER
Qt VOICE EVAC SPEAKER AND STROBE LIGHT, FLUSH MOUNTED
D DOOR HOLDER
TS TAMPER SWITCH
FS FLOW SWITCH
BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR
�""- \ IN WALL, SLASH MARKS INDICATE NUMBER OF
CONDUCTORS, LONGER SLASH IS NEUTRAL, (GROUND WIRE
NOT SHOWN). 2 #12, 1 #12 GROUND IN A 3/4" CONDUIT
MINIMUM (UNLESS OTHERWISE NOTED OR MARKED).
QUANTITY OF ARROWS INDICATE QUANTITY OF HOMERUNS
TO PANELBOARD. PROVIDE EQUIPMENT GROUNDING
CONDUCTOR IN ALL BRANCH CIRCUITS.
;V____'%,,, BRANCH CIRCUIT CONDUIT CONCEALED BELOW SLAB OR
UNDERGROUND.
ELECTRICAL SYMBOL LEGEND NOTES:
1. AN OUTLET BOX OF THE APPROPRIATE SIZE AND TYPE SHALL BE PROVIDED
FOR ALL DEVICES, LIGHTING FIXTURES, SWITCHES, RECEPTACLES, ETC.
2. SWITCHES AND RECEPTACLES SHALL BE SPECIFICATION GRADE 20A MINIMUM.
ALL RECEPTACLES IN PATIENT CARE AREAS SHALL BE HOSPITAL GRADE
20A MINIMUM UNLESS OTHERWISE NOTED. ALL NORMAL DEVICES TO BE
IVORY (COORDINATE COLOR WITH ARCHITECT PRIOR TO ORDER) AND ALL
CRITICAL DEVICES TO BE RED.
3. COORDINATE ALL LOCATIONS, HEIGHTS AND COLORS WITH ARCHITECTURAL
DRAWINGS/DIAGRAMS PRIOR TO ROUGH IN.
4. ALL NEW AND EXISTING COVER PLATES IN THE PROJECT AREA SHALL BE
ENGRAVED WITH PANEL AND CIRCUIT INFORMATION. METAL PLATES SHALL BE
RED LETERING FOR CRITICAL CIRCUITS AND BLACK LETTERING FOR NORMAL
CIRCUITS. PHENOLIC PLATES SHALL BE A RED PLATE WITH WHITE LETTERING
FOR CRITICAL CIRCUITS AND IVORY/WHITE/MATCH EXISTING PLATES WITH
BLACK LETTERING FOR NORMAL CIRCUITS.
5. PROVIDE A PULL STRING IN ALL EMPTY CONDUITS.
6. ALL JUNCTION BOX COVERS SHALL BE MARKED WITH PANEL, CIRCUIT
NUMBER AND VOLTAGE WITH PERMANENT BLACK MARKER.
7. JUNCTION BOXES SHALL NOT BE MOUNTED TO THE PARTITION TOP PLATE.
8. PROVIDE ACOUSTICAL FOAM AND SEALANT AT ALL DEVICES ON DEMISING
PARTITIONS. IF PARTITION IS FIRE RATED, PROVIDE FIREPROOF COMPOUND
ON BACK AND SIDES OF THE BOX OR 5 SIDED WITH APPROVED MATERIAL AS
REQUIRED.
9. WHERE TELEPHONE AND ELECTRICAL OUTLETS APPEAR ON PLANS AS BACK
TO BACK, OUTLETS SHALL BE STAGGERED TO REDUCE NOISE TRANSMISSION.
WHERE WALLS AND PARTITIONS ARE REQUIRED TO HAVE A MINIMUM OF
1 -HOUR FIRE -RESISTANCE RATING, BOXES SHALL BE SEPARATED BY A
MINIMUM HORIZONTAL DISTANCE OF 24" INCHES OR PROTECTED WITH UL
LISTED PUTTY PADS.
AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED
BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED.
UTiUTiES AND SERVICES INDICATED ARE TAKEN FROM VARIOUS OLD AND
NEW SURVEYS AND FIELD INVESTIGATION. IT IS TO BE UNDERSTOOD THAT
UNFORESEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT BE
FIELD LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COOPERATION
WITH OTHER TRADES IN ROUTING AND/OR BURIAL DEPTHS, AS
DETERMINED DURING CONSTRUCTION AND AS DIRECTED BY THE
ARCHITECT/ENGINEER, MAY BE NECESSARY AND IT IS INTENDED THAT
SUCH DEVIATIONS SHALL BE CONSIDERED AS PART OF THIS CONTRACT. IT
IS ALSO UNDERSTOOD THAT THE PLANS ARE NOT COMPLETELY TO SCALE.
THIS CONTRACTOR IS TO FIELD VERIFY DIMENSIONS OF ALL SITE UTILITIES,
ETC., PRIOR TO BID, AND INCLUDE ANY DEVIATIONS IN THE CONTRACT.
9. WHERE NEW OPENINGS ARE CUT AND CONCEALED CONDUITS, ETC.,
ARE ENCOUNTERED, THEY SHALL BE REMOVED OR RELOCATED AS
REQUIRED. WHERE CONDUIT TO BE REMOVED STUBS THROUGH
FLOORS, WALLS, AND CEILINGS SUCH CONDUIT SHALL BE REMOVED
TO THE POINT WHERE THE FINISH SURFACES CAN BE PATCHED
ADEQUATELY SO THAT NO EVIDENCE OF THE FORMER INSTALLATION
REMAINS. ELECTRICAL CONTRACTOR SHALL FIRE PROOF ANY WALL
OPENINGS ON FIRE RATED WALLS. REFER TO BUILDING STANDARDS
FOR METHOD TO BE USED.
10. THIS CONTRACTOR SHALL FURNISH AND PROVIDE ALL DEMOLITION
REQUIRED TO ACCOMMODATE THIS PROJECT WHETHER INDICATED ON
DRAWINGS, OR DIRECTED IN THE FIELD.
11. ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY POWER
AND LIGHTING.
12. ELECTRICAL CONTRACTOR SHALL TRACE BRANCH CIRCUITS OF
EXISTING PANELS TO IDENTIFY CIRCUIT BREAKERS SERVING
REMODELED AREA. CIRCUIT BREAKERS BEING USED TO SERVE
EXISTING SPACES SHALL REMAIN UNTOUCHED.
13. PROVIDE TYPED, UPDATED PANEL DIRECTORIES FOR EXISTING AND NEW
PANELS USED IN THIS PROJECT.
PROVIDE PHENOLIC NAMEPLATES ON ALL PANELBOARDS, SWITCHBOARDS,
DISCONNECTS, TRANSFORMERS, ETC, INDICATING DESIGNATION, CIRCUIT
NUMBER(S), VOLTAGE AND WHERE UNIT IS FED FROM. SECURE
NAMEPLATES WITH AT LEAST TWO SCREWS OR RIVETS. CEMENTING AND
ADHESIVE INSTALLA11ON IS NOT ACCEPTABLE.
14. EXISTING OUTLETS, CONDUIT, WIRE AND EQUIPMENT WHICH DOES
NOT INTERFERE WITH THE CONSTRUCTION OF THE PROJECT SHALL
REMAIN UNTOUCHED.
15. AREAS AFFECTED BY CONSTRUCTION SHALL BE CONTACTED FOR
COORDINATION OF WORK PRIOR TO RENOVATION.
16. JUNCTION BOXES, CONDUIT, SWITCHES, CIRCUIT BREAKERS,
ETC., ARE TO BE SUPPLIED AND INSTALLED BY ELECTRICAL
CONTRACTOR.
17. CONDUIT RUNS SHALL HAVE SWEEP RADIUS BENDS.
18. CONDUIT SHALL NOT BE RUN IN STAIRWELLS.
19. MAINTAIN SEGREGA11ON OF ALL POWER TYPES, DO NOT
COMBINE BRANCHES.
20. USE A MINIMUM 2#12, 1#12 GND-3/4"C. UNLESS
OTHERWISE NOTED.
21. FOR ALL MEDICAL GAS, FIRE ALARM, POWER PANELS. DISCONNECTS
AND EQUIPMENT, PROVIDE AN ENGRAVED TAG WITH PANEL
DESIGNATION. FOR POWER PANELS, DISCONNECTS AND EQUIPMENT,
PROVIDE PROPER VOLTAGE, PHASE, WHERE FED FROM AND THE TYPE
OF POWER (NORMAL, CRITICAL, EQUIPMENT OR LIFE SAFETY). COLORS
OF EACH POWER TYPE ARE AS FOLLOWS:
NORMAL POWER = BLACK FIELD WITH WHITE LETTERS
CRITICAL POWER = ORANGE FIELD WITH WHITE LETTERS
EQUIPMENT POWER = GREEN FIELD WITH WHITE LETTERS
LIFE SAFETY POWER = YELLOW FIELD WITH WHITE LETTERS
FIRE ALARM = RED FIELD WITH WHITE LETTERS
NOTE: THE CONDUITS, FITTINGS & J -BOXES MUST BE SPOT
PAINTED TO INDICATE THE POWER TYPE. SEE THE COLOR
SCHEDULE ABOVE OR PER HOSPITAL STANDARDS.
22. ABANDONED LOW VOLTAGE CABLES WITHIN CEILING SPACES SHALL BE
REMOVED AS PER ARTICLE 725.61 (A) OF THE NFPA-70.
23. DEVICES LOCATED IN RATED WALLS (REFER TO ARCHITECTURAL
DRAWINGS FOR LOCATION OF RATED WALLS) SHALL BE PROPERLY
PROTECTED AS REQUIRED BY LOCAL CODES. PROVIDE 5 SIDED OF
J -BOXES OR PUDDY PACKS AS NECESSARY.
EXISTING TO REMAIN FIXTURES, SPEAKERS, CONDUITS, J -BOXES,
24. CABLES (TELE/DATA, NURSE CALL, COMPUTER, ACCESS CONTROLS
ETC.) LOCATED IN WALLS OR ABOVE THE CEILINGS IN THE WORK AREA
SHALL BE PROPERLY SUPPORTED PER NEC, NFPA, AND ALL STATE,
FEDERAL AND LOCAL CODES AND REVISIONS. PROVIDE LABOR AND
MATERIAL AS REQUIRED.
