HomeMy WebLinkAbout1829 WP Ball Blvd (fr sprnklr) + (a) (2)0, 1
CITY OF SANFORD
BUILDING & FIRE PREVENTION
OCT 18 20i6 PERMIT APPLICATION
ni
Application No: & ' / aZ
Documented Construction Value: S (0
Job Address: C)CI lK)2 2n\\ G\\/ J , 11( Historic District: Yes No
Parcel ID: Residential Commercia14
Type of Work: New Addition Alteration @ Repair Demo Change of Use Move -
Description of Work: 0S\C\ a\r\A\ 'a \(cC.. c'o 'aC
Plan Review Contact Person:
Phone: U- Fax: \-0J2S— Q&2$ Email:
Name
Street
City, State Zip:
Property Owner Information
Phone:
Resident of property? :
Contractor Information
Name - Q SCZ Phone:
Street: k. Fax: y Q V 9--c»S
City, State Zip: MPS(' \A \S\O,nState License No.: F-PC 1S' OUY C A Architect/
Engineer Information Name:
Phone: Street:
Fax: City,
St, Zip: Bonding
Company: Address:
E-
mail: Mortgage
Lender: Address:
WARNING
TO OWNER: YOUR FAILURE TO RECORD A NOTICE OF COMMENCEMENT MAY RESULT IN YOUR PAYING
TWICE FOR IMPROVEMENTS TO YOUR PROPERTY. A NOTICE OF COMMENCEMENT MUST BE RECORDED
AND POSTED ON THE JOB SITE BEFORE THE FIRST INSPECTION. IF YOU INTEND TO OBTAIN FINANCING,
CONSULT WITH YOUR LENDER OR AN ATTORNEY BEFORE RECORDING YOUR NOTICE OF COMMENCEMENT.
Application
is hereby made to obtain a permit to do the work and installations as indicated. I certify that no work or installation has commenced
prior to the issuance of a permit and that all work will be performed to meet standards of all laws regulating construction in
this jurisdiction. 1 understand that a separate permit must be secured for electrical work, plumbing, signs, wells, pools, furnaces,
boilers, heaters, tanks, and air conditioners, etc. FBC
105.3 Shall be inscribed with thedateof application and the code in effect as of that date: 5t° Edition (2014) Florida Building Code 71 Revised:
June30, 2015 rPermit Application t'
NOTICE: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that may be
found in the public records of this county, and there may be additional permits required from other governmental entities such as water
management districts, state agencies, or federal agencies. r
Acceptance of permit is verification that I will notify the owner of the property of the requirements of Florida Lien Law, FS 713.
The City of Sanford requires payment of a plan review fee at the time of permit submittal. A copy of the executed contract is required
in order to calculate a plan review charge and will be considered the estimated construction value of the job at the time of submittal.
The actual construction value will be figured based on the current ]CC Valuation Table in effect at the time the permit is issued, in
accordance with local ordinance. Should calculated charges figured off the executed contract exceed the actual construction value,
credit will be applied to your permit fees when the permit is issued.
OWNER'S AFFIDAVIT: I certify that all of the foregoing information is accurate and that all work will
be done in compliance with all applicable laws regulating construction and zoning,
Signature of Owner/Agent Date
Print Owner/Agent's Name
Signature of Notary -State of Florida Date
Owner/Agent is Personally Known to Me or
Produced ID Type of ID
JULIE M. KNOX
Notary Public • State of Florida
N Commission N FF 949427
a „d;:'fly Comm. Expires Feb 5. 2Qa0
Date
CL
is / /
D to
rally Known to Me or
Produced ID - Type of ID
BELOW IS FOR OFFICE USE ONLY
Permits Required: Building Electrical Mechanical Plumbing Gas Roof
Construction Type:
Total Sq Ft of Bldg:
Occupancy Use:
Min. Occupancy Load:
Flood Zone:
of Stories:
New Construction: Electric - # of Amps Plumbing - # of Fixtures,
Fire Sprinkler Permit: Yes No
APPROVALS: ZONING:
1:Q[6JIN:1"IN"
COMMENTS:
of Heads
UTILITIES:
FIRE:
Fire Alarm Permit: Yes No
WASTE WATER:
BUILDING:
Revised: June 30, 2015 Permit Application
h
PERMIT
420 Manor Drive
Merritt Island, Florida 32952
Ph: 321-783-1040 Fax: 321-783-1516
FLORIDA LICENSE NO. 57874200012005
Fire Sprinkler System
Equipment Submittal
For
OLEA MEZZE GRILLE
1829 WP BALL BLVD
SANFORD, FL. 32771
Plan's
OCT _ .
e®vec,
By Ire
0
OFFICE
Note: The following Equipment Material Submittals may be substituted
in field by another manufacture as long as devices are equal.
Proprietary mill coating
ensures clean, corrosion -
resistant surface
Outperforms and
outlasts standard
lacquer -coated pipe
Easily painted, without
special preparation
Available with
hot -dip galvanizing
Also available in black
WEIGHTS AND
DIMENSIONS CHART
NOMINAL
SIZE OD SCHEDULE 40
In.
Wall WL Wt./FL
Inches lbs./ft. HBO Filled
1 1.315 133 1.68 2.055
1% 1.660 140 2.27 2.922
1% 1.900 145 2.72 3.602
2 2.375 154 3.66 5.109
2% 2.875 203 5.80 7.871
3 3.500 216 7.58 10.783
3 % 4.000 226 9.12
4 4.500 237 10.80 16.311
S 5.563 258 14.63 23.262
6 6.625 280 18.99 31.498
Schedule 10 and Schedule 40
High quality,
high performance
Wheatland's Schedule 10 and Schedule 40 steel fire sprinkler pipe
are subjected to the toughest possible testing to ensure the highest
possible quality -not to mention reliable, long-lasting performance.
TECHNICAL DATA CHART
WT./FT. WT./FT. WT./LIFT WT./LIFT WT./LIFT
MPS MOM ID LBS. H.OFILLED PCS./LIFT 21' 24' 25'
1'/• 1.442 1807 2.514 61 2315 2645 2756
1'b 1.682 2.087 3049 61 2673 3055 3183
2 2.157 2 640 4.222 37 2051 2344 2442
236 2 635 3 534 5.895 30 2226 2544 2651
3 3.260 4.336 7949 19 1730 1977 2060
4 4.260 5.619 11.789 19 2242 2562 2669
5 5.29S 7780 17309 13 2124 2427 2529
6 6.357 9 298 23.038 10 1953 2232 2325
8 8.249 16.96 40086 7 2493 2849 2968
SCHEDULE 10 SPECIFICATIONS
NOMINAL
NPS MOM OD MOM ID NOMINAL WALL WEIGHT UL PIECES
in. mm In. mm In. mm lbs./k. kg/m CRR' Lift
11% 1.660 42.2 1.442 366 109 277 181 2.69 7.3 61
1'A 1.900 483 1.682 42.7 109 2.77 2.09 311 5.8 61
2 2.375 60.3 2.157 548 109 277 2.64 3.93 4.7 37
2% 2.875 730 2.635 66.9 320 3.05 3.53 526 3.5 30
3 3.500 889 3.260 828 120 305 4.34 6.46 2.6 19
4 4.S00 114.3 4.260 108.2 120 3.05 562 8.37 1.6 19
S 5.563 141.3 5.295 1345 134 3.40 7.78 Il 58 1.5 13
6 6.625 1683 6.357 161.5 134 3.40 930 1385 1.0 10
8 8.625 219.1 8249 209.5 188 478 16.96 25.26 2.1 7
Calculated using Standard UL CRR formula, UL Fire Protection Directory, Category VXY.
The CRR Is a ratio value used to measure the ability of a pipe to withstand corrosion. Threaded Schedule 40 steel pipe
Is used as the benchmark (value of I.0).
SCHEDULE 40 SPECIFICATIONS
NOMINAL
NPS MOM OD MOM ID NOMINAL WALL WEIGHT UL PIECES
in, mm In. mm In. mm lbs./tL kg/m CPR, Lift
1 1.315 33.4 1.049 266 133 338 1.68 2.50 1.00 70
1% 1.660 422 1.380 353 340 3.56 2.27 339 1.00 51
1'A 1.900 483 1.610 40.9 145 368 2.72 4.05 1.00 44
2 2.375 60.3 2.067 S2.5 154 3.91 3.66 5.45 1.00 30
Calculated using Standard UL CRR fomlu/a, UL Fire Protection Directory, Category VIZY.
