HomeMy WebLinkAbout1512 W 13th Pl 04-1371 (energy calcs)Dq-0-l31l N-Master(c) COMMERCIAL HEAT LOSS / GAIN Based on ACCA MANUAL N MANUAL N Copyrighted (c) 1988 by ACCA Project name : M.P. Room - Kitchen Address : 1512 West 13th Place City/State : Sanford Owner : Builder : HVAC contr.: Barnes Htg ----------------------------------------------------------------- & Ac COOLING PARAMETERS --------------------------------------------------------------------- Geographical Location ----> ---------------------------------------------------------------------- State FLORIDA City : Sanford North Latitude / Elevation I 28 o / 14 Ft. Above Sea Level Relaltive Humidity I 50 Grains / Lb.(inside) I 63 Outdoor Dry Buld (Deg Fra) I 93 o Outdoor Wet Bulb (Deg Fra) I 76 o Indoor Dry Bulb (Deg Fo) I 75 o Indoor Wet Bulb (Deg Fra) 61.3 o Outdoor Humidity Ratio I 110 Daily Range I 16 o Peak Load Time I 1200 Hours Temperature Differance (Td)(Deg Fo) I 18 o Cooling Load Td Correction (Deg Fra) I 30(+) ----------------- ---------------------------------------------------------- HEATING SUMMARY COOLING SUMMARY TOTAL LOSS : 23778.31 TOTAL SENSIBLE 44038.86 LATENT GAINS 17423.96 TOTAL GAIN : 61462.82 -------------------------------------------------------------------- SENSIBLE OVERSIZE @ 20% 8807.771 ------------------------------------------------------------------------ HVAC Equipment Heating Manufacturer Htg System lOkw 34.1 MBTU COP/HSPF 1 ------------------------------------------------------------------------- Cooling Clg System 5 Ton 60.0 MBTU (S) EER 10 Air Handler Vert @ cfm ------------------------------------------------------------------------ HTG AIR FLOW FACTOR = .093538 CLG AIR FLOW FACTOR = .050505 ZONE CFM = 584.2336 ZONE CFM = 2224.182 SENSIBLE HEAT RATIO = .72 PLANS REVIEWED CITY OF SANFORD GLASS _SOLAR -------------------------------------------------------------- TYPE GLASS FACES AREA Sc U -VALUE LOSS/BTUH GAIN/BTUH SINGLE CLEAR East 33 1 1221 1947 SINGLE CLEAR West 49 1 1813 1813 GLASS _CONDUCTION ---------------------------------------------------------- SINGLE CLEAR 33 1 366 356.02 SINGLE CLEAR 49 1 542 527.22 WALLS----------------------------------------------------------------------- WA.LL FACES AREA R -VALUE U -VALUE LOSS/BTUH GAIN/BTUH North 319 4 .15 1770.45 478.5 TYPE :8in.CONC.N/W BLK East 311 4 .15 1726.05 1399.5 TYPE :8in.CONC.N/W BLK West 111.7 4 .15 619.93 201.06 TYPE :8in.CONC.N/W BLK WALL SUB TOTAL 4116.43 2079.06 DOORS----------------------------------------------------------------------- DOOR FACES AREA R -VALUE U -VALUE LOSS/BTUH GAIN/BTUH North 21 n/a .26 945 87.36 TYPE :STEEL CEILINGS-------------------------------------------------------------------- AREA R -VALUE U -VALUE LOSS/BTUH GAIN/BTUH TYPE :WD TRUSS W/VENT. ATTIC WITH STANDARD CEILING ROOF COLOR: DARK 857 19 .05 1585.45 2613.85 FLOORS---------------------------------------------------------------------- SLAB PERIMETER ---------------------------------------------------------------------------- 81.17 0 .81 2629.908 000.00 STRUCTURAL SUB TOTALS ---------------------------------------------------------------------------- 13239.79 9443.94 OTHER SENSIBLE GAINS PEOPLE 40 N/A 11000 FLOUR/LIGHTING 1280 Watts N/A 4425.34 ICAND/LIGHTING 0 " N/A 0 INTERNAL GAINS N/A 12000 VENTILATION 300 CFM 7437 3907.44 ROOM SENSIBLE 20676.79 40776.72 DUCT LOSS & GAIN 3101.519 3262.137 TOTAL SENSIBLE ---------------------------------------------------------------------------- 23778.31 44038.86 LATENT GAINS PEOPLE N/A 11000 VENTILATION N/A 6423.96 TOTAL LOAD 23778.31 61462.82 OUTSIDE AIR CALCULATION - per ASHRAE 62-89 ,Table 2 Assembly 40 people cfm = 7.5 40 people x 7.5 cfm = 300 cfm usage less than 3 hours per day TOTALS 300 cfm 300 cfm required 300 cfm provided ************************************************************************* N-Master(c) COMMERCIAL HEAT LOSS / GAIN Based on ACCA MANUAL N MANUAL N Copyrighted (c) 1988 by ACCA -------------------------------------------- Project name : Office Chior Address : 1512 West 13th Place City/State : Sanford Owner Builder HVAC contr.: Barnes Htg & Ac ---------------------------------------------------- COOLING PARAMETERS -------------------------------------------------- Geographical Location ----> State FLORIDA City : Sanford ------------------- ------------------- North Latitude / Elevation 28 o / 14 Ft. Above Sea Level Relaltive Humidity 50 o Grains / Lb.