PANEL BONDING=
THE EQUIPMENT GROUNDING TERMINAL BUSSES OF THE NORMAL AND
ESSENTIAL BRANCH CIRCUIT PANELBOARDS SERVING PATIENT ROOMS SHALL
BE BONDED TOGETHER WITH AN INSULATED CONTINUOUS COPPER
CONDUCTOR NOT SMALLER THAN #10.
POLICY FOR PLANNED OUTAGES
AND DISRUPTIONS:
PRIOR TO SHUTTING OFF, DISRUPTING, OR MODIFYING THE EXISTING
SERVICES, THE CONTRACTOR MUST SUBMIT IN WRITING TO THE FACIUTY AT
LEAST (3) WORKING DAYS PRIOR TO THE PLANNED OUTAGE OR DISRUPTION
OF SERVICE FOR APPROVAL OF THE WORK.
SELECTIVE KEYNOTES D
FIRE ALARM
A. PROVIDE MODIFICATIONS/ADDITIONS TO THE EXISTING FIRE ALARM SYSTEM TO COMPLY WITH
NFPA 101, NFPA 72, FLORIDA ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION, AND THE
CITY OF ORLANDO REQUIREMENTS.
B. CHIME/HORN/STROBE/SPEAKER TO MEET db AND CANDELA AS PER ADA AND NFPA-72
REQUIREMENTS. ACCEPT NO LESS THAN 75 CANDELA AND 82 DECIBEL. REFER TO NFPA 72
TABLES 4.4.4.1.1., 4-4.4.1.1(a) AND 4-4.4.2.1.
C. PROVIDE PROPER ANNUNCIATION AND COMPARTMENT IDENTIFICATION FOR THE ALARM DEVICES
LOCATED IN EACH SMOKE COMPARTMENT. COORDINATE PROGRAMMING AND IDENTIFICATION
WITH HOSPITAL ELECTRONICS DEPARTMENT.
D. VISIT THE SITE AND BECOME FAMILIAR WITH EXISTING FIRE ALARM SYSTEM. PROVIDE
NECESSARY UPGRADES, ZONES, POWER EXPANDERS, AMPLIFIERS, ETC.
E. FIRE ALARM CONTRACTOR SHALL REVIEW MECHANICAL DRAWINGS FOR DUCT SMOKE
DETECTORS AND SMOKE DAMPER REQUIREMENTS. INCLUDE CONNECTION COST WITHIN BASE
BID.
F. ELECTRICAL CONTRACTOR SHALL OBTAIN THE SERVICES OF A FACILITY APPROVED FIRE
ALARM CONTRACTOR FOR DESIGN, INSTALLATION AND PERMITTING OF THE FIRE
ALARM WORK. INCLUDE COST WITHIN BASE BID. CONSULT FACILITY "APPROVED VENDOR LIST"
PRIOR TO BID.
G. PROVIDE SIGNED AND SEALED FIRE ALARM SHOP DRAWINGS PREPARED BY A LICENSED
PROFESSIONAL ENGINEER IN THE EMPLOYMENT OF THIS CONTRACTOR FOR BUILDING
DEPARTMENT REVIEW AND PERMIT. FIRE ALARM CONTRACTOR SHALL PROVIDE THIS COST IN
BID.
H. SMOKE DETECTORS SHALL NOT BE LOCATED LESS THAN S -O" FROM HVAC
GRILLES.(DRAWINGS SHOW GENERAL LOCATION ONLY.)
I. FIRE ALARM SYSTEM CABLES SHALL BE #14 COPPER MINIMUM ENCLOSED IN 3/4" OR
LARGER EMT CONDUIT. BOXES FOR DEVICES SHALL BE 2 1/8" DEEP.
J. CONNECT NEW FIRE ALARM DEVICES TO EXISTING FIRE ALARM SYSTEM. WIRE PER
MANUFACTURER RECOMMENDATIONS. PROVIDE NEW MODULES AND UPGRADES AS
REQUIRED.
K. FINAL QUANTITY OF CHIME/STROBE/HORNS TO BE DETERMINED BY FIRE MARSHAL INCLUDE
CONTINGENCY FOR 1 ADDITIONAL CHIME/STROBE/HORNS AND 1 SMOKE DETECTORS IN BASE
BID.
L. AS PER 2004 FLORIDA BUILDING CODE, FLORIDA ACCESSIBILITY CODE CHAPTER 11 SECTION
11-4.1.3(14) ALLOWS "EMERGENCY WARNING SYSTEMS IN MEDICAL CARE FACILITIES MAY BE
MODIFIED TO SUIT STANDARD HEALTH CARE ALARM DESIGN PRACTICE". NOTIFICATION DEVICES
ARE NOT REQUIRED IN PATIENT CARE ROOMS AND TREATMENT AREAS CONTROLLED BY THE
STAFF.
M. FIRE ALARM STROBES SHALL BE SYNCHRONIZED.
N. FIRE ALARM CONTRACTOR SHALL FIELD VERIFY EXISTING AUDIBLE AND VISUAL DEVICES AND
MATCH EXISTING AND MUST COMPLY WITH ADA AND NFPA-72 REQUIREMENTS.
R. FIRE ALARM CONTRACTOR SHALL PERFORM AND PROVIDE IN WRITING ALL REQUIRED BATTERY
CALCULATIONS AS REQUIRED BY ALL INSPECTING AGENCIES.
S. 69A-3 FLORIDA ADMINISTRATIVE CODE COMPLIANCE:
A) 4.4.1.5.3.1 UNLESS OTHERWISE PERMITTED OR REQUIRED BY 4.4.1.5.3.1 (A) OR 4.4.1.5.3.1 (B),
THE SECONDARY POWER SUPPLY SHALL HAVE SUFFICIENT CAPACITY TO OPERATE THE FIRE
ALARM SYSTEM UNDER QUIESCENT LOAD (SYSTEM OPERATING IN A NONALARM CONDITION) FOR
A MINIMUM OF 24 HOURS AND, AT THE END OF THAT PERIOD, SHALL BE CAPABLE OF
OPERATING ALL ALARM NOTIFICATION APPLIANCES USED FOR EVACUATION OR TO DIRECT AID TO
THE LOCATION OF AN EMERGENCY FOR 5 MINUTES.
(a) THE SECONDARY POWER SUPPLY FOR EMERGENCY VOICE/ALARM COMMUNICATIONS SERVICE
SHALL BE CAPABLE OF OPERATING THE SYSTEM UNDER QUIESCENT LOAD FOR A MINIMUM OF
24 HOURS AND THEN SHALL BE CAPABLE OF OPERATING THE SYSTEM DURING A FIRE OR
OTHER EMERGENCY CONDITION FOR A PERIOD OF 15 MINUTES AT MAXIMUM CONNECTED LOAD.
(b) THE SECONDARY POWER SUPPLY CAPACITY FOR SUPERVISING STATION FACILITIES AND
EQUIPMENT SHALL BE CAPABLE OF SUPPORTING OPERATIONS FOR A MINIMUM OF 24 HOURS.
4.4.1.5.3.2 THE SECONDARY POWER SUPPLY CAPACITY REQUIRED SHALL INCLUDE ALL POWER
SUPPLY LOADS THAT ARE NOT AUTOMATICALLY DISCONNECTED UPON THE TRANSFER TO
SECONDARY POWER SUPPLY.
B) SHOW REQUIRED INTER -TIES TO ALL EXISTING FIRE ALARM SYSTEM COMPONENTS
REQUIRED TO MAKE SYSTEMS OPERATE AS ONE PER NFPA.
C) PROVIDE AUDIBLE NOTIFICATION 15 DECIBEL ABOVE AMBIENT NOISE LEVELS. SEE
NFPA 72. PROVIDE VISUAL NOTIFICATION PER NFPA 72 AND FLORIDA BUILDING CODE.
D) CONDUCTORS SHALL BE U.L. LISTED FPL MANUFACTURED AND INSTALLED PER
NFPA 70. PROVIDE POWER LIMITED SYSTEM. EXPOSED CABLES IN
PLENUMS SHALL BE RATED FOR THE USE.
T. FIRE ALARM CONTRACTOR SHALL TEST/VERIFY EXISTING SYSTEM OPERATES PROPERLY PER
NFPA 72&101.
U. NFPA-72.1-5.1.4 SYSTEM INSTALLATION - INSTALLATION PERSONNEL SHALL BE SUPERVISED
BY PERSONS WHO ARE QUALIFIED AND EXPERIENCED IN THE INSTALLATION, INSPECTION AND
TESTING OF FIRE ALARM SYSTEMS. EXAMPLES OF QUALIFIED PERSONNEL SHALL INCLUDE, BUT
NOT LIMITED TO, THE FOLLOWING:
(1) FACTORY TRAINED AND CERTIFIED PERSONNEL
(2) NATIONAL INSTITUTE OF CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET) FIRE ALARM
LEVEL II CERTIFIED PERSONNEL
(3) PERSONNEL LICENSED OR CERTIFIED BY STATE OR LOCAL AUTHORITY
DRAWING INDEX
SHEET
NUMBER
SHEET NAME
EO.1
SYMBOL LEGEND, GENERAL NOTES, SPECS. & DETAILS
E1.1
LOCATION PLAN FIRST FLOOR
E1.2
PHASING PLAN FIRST FLOOR
E2.1
DEMOLITION/RENOVATION FIRST FLOOR POWER & SYSI
E2.2
DEMOLITION/RENOVATION FIRST FLOOR NURSECALL
E3.1
DEMOLITION/RENOVATION FIRST FLOOR LIGHTING
E6.1
PANEL SCHEDULES
E6.2
PANEL SCHEDULES
E7.2
RISER DIAGRAM ELECTRICAL
PENINSULA ENGINEERING INC.
CONSULTING ENGINEERS
ESTABLISHED IN 1977 C - ght
009
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 • 407.246.1688 • EB 3089 0
Copyright - All ideas, designs, methods and plans indicated or represented by this drawing
are owned by and the property of Peninsula Engineering. Inc. and were created, evolved and JOB#.
developed for use on and M connection with the specified project None of the ideas, designs,
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
JEA BS
issue date drawn by approved by project number
REVISION SCHEDULE
I Al DATE I DESCRIPTION
SYMBOL LEGEND, GENERAL EON1
NOTES, SPECS. & DETAILS
sheet number
T+IESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
OR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
RITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
NOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
,``tttlillif10 i
.-,%` ` C, SPAN '<<�
Co : .�
•
No. N
- * : '>Ar • • CL a
ST F t ... ?F
-1 IG'• bb�q
'' .VPE,
)N&LI 0- 61 BURKE HOGUE MILLS, INC.