The CRR Is a ratio value used to measure the ability of a pipe to withstand corrosion. Threaded Schedule 40 steel pipe
Is used as the benchmark (value of 1.0).
Schedule 10 and Schedule 40 Meet or Exceed These Standards:
UL, C-UL and FM Listed ASTM A53, Type E, Grade B (Schedule 40 5-6)
FM Approved ASTM A795, Type E, Grade A (Schedule 40)
ASTM A135, Type E, NFPA 13
Grade A (Schedule 10)
AN Btar-
Fire Products Dmsion or Anva• International
SPF/taNVIL' Ductile Iron
r
Submittal Sheet
STRAIGHT
Nominal
Size
Anvil Ilem
Number
Universal
Number
Mox. Working
Pressure
Dimensions 4 Fox.
Wt. Each
A 8
la. (mm) P.SI 0,,o'„I In. WRO la MM- W8 Wg)=
1 840003164 DT333 SOIL 1.50 1.50 0.85
25 1 3450 38.10 3810 0.3c
1'A 840003172 DT444 Soo 1.75 1.75 1.22
32 31,50 44.45 411.45 0.55
11h 840003180 DT555 500 1.94 1.94 1.55
40 3450 0Y 0.7 0.70
2 840003198 D1666 Soo 2.25 2.25 2.45
50 3450 57.15 57.15 1 1 i
Ductile iron threaded fittings are UL & ULC Listed & Dimensions conform to ASME B16.3 Class 150. UL QFactoryMutualApprovedfor500psiservice. Threads are NPT per ANSI/ASME B1.20.1.
Ductile iron per ASTM A536 Class 65-45-12. A/
AForListiningg /Ap proval N071M
Ductile iron Wings have higher tensile sire th than that of steel I Therefore, o+er hteni °g °y cause concausedamagetothreadswhichmleakage. Ductile gdetails
contact your AnvilStarw
Representative. iron (icm fittings shouldbeIghlenedThreeturnsbeyondbond tight, but nomoree than than lourturns PROJECTr r
APPROVAL Project: Date:
Phone:
Architect / Engineer:
Contractor: Address:
Notes
1:
Notes 2:
SPF Cast &
Ductile Iron Fittings For the latest UUULC Listed and FM Approved pressure ratings, versus pipe schedule,I)\INIIIL REV 03.03 060013 go to www.anvilstar.com or contact your local AnvilStar representative
A-N4LStar-
Fire Products Owmion or Nrve• ImemsWitel
Ductile Iron
I
Submittal Sheet
REDUCING TEE REDUCING TEE
Nominal Anvil Item Universal M°x' Dimensions
Working
Approx.
wt.
Nominal
Site
Anvilltem
Number
Universal
Number
Max'
Working
Dimensions Approx.
Wt.
Site Number Number Pressure E°ch Pressure Each
A 8 A 8
In. (mm) PSI
In. (mm) In. (mm) In (mm) Ibs.(kg) In. Imm) PSI In. (mm) In (mm) In. (mm) Ibs.(kg)
1 x h x 1 840004196 DT313 500 1.50 1.36 1.50 0.64 1 h x 1 /4 x 1 840004428 D1543 500 1.65 1.58 1.80 1.15
1151 4-50 3810 3d 5d 3810 r ; 3e' 41 cl 1? dr7 17
1 x /4 x 1 840004204 D1323 500 1,50 1.45 1.50 11 x 1 A x 2 840004436 D1546 50D 2.16 2.10 2.02 1.90
79, 70, 50 I 53 1 s0 3a" 5 34 51 ^o P
1 x 1 x h 840004212 01331 500 1.26 1.26 1.36 1 h x 1 h h 840004444 DT551 50D 1.41 1.41 1.16 1.15
Y°5 1; d S' 7G a'4 4 ,40, 15 4 5 1 1 9!
1 x 1 x / 840004220 OT332 500 1.37 1.37 1.45 1 hx1hx /4 840004451 DT552 500 1.52 1.52 1.75 1.24
4 34 a 0 40, 401 0 3450 3861 1 4445 0.56 1
x 1 x 1 /4 840004238 DT334 500 1.67 1.67 1.58 0.98 1 Ih x 1 1h x 1 84DO04469 DT553 500 1.65 1.65 1.80 1.30 7;)
75 j3? 1 315 741 a 11 1 4013 dd 4 4 r ; 34' alol 419i dr7 Ot 1
x 1 x 1 h 840004246 DT335 500 1.80 1.80 1.65 1.16 1 h x 1 h x 1 / 84DO04477 DT554 500 1.81 1.62 1.88 1.48 75 >
7 > 4n 3450 a 77 457 4191 0 "^ a a 7 91513450 4673 462.1 477 7 1 /
x 1 x h 840004253 DT431 500 1.34' 1.26 1.53 0.82 1 h x x 2 840004485 DT556 500 2,16 2.16 2.02 1.98 IS
4 7 7 a , 4 , 3450 5456 d 51.70 9 1 /
4 x 1 x /4 840004261 D1432 500 145 1.37 1.62 0,90 2 x 1 x 2 840004493 D1636 500 2.25 2.02 2.25 2.15 37 ;
34 3 83 34 a 15 e; 01 , n 3450 3715 1 1 5715 098 1 /
4 x 1 x 1 840004279 DT433 500 1.58 1.50 1.67 1.00 2 x 1 A x 2 840004501 DT646 500 2.25 2.10 1.25 1.30 7,
75, 7 34-t 40,15 Irl 4242 45 3450 1; 53 34 57 1' 14 1 /
4 x 1 x 1 /4 840004287 D1434 50D 1.75 167 1.75 1.08 2 x 1 h x h 840004519 DT651 500 1.49 1.41 1.88 1.50 7,
7 ,^7 4S dda• 4 4445 9 a I" 3a' 3581 4715 1 /
4 x 1 x 1 h 840004295 DT435 500 1.88 1.80 It 1.42 2 x 1 h x /'4 840004527 DT652 500 1.60 1.52 1.97 1.62 40
d 4773 4572 4 4 4 4 40 '4 1 073 1 /
4 x 1 /4 x h 840004303 DT441 500 1.34 1.34 1.53 0.86 1 x 1 h x 1 840004535 DT653 500 1.73 1.65 1.02 164 3'
131 x 15 3450 3404 d 04 3866 0,19 5QY4QY2, 3e; 30 41 91 1 ;131 074 1 /
4 x 1 /4 x / 840004311 DT442 500 1.45 1.45 1,62 0.92 1 x 1 1h x 1 /4 840004543 111654 SOD 1.90 1.81 2.10 1,80 37, ^
7, 7 3450 3683 1 14 53 4115 a7 5n e 3 74; 4' a 082 1 /
4 x 1 /4 x 1 840DO4329 D1443 500 1.58 1.58 1.67 0.95 1 x 1 h x 1 h 840004550 DT655 500 2.02 1.94 2.16 2.00 3 ,
37,75 a 0 4013 4013 4 043 x, n I c 4 cl 1 /
4 x 1 / x 1 h 840DO4337 DT445 50o 1.88 1.88 1.81 1.45 1 x 1 h x 2 840004568 DT656 500 7.75 2.16 2.25 2.35 3'
r 4G 4775 4775 4612 1 , 4 Si ; d 57 1 /
4 x 1 / x 1 840004345 01446 500 2.10 2.10 1.90 1.75 2 x 2 x h 840004576 DT661 500 1.49 1.49 1.88 1.60 3
r? 5r 3450 5?.?4 3;a 48 7 S 345 37.85 31 77i 13 1
h x 1 x h 840004352 DT531 500 1.41 1.34 1.66 0.95 2 x 2 x /4 840004584 DT662 500 1.60 1.60 1.97 1.68 d0,
7 , I r 34' 81 e d 4? ' 043 50 ' t 3e 46164 4064 4 07 1
h x 1 x /4 840004360 OT532 500 1.52 1.37 1.75 1.14 2 x 2 x 1 840004592 D1663 500 1. 3 1. 3 2.02 1.85 40, ?