111111%. 1130 Business Center Drive, Lake Mary, FL
32746
407.333.2005 AAC000233
W W W B H M U S
M
o
/71
k__j
_ rl
Z.l
O
- CC
i
Lf-%^ATioN PLAN FIRST FLOOR i
CALE:1 " = 20'-0" !
9 , , OWN R REFE NCE ON 4 3 z , z
�31
0
OOA PANEL PANEL !
NEC 1 NEC 2
N PANEL
PANEL
75KVA NA 2
200A
45KVA
rl-"), ENLARGED PLAN
E1.1 SCALE: 1/4" = 1'-0"
SHOWN FOR REFERENCE ONLY.
SELECTIVE KEYNOTES Q
PENINSULA ENGINEERING INC.
CONSULTING ENGINEERS
ESTABLISHED IN 1977Wi
nt
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 • 407.246.1688 • EB 3089 2009 0
Copyright — All ideas, designs, methods and plans indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and
developed for use on and in connection with the specified project. None of the ideas, designs, JOBJ:
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
JEA BS
issue date drawn by approved by
REVISION SCHEDULE
F?MDATE I DESCRIPTION
project number
LOCATION PLAN FIRST FLOOR El .
1
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURL, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
�%%%G, SPA
%
do
'a T�TQ] r L
:.0 P i
W .
,,9 ,
i!���� BURKE HOGUE MILLS, INC.
�r;aL 1130 Business Center Drive, Lake Mary, FL
��lj/liltl�tl
32746
407.333.2005 AAC000233
W W W B H M U S C 0 M
.M
O
rn
v
�O01
n
— fl
�1
.n,
v
a
n
C
I PLAN N FIRST LOOR j I
I �Lwf'**il.�ATION
! CALF: 1" = 20'-0"
OWNR REFS ENCE ON 5. 4 3 Z z zri 3,
15 14 13
n
L�-O--
I -
I
i Lt OOA PANEL NPANEL2 j
NEC 1 EC
N PANEL
PANEL
75KVA NA 2
200A
45KVA
ENLARGED PLAN
E1.1 SCALE: 1/4" = 1'-0"
SHOWN FOR REFERENCE ONLY.
SELECTIVE KEYNOTES O
PENINSULA ENGINEERING INC.
CONSULTING ENGINEERS
ESTABLISHED IN 1977 *2OrO9ght
200
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 • 407.246.1688 • EB 3089
Copyright — All Ideas, designs, methods and plans Indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and JOB
developed for use on and in connection with the specified project. None of the ideas, designs.
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
JEA BS
issue date drawn by approved by project number
REVISION SCHEDULE
A I DATE I DESCRIPTION
LOCATION PLAN FIRST FLOOR El 0 1
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPEOFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
Ile
4�:': \0, ENS
N 1
w � • • a
� •; STT OF
• • (/ 4
'"!!111104,
W W W
BURKE HOGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL
32746
407.333.2005 AAC000233
B H M U S
O M
RTRW�I !
ETR STOR,
EXISTi T1 S N
G
1_0
PANEL ECOBET
E
F_ ERL LEFT/RIGHT ETR
ETR
— J — I ETR AP, E7R JL::D�T!R QI
— —
nR AICD ELIVERY L&7 �
EOB-35
ME NURSES�FIREOBSA
ETR ETR FIRE AL RM
I SOLE_
_ANNUNgI TOR
rXR41 T� 3
0S-�1 —TLT"EC _
f I III_
I
T 1 512 fifi 3 DOOR
i o NO1 135 ORELEASq II I
ERL LJ rQ W i: ERLER
F '�L
�- ----- �°--_ -�
NOB -35 I ( / / ECOB- 9 '
11 ETR 4
DFFICE ECOB_29
�-� .C�+ DIR'
T1520
IDGF ECOB-3
NOB- -�G —ERLo_ I ERer_z I ETR O FIC E
-Tf I ��d1-= T1521
a � I Nl'0� 35
X
I NOB -351
— —
NO&435
NOB -35 / i II
OBSOLETE f
INOB-35
i T 11
''
%z !' REDIATRIC
DEMOLITION PLAN POWER AND SYSTEMS
SCALE:1 /4" = 1'-0"
GENERAL DEMOLITION NOTES:
'.ALL DEVICES SHOWN ARE TO BE REMOVED
UNLESS NOTED OTHERWISE.
2. REFER TO RENOVATION PLAN AND PANEL SCHEDULES FOR MORE INFORMATION.
3. CIRCUITS INDICATED ARE FROM A PREVIOUS PROJECT. ELECTRICAL CONTRACTOR
SHALL TRACE AND IDENTIFY ALL CIRCUITS WITHIN THE WORK AREA AND KEEP A
WRITTEN RECORD. PROVIDE NEW ENGRAVED COVER PLATES FOR ALL DEVICES AS
PER SPECIFICATIONS.
4. PER 2008 NEC THE ELECTRICAL CONTRACTOR SHALL PROVIDE A DEDICATED
NEUTRAL FOR ALL CIRCUITS RE -USED. SHARED NEUTRALS SHALL NOT BE ALLOWED.
5. ALL CONDUIT AND WIRE REMOVED SHALL BE TAKEN BACK TO THE SOURCE OF
SUPPLY.
6. ALL REUSABLE DEVICES, FIXTURES AND EQUIPMENT SHALL BE TURNED OVER TO
THE OWNER.
7. ALL DEVICES, CONDUIT AND WIRE MADE OBSOLETE IN THIS PROJECT SHALL BE
REMOVED.
8. DASHED WALLS/LINES ARE TO BE DEMOUSHED. DEVICES, CONDUIT, BOXES, ETC.
SHALL BE REMOVED.
9. ELECTRICAL CONTRACTOR SHALL VERIFY ALL EXISTING RECEPTACLES IN THE
PROJECT AREA ARE HOSPITAL GRADE. PROVIDE NEW AS REQUIRED. NORMAL
CIRCUIT RECEPTACLES TO BE IVORY (VERIFY WITH ARCHITECT) AND CRITICAL
CIRCUIT RECEPTACLES TO BE RED.
10. ELECTRICAL CONTRACTOR SHALL VERIFY ALL EXISTING SWITCHES IN THE PROJECT
AREA ARE SPEC GRADE. PROVIDE NEW AS REQUIRED. NORMAL CIRCUIT SWITCHES
TO BE IVORY (VERIFY WITH ARCHITECT) AND CRITICAL CIRCUIT SWITCHES TO BE
RED.
11. REFER TO PHASING PLAN E1.2 AND E2.2 FOR ADDITIONAL WORK IN THIS PROJECT.
12. ELECTRICAL CONTRACTOR SHALL PROPERLY SUPPORT ALL CONDUITS, J -BOXES,
CABLING, FLEX, ETC. WITH APPROVED SUPPORT DEVICES IN THE PROJECT AREA.
I•
KEYED RENOVATION NOTES:
O COORDINATE NEW LOCATION FOR EXISTING CCN MONITOR WITH THE FACILITY
PRIOR TO ROUGH IN.
Q2 COORDINATE NEW LOCATION FOR EXISTING MONITOR WITH THE FACILITY
PRIOR TO ROUGH IN.
Q3 COORDINATE NEW LOCATION FOR EXISTING DOOR RELEASE BUTTON WITH THE
FACILITY PRIOR TO ROUGH IN.
® COORDINATE WITH THE FACILITY IF KEY PAD IS STiLL OPERATIONAL REMOVE
IF OBSOLETE.
05 COORDINATE WITH THE FACILITY IF DEVICE IS STiLL OPERATIONAL. REMOVE
IF OBSOLETE.
PER 2008 NEC THE ELECTRICAL CONTRACTOR SHALL PROVIDE
A DEDICATED NEUTRAL FOR ALL NEW AND RE -USED CIRCUITS.
SHARED NEUTRALS WILL NOT BE ALLOWED.
I
f
EQUIPMEN
STORAGE
-.- EEI'
E 1C.E
ECB NLSIS G
- � - I-
I STATION � I
I ECOB-29 F
NOURISHMENT NL
ROOM
I
I I AL NEC -27
L — I — A — — —
STATiO
URSE' o II
ST N
F NEC -29 i
'�NNA-11
� NA -9
DOOR RELEASE
SIE o
0
iCl
I
I
I
I o
I
DICTATION
STATIONS
I B
I I
i I
I
— — — — —
0
i
I
i
Ng
Ll
e - v
7
I
I 'I CRR,
I' T 1312'
I I�
I � I
i
' - I PEDIATRTiL I
DIVI
I Ii
T
RENOVATION POWER AND SYSTEMS
SCALE: 1 /4 = 1'-0"
GENERAL RENOVATION NOTES:
1. ALL DEVICES SHOWN ARE NEW UNLESS
NOTED OTHERWISE.
2. REFER TO RISER DIAGRAM, ELECTRICAL DETAILS AND PANEL SCHEDULES FOR
MORE INFORMATION.
3. PER 2008 NEC A DEDICATED NEUTRAL SHALL BE PROVIDED FOR ALL
CIRCUITS. SHARED NEUTRALS SHALL NOT BE ALLOWED.
4. COORDINATE ALL DEVICE/LIGHT LOCATIONS WITH ARCHITECTURAL,
MECHANICAL AND MILLWORK DRAWINGS AND DIAGRAMS PRIOR TO ROUGH IN.
5. PROVIDE NEW NAME ENGRAVED COVER PLATES INDICATING SUPPLY PANEL
AND CIRCUIT NUMBER(S) FOR ALL ELECTRICAL DEVICES IN THIS PROJECT.
ENGRAVING SHALL BE WHITE/BLACK LETTERS ON RED PLATE FOR CRITICAL
AND BLACK LETTERS ON SPECIFIED COLOR PLATE FOR NORMAL CIRCUITS.
6. PROVIDE NEW UPDATED TYPED PANEL SCHEDULES FOR ALL PANELS USED IN
THIS PROJECT. VERIFY EXACT PANEL IDENTIFICATION WITH OWNER. PROVIDE
NEW NAME ENGRAVED PLATES FOR ALL PANELS NOT IDENTIFIED PROPERLY.
VERIFY PRIOR TO ORDERING.
7. PROVIDE PHENOLIC NAMEPLATES ON ALL PANELBOARDS, SWITCHBOARDS,
DISCONNECTS, TRANSFORMERS, ETC, INDICATING DESIGNATION, CIRCUIT
NUMBER(S), VOLTAGE AND WHERE DEVICE IS FED FROM. SECURE
NAMEPLATES WITH AT LEAST TWO SCREWS/RIVETS OR APPROVED
CEMENT/ADHESIVE. NAMEPLATES SHALL BE COLORED AS PER
SPECIFICATIONS.
8. REFER TO E2.2 FOR ADDITIONAL WORK IN THIS PROJECT.
PER 2008 NEC THE ELECTRICAL CONTRACTOR SHALL PROVIDE
A DEDICATED NEUTRAL FOR ALL NEW AND RE -USED CIRCUITS.
SHARED NEUTRALS WILL NOT BE ALLOWED.
SELECTIVE KEYNOTES O
PENINSULA ENGINEERING INC.
CONSULTING ENGINEERS
ESTABLISHED IN 1977 C�2hyrig
t
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 • 407.246.1688 • EB 3089 009 0
Copyright — All ideas, designs, methods and plans indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and
developed for use on and in connection with the specified project None of the ideas, designs, JO
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
JEA BS
issue date drawn by approved by
REVISION SCHEDULE
DATE I DESCRIPTION
project number
DEMOiRENO POWER AND E1
SYSTEMS ■
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS. >
``%,%%IIiII1ly!!!
G SPA V l.�,�
Ile
o
STAT�Q •
• ��:
%�•c+ ry ff�a pd• [.SPE,
BURKE HOGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL
111 32746
407.333.2005 AAC000233
W W W B H M U
0 -M
I
DEMOLITION PLAN FIRST FLOOR NURSE CALL
SCALE: 1/8" = 1'-0"
RENOVATION PLAN FIRST FLOOR NURSE CALL
SCALE: 1/8" = 1'-0"
ERICO CADDY
BC400 BEAM CLAMP
J—HOOK
HANGERS
4" SPACE FOR
CABLE
5'-0" O.C.�� ° r6 PLACEMENT
/(TYPICAL)
°
SYSTEMS CABLING °
SYSTEMS CABLING
SYSTEMS CABLING ---
J -HOOK SUSPENDED MOUNTING DETAIL
SCALE: NONE
SYSTEMS CABLING
SYSTEMS CABUNG
SYSTEMS CABLING
GENERAL NOTES=
1. ALL EQUIPMENT, DEVICES, CONDUIT, WIRE, BOXES ETC. MADE OBSOLETE
IN THIS PROJECT SHALL BE REMOVED WHEN THE NEW SYSTEM IS FULLY
OPERATIONAL.
2. EXISTING CABLE TRAY, J -HOOKS OR CONDUIT SYSTEM LOCATED ABOVE
CEILING SHALL BE REUSED IF POSSIBLE FOR NEW INSTALLATION. REMOVE
SYSTEMS MADE OBSOLETE.
3. ALL DEVICE LOCATIONS SHALL BE FIELD VERIFIED.
4. ALL REUSABLE DEVICES NOT USED SHALL BE TURNED OVER TO THE
OWNER.
5. ALL DEVICES SHOWN ARE EXISTING TO REMAIN UNLESS NOTED
OTHERWISE.
6. EXISTING NURSE CALL SYSTEM IS A RAULAND RESPONDER III PLUS.
7. ELECTRICAL CONTRACTOR SHALL PROVIDE AND COORDINATE CONDUIT
ROUTING AND J -BOX LOCATIONS WITH NURSE CALL SUPPIER/VENDOR.
SUPPORT PER NEC. UTILIZE EXISTING NURSE CALL CONDUIT/CABLE TRAY
WHERE ABLE. REFER TO NURSE CALL SUPPIER/VENDOR DRAWINGS FOR
MORE INFO.
8. ALL CABLING TO BE FIELD TERMINATED BY INSTALLING CONTRACTOR.
9. DEVICE LOCATIONS ARE FOR ILLUSTRATION ONLY. FIELD DETERMINE
ACTUAL PLACEMENT.
10. PROVIDE INSULATING GROMMETS WITH STRAIN RELIEF AT ALL REQUIRED
LOCATIONS.
11. FOR CIRCUITING/WIRING. COORDINATE WITH NURSE CALL SUPPIER/VENDOR
DRAWING.
12. PROVIDE PROGRAMMING/REPROGRAMMING AS NECESSARY FOR PROPER
OPERATION.
13. ELECTRICAL CONTRACTOR SHALL PROVIDE & COORDINATE NEW CONDUIT
ROUTING & J -BOX LOCATIONS WITH NURSE CALL SUPPIER/VENDOR.
14. ELECTRICAL CONTRACTOR SHALL PROPERLY SUPPORT ALL EXISTING AND
NEW FREE WIRED CONDUCTORS WITH J -HOOKS OR APPROVED SUPPORT
DEVICES IN THE PROJECT AREA. REFER TO DETAILS THIS SHEET FOR
MORE INFORMATION.
15. REFER TO PHASING PLAN E1.2 FOR ADDITIONAL WORK IN THIS PROJECT.
KEYED NOTES:
O1 ELECTRICAL CONTRACTOR SHALL TRACE AND IDENTIFY EXISTING CIRCUIT AND
PROVIDE A PHENOLIC NAMEPLATE INDICATING DESIGNATION, CIRCUIT
NUMBER(S), VOLTAGE AND WHERE DEVICE IS FED FROM. SECURE NAMEPLATES
WITH AT LEAST TWO SCREWS/RIVETS OR APPROVED CEMENT/ADHESIVE.
NAMEPLATE SHALL BE COLORED AS PER SPECIFICATIONS.
NURSE CALL
SYMBOL
DESCRIP11ON
FN -C -M-4
NURSE CALL MASTER STATION
NTC
NURSE CALL TERMINATION CABINET
FOD
DUTY STATION
FOS
STAFF STATION
J -HOOK WALL MOUNT DETAIL
SCALE: NONE
" SPACE FOR
" CABLE
PLACEMENT
SELECTIVE KEYNOTES O
PENINSULA ENGINEERING INC.
CONSULTING ENGINEERS
ESTABLISHED IN 1977 pyright
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 • 407.246.1688 • EB 3089 2009
Copyright — All Ideas, designs, methods and plans indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and
developed for use on and in connection with the specified project. None of the ideas, designs. JOB#:
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
JEA BS
issue date drawn by approved by
REVISION SCHEDULE
DATE I DESCRIPTION
project number
DEMO/RENO E2N2
PLAN NURSE CALL sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
m4�:'X �\GENSF.'
' No. 1 ;
10teTKTISP-ngleir E
ZONAL
BURKE HOGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL
32746
Am AAA 2171171-9 AAr_nnn2-a!q
W W W B H M U S C 0 M
�► CRI
ii
T,131
'II PEDTATRTC
-r�►- _ - --CSL
T�
DEMOLITION PLAN LIGHTING
SCALE: 1 /4" = 1'-0"
GENERAL NOTES:
1. ALL DEVICES SHOWN ARE TO BE
REMOVED UNLESS NOTED OTHERWISE.
2. REFER TO RISER DIAGRAM AND PANEL SCHEDULES FOR MORE
INFORMATION.
3. ELECTRICAL CONTRACTOR SHALL TRACE AND IDENTIFY ALL CIRCUITS WITHIN
THE WORK AREA AND KEEP A WRITTEN RECORD. PROVIDE NEW ENGRAVED
COVER PLATES FOR ALL DEVICES AS PER SPECIFICATIONS.
4. PER 2008 NEC THE ELECTRICAL CONTRACTOR SHALL PROVIDE A DEDICATED
NEUTRAL FOR ALL CIRCUITS RE -USED. SHARED NEUTRALS SHALL NOT BE
ALLOWED.
5. ALL CONDUIT AND WIRE REMOVED SHALL BE TAKEN BACK TO THE SOURCE
OF SUPPLY.
6. ALL REUSABLE DEVICES, FIXTURES AND EQUIPMENT SHALL BE TURNED
OVER TO THE OWNER.
7. ALL DEVICES, CONDUIT AND WIRE MADE OBSOLETE IN THIS PROJECT SHALL
BE REMOVED.
8. DASHED WALLS/LINES ARE TO BE DEMOLISHED. DEVICES, CONDUIT, BOXES,
ETC. SHALL BE REMOVED.
9. ELECTRICAL CONTRACTOR SHALL VERIFY ALL EXISTING SWITCHES IN THE
PROJECT AREA ARE SPEC GRADE. PROVIDE NEW AS REQUIRED. NORMAL
CIRCUIT SWITCHES TO BE IVORY (VERIFY WITH ARCHITECT) AND CRITICAL
CIRCUIT SWITCHES TO BE RED.
10. REFER TO PHASING PLAN E1.2 FOR ADDITIONAL WORK IN THIS PROJECT.
KEYED NOTES:
O1 ELECTRICAL CONTRACTOR SHALL TRACE AND IDENTIFY EXISTING KEY SWITCH.
COORDINATE WITH FACILITY AND STAFF IF SWITCH IS STILL IN USE. REMOVE IF
OBSOLETE.
PER 2008 NEC THE ELECTRICAL CONTRACTOR SHALL PROVIDE
A DEDICATED NEUTRAL FOR ALL NEW AND RE -USED CIRCUITS.
SHARED NEUTRALS WILL NOT BE ALLOWED.
SELECTIVE KEYNOTES D
i '
i
EQUIPMENT
LSTORAGE
0
o�
— — ;E1—
i STATION
NOURISHME :71F
3ROOM
A
FETAL
— -- MONITOR — —
STATIO
I
I
F StATION A
L�,R N o
I
I . A
i I T I
I
_ A A
Ii
I I
I 1
I I
►; �I CCS
I
j T 13 1
I li
I
t
CCCCTCC
_-CCC
� E I
I €I ^ i
RENOVATION PLAN LIGHTING
SCALE: 1 /4" = 1'-0"
GENERAL NOTES:
1, REFER TO RISER DIAGRAM, ELECTRICAL DETAILS AND PANEL SCHEDULES FOR
MORE INFORMATION.
2. PER 2008 NEC A DEDICATED NEUTRAL SHALL BE PROVIDED FOR ALL CIRCUITS.
SHARED NEUTRALS SHALL NOT BE ALLOWED.