5 , 70 1 34SO 39 1 1 94 80 44 45 0 7 501 " x 2S 3,J50 4394 4194 1 "I 0 841 4
x 1 x 1 840004378 01533 500 1.65 1.50 1.80 1.17 1 x 2 x 1 /4 840004600 OT664 500 1.90 1.90 2.10 2.04 4
r ; ; 34 4191 1 4; l 03.7 d 44 4 4e 45 9 1
h x 1 x 1 /4 840004386 DT534 500 1.82 1.67 1.88 1.34 1 x 1 x 1 h 840004618 D1665 500 1.02 2.02 2.16 2.18 345
4 ?? 7 d7 7 61 40 3450 44 45 47 47 4-45 099 840004394
DT535 500 1.94 1.80 1.94 IAA 2 x 2 x 2 h DT667 500 2.60 2.60 2.39 3.61 4979
457 40:P 0 b 745 a • 474 de{ 1.64 gl/4 840004402 OT541 500 1.41 1.34 1.66 1.05 2 h x 2 x A DT762 500 1.74 1.60 2.32 2.78 e
1 7 5 , 7n ear 4d 4747 e4 Js 1n/1
840004410 D1542 SOD 1.52 1.45 1.75 1.15 Sn
3R'i r' aJdS n5 MATERIAL
SPECIFICATIONS Ductile
iron threaded fittings are UL & ULC Listed & Dimensions conform to ASME B16.3 Class 150. UL Factory
Mutual Approved for 500 psi service. Threads are NPT per ANSI/ASME B 1.20.1. F°"
Ductile
iron per ASTM A536 Class 65-45-12. Ating/AO ForListingApprovalNOTICE
Ductile iron Wings have higher tensile strength than d of of sled , Therdorc, over lightening con cause dam a to threods which couse lea e. Ductile details contact your g6aa
pipe. °g P'Pe 't'% AnvilStarn'
Representative iron6thngsshouldbetightenedthreetomsbeyondhoodtight, Iwt ro more than four turns. PROJECT
r s APPROVAL Project:
Date:
Phone: Architect /
Engineer: Contractor:
Address:
Notes
1: Notes
2: SPF
Cast & Ductile Iron Fittings For the latest UUULC Listed and FM Approved pressure ratings, versus pipe schedule,-W/fIVVIL REV. 03.03.0a0014 go to www.anviIslar.com or contact your local AnvilStar representative
Star„
Foe Rodugs Dmsion of AnW' Intemaoonal
Ductile Iron Submittal Sheet
900 ELBOW
NominalNominal Anvil Item Universal Max. Dimensions -
Working AppFOX.
EachSiteNumberNumber
Pressure
A B
In. (mm) IN UPIRTUR Ia (nun) la Imm) Ibs fkgl
1 840000004 DB90033 500 1.50 1.50 0.62
10 3450 38.10 3:.10 0.?8
11/4 840000012 DB90044 500 1.75 1.75 0.90
3? 3450 44,45 44.45 0.41
Ilk 840000020 DB90055 500 1.94 1.94 1.20
40 3430 4,,?J6 49176 0.54
2 840000038 DB90066 500 251715 2.25 1.85
50 3450 57.15 1 084
Ductile iron threaded fittings are UL & ULC Listed & Dimensions conform to ASME B16.3 Class 150. UL
Factory Mutual Approved for 500 psi service. Threads are NPT per ANSI/ASME B 1.20,1.
F"'
Ductile iron p er ASTM A536 Class 65-45-12. For Listing ApprovalMing/AD
NOTICE: Ductile- iron bar s have higher tensile s1 than that of sled I Therefore, over fi hteni con cause dam a to threods which couse leakage. Ductilen89pipe. g ^B a9 pipe "'oY kO9 details contact your
AnvilStarTM Representative. iron (icings should be tightened three turns beyond bond tight, but ro more Ihon lour turnsclhand
PROJECTr r APPROVAL
Project:
Date: Phone:
Architect / Engineer:
Contractor:
Address:
Notes 1:
Notes 2:
SPF Cast & Ductile Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule, M/ILREV. 03.03.06-0010 go to www.anvilstar.com or contact your local AnvilStar representative
A-N-K&Star-
Fire Products Division of Anvlr international
SPF/RI`ML.- Ductile Iron ISubmittal Sheet
Nominal Anvil Item Universal Mox. Working Dimensions- Fox.
Size Number Number Pressure WI. Eoch
A B
In. (min) PSI (k,,a) In. (min) In. (min)
1 840002133 DB45033 500 1.12 1.12 0.46
15 1 3450 2844 28 s/ 0.71
11/4 840DO2141 D845044 500 1.29 1.29 0.73
3? 3450 3?.16 31.7E 033
11h 840002158 DB45055 500 1.43 1.43 0.92
40 1 1 34:0 36.32 36.32 0.42
2 840002166 D845066 500 1.68 1.68 1.50
50 3a50 41.67 41.67 0.68
0
iFA
i
Ductile iron threaded fittings are UL & ULC Listed & Dimensions conform to ASME B16.3 Class 150. UL C
Factory Mutual Approved for 500 psi service. Threads are NPT per ANSI/ASME B1,20.1.
F"
Ductile iron per ASTM A536 Class 65-A5-12. APPROVED
For Listing / Approval
NOTICE Ductile iron Wings have higher tensile strength than that of steel t Therefore, over 6 hteni can cause dam a to i threads which cause lea DuctilegU'9 pipe. 9 n9 ag pipe "'aY
details contact your
AnvilStarTM Representative.
iron filhrgs should be tightened three turns beyond bond tight, but ro more than lour lams. a
PROJECTr n APPROVAL
Project:
Date: Phone:
Architect / Engineer:
Contractor:
Address:
Notes 1:
Notes 2:
SPF Cost 6 Ductile Iron Fittings For the latest UUULC Listed and FM Approved pressure ratings, versus pipe schedule,
REV. 03.03.06-0011 go to www.anvilstar.com or contact your local AnvilStar representative A!WL
A-m4i...Star-
Fore Produpa Dmsnn of Anil' Inlematoonel
Ductile Iron ISubmittal Sheet
Nominal
Site
Anvil Item
Number
Universal
Number
Dimensions 7 Ali 11.
Wt. Each
A B C
HITERNIn. (mm) In. RIMMO Ia. (m_ml Ibs'ft1 1
x'h 840600001 DBUSH31 0.75 0.25 1.42 Outside 0.22 25
x 15 1 19.05 6.35 3606 0.10 1
x 3/x 840600019 DBUSH32 0.75 0.25 1,42 Outside 0,17 15
x 20 19.05 6.35 36 06 0.06 1'/
4 x 1 840600027 DBUSH43 0.80 0.28 1.76 Outside 0.28 311ai
1 2032 711 d470 013 1'
h x 1 840600035 OBUSH53 0.83 0.31 2.00 Outside OAS 40
s ?5 21.08 7.871 30.80 0.20 1'
h x 1'/4 840600043 DBUSH54 0.83 0.31 2.00 Outside 0.30 40
x 3? 1.08 7.874 5080 0.14 2
x 1 840600050 DBUSH63 0.88 0.41 1.95 Inside 0.67 50
x 25 1?.35 10.414 49.53 030 2
x 1'/4 840600068 DBUSH64 0,88 0.34 2.48 Outside 0.73 30132
2? 35 5.636 6'; 00 033 2
x 1'h 840600076 DBUSH65 0.88 0.34 2.48 Outside 0.61 50
s 40 22.35 8.636 62 99 CM 6
A
Inside
Head Outside
Head Ductile
iron threaded fittings are UL & ULC Listed & Dimensions conform to ASME B16.3 Class 150, U Factory
Mutual Approved for 500 psi service. Threads are NPT per ANSI/ASME B1.20,1. Ductile
iron p er ASTM A536 Class 65-45-12. For Listing Approval Ming/AD N071M
Ductile iron fief shove higher tensile strength than that of seed Therefore, over lightening con cause damage ro i threads which m cause leakage Ductile gthep °y °g details
contact your AnvilStar"
Representative iron
keings should be tightened three toms beyond bond tight, but ro more than four toms. ePROJECT
r. r APPROVAL Project:
Date:
Phone: Architect /
Engineer: Contractor:
Address:
Notes
1: Notes
2: SPF
Cast 6 Ductile Iron Fittings For the latest UUULC Listed and FM Approved pressure ratings, versus pipe schedule, WWARML REV0303060020gotowww.anvilstar.com or contact your local AnvilStar representative
SPF/RNVIL.- Ductile Iron
Nominal Anvil Item Universal Dimensions 70-7101(
hSizeNumberNumberA
In. Im_m! In. (mml
1 840008691 D(L033 1.67 0.40
25 4747 0.18
11/4 840008700 DCL044 1.93 0.57
32 49 0? 026
ilk 840008718 DCLO55 2.15 0.75
40 5461 0.34
2 840008726 DCL066 2.53 1.15
SD 1 64.26 0.51,
A-m-i-ALStar-
Fue Products Dtmion of ArhN' International
Submittal Sheet
Ductile iron threaded fittings are UL & ULC Listed & Dimensions conform to ASME B16.3 Class 150. U QFactoryMutualApprovedfor500psiservice. Threads are NPT per ANSI/ASME B1.20.1.