3. COORDINATE ALL DEVICE/LIGHT LOCATIONS WITH ARCHITECTURAL, MECHANICAL
AND MILLWORK DRAWINGS AND DIAGRAMS PRIOR TO ROUGH IN.
4. PROVIDE NEW NAME ENGRAVED COVER PLATES INDICATING SUPPLY PANEL AND
CIRCUIT NUMBER(S) FOR ALL ELECTRICAL DEVICES IN THIS PROJECT. ENGRAVING
SHALL BE WHITE/BLACK LETTERS ON RED PLATE FOR CRITICAL AND BLACK
LETTERS ON SPECIFIED COLOR PLATE FOR NORMAL CIRCUITS.
5. PROVIDE NEW UPDATED TYPED PANEL SCHEDULES FOR ALL PANELS USED IN
THIS PROJECT. VERIFY EXACT PANEL IDENTIFICATION WITH OWNER. PROVIDE NEW
NAME ENGRAVED PLATES FOR ALL PANELS NOT IDENTIFIED PROPERLY. VERIFY
PRIOR TO ORDERING.
6. CLEAN, RELAMP AND REFURBISH ALL ETR/NL FIXTURES. CHECK SWITCHES AND
DIMMERS FOR PROPER OPERATION. REPLACE LIGHTS/DEVICES IF NECESSARY
(MATCH EXISTING).
7. ELECTRICAL CONTRACTOR SHALL PROVIDE A 'LUMINAIRE DISCONNECT
CONNECTOR' FOR ALL FLUORESCENT FIXTURES. UL LISTED CONNECTORS ARE
MANUFACTURED BY IDEAL, THOMAS AND BETTS AND WAGO. ANY UL LISTED
CONNECTOR WILL BE ACCEPTABLE. INSTALL PER MANUFACTURERS
SPECIFICATIONS.
KEYED NOTES:
O1 PROVIDE A NEW FIXTURE TO MATCH EXISTING.
O2 CONNECT TO EXISTING CRITICAL LIGHTING CIRCUIT RETAINED DURING DEMOLITION.
O3 CONNECT TO EXISTING NORMAL LIGHTING CIRCUIT RETAINED DURING DEMOLITION.
PER 2008 NEC THE ELECTRICAL CONTRACTOR SHALL PROVIDE
A DEDICATED NEUTRAL FOR ALL NEW AND RE -USED CIRCUITS.
SHARED NEUTRALS WILL NOT BE ALLOWED.
PENINSULA ENGINEERING INC.
CONSULTING ENGINEERS
ESTABLISHED IN 1977 &yright
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 • 407.246.1688 • EB 3089 2009
0
Copyright — All ideas. designs, methods and plans indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and
developed for use on and in connection with the specified project. None of the ideas, designs, JOB#:
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
JEA BS
issue date drawn by approved by
REVISION SCHEDULE
0 DATE DESCRIPTION
project number
DEMO/RENO LIGHTING E3N1
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
``,tlllllifill
Js
a SP,q�'s,`P
0.64601
• P
,t
rS.,,TATE OF •4
Bryari� •a It1P •' ���
FL Reg!��t s+ $Ole"'"
�� BURKE HOGUE MILLS, INC.
Ne i %%%1 130 Business Center Drive, Lake Mary, FL
32746
- - - - -- - 407.333.2008 AAC000233
W W W B H M U S C 0 M
FIXTURE SCHEDULE
FIXTURE
TYPE
DESCRIPTION
MANUFACTURER
CATALOG NUMBER
MOUNTING
VOLTS
LAMP
LAMP
LAMP
LAMP
KEY
QTY
TYPE
WATTS
COLOR
NOTE
A
2' x 4' RECESSED FLUORESCENT .125 LENSED TROFFER
PER
MOOAL UX
2GRB-332A-UNV-EB81-U
RECESSED
UNV
3
F32T8
32
(3500K)
GENERAL NOTES:
A.
ALL NOTES SHALL BE REVIEWED AND SHALL COMPLY TO FIXTURE SCHEDULE.
B.
FIXTURE SHALL BE INSTALLED PER MANUFACTURERS' INSTRUCTIONS.
C.
VERIFY EXACT MOUNTING INSTRUCTIONS WITH ARCHITECTURAL AND STRUCTURAL DETAILS.
D.
VERIFY CATALOG NUMBER OF LIGHT FIXTURE PRIOR TO RELEASE. VERIFY AGAINST PLANS.
E.
NOT USED.
F.
NOT USED.
G.
OSRAM SYLVANIA LAMPS AND BALLASTS OR APPROVED EQUAL.
H.
LAMPS AND BALLASTS SHALL MATCH TO PROVIDE 36 MONTH WARRANTY ON LAMPS AND 60 MONTH WARRANTY ON BALLASTS.
I.
THE DIVISON 16 CONTRACTOR SHALL REGISTER THE PROJECT AND PROVIDE ALL INFORMATION AT CLOSE OUT.
J.
APPROVED EQUALS BY SESCO/DAYBRITE, LIGHTING PARTNERS/METALUX AND LANDRETH/LITHONIA NO OTHER MANUFACTURER SHALL BE ACCEPTABLE OR APPROVED.
K.
ALL DIVISION 16 EQUALS SHALL BE ENGINEER APPROVED 10 DAYS PRIOR TO CLOSE OF BID FOR PROJECT.
KEY NOTE:
PENINSULA ENGINEERING INC.
CONSULTING ENGINEERS
ESTABLISHED IN 1977 &yright
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 • 407.246.1688 • EB 3089 2009
0
Copyright — All ideas. designs, methods and plans indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and
developed for use on and in connection with the specified project. None of the ideas, designs, JOB#:
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
JEA BS
issue date drawn by approved by
REVISION SCHEDULE
0 DATE DESCRIPTION
project number
DEMO/RENO LIGHTING E3N1
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
``,tlllllifill
Js
a SP,q�'s,`P
0.64601
• P
,t
rS.,,TATE OF •4
Bryari� •a It1P •' ���
FL Reg!��t s+ $Ole"'"
�� BURKE HOGUE MILLS, INC.
Ne i %%%1 130 Business Center Drive, Lake Mary, FL
32746
- - - - -- - 407.333.2008 AAC000233
W W W B H M U S C 0 M
CYICT1AIn nnKIr%rnnKI
NO SERIES RATING FAULT CURRENT ALLOWED.
PANELBOARD SCHEDULE: NA LEFT BOLT -ON ■ NEW ❑ SINGLE PANEL ■ NORMAL ■
PLUG-IN ❑ EXISTING ■ DOUBLE PANEL ❑ CRITICAL ❑
VOLTS: 120 208 30 4 WIRE PANEL RATED 0 225 AMPS: M C B: 0 INDOOR ■ SURFACE ■ LIFE SAFETY ❑
TYPE: SQ D NQO NEMA 1 kAIC 10 PANEL OVERLOAD 225 AMPS:
— PROTECTION M.L.O: ❑ OUTDOOR ❑ RECESSED ❑ EQUIPMENT ❑
FED FROM: NWSB #1 VIA 75KVA LOCATION: AS SHOWN
PANELBOARD SCHEDULE: NA RIGHT
N
(AMPS)
LOAD AMPS
IDENTIFICATION
Ash BO CO
C.B.
AMP
w
�
o
a
CKT.
N0.
CKT.
N0.
w
�
p
a
C.B. LOAD (AMPS)
AMP A0 BO CO
IDENTIFICATION
N
0
T
N
0
T
(AMPS)
LOAD AMPS
IDENTIFICATION AO BO CO
C.B.
AMP
w
�
a
CKT.
NO.
CKT.
NO.
w
a
C.B. LOAD (AMPS)
AMP AO BO CO
IDENTIFICATION
0
0
T
DR. LOUNGE,URCA RM. LIGHTS --
BO CO
20
1
1
2
1
20 --
MED RECORDS LTS.
2
1
WORK CONF. REC. --
MED RECORDS LTS.
20
1
43
44
1
20 --
SEC. REC. SOUTH SIDE
1
43
44
CONF., COPIER,OFFICE RM LTS. --
20
1
3
4
1
20
--
MED RECORDS LTS.
--
20
DR. LOUNGE,BATH,OUTSIDE GFI --
20
1
45
46
1
20
--
SEC. REC. SOUTH SIDE
20
1
45
BOARDROOM LTS. --
20
1
5
6
1
20
--
ASST. ADMIN. OFFICE LTS.
BOARDROOM LTS.
MICROFILM PRINTER/READER REC. --
20
1
47
48
1
20
--
REC. MED RECORDS N. COLUMM
MICROFILM PRINTER/READER REC.
TRANSCRIPTION,EQUIP. STOR. LTS. --
20
1
7
8
1
20 --
LTS. OUT PAT. STAGING
-- REC. MED RECORDS N. COLUMM
ELETRIEVER REC. --
20
1
49
50
1
20
--
REC. MED RECORDS CUBICLES
1
1
SPARE
--
20
1
9
10
1
20
--
LTS. CHANGE ROOM
1
49
REC. MED RECORDS, LOUNGE
--
20
1
51
52
1
20
--
COPIER REC.
1
REC. NURSE STATION LABOR/DELIV.
1
SPARE
--
20
1
11
12
1
20
--
U.R. REC. EAST & SOUTH WALL
REC. MED RECORDS, LOUNGE
DIR. MED RECORDS REC.
--
--
20
1
53
54
3
60
--
PANEL NOB
--
COPIER REC.
0. A. - REC.
--
20
1
13
14
1
20
--
U.R. REC. EAST & SOUTH WALL
6
PANEL NA1
--
60
3
55
56
-
-
--
-
CONFERENCE REC.
--
--
20
1
15
16
1 1
20
--
OFFICE REC.
-- PANEL NOB
-
--
-
-
57
58
-
-
--
-
20
MED RECORDS REC. LEFT OF EXIT
MED RECORDS REC. RIGHT OF EXIT
--
--
20
20
1
1
17
19
18
20
1
1
20
20
--
--
COPIER OFF. REC. SOUTH WALL
EQUIP. STOR. REC. NORTH WALL
-
ASST ADMIN REC.