F""
Ductile iron p er ASTM A536 Class 65-45-12. APPRovtpForListing /Approval
ng gpipe. damage b pipe % ka9NOTO: Ductile iron hni s have higher tensile strength than that of steel t Therelore, over tightening can cause do threads which m cause leakage. Ductile details contact your
AnvilStarn' Representative. iron hthrtgs should be tightened three lamd fr sbeyondtight, but no more than four turns PROJECTINFORMATION:
APPROVAL Project:
Date:
Phone: Architect /
Engineer: Contractor:
Address:
Notes
1: Notes
2: SPF
Cost & Ductile Iron Fittings For the latest UUULC Listed and FM Approved pressure ratings, versus pipe schedule,'L REV. 03.03.06001e go to www.anvitstar.com or contact your local AnvilStar representative
Star-
Fue Products Dromkon of Anvr International
sPFiFwvt<: Ductile Iron Submittal Sheet
Nominal" Anvil llem Universal Max'
Working DimensionsAp prox.
Site Number Number
Press ure A Wt. Eoth
141 In. IM i jjj.l' RA51l In fm_ml jjj lbs. lk 1
1 840005615 D(P003 5o0 1,16 0.32
25 1 3450 9.45 1 0.15
1'A 840005623 1)(1'004 500 1.18 0.43
3? 3`150 3? 51 0.20
114 840005631 D(P0g5 5o0 1.33 0.60
40 3450 33.78 017
1 840005649 D(P006 500 1.45 0,91
50 SO 3683 0.41
i
A
Ductile iron threaded fittings are UL & ULC Listed $ Dimensions conform to ASME B16.3 Class 150. 0
Factory Mutual Approved for 500 psi service. Threads are NPT per ANSI/ASME B 1,20,1.
F"
Ductile ironEDperASTMA536Class65-45-12. A
For Listing / Approval
NOTICE Ductile iron fittings have higher tensile strength than that of steel 1 Therefore, over tightening con cause dam a to threads which cause leakage Ductilen808pipe "'aY a8
details contact your
AnvilStarTM Representative.
ahaa thanironfillingsshouldbelightenedthreetomsbeyondbondtight, but no more thou four turns
PROJECTINFORMATION: APPROVAL
Project:
Date: Phone:
Architect / Engineer:
Contractor:
Address:
Notes 1:
Notes 2:
SPF Cast & Ductile Iran Fittings For the latest UUULC Listed and FM Approved pressure ratings, versus pipe schedule,
REV. 03.03.06-0019 go to www.anvilstar.com or contact your local AnvilStar representative A111NiIL
Threaded Mechanical Branch Tee
The MT90 mechanical tee serves the
some function as the MT 1 and MT 8, but
uses a steel electro-plated u-bolt to save
space for easier installation in tight
places. The MT90 is ideal for direct
connections with sprinkler heads and
drop nipples.
For the latest UL/ULC listed, LPCB, VdS
and FM Approved pressure ratings versus
pipe schedule, see www.anvilintl.com or
contact your local Anvil Representative.
HOUSING:
Ductile Iron conforming to ASTM A-536, Grade 65-45-12
OLT & NUTS:
U-bolt is carbon steel SAE J429 Gr. 2, zinc plated complete with hex Ranged lock
nuts conforming to ASTM A-563 Gr. A or B of SAE J995 Gr. 2.
THREADS:
BSPr pipe thread
AJY%nL°
C . Ut<S> HUMDAPPROVEDR
For I WwgslADPouol D@U b sritl Larsulsru, wsa our msome pl
rrw4-bl .00m o, w tw w A""P Saks Aeprew w.,e.
COATINGS:
Zinc Electroploted
Other available options: Example: RAL3000 or RAL9000 Series
GASKETS: Materials
Properties as designated in accordance with ASTM D-2000.
Grade "E" EPDM (Green color code)
40°F to 2307 (Service Temperature Range)(-40*C to 110aC)
Recommended for water service, diluted acids, alkalies solutions,
oil -free air and many chemical services not involving hydrocarbons, oils
or gases.
NOT FOR USE WITH HYDROCARBONS.
PROJECTr APPROVAL r
Project: Approved
Address: Approved as noted
Contractor. Not approved
Engineer: Remarks:
Submittal Date:
Notes 1:
Notes 2:
FP-4.12
Threaded Mechanical Branch Tee = /MyVIL
i
i
THREADED MECHANICAL BRANCH
Nominal
Size
Pipe
O.D.
Hole Dimensions Dimensions
Approx.
Wt. Eo.
Max.
Working
Pressure Min. Diameter Max. Diameter A B T
Take-out
910',/llNImm1 InIMiI N A ft /ii 41 VIn'./IU awborw IN16%mm'"W?j+?WO/mm r, In't eim.!44- 1-AI m AVess R"
I % x'h 1.660 x 0.840 1'/u 15/4 300 2% 3'h 2'% 11/8 0.8
3? x 11 424 x 213 30 33 20.7 54 89 S7 2 42 0.4
1''A x s/, 1.660 x 1.050 1'hs 300 114 31h 2'% 114 0.8
3? x 19 424 x 26.7 30 33 20.7 54 89 S7 2 42 0.4
I % x 1 1.660 x 1.315 1V4 l SA 300 2% 3'h 2% 1'A 1.1
32 125 41.4 x 337 30 33 207 55 89 572 41 CM
I1h x'h 1.900 x 0.840 1'A& lsht 300 2% 3'h 2% 11Y, 0.8
40 A 11 48.3 x 1 i.3 30 33 10.1 T 89 57.1 45 0.4
1'h x'/t 1.900 x 1.050 11rit 1 S/tt 300 2'/4 3'h 2% 11Y, 0.9
40 x 19 46.3 , 26.7 30 33 20.7 57 89 57.? 45 04
11h x 1 1.900 x 1.315 1'/tt 1S/u 300 2% 3'h 2% 1'/, 1.1
40 x ?5 JF 3 s 33.7 30 33 207 61 89 57.1 48 0.5
1 x'h 2.375 x 0.840 1'ht lsht 300 2'h 3'b 2% 2 0.9
50x 11 60.3A?13 30 33 207 64 95 57.2 51 04
2 x 3/, 2.375 x 1.050 1'ht lsht 300 21h 33/, 2% 2 0.9
50 x 19 60 3 x 16.7 JO 33 207 64 93 5T ? 51 0 d
2 x 1 2.375 x 1.315 13/tt 1S/It 300 21A 3'Y, 2% 2 1.1
50 x 25 60.3 135.7 30 J3 20.7 67 9S 57.2 50 0.5
3 O.D. x'h 2.996 x 0.840 1'A1 11h6 300 2% 4% 2% 2% 0.9
761 x 12 161 x 21.3 30 33 4107 73 108 57.2 39 04
3 O.D. x'/, 2 996 x 1.050 13/tt 1Sht 300 2% 4% 2% 2% 0.9
76 ) x 19 76.1 x 26.7 30 33 207 73 105 5172 59 0.4
3 O.D. x 1 2.996 x 1.315 1'h4 1S/It 300 3 4% 2% 2% 1.1
76.1 r 15 76.1 x 33 7 30 33 2017, 76 108 37.1 55 0.5
Working pressure Ratings are for reference only and based on Sch. 40 pipe. For the latest UL/ULC, FM, VdS and IPCB pressure
ratings versus pipe sdiedule, please visit onvilintl.eorn or eonW your local Anvil Representative A WARNING
Note; Tighten nuts alternately to a reoanmended tongue of 18.22 h.-lbs. (25.30 Nm) on pipe wall less than sdsedule 10 IDin 2440) For dry pipe sly and freer appr--ions
or 23.27 h.-Ibs. (31.37 Nm) on pipe walls sdsedule 10 (DIN 2440) and above. lubrication of the gasket is required,
Cwuv ke XtremeT10 lubricant is required.
FP-4.12
PIPE RINGS
Fig, 69
Size Range: '/i'through 8"
Material: Carbon steel
Finish: Galvanized
Adjustable Swivel Ring, Tapped Per NFPA Standards
Service: Recommended for suspension of non -insulated stationary pipe line.