--
--
-
20
-
1
59
61
60
62
1
1
20
20
--
--
CHANGE RM. N. SIDE CORR. 195-201
CHANGE RM. S. SIDE 203-207
-
DR. GATE --
20
1
21
22
1
20
--
REC. MED RECORDS CUBICLES
20
SPARE
--
20
1
63
64
1
20
--
3 NURSE STATION
--
-
MOBILE FILES REC. --
20
1
23
24
1
20
--
REC. MED RECORDS CUBICLES
SPARE
--
20
1
65
66
1
20
--
GA COUNTER PAT. OBSERVE
17
18
COPIER MEDS RECORDS --
20
1
25
26
1
20
--
REC. MED RECORDS
--
-
REC. WAIT RM W.&TV, PED CHANGE
--
20
1
67
68
1
20
--
REC. CONSULT 0184 & PAT. OBSERVE
DICT., SEC., REC. --
20
1
27
28
1
20
--
TRANSCRIPTION REC. WEST WALL
20
1
PAT. OBSERVE 0183 S. WALL REC.
--
20
1
69
70
1
20
--
REC. VESTIBULE & WAITING 0180
61
62
1
20
SNACKS GF] REC. --
20
1
29
30
1
20
--
SNACKS GA
--
SPACE
--
1
1
71
72
1
-- REC. MED RECORDS CUBICLES
--
SPACE
SPARE
TRANSCRIPTION REC. EAST WALL --
20
1
31
32
1
20
--
STEAMER IN BOARDROOM
--
3 NURSE STATION
SPACE
--
1
73
74
1
--
SPACE
1
23
SNACKS REC. NORTH WALL
--
20
1
33
34
1
20
--
STEAMER IN BOARDROOM
20
1
SPACE
--
1
1
75
76
1
--
SPACE
COPIER MEDS RECORDS
BOARDROOM REC. --
20
1
35
36
1
20
--
BOARDROOM CORR. REC.
-- REC. MED RECORDS
SPACE
--
--
1
77
78
1
67
--
SPACE
20
--
ADMIN BATHRM. REC. --
20
1
37
38
1
20
--
ASST. ADMIN. REC. EAST & SOUTH
--
SPACE
--
27
1
79
80
1
--
SPACE
--
ASST. ADMIN. OFFICE REC.
--
20
1
39
40
1
20
--
ASST. ADMIN. REC. NORTH & SOUTH
SPACE
--
1
81
82
1
29
--
SPACE
20
-- SNACKS GFI
COND. UNIT REC. AHU-8 --
20
1
41
42
1
20
--
SNACKS GFl
SPACE
--
1
83
84
1
--
SPACE
SUBTOTAL AMPS -- -- --
20
1
31
32
1
-- -- --
SUBTOTAL AMPS
SUBTOTAL AMPS
-- -- --
SPACE
1 1
-- -- --
SUBTOTAL AMPS
1
--
SPACE
SNACKS REC. NORTH WALL
TOTAL AMPS SECT. 1 "A" PHASE: -
TOTAL AMPS SECT. 1 "B" PHASE: -
TOTAL AMPS SECT. 1 "C" PHASE: -
TOTAL AMPS SECT. 2 "A" PHASE: - TOTAL AMPS "A" PHASE: - MAXIMUM CONNECTION PHASE AMPS: -
TOTAL AMPS SECT. 2 "B" PHASE: - TOTAL AMPS "B" PHASE: - TOTAL CONNECTED kVA: -
TOTAL AMPS SECT. 2 "C" PHASE: - TOTAL AMPS "C" PHASE: - TOTAL DEMAND kVA/AMPS: NOTE 2
NOTES:
1. UTILIZE EXISTING SPARE 20A/1P BREAKER.
2. EXISTING LOAD RELOCATED FROM PANEL NOB TO THIS PANEL. NO NEW LOAD ADDED IN THIS PROJECT.
NOTES:
Rm/mr- n tv`nAInIT1rW
NO SERIES RATING FAULT CURRENT ALLOWED.
PANELBOARD SCHEDULE: NA LEFT BOLT -ON ■ NEW ❑ SINGLE PANEL ■ NORMAL ■
PLUG-IN ❑ EXISTING ■ DOUBLE PANEL ❑ CRITICAL ❑
VOLTS: 120 208 30 4 WIRE PANEL RATED 0 225 AMPS: M.C.B: ■ INDOOR ■ SURFACE ■ LIFE SAFETY ❑
TYPE: SQ D NQO NEMA 1 kAIC 10 PANEL OVERLOAD 225 AMPS:
— PROTECTION M.L.O: ❑ OUTDOOR ❑ RECESSED ❑ EQUIPMENT ❑
FED FROM: NWSB #1 VIA 75KVA LOCATION: AS SHOWN
PANELBOARD SCHEDULE: NA RIGHT
N
0
E
LOAD (AMPS)
IDENTIFICATION A� BO CO
C.B.
AMP
UJ
�
CO)
CKT.
NO.
CKT.
NO.
w
�
a_
C.B. LOAD (AMPS}
IDENTIFICATION
AMP q� gO CO
N
O
T
N
O
E
LOAD
IDENTIFICATION
(AMPS)
(
C.B.
AMP
w
p
a
CKT.
N0.
CKT.
N0.
w
p
a
C.B. LOAD
AMP
(AMPS)
IDENTIFICATION
0
T
AO
BO CO
A0 BO CO
DR. LOUNGE,URCA RM. LIGHTS --
20
1
1
2
1
20 --
MED RECORDS LTS.
WORK CONE REC.
--
20
1
43
44
1
20
--
SEC. REC. SOUTH SIDE
CONE, COPIER,OFFICE RM LTS.
--
20
1
3
4
1
20 -- MED RECORDS LTS.
DR. LOUN GE,BATH, OUTSIDE GFI
--
20
1
45
46
1
20
-- SEC. REC. SOUTH SIDE
BOARDROOM LTS.
--
20
1
5
6
1
20 -- ASST. ADMIN. OFFICE LTS.
MICROFILM PRINTER/READER REC.
--
20
1
47
48
1
20
-- REC. MED RECORDS N. COLUMM
TRANSCRIPTION,EQUIP. STOR. LTS.
--
20
1
7
8
1
20
-- LTS. OUT PAT. STAGING
ELETRIEVER REC.
--
20
1
49
50
1
20
--
REC. MED RECORDS CUBICLES
1
REC. NURSE STATION LABOR/DELIV.
6
20
1
9
10
1
20
-- LTS. CHANGE ROOM
REC. MED RECORDS, LOUNGE
--
20
1
51
52
1
20
--
COPIER REC.
1
REC. NURSE STATION LABOR/DELIV.
6
20
1
11
12
1
20
-- U.R. REC. EAST & SOUTH WALL
DIR. MED RECORDS REC.
--
20 1
1
53
54
3
60
-- PANEL NOB
Q.A. - REC.
--
20
1
13
14
1
20
-- U.R. REC. EAST & SOUTH WALL
PANEL NA1
--
60
3
55
56
-
-
--
-
CONFERENCE REC.
--
20
1
15
16
1
20
-- OFFICE REC.
-
--
-
-
57
58
-
-
--
-
MED RECORDS REC. LEFT OF EXIT
--
20
1
17
18
1
20
-- COPIER OFF. REC. SOUTH WALL
-
--
-
-
59
60
1
20
-- CHANGE RM. N. SIDE CORR. 195-201
MED RECORDS REC. RIGHT OF EXIT
--
20
1
19
20
1
20
-- EQUIP. STOR. REC. NORTH WALL
ASST ADMIN REC.
--
20
1
61
62
1
20
--
CHANGE RM. S. SIDE 203-207
DR. GATE
--
20
1
21
22
1
20
-- REC. MED RECORDS CUBICLES
SPARE
--
20
1
63
64
1
20
--
3 NURSE STATION
MOBILE FILES REC.
--
20
1
23
24
1
20
-- REC. MED RECORDS CUBICLES
SPARE
--
20
1
65
66
1
20
-- GFI COUNTER PAT. OBSERVE
COPIER MEDS RECORDS
--
20
1
25
26
1
20
-- REC. MED RECORDS
REC. WAIT RM W.&TV, PED CHANGE
--
20
1
67
68
1
20
--
REC. CONSULT 0184 & PAT. OBSERVE
DICT., SEC., REC.
--
20
1
27
28
1
20
-- TRANSCRIPTION REC. WEST WALL
PAT. OBSERVE 0183 S. WALL REC.
--
20
1
69
70
1
20
--
REC. VESTIBULE & WAITING 0180
SNACKS GFI REC.
--
20
1
29
30
1
20
-- SNACKS GFI
SPACE
--
1
71
72
1
-- SPACE
TRANSCRIPTION REC. EAST WALL
--
20
1
31
32
1
20
-- STEAMER IN BOARDROOM
SPACE
1 1
73
74
1
--
SPACE
SNACKS REC. NORTH WALL
--
20
1
33
34
1
20
-- STEAMER IN BOARDROOM
SPACE
--
1
75
76
1
--
SPACE
BOARDROOM REC.
--
20
1
35
36
1
20
-- BOARDROOM CORR. REC.
SPACE
--
1
77
78
1
-- SPACE
ADMIN BATHRM. REC.
--
20
1
37
38
1
20
-- ASST. ADMIN. REC. EAST & SOUTH
SPACE
--
1
79
80
1
--
SPACE
ASST. ADMIN. OFFICE REC.
--
20
1
39
40
1
20
-- ASST. ADMIN. REC. NORTH & SOUTH
SPACE
--
1
81
1 82
1
--
SPACE
COND. UNIT REC. AHU-8
--
20
1
41
42
1 1
20
-- SNACKS GFI
SPACE
--
1
83
84
1
-- SPACE
SUBTOTAL AMPS
--
--
--
-- -- -- SUBTOTAL AMPS
SUBTOTAL AMPS
-- --
--
--
--
-- SUBTOTAL AMPS
TOTAL AMPS SECT. 1 "A" PHASE: -
TOTAL AMPS SECT. 1 "B" PHASE: -
TOTAL AMPS SECT. 1 "C" PHASE: -
TOTAL AMPS SECT. 2 "A" PHASE: - TOTAL AMPS "A" PHASE: - MAXIMUM CONNECTION PHASE AMPS: -
TOTAL AMPS SECT. 2 "B" PHASE: - TOTAL AMPS "B" PHASE: - TOTAL CONNECTED kVA: -
TOTAL AMPS SECT. 2 "C" PHASE: - TOTAL AMPS "C" PHASE: - TOTAL DEMAND kVA/AMPS: -/-
NOTES:
1. NEW LOAD ADDED IN THIS PROJECT.
PROVIDE A NEW UPDATED TYPED PANEL SCHEDULE.