Maximum Temperature: 650• F
Approvals: Complies with Federal Specification A-A-1192A (Type 10), WW-H-171-E (Type 10),
ANSI/MSS SP-69 and MSS SP-58 (Type 10). UL Listed and FM Approved (Sizes 3/4" - 8").
Features:
Threads are countersunk so that they cannot become burred or damaged.
Knurled swivel nut provides vertical adjustment after piping is in place.
Captured swivel nut in the'/i' through 6" sizes The capture is permanent in the bottom
portion of the band, allowing the hanger to be opened during installation if desired, but
not allowing the nut to fall completely out.
Ordering: Specify size, figure number and name.
Note: The acceptability of galvanized coatings at temperatures above 450•F is at the discretion
of the end user.
Metric nut available upon request. Non -captured nut also available upon request.
FIG. 69: LOADS (LBS) • WEIGHT (LBS) • DIMENSIONS (IN)
Pipe Size Max Load Weight RodSizeB C F Width
h
300
0.
10 2'A 2 19/,6 5 !
e 3/
i 0.10 23/i 11/6 1 5/,6 1
0.10 2'/16 111/'6 1 1
Y4 0.10 2% 13/4 rA
11/
x 0.10 23/i 1'A 2
0.11 3'/4 23/e 1 %6 2%
525
0.
20 4 23/4 15/16 3/
4 3
0.20 313/4 215/16 13/,6 4
650 0.30 411/,6 3t3/16 1s/
t6 5
1,
000 0.
54 55/6 4% 6
0.65 6"/,6 59/,6 21/4 8
1.00 8 7 2"/,6 1 Note:
Reflects changes in rod diameter from previously published data per recent revisions in MSS-SP-58 & 69 UL
us <F> UMD
APPROVED yr
A F
iD 7"
through 1" pipe 1'/."
through 8" pipe PROJECT
INFORMATION APPROVAL STAMP Project:
Approved Address:
F] Approved as noted Contractor. [-]
Not approved Engineer:
Remarks: Submittal
Date: Notes
1: Notes
2: PH-
11.11
HANGER RODS
Fig. 146
Size Range:'/4" through 1'/2" Stocked in six, ten, and twelve foot
lengths. Other even foot lengths can be furnished to order.
Material: Carbon steel or Stainless Steel Gr 304
Threads: National Coarse (USS), rod threaded complete length.
Finish: Plain or Galvanized.
Maximum Temperature: 650' F.
Ordering: Specify rod diameter and length, figure number,
name and finish.
Note: The acceptability of galvanized coatings at temperatures
above 450•F is at the discretion of the end user.
Length
t
A
AMIIL;
Continuous Threaded Rod
FIG. 146:
LOADS (LBS) • WEIGHTS (LBS) • DIMENSIONS (IN)
Rod Size
A
Threads
per Inch
Max Load
650• F
Weight
per Ft.
IA 20 240 0.12
16 730 0.30
h 13 1,350 0.53
11 2,160 0.84
14 10 3,230 1.20
7A 9 4,480 1.70
1 8 5,900 2.30
11/ 7 1 9,500 3.60
1'h 1 6 1 13,800 1 5.10
Note: Other rod sizes available upon request. Gass 2 fit is available upon request.
PROJECTi
Project: Approved
Address: Approved as noted
Contractor. [-]Not approved
Engineer: Remarks:
Submittal Date:
Notes 1:
Notes 2:
0
BEAM CLAMPS Z /M/IL
Fig. 92 Universal C-type Clamp (Standard Throat)
Size Range: ;/e' and'/z"
Material: Ductile iron, hardened steel cup point set screw and locknut.
Finish: Plain or Galvanized
Service: Recommended for use under roof installations with bar joist type construction,
or for attachment to the top or bottom flange of structural shapes where the
vertical hanger rod is required to be offset from the edge of the flange and where
the thickness of joist or flange does not exceed 3/."
Approvals: Complies with Federal Specification A-A-1192A (Type 19 & 23)
WW-H-171-E (Type 23), ANSI/MSS SP-69 and MSS SP-58 (Type 19 & 23).
LIL, ULC Listed and FM Approved.
How to size: Size of clamp is determined by size of rod to be used.
Installation: Follow recommended set screw torque values per MSS-SP-69
See table on page 233)
Features:
They may be attached to horizontal flanges of structural members in either the top beam
bottom beam positions.
Secured in place by a cup -pointed Set Screw tightened against the flange.
A )am Nut is provided for tightening the Set Screw against the Body Casting.
Thru tapping of the body casting permits extended adjustment of the threaded rod.
Can be used with Fig 89X retaining clip for seismic applications.
Ordering: Specify rod size, figure number, name of clamp and finish.
3/:
JAM
H
SET SCREW
E
AT LEAST ONE
1
FULL THREAD
OF ROD MUST
BE EXPOSED x
I
D
CASTING
A
c UL us <FM>
LISTED APPROVED
FIG. 92: LOAD (LBS) WEIGHT (LBS) • DIMENSIONS (IN) . TORQUE (IN-LBS)
Rod Size
A
Set Screw
Size
Torque
Value
Max Loads
Weight C D E F G H
Top Bottom
3/6 60 500 250 0.34 11/16 19/i6 9/16 13/6 3h h
h z 125 950 760 0.63 1% 113/,6 h 1'/,6 TA6 13h2
Maximum temperature o1450• F
PROJECT INFORMATION APPROVAL STAMP
Project: []Approved
Address: [:]Approved as noted
Contractor. Not approved
Engineer: Remarks:
Submittal Date:
Notes 1:
Notes 2:
PH-11.11
Page 1 of 6
N41KJNG* MICROFAST11 QUICK
RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-946-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
1. DESCRIPTION
The Viking Microfastm Quick Response Pendent Sprinkler VK302 is a small thermo-
sensitive glass bulb spray sprinkler available with various finishes and temperature
ratings to meet design requirements. The special Polyester and Electroless Nickel
PTFE ( ENT) coatings can be used in decorative applicationswhere colors aredesired.
In addition, these coatings have been investigated for installation in corrosive atmos-
pheres and are listed/approved as corrosion resistant as indicated in the Approval
Charts. (Note. FM Global approves ENT finish as corrosion resistant. FM
Global has no approval classification for Polyester coatings as corrosion resistant.)
2. LISTINGS AND APPROVALS
coos cULus Listed: Category VNIV
FM Approved: Class Series 2000
vds VdS Approved: Certificates G414009 and G414010
LPCB Approved
E CE Certified: Standard EN 12259-1:1999, A3:2006 Certificate of Constancy of Performance 0832-CPR-SO021
CCCF Approved: Approved by the China Certification Center for Fire Products (CCCF)
Refer to Approval Chart 1 and Design Criteria cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria
for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)
Rated to 175 psi (12 bar) water working pressure
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size- 1/2' NPT, 15 mm BSP
Nominal K-Factor. 5.6 U.S. (80.6 metric")
Glass -bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-1/4' (58 mm)
cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
Material Standards:
Frame Casting: Brass UNS-CB4400 or QM Brass
Deflector. Phosphor Bronze UNS-051000 or Copper UNS-C19500
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-Cl1000 and Stainless Steel UNS-S30400
For Polyester Coated Sprinklers: Belleville Spring -Exposed
For ENT Coated Sprinklers: Belleville Spring -Exposed, Screw and Pipcap - ENT plated.
Ordering Information: (Also refer to the current Viking price list )
Omer Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate
suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-B, and ENT = JN
Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 "C) = D, 200 °F (93 °C) = E, 286 °F (141 °C) = G
For example, sprinkler VK302 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No 12979AB
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the current Viking price list.)
Form No. F_033314 16.10.06 Rev 16.4 Replaces Form No. F_033314 Rev 16.3
Removed term -upright)
Page 2 of 6
N41KJNG* MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupine.com
Sprinkler Wrenches:
A. Standard Wrench: Part No. 10896W/13 (available since 2000).
B. Wrench for Recessed Pendent Sprinklers: Part No. 13655W/B•• (available since 2006)
C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool— Part No. 15915 (available since 2010)
A W ratchet is required (not available from Viking).
Allows use from the floor by attaching a length of 1" diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F 051808.