NOTES:
EXISTING CONDITION
NA RIGHT &LEFT
REVISED CONDITION
NA RIGHT &LEFT
SELECTIVE KEYNOTES O
PENINSULA ENGINEERING �NCo
CONSULTING ENGINEERS
ESTABLISHED IN 1977 01p�9ht
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 • 407.246.1688 • EB 3089
Copyright — All Ideas, designs, methods and plans indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc. and were created, evolved and
developed for use on and in connection with the specified project None of the ideas, designs, JOB#:
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
JEA BS
issue date drawn by approved by project number
REVISION SCHEDULE
DATE DESCRIPTION
rl =Emma
PANEL SCHEDULES
ei orToirni
E6E1
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.
`��ttl{1111,lf
s
%` N G SP,g '� r
�`Q� P•• C -NSF': �� ��
601
r �D 't• STATE OF =
-0 ?40RI01".0
Bryan G,••••�PW,�.4,��
FL Reg. No. fj�} It+iO��` BURKE HOGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL
32746
407.333.2005 AAC000233
W W W B H M U S
EXISTING CONDITION
NO SERIES RATING FAULT CURRENT ALLOWED.
PANELBOARD SCHEDULE: NEC LEFT BOLT -ON ■ NEW ❑ SINGLE PANEL ■ NORMAL O
PLUG-IN ❑ EXISTING ■ DOUBLE PANEL ❑ CRITICAL ■
VOLTS: 120/208 30 4 WIRE PANEL RATED 0 225 AMPS: M.C.B: ■ INDOOR ■ SURFACE ■ LIFE SAFETY ❑
TYPE: SQ D NQO NEMA 1 kAIC 10 PANEL OVERLOAD 150 AMPS:
— PROTECTION M.L.O: ❑ OUTDOOR ❑ RECESSED ❑ EQUIPMENT ❑
FED FROM: NWSB #1 VIA 75KVA LOCATION: AS SHOWN
PANELBOARD SCHEDULE:
NEC
RIGHT
N
T
E
N
T
IDENTIFICATION
(AMPS) C.B.
BO CO AMP
LOAD
(AMPS)
C.B.
AMP
-
0-
CKT.
N0.
CKT.
N0.
_
O
a
C.B.
AMP
LOAD
AO
(AMPS)
IDENTIFICATION
BO CO
N
T
N
T
IDENTIFICATION
LOAD
AO
(AMPS) C.B.
BO CO AMP
�
a
CKT.
N0.
CKT.
N0.
�
0
a
C.B.
AMP
LOAD (AMPS)
IDENTIFICATION
AO BO CO
N
T
AO
BO
CO
CO
MED FILES &RECORDS LTS.
MED FILES &RECORDS LIS.
--
20
1
20
1
1
2
1
20
--
ADMIN. &SEC. OFFICE REC.
ECOB PANEL
--
ECOB PANEL
--
60
3
31
32
3
60
-- NEC1 PANEL
DICT. LTS.
NEC1 PANEL
--
DICT. LTS.
20
1
3
4
1
20
20
-- LTS. NURSE STATION
-- LTS. NURSE STATION
-
-- -
-
33
34
-
-
-- -
33
34
-
-
COMPUTER EQUIP. STOR. REC.
--
-
--
20
1
5
6
1
20
6
-- LTS. 0197 OUT PAT. STAGING
20
-
-- -
-
35
36
-
-
-- -
-
-
35
36
COMPUTER EQUIP. STOR. REC.
-
--
--
20
1
7
8
1
20
--
COMPUTER EQUIP. STOR. REC.
7
8
CHANGE ROOM S. WALL
--
20
-- 20
1
37
38
1
20
-- REC. W. WALL S.U. ROOM
COMPUTER EQUIP. STOR. REC.
1
1
20
1
9
10
1
20
-- COMPUTER EQUIP. STOR. REC.
REC. W. WALL S.U. ROOM
CORR. REC.
1
39
40
1
20
-- REC. BEHIND W. NURSE STA., SOIL
20
-- COMPUTER EQUIP. STOR. REC.
COMPUTER EQUIP. STOR. REC.
CORR. REC.
--
20
1
11
12
1
20
1
-- COMPUTER EQUIP. STOR. REC.
12
1
CHANGE ROOM N. WALL
-- 20
1
41
42
1
20
-- WARMER REC.BEHIND W. NURSE STA
--
20
1
COMPUTER EQUIP. STOR. REC.
42
--
20
20
1
13
14
1
20
--
COMPUTER EQUIP. STOR. REC.
COMPUTER EQUIP. STOR. REC.
--
E. NURSE STA. CHANGE ROOM
--
20
1
43
44
1
20
-- REC. C.U. N & S WALL REC.
E. NURSE STA. CHANGE ROOM
--
COMPUTER EQUIP. STOR. REC.
20
1
--
44
20
1
15
16
1
20
REC. C.U. N & S WALL REC.
-- COMPUTER EQUIP. STOR. REC.
COMPUTER EQUIP. STOR. REC.
ELEC. ROOM REC.
-- 20
-- 20
1
45
46
1
20
-- REC. C.U. FRIDGE
ELEC. ROOM REC.
TRANSCRIPTION REC. E. SIDE
20
1
45
--
20
1
17
18
1
20
REC. C.U. FRIDGE
-- TRANSCRIPTION REC. E. WALL
TRANSCRIPTION REC. E. SIDE
SPACE
-- 20
--
1
47
48
1
-- SPACE
SPACE
SNACK REC. W. WALL
DRS. LOUNGE REC.
--
--
1
20
1
19
20
1
20
--
SNACK FRIDGE REC.
--
SPACE
SPACE
--
1
49
50
1
19
-- SPACE
1
20
1
21
22
1
20
--
-- SNACK FRIDGE REC.
SPACE
49
--
1
1
51
53
52
54
1
1
SPACE
-- SPACE
-- SPACE
DRS. LOUNGE REC.
ADMIN. OFFICE REC.
1
21
22
--
20
1
23
24
1
20
-- SPARE
1
SPACE
51
--
1
--
--
'IS-DEUV' PANEL
--
20
1
25
26
2
20
--
SPARE
20
4.5 DICTATION LABOR/DELIV.
SPACE
--
SPACE
1
55
56
1
1
-- SPACE
54
1
1
SPARE
SPACE
--
20
1
27
28
-
-
-- -
2
20 --
SPACE
SPACE
--
--
1
1
57
59
58
60
1
1
-- SPACE
-- SPACE
1
1
SPARE--
1
20
1
29
30
1
20 -- DRS. LOCKERS 0210 N. WALL REC.
6 20
SUBTOTAL AMPS
--
-- --
-
-
-- -
--
-- -- SUBTOTAL AMPS
SUBTOTAL AMPS --
-- --
1
57
58
1
-- -- -- SUBTOTAL AMPS
--
SPACE
1 REC. NURSE STATION LABOR/DELIV.
SUBTOTAL AMPS --
7.5 20
-- --
1
29
30
1
TOTAL AMPS SECT. 1 "A"
TOTAL AMPS SECT. 1 "B"
TOTAL AMPS SECT. 1 "C"
PHASE: -
PHASE: -
PHASE: -
SPACE
SUBTOTAL AMPS --
--
-- --
1
TOTAL AMPS SECT. 2 "A" PHASE: -
TOTAL AMPS SECT. 2 "B" PHASE: -
TOTAL AMPS SECT. 2 "C" PHASE: -
TOTAL AMPS
TOTAL AMPS
TOTAL AMPS
"A"
"B"
"C"
PHASE: -
PHASE: -
PHASE: -
--
-- -- --
MAXIMUM CONNECTION PHASE AMPS: -
TOTAL CONNECTED kVA: -
TOTAL DEMAND kVA/AMPS: NOTE 2
NOTES:
1. UTILIZE EXISTING SPARE 20A/1P
2. EXISTING LOAD RELOCATED FROM
BREAKER.
PANEL ECOB TO THIS PANEL. NO NEW LOAD ADDED IN THIS PROJECT.
NOTES:
TOTAL AMPS SECT. 1 "A" PHASE: -
TOTAL AMPS SECT. 1 "B" PHASE: -
TOTAL AMPS SECT. 1 "C" PHASE: -
REVISED CONDI110N
NO SERIES RATING FAULT CURRENT ALLOWED.
PANELBOARD SCHEDULE: NEC LEFT BOLT -ON ■ NEW ❑ SINGLE PANEL ■ NORMAL ❑
PLUG-IN ❑ EXISTING ■ DOUBLE PANEL ❑ CRITICAL ■
VOLTS: 120 208 30 4 WIRE PANEL RATED ® 225 AMPS: M.C.B: ■ INDOOR ■ SURFACE ■ LIFE SAFETY ❑
TYPE: SQ D NQO NEMA 1 kAIC 10 PANEL OVERLOAD 150 AMPS:
— PROTECTION M.L.O: ❑ OUTDOOR ❑ RECESSED ❑ EQUIPMENT ❑
FED FROM: NWSB #1 VIA 75KVA LOCATION: AS SHOWN
PANELBOARD SCHEDULE:
NEC
RIGHT
N
T
E
IDENTIFICATION
LOAD
AO
(AMPS) C.B.
BO CO AMP
o
a
CKT.
NO.
CKT.
NO.
o
a
C.B.
AMP
LOAD
AO
(AMPS)
IDENTIFICATION
BO CO
N
O
T
N
0
T
E
IDENTIFICATION
LOAD
(AMPS)
C.B.
AMP
_uJJ
0
a
CKT.
N0.
CKT.
N0.
�
C.B.
AMP
LOAD (AMPS)
IDENTIFICATION
N
T
A0 BO
CO
AO
BO
CO
MED FILES &RECORDS LIS.
--
20
1
1
2
1
20
--
ADMIN. & SEC. OFFICE REC.
ECOB PANEL
--
60
3
31
32
3
60
--
NEC1 PANEL
DICT. LTS.
-- 20
1
3
4
1
20
-- LTS. NURSE STATION
-
--
-
-
33
34
-
-
--
-
COMPUTER EQUIP. STOR. REC.
-- 20
1
5
6
1
20
-- LTS. 0197 OUT PAT. STAGING
-
--
-
-
35
36
-
-
--
-
COMPUTER EQUIP. STOR. REC.
--
20
1
7
8
1
20
--
COMPUTER EQUIP. STOR. REC.
CHANGE ROOM S. WALL
--
20
20
1
1
37
39
38
40
1
1
20
20
--
--
REC. W. WALL S.U. ROOM
COMPUTER EQUIP. STOR. REC.
- 20
1
9
10
1
20
-- COMPUTER EQUIP. STOR. REC.
CORR. REC.
--
REC. BEHIND W. NURSE STA., SOIL
COMPUTER EQUIP. STOR. REC.
-- 20
1
11
12
1
20
-- COMPUTER EQUIP. STOR. REC.
CHANGE ROOM N. WALL
--
20
1
41
42
1
20
--
WARMER REC.BEHIND W. NURSE STA
COMPUTER EQUIP. STOR. REC.
--
20
1
13
14
1
20
--
COMPUTER EQUIP. STOR. REC.
E. NURSE STA. CHANGE ROOM
--
20
1
43
44
1
20
--
REC. C.U. N & S WALL REC.
COMPUTER EQUIP. STOR. REC.
-- 20
1
15
16
1
20
-- COMPUTER EQUIP. STOR. REC.
ELEC. ROOM REC.
--
20
1
45
46
1
20
--
REC. C.U. FRIDGE
TRANSCRIPTION REC. E. SIDE
-- 20
1
17
18
1
20
-- TRANSCRIPTION REC. E. WALL
SPACE
--
1
47
48
1
--
SPACE
SNACK REC. W. WALL
--
20
1
19
20
1
20
--
SNACK FRIDGE REC.
SPACE
--
1
49
50
1
--
SPACE
DRS. LOUNGE REC.
-- 20
1
21
22
1
20
-- SNACK FRIDGE REC.
SPACE
--
1
51
52
1
--
--
SPACE
ADMIN. OFFICE REC.
-- 20
1
23
24
1
20
4.5 DICTATION LABOR/DELIV.
1
SPACE
--
1
53
54
1
SPACE
'IS-DELIV' PANEL
--
20
1
25
26
2
20 --
SPARE
SPACE
--
1
55
56
1
--
SPACE
1
REC. NURSE STATION LABOR/DEUV.
6 20
1
27
28
-
-
-- -
SPACE
--
1
57
58
1
--
SPACE
1 REC. NURSE STATION LABOR/DELIV.
SUBTOTAL AMPS --
7.5 20
-- --
1
29
30
1
20
--
-- DRS. LOCKERS 0210 N. WALL REC.
-- -- SUBTOTAL AMPS
SPACE
SUBTOTAL AMPS --
--
-- --
1
59
60
1
6
--
-- -- --
SPACE
SUBTOTAL AMPS
TOTAL AMPS SECT. 1 "A" PHASE: -
TOTAL AMPS SECT. 1 "B" PHASE: -
TOTAL AMPS SECT. 1 "C" PHASE: -
TOTAL AMPS SECT. 2 "A" PHASE: -
TOTAL AMPS SECT. 2 "B" PHASE: -
TOTAL AMPS SECT. 2 "C" PHASE: -
TOTAL AMPS
TOTAL AMPS
TOTAL AMPS
"A"
"B"
"C"
PHASE: -
PHASE: -
PHASE: -
MAXIMUM CONNECTION PHASE AMPS: -
TOTAL CONNECTED kVA: -
TOTAL DEMAND kVA/AMPS: -/-
NOTES:
1. NEW LOAD ADDED IN THIS PROJECT.
PROVIDE A NEW UPDATED TYPED PANEL SCHEDULE.
NOTES:
EXISTING CONDITION
NEC RIGHT & LEFT
REVISED CONDITION
NEC RIGHT & LEFT
SELECTIVE KEYNOTES O
PENINSULA ENGINEERING INC.
CONSULTING ENGINEERS
ESTAELISHED IN 1977 —yright
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 • 407.246.1688 • EB 3089 2009
Copyright — All ideas, designs. methods and plans Indicated or represented by this drawing
are owned by and the property of Peninsula Engineering. Inc. and were created, evolved and JOB#
developed for use on and In connection with the specified project None of the Ideas, designs,
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
JEA BS
issue date drawn by approved by project number
REVISION SCHEDULE
DATE I DESCRIPTION
PANEL SCHEDULES E6E2
• ELECTRICAL sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BURKE, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY ``;N{4Wffill.,
%% N G. SP,44f, -fl-le
4101
`� ;• `GEN •.' ,[ ��
No.
T�EOF ;•� s
Bf, lV$o:JOE,
1 BURKE HOGUE MILLS, INC.
1130 Business Center Drive, Lake Mary, FL
32746
407.333.2005 AAC000233
- -- - - --- -- -- -- _ - - - - -- - --- 11N Vit - -_ 1At - - B - - -1 -tJ S__ I C 0 M
NODE
O
FAULT CURRENT SCHEDULE
10
32552
A
AVAILABLE (NORMAL) UTILITY TRANSFORMER
20
29205
A
AVAILABLE (NORMAL)
30
4550
A
AVAILABLE (NORMAL)
40
25169
A
AVAILABLE (NORMAL)
50
21172
A
AVAILABLE (NORMAL)
60
2022
A
AVAILABLE (NORMAL)
NORMAL POWER LOAD CALCULATION
30 DAY RECORDED LOAD FOR NMSB #1 = 2180.5AMPS/1812KVA
CHILLER #1 LOAD REDUCED IN THIS PROJECT =-360.OAMPS/298.9KVA
TOTAL LOAD = 1820.5AMPS/1513.1 KVA
25% INCREASE PER NEC = +455.1 AMPS
NEW TOTAL LOAD = 2275.6AMPS/1891.8KVA
NORMAL POWER SYSTEM �- — — — —
FPL SERVICE #1 10
30 277/480V SECONDARY I
1 A A A /
r v 11500KVA
iJ-B0
EMERGENCY GENERATOR #11
L T J 565KW/706.3KVA
1 20 NMSB #1 1000A i<,* -y G 1
------------- T ----------------T ------ _ W/GFI
�E--— — — — — — — — — — — — — TrvsS�
IL
o j o 11 I I =
I °lI ° I 1 L—�-------------- ES _
- — — — A -Y I A I I 7
I — — TVSS 1
1 4 1 1 1 1 2 I 4 3 4 9 1 4 4 4 4 I I 4 2 4 2 1
1 2 0 5 0 0 7 5 1 0 6 6 9 8 6 5 0 0 1 5 5 0 0 I 9
1 5 0 0 0 0 5 0 0 0 0 0 0 0 0 0 A 0 0 0 0 I 0 ° 0 0 0—J
A A A A A A A i A A A A A A A A I A A A A I I A A A A A
I
L—I-- —--I-4----I--1--4_4__I--4—_�--__-__1--tl—I--�—I---�J L-- — ---� — -- --� 75HP
I I I I I I I I I I I I I I I I I L- I I L �� PUMP
I I I I I I I I I I I I I I I I I I I L—__ f=_—__ � I __ �—_—_—_—_—_—_---
XH E M M C M 2A T T LN E T HN I
Q E E 0 S W W N V I H H I-------- I I I
U C C N C P P D S I I 401_( F-
30 I F H H D 1 0 S I 1 2 ATS -EC I ATS -EA I ATS-EQE — ATS -EQ
O I R R N 2 1 � I I I N E 1400A I I N E 1100A I I1 E 400A N 1 E 400A
F�� R M M S ° I I I I I
L J M W I P I L- —J L. --� I L —I L- i I
I E A G Y I (BRA CHL (SAFETY I (BRANCH (BRANCH
T T U I I I I (BRANCH I I 1
�75KVA L_ — I
1_A_--A_� N I -------- __--1 ^l- I �-
'-Y-,�-Y- T E ------------ -------------- IEA� EQE EQ
I
L--------1 1
NA I NA O1 1 50 _ EC _
(LEFT I — RIGHT
-----1 1--------)----------
TVSS�
I 225A)° — — I
50
1 I1
60A °° f 0 0 0 00° L
—J
AA Aq A A A A A
I
---- -----� 1 I L L - —--l--I--1--I —I— I --I
I I CEC I
2EC I I ECA I C (
J I I,1 (ECC ECD
r----- � XEC 1 OR EC
� NA1 I NOB O1 I
soA( I �NPJ
I I I I 1 LIJ1 OOA
I I I I
I
I 45KVAi
L -----J L---`A_/-J
lY'y�Y
I 1
NEC NEC I _ RIGHT
150A) 1,60A1----
1 SOA
I
1 NEC1 ECOB ILEI ECOB RIGHT
I I 60A I I
I I I 1 I I I
L -----J L---��----J
EXISTING RISER DIAGRAM SERVICE #1
SCALE: NONE
1. DASHED LINE REPRESENTS EXISTING TO REMAIN.
JI7V�lt`I T OI\ RETERENCE ONLY.
KEYED NOTES:
O1 PROVIDE NEW TYPED UPDATED PANEL DIRECTORIES.
SELECTIVE KEYNOTES Q
PENINSULA ENGONEEMNG WC.
INSULTING ENGINEERS
ESTABLISHED IN 1977 &pyright
2016 ALDEN ROAD, ORLANDO, FLORIDA, 32803 • 407.246.1688 • EB 3089 2009
0
Copyright — All ideas, designs, methods and plans indicated or represented by this drawing
are owned by and the property of Peninsula Engineering, Inc, and were created, evolved and
developed for use on and in connection with the specified project, None of the Ideas, designs, JOB#:
arrangements, methods or plans shall be used by or disclosed to any person, firm or 10333
corporation for any purpose whatsoever without the written permission of Peninsula Engineering, Inc.
JEA BS
issue date drawn by approved by Droiect number
REVISION SCHEDULE
DATE DESCRIPTION
RISER DIAGRAM - ELECTRICAL E7N
sheet number
THESE DOCUMENTS AND THEIR CONTENTS ARE THE PROPERTY OF BUFF, HOGUE & MILLS ASSOCIATES, INC. AND ARE ISSUED ONLY
FOR THE SPECIFIC PROJECT NOTED ON THESE DRAWINGS. ANY REPRODUCTION AND/OR REDISTRIBUTION WITHOUT THE EXPRESSED
WRITTEN CONSENT OF BURKE, HOGUE & MILLS ASSOCIATES, INC. IS PROHIBITED BY LAW. TO THE BEST OF THE ARCHITECTS
KNOWLEDGE, THESE PLAN AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE
SAFETY STANDARDS.