Sprinkler Cabinets:
A. Six -head capacity: Part No 01724A (available since 1971)
B. Twelve -head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat -sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Microfaste Quick Response Pendent Sprinkler VK302 is available through a network of domestic and international dis-
tributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Protective Sprinkler
Clip
rench Flat
five Sprinkler
r, 10896 •
Figure 1: Standard Sprinkler Wrench 10896W/B
Form No. F_033314 16.10.06 Rev 16.4
Cap
Page 3 of 6
MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature Sprinkler Nominal Maximum Ambient
Bulb Color
Classification Temperature Rating' Ceiling Temperature=
Ordinary 135 -F (57 -C) 100 -F (38 -C) Orange
Ordinary 155 -F (68 -C) 100 -F (38 -C) Red
Intermediate 175 -F (79 -C) 150 -F (65 -C) Yellow
Intermediate 200 -F (93 -C) 150 -F (65 -C) Green
High 286 -F (141 -C) 225 -F (107 -C) Blue
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT
Corrosion -Resistant Coatings': White Polyester, and Black Polyester. ENT in all temperature ratings except 135 -F (57 -C)
Footnotes
The sprinkler temperature rating is stamped on the deflector.
Based on NFPA-13.Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3 The corrosion -resistant coatings have passed the standard contusion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible contusive environments. Prior to installation, verity through the end -user that the coatings are com-
patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces
only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated.
Sprinkler wrench 13655M
for recessed pendent
sprinklers
A 1/2" ratchet is requin
not available from Viking
Carefully slide the wrench sideways around
the protective cap, ensuring engagement with
the sprinkler wrench flats
Figure 2: Wrench 13655W/B for Recessed Pendent Sprinklers
Form No. F_033314 16.10.06 Rev 16.4
Page 4 of 6
MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Approval Chart 1 (UL)
T KEYVikingWcrofastoQuickResponse
Pendent Sprinkler VK302 AG Facvwroon fu applicW0
Maximum 175 PSI (12 Bar) WWP
Base
Sprinkler Thread Size
Nominal Overall Listings and Approvals'
Part SIN K-Factor Length Refer also to Design Criteria.)
Number'
Style
NPT BSP U.S. Inches mm cULus' VdS LPCB
12979 VK302 Pendent 1/2' 15 mm 5.6 Emelhe 2.1/4 58 A1Z, B1Y, D2, C2X Al A1Z, B1Y D17, C1Y
19780 VK302 Pendent 1/2' 5.6 80.6 2-114
NOTICEOffice)
06662E VK302 Pendent 1/2' 15 mm 1 5.6 1 806 2-1/4 58 A1Z, B1Y, D2, C2X I — I —
18021 VK302 I Pendent 1 1/2' 115 mm1 5.6 1 806 2-1/4 58 A1X, B1Y Al I A1X, B1Y DIX. C1Y8 D1X, cir
Approved Temperature Ratings Approved Finishes Approved Escutcheons
A - 135 -F (57 -C), 155 -F (68 -C), 175 -F 1 Brass, Chrome, White X - Standard surface -mounted escutcheon or the
79 -C), 200 -F (93 -C), 286 -F (141 -C) Polyester", Black Polyes- Viking Micromatic• Model E-1 Recessed Escutcheon
B - 135 -F (57 -C), 155 •F (68 •C), 175 •F ter••• Y - Standard surface -mounted escutcheon or the
79 •C), and 200 'F (93 *C) 2 - ENr Viking Microfast• Model F-1 Adjustable Escutcheon, or recessed with the Viking Micro-
C - 155 -F (68 -C), 175 'F (79 'C), and 3 - Chrome main• Model E-1, E-2, or E-3 Recessed Escutcheon
200 -F (93 -C) Z - Standard surface -mounted escutcheon or the
D - 155 -F (68 -C), 175 -F (79 'C), 200 -F Viking Microfast• Model F-1 Adjustable Escutcheon
93 -C), 286 -F (141 -C)
Footnotes
Base pan number shown. For complete part number, refer to Viking's current price schedule.
Metric K-factor measurement shown is when pressure is measured in Bar When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
This table shows the listings and approvals available at the time of printing. Other approvals may be in process.
Listed by Underwriters Laboratories Inc for use in the U.S. and Canada.
cULus Listed as corrosion -resistant
Other colors are available on request with the same Listings and Approvals as the standard colors
CE Certified, Standard EN 12259-1, EC -certificate of conformity 0832-CPD-2001.
CE Certified, Standard EN 12259-1, EC -certificates of conformity 0832-CPD-2001 and 0832-CPD-2003.
MED Certified, Standard EN 12259-1, EC -certificates of conformity 0832-MED-1D03 and 0832-MED-1008
cULus Listing Reauirements:
The Viking Microfast• Quick Response Pendent Sprinkler VK302 is cULus Listed as indicated in the Approval Chart for installation in
accordance with the latest edition of NFPA 13 for standard spray sprinklers.
Designed for use in Light and Ordinary occupancies.
The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form
No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in
accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD,
VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and stan-
dards, whenever applicable.
Form No. F_033314 16.10.06 Rev 16.4
Page 5 of 6
MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Approval Chart 2 (FM) T•mPffm a KEY
The Viking Microfas? Quick Response Fwfth
Pendent Sprinkler VK302 m i
Maximum 175 PSI (12 Bar) WWP
Base Part Sprinkler Thread Size Nominal K-Factor Overall Length FM Approvals'
Number"
SIN
Style Refer also to Design Criteria.) NPT BSP U.S. metric= Inches mm
12979 VK302 Pendent 1/2" 1 15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2X, C2
NOTICEOffice)
06662B VK302 Pendent 1/2" 15 min 1 5.6 80.6 2-1/41 58 A1Z, B1Y, D2X, C2
18021 VK302 Pendent 1/2" 1 15 min 1 5.6 80.6 2-1/4 1 58 1 A1Z, B1Y
Approved Escutcheons
Approved Temperature Ratings X - Standard surface -mounted escutcheon or the
A - 135 -F (57 -C), 155 -F (68 -C), 175 -F (79 -C), 200 -F Viking Micromatic' Model E-1 Recessed
93 -C), 286 -F (141 -C) Approved Finishes Escutcheon
B - 135 -F (57 -C), 155 -F (68 -C), 175 -F (79 -C), and 1 - Brass, Chrome, White Polyester•, Y - Standard surface -mounted escutcheon or the
200 -F (93 -C) and Black Polyester' Viking Microfast° Model F-1 Adjustable Escutcheon,
C - 155 -F (68 -C), 175 -F (79 -C), 200 -F (93 -C), 286 2 - ENT$ or recessed with the Viking Micromatice Model E-1
F (141 -C) or E-2 Recessed Escutcheon
D - 155 -F (68 -C), 175 -F (79 -C), 200 -F (93 -C) Z - Standard surface -mounted escutcheon or the
Viking Microfast• Model F-1 Adjustable Escutcheon
Footnotes
Base part number shown. For complete part number, refer to Vikmg's current price schedule.
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K4actor shown by
10.0.
3 This table shows the FM Approvals available at the time of printing. Other approvals may be in process.
Other colors are available on request with the same Approvals as the standard colors.
FM approved as corrosion resistant.
DESIGN CRITERIA - FM
Also refer to Approval Chart 2 above.)
FM Approval Reouirements:
The Viking Microfast• Quick Response Pendent Sprinkler VK302 is FM Approved as quick response Non -storage pendent sprinklers
as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss
Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not
limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable
spacing, and deflector distance below the ceiling.
NOTE: The FM installation stuidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
Form No. F_033314 16.10.06 Rev 16.4
Page 6 of 6
MICROFAST® QUICK
RESPONSE PENDENTN41KJNG*SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9601 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupine.com
Ceiling Opening Size:
2-5/16" (59 mm) minimum
1/2" (
15 mm)
2-1/2" (64 mm) maximum
NPT
rg S r JV
24/4"
57
1-3/4" 2" (38 mm)
45 mm) (
51 mm) Min.
Max.
Installed with a standard Installed with a Microfast Note: At maximum, adapter
1/8" surface -mounted Model F-1 Adjustable is exposed 1/2" (13 mm)
escutcheon Escutcheon from face of ceiling
Figure 3: Sprinkler Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon
Ceiling Opening Size:
2-5/16" (69 mm) minimumfff2-1/2" (64 mm) maximum
tied 2-1/8" 24/8" _.
54 mm) (54 mm)
1-3/4" (29 mm) 2"" (29 mm)
45 mm) Min. (61 mm) Min.
Max. Max.
Installed with a Installed with a Model
Model E-1 Recessed E-2 Thread -on Recessed
Escutcheon Escutcheon
Figure 4: Sprinkler Dimensions with the Model E-1 and E-2 Recessed Escutcheons
Form No. F_033314 16.10.06 Rev 16.4 Replaces Form No. F_033314 Rev 16.3
Removed term -upright)
June 28, 2013 Sprinkler 83q
EC/QREC ORDINARY
HAZARD PENDENTN4IKJNG4SPRINKLERVK572 (K14.0)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
Viking Standard/Quick Response Extended Coverage Ordinary Hazard (ECOH)
Pendent Sprinkler VK572 is a thermosensitive glass bulb spray sprinkler with a
14.0 (202 metric') nominal K-Factor. The sprinkler produces the flows required to
meet Ordinary Hazard density requirements at lower pressures than 8.0 or 11.2
115.2 or 161.4 metric') K-Factor sprinklers. The glass bulb operating element and
special deflector characteristics meet the challenges of quick response extended
coverage standards. Viking EC/QREC Ordinary Hazard Sprinklers are available in
various finishes and temperature ratings to meet design requirements. The spe-
aal PTFE, Polyester, and Electroless Nickel PTFE (ENT) coatings can be used
in decorative applications where colors are desired. In addition, ENT coating has
been investigated for installation in corrosive atmospheres. See Approval Charts.
The Viking VK572 Sprinkler may be ordered and/or used as an open sprinkler
glass bulb and pip -cap assembly removed) on deluge systems. Refer to Ordering
Instructions on the next page.
2. LISTINGS AND APPROVALS
c&$
clJLus Listed: Category VNIV
FM Approved: Class 2022
NYC Approved: MEA 89-92-E, Volume 38
Refer to Approval Chart 1 and Design Criteria on pages 83t-u for cULus Listing requirements and refer to Approval Chart
2 and Design Criteria on page 83v for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 20D4.
Minimum Operating Pressure. Refer to the Approval Charts.
Maximum Working Pressure. 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).
Thread size: 3/4" (20 mm) NPT
Nominal K-Factor. 14.0 U.S. (202 metric')
Metric K-faclor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Glass -bulb fluid temperature rated to -65 °F (-55 "C)
Overall Length: 2-7/16" (62 mm) Viking Technical Data may be found on
Material Standards: The Viking Corporation's Web site at
Sprinkler Frame: Brass UNS-C84400 hnp://www.vikinggroupinc.com.
Deflector. Phosphor Bronze UNS-051000
The Web site may include a more recent
Bulb: Glass, nominal 3 mm diameter
Pip Cap: Brass UNS-C31400 or UNS-C31600
edition of this Technical Data Page.
Compression Screw: Brass UNS-C36000
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
For PTFE Coated Sprinklers: Belleville Spring -Exposed, Screw -Nickel Plated, Pip Cap-PTFE Coated
For Polyester Coated Sprinklers: Belleville Spring -Exposed
For ENT Coated Sprinklers: Belleville Spring -Exposed, Screw and Pipcap-ENT plated.
Ordering Information: (Also refer to the current Viking price list.)
Order EC/QREC Ordinary Hazard Pendent Sprinkler VK572 by first adding the appropriate suffix for the sprinkler finish and then
the appropriate suffix for the temperature rating to the sprinkler base part number
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-NV, Black Polyester = M-/B, Black PTFE = N, and ENT = JN
Temperature Suffix (°Frc): 155°/68" = B, 175°/79° = D, 200°/93° = E, and 286*/141 ° = G, OPEN = Z (PTFE only).
For example, sprinkler VK572 with a Brass finish and a 155 °F/68 "C temperature rating = Part No. 13722AB.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book )
Sprinkler Wrenches:
Form No. F_072313 New page 83q-v, issue July 22, 2013,
New Data Sheet for VK572 and Added ENT Finish.)
Sprinkler 83r June 28, 2013
EC/QREC ORDINARY
HAZARD PENDENT
SPRINKLER VK572 (K14.0)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
A. Standard Wrench: Part No. 07297W/B (available since 1991)
B Wrench for coated and/or recessed pendent sprinkler: Part No
13032W/13-- (available since 2004)
A W ratchet is required (not available from Viking).
Sprinkler Cabinets:
A. Six -head capacity, Part No. 01724A (available since 1971)
B. Twelve -head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
S. OPERATION
During fire conditions, when the temperature around the sprinkler reaches
its operating temperature, the heat -sensitive liquid in the glass bulb
expands, causing the bulb to shatter, releasing the pip cap and sealing
spring assembly. Water flowing through the sprinkler orifice strikes the
sprinkler deflector, forming a uniform spray pattern to extinguish or control
the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Model VK572 Sprinkler is available through a
network of domestic and international distributors. See The Viking Corpora-
tion web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact
Viking directly
Wrench -
Flat -
Protective
Sprinkler
W Shield
VIKING o z» Q
Figure 1:
Standard Sprinkler Wrench 07297W/B
Pendent Sprinkler VK572 shown)
f
r'------------- rJ-
L
1
Sprinkler
Wrench
Part No.
13032W/Bww
1
NNA 1/2' ratchet
is required. Step 2: Carefully pressStep1: Carefully slide the (Not ovallable
1
the wrench upward and
wrench sideways around the
deflector and protective shield. from Viking). i _ _1 turn slightly to ensure
engagement with the
Note the orientation of the 1 1 - , sprinkler wrench flats.
of the shield in the wrench.)
Figure 2: Wrench 13032W/B for Recessed and/or Coated Sprinklers (Pendent Sprinker VK572 shown)
June 28, 201'3 Sprinkler 83s
EC/QREC ORDINARY
HAZARD PENDENT
SPRINKLER VK572 (K14.0)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-946-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
S rri 1 I r nature S rink er No In MaI um mbien
Bulb Col r
Czla anon Um ra ure a ' C-eihn empe
Ordinary 155 °F (68 °C) 100 7 (38 °C) Red
Intermediate 175 °F (79 -C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 -C) Blue
Available Sprinkler Finishes: Brass, Chrome, White Polyester', Black Polyester', Black PTFE3, and ENT
Corrosion -Resistant Coatings'._ENT
Footnotes
The sprinkler temperature rating is stamped on the deflector.
Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific
installation standards.
The coatings indicated are applied to the exposed exterior surfaces only. The spring is exposed on sprinklers with PTFE and Polyester coatings. For PTFE coated open
sprinklers only, the waterway is coated
The corrosion -resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verity through the end -user that the coatings are compatible with or suitable for the proposed
environment For all ENT sprinklers, all exposed surfaces and the waterway are coated but note that the spring is exposed.
Ceiling Opening Size:
2-5/16' (58.7 mm) minimum
2-1/2' (635 mm) moximum
3/4'
C20 mr,,;\_TNPT
T_ 2-7/36' 1-1/2' (38.1 mm)
1-11/16' (62 mm) 1-3/4' 2' (50.8 mm) Minimum
42.) C44.5 mm) Maximum 1
1-3/4-
44.5 mm) Installed with a lnstolled with a Microfost
standord 1/8' (3.1 mm) Model F-1 Adjustable Escutcheon
Pendent Sprinkler surfoce-mounted escutcheon
13722 (VK572)
Figure 3: Pendent Sprinkler VK572 Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon
Sprinkler 83t June 28, 2013
EC/QREC ORDINARY
HAZARD PENDENT
SPRINKLER VK572 (K14.0)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
p• a C a
n Q c Respo se rid ve e ,
rd nary en en S n le 1 .0
Sprinkler Base NPT Thread Size Nominal K-Factor Maximum Water Overall Length
SIN
Part Number' Inches mm U.S. metric= Working Pressure Inches mm
13722 Pendent VK572 3/4 20 14.0 1 202 175 psi (12 bar) 2-7/16 62
Minimum Water Supply Requirements (cULus only) cULusWC
Maximum Maximum Listings""
Sprinkler Spacing Area per Ordinary Hazard Group I Ordinary Hazard Group II SeeDesign Criteria
L x Ws Sprinkler
Flow / Pressure Flow / PressureIr- on pg M.)
Pendent
VK572StandardResponse
16 It x 16 Q (4.9 m x 4.9 m) 256 R2 (23.8 rn 39 gpm @ 7 8 psi (147.6 Umin @ 0.54 bar) 51 gpm @ 13.3 psi (193.1 Umin @ 0.92 bar) AIX, B1Y, B27, A2W
18It x 18 Q (5 5 m x 5.5 m) 324 fl2 (30.1 m2) 49 gpm @ 12.3 psi (185.5 Vmin @ 0.85 bar) 65 gpm @ 21.6 psi (246.1 Umin @ 1.49 bar) AIX, B1Y, B2Z, A2W
20 It x 20 It. (61 m x 6.1 m) 400 ft' (37.2 m?) 60 gpm @ 18.4 psi (227.1 Umin @ 1.27 bar) 80 gpm @ 32.7 psi (302.8 Umm @ 2.25 bar) AIX, B1Y, B2Z, A2W
Quick Response"
12 It x 12 It. (3 7 m x 3.7 m) 144 fl2 (13.4 m 39 gpm @ 7.8 psi (147.6 Umin @ 0.54 bar) 39 gpm @ 7.8 psi (147.6 Umm @ 0.54 bar) AIX, 131Y, B2Z, A2W
14 It x 14 It, (4.3 m x 4.3 m) 196 f12 (18.2 m2) 39 gpm @ 7.8 psi (147.6 Umin @ 0.54 bar) 39 gpm @ 7 8 psi (147.6 Umm @ 0.54 bar) AIX, B1Y, B2Z, A2W
Approved Escutcheons
W - Standard surface -mounted escutcheons only.
Approved Temperature Ratings
Approved Finishes X - Standard surface -mounted escutcheons or the Microfast•
A - 155 -F (68 -C), 175 °F (79 °C), 200 -F
C), -F °C)c
1 -Brass, Chrome, White Polyester, Black
Model F-1 Adjustable Escutcheon
Microfast• 93 and 286 (141
Polyester, and Black PTFE
Y - Standard surface -mounted escutcheons or the
B - 155 -F (68 °C), 175 °F (79 -C), and 2 ENT, Model F-1 Adjustable Escutcheon, or recessed with the
200 -F (93 -C) Micromalic' Model E-1 or E-2 Recessed Escutcheon
Z - Standard surface -mounted escutcheons or recessed
with the Micromatic Model E-1 Escutcheon.
Footnotes
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This chart shows listings and approvals available at time of printing. Other approvals may be in process. Check with the manufacturer for any ad-
ditional approvals.
cULus Listed for use in the U.S and Canada.
s To determine "Minimum Water Supply Requirement" for areas of coverage where length and width of actual sprinkler spacing are not equal, select
the "Maximum Sprinkler Spacing" from the chart that is equal to or greater than the larger of the actual spacing (length or width) dimensions used.
Example: When using 10 ft 6 in x 13 fl (3.2 m x 4 m) sprinkler spacing, provide the "Minimum Water Supply Requirement" listed in the chart for 14 it x
14 It (4.3 m x 4.3 m) spacing. For areas of coverage smaller than shown, use the "Minimum Water Supply Requirement" in the appropriate hazard
group for the next larger area listed. The distance from sprinklers to walls shall not exceed one-half the "Maximum Sprinkler Spacing" listed for the
Minimum Water Supply Requirement" used.
For Sprinkler VK572 with High Temperature 286 °F rating, UL restricts the OR listing to their use in Ordinary Hazard occupancies to the high temperature
zones within a building only. VK572 quick response sprinklers with this temperature rating cannot be used throughout the property.
Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol 38.
cULus Listed as corrosion -resistant.
Prior to 2007, sprinkler VK572 was classified as Standard Response for all room sizes.
June 28, 2013 Sprinkler 83u
EC/QREC ORDINARY
HAZARD PENDENT
SPRINKLER VK572 (K14.0)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
cULus Listing Requirements: ECOH Pendent Sprinkler VK572 is cULus Listed as Standard and Quick Response for installation in accordance with
the latest edition of NFPA 13 for extended coverage pendent spray sprinklers as indicated below,
The minimum water supplies and maximum areas of coverage shown in Approval Chart 1 are designed to provide the following design densities.
0.15 gpm/ft2 (6.1 mm/min) for Ordinary -Hazard Group I densities: 0.2 gpm/ft.2 (8 1 mm/min) for Ordinary -Hazard Group II densities.
The sprinkler installation rules contained in NFPA 13 for extended coverage pendent spray sprinklers must be followed with the exception that
Viking ECOH Pendent Sprinklers are cULus Listed for use in unobstructed construction, and noncombustible obstructed construction consisting
of solid steel and/or concrete beams as defined in the latest edition of NFPA 13.
Ceiling slope not to exceed 2/12 (9.5°).
Also. Viking ECOH Pendent Sprinkler VK572 is specifically cULus Listed for:
For non-combustible obstructed construction within trusses or bar joists having non-combustible web members greater than 1" (25.4 mm) when
applying the 4 times obstruction criteria rule as defined in NFPA 13 under "Obstructions to Sprinkler Discharge Pattern Development".
For installation under concrete tees when installed as follows.
1. The stems of the concrete tee construction must be spaced between 3 ft (0.9 m) and 7 ft-6 in (2.3 m) on center. The depth of the concrete
tees must not exceed 30 in (762 mm). The maximum permitted concrete tee length is 32 ft (9.8 m). However, where the concrete tee
length exceeds 32 It (9.8 m), non-combustible baffles, equal in height to the depth of the tees, can be installed so that the space between
the tees does not exceed 32 It (9.8 m).
2. The sprinkler deflector is to be located in a horizontal plane at or above 1" (25.4 mm) below the bottom of the concrete tee stems.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
EC1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor-
dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS
or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards,
whenever applicable.
Sprinkler 83v June 28, 2013
EC/QREC ORDINARY
HAZARD PENDENT
SPRINKLER VK572 (K14.0)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Approval Chart 2 (FM) T---bne KEY
Quick Response Extended Coverage Pendent Sprinkler VK572 (K14.0) Fl"m'
AIX 4- EsaAdmm (b appimMs)
For HC-1, HC-2, and HCS Occupancies
Sprinkler Base
SIN
NPT Thread Size Nominal K-Factor Maximum Water Overall Length
Inches mm U.S. metric, Inches mmPartNumber' Working Pressure
13722 VK572 3/4 1 20 14.0 202 175 psi (12 bar) 2-7/16 62
Maximum Sprinkler Spacing Maximum Area FM Approvals'
L x W per Sprinkler
Refer to Design Criteria below_
NOTE: FM installation guidelines may differ
Pendent Sprinkler VK572
12 ft. x 12 ft. (3.7 m x 3.7 m) 144 ft2 (13.4 m A1X
14 ft. x 14 ft. (4.3 m x 4.3 m) 196 112 (18.2 m2) A1X
from cULus and/or NFPA criteria. Refer to the
latest applicable FM Loss Prevention
Data Sheets (including 2-0 and 3-26).
16 ft. x 16 ft. (4.9 m x 4.9 m) 256 ft' (23.8 m A1X
18 ft. x 18 ft. (5.5 m x 5 5 m) 324 ft= (30.1 m2) A1X
20 ft. x 20 ft. (6.1 m x 6.1 m) 400 W (37.2 m2) A1X
Approved Temperature Ratings Approved Finish Approved Escutcheons
A - 155 "F (68 "C), 175 °F (79 °C), 200 "F (93 °C), and 286 °F (141 "C)e 1 - Brass X - Standard surface -mounted escutcheons
Footnotes
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 Metric K-factor measurement shown is when pressure is measure in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This chart shows the FM Approvals available at time of printing. Other approvals may be in process. Check with the manufacturer for any additional
approvals
To determine "Minimum Water Supply Requirement" for areas of coverage where length and width of actual sprinkler spacing are not equal, select
the "Maximum Sprinkler Spacing" from the chart that is equal to or greater than the larger of the actual spacing (length or width) dimensions used
Example: When using 10 ft 6 in x 13 ft (3.2 m x 4 m) sprinkler spacing, provide the "Minimum Water Supply Requirement" listed in the chart for 14 ft
x 14 ft (4.3 m x 4.3 m) spacing. For areas of coverage smaller than shown, use the "Minimum Water Supply Requirement" in the appropriate hazard
group for the next larger area listed. The distance from sprinklers to walls shall not exceed one-half the "Maximum Sprinkler Spacing" listed for the
Minimum Water Supply Requirement" used.
DESIGN CRITERIA - FM
Also refer to Approval Chart 2 above.)
FM ADoroval Requirements:
Sprinkler VK572 is FM Approved as a quick response Non -Storage extended coverage pendent sprinkler as indicated in the FM Approval Guide for
use in occupancy hazard classifications HC-1, HC-2, and HC-3. For specific application and installation requirements, reference the latest applicable
FM Loss Prevention Data Sheets (including Data Sheet 2-0 and 3-26). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not
limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflec-
tor distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
EC1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
Form No. F_072313 New page 83q-v, issue July 22, 2013.
New Data Sheet for VK572 and Added ENT Finish.)