(inside) 63 Outdoor Dry Buld (Deg Fo) 93 o Outdoor Wet Bulb (Deg Fo) 76 o Indoor Dry Bulb (Deg Fo) 75 o Indoor Wet Bulb (Deg Fo) 61.3 o Outdoor Humidity Ratio 110 Daily Range 16 o Peak Load Time 1200 Hours Temperature Differance (Td)(Deg Fo) 18 o Cooling Load Td Correction (Deg Fo) 30(+) ------------------------------------------------------ HEATING SUMMARY COOLING SUMMARY TOTAL LOSS : 14845.81 TOTAL SENSIBLE 18628.66 LATENT GAINS 6204.6 TOTAL GAIN : 24833.26 SENSIBLE OVERSIZE @ 20% 3725.732 -------------------------------------------------------- HVAC Equipment ---------------------------------------------------------- Heating Manufacturer Htg System 5kw 17.1 MBTU COP/HSPF 1 ---------------------------------------------------------- Cooling Clq System 4.0 Ton 48.0 MBTU (S) EER 10 Air Handler Vert @ cfm --------------------------------------------------------- HTG AIR FLOW FACTOR = .063374 CLG AIR FLOW FACTOR = .050505 ZONE CFM = 364.7619 ZONE CFM '= 940.8405 SENSIBLE HEAT RATIO = .75 GLASS ------------NON INSTALLED ---------------------------------------------- ---------------------------------------------WALLSWALL WALLS WALLFACES AREA R -VALUE U -VALUE LOSS/BTUH GAIN/BTUH East 119 4 .15 660.45 535.5 TYPE :8in.CONC.N/W BLK West 340 4 .15 1887 612 TYPE :8in.CONC.N/W BLK WALL SUB TOTAL : 2547.45 1147.5 DOORS DOOR FACES AREA R -VALUE U -VALUE LOSS/BTUH GAIN/BTUH East 21 n/a .26 945 87.36 TYPE :STEEL CEILINGS-------------------------------------------------------------------- AREA R -VALUE U -VALUE LOSS/BTUH GAIN/BTUH TYPE :WD TRUSS W/VENT. ATTIC WITH STANDARD CEILING ROOF COLOR: DARK 678 19 .05 1254.3 2067.9 FLOORS SLAB PERIMETER ----------------------------------------------------------- 48 0 .81 1555.2 000.00 STRUCTURAL SUB TOTALS ------------------------------------------------------------ 7914.4 3329.02 OTHER SENSIBLE GAINS PEOPLE 18 N/A 3870 FLOUR/LIGHTING 1280 Watts N/A 4425.34 ICAND/LIGHTING 0 TY N/A 0 INTERNAL GAINS N/A 3000 VENTILATION 135 CFM 4995 2624.4 ROOM SENSIBLE 12909.4 17248.76 DUCT LOSS & GAIN 1936.41 1379.901 TOTAL SENSIBLE ------------------------------------------------------------- 14845.81 18628.66 LATENT GAINS PEOPLE N/A 1890 VENTILATION N/A 4314.6 TOTAL LOAD 14845.81 24833.26 OUTSIDE AIR CALCULATION - per ASHRAE 62-89 ,Table 2 Offices 18 people cfm = 7.5 18 people x 7.5 cfm = 135 cfm usage less than 3 hours per day TOTALS 135 cfm 135 cfm required 135 cfm provided N-Master(c) COMMERCIAL HEAT LOSS / GAIN Based on ACCA MANUAL N MANUAL N Copyrighted (c) 1988 by ACCA ------------------------------------------------------------------ Project name Sanctuary - R.R.'s Address 1512 West 13th Place City/State : Sanford Owner f Builder HVAC contr.: Barnes Htg & Ac -------------------------------------------------------------------- COOLING PARAMETERS -------------------------------------------------------------------- Geographical Location ----> State FLORIDA City : Sanford ------------------------------------------------------------------- North Latitude / Elevation 28 o / 14 Ft. Above Sea Level Relaltive Humidity 50 Grains / Lb.(inside) 63 Outdoor Dry Buld (Deg Fra) 93 o Outdoor Wet Bulb (Deg Fo) 76 o Indoor Dry Bulb (Deg Fra) 75 o Indoor Wet Bulb (Deg Fo) 61.3 o Outdoor Humidity Ratio 110 Daily Range 16 o Peak Load Time 1200 Hours Temperature Differance (Td)(Deg Fo) 18 o Cooling Load Td Correction (Deg Fo) 30(+) ------------------------------------------------------------------------- HEATING SUMMARY COOLING SUMMARY TOTAL LOSS : 55349.95 TOTAL SENSIBLE 64235.78 LATENT GAINS 32401.8 TOTAL GAIN : 96637.58 SENSIBLE OVERSIZE @ 200 12847.16 ---------------------------------------------------------------------------- HVAC Equipment ---------------------------------------------------------------------=------ Heating Manufacturer Htg System (2) 10kw 34.1 MBTU COP/HSPF 1 ---------------------------------------------------------------------------- Cooling Clg System (2) 5 ton 60.0 MBTU (S) EER 10 Air Handler Vert @ cfm ---------------------------------------------------------------------------- HTG AIR FLOW FACTOR = .058613 CLG AIR FLOW FACTOR = .050505 ZONE CFM = 1359.95 ZONE CFM = 3244.228 SENSIBLE HEAT RATIO = .66 GLASS_SOLAR --------------------------------------------------------------- TYPE GLASS FACES AREA Sc U -VALUE LOSS/BTUH GAIN/BTUH SINGLE CLEAR East 48.6 1 1798.2 2867.4 SINGLE CLEAR West 48.6 1 1798.2 1798.2 GLASS _CONDUCTION ---------------------------------------------------------- SINGLE CLEAR 48.6 1 537.6 522.94 SINGLE CLEAR 48.6 1 537.6 522.94 WALLS--------------------------------------- WALL FACES AREA R -VALUE U -VALUE East 401.4 4 .15 TYPE :8in.CONC.N/W BLK 3000 26085 South 319 4 .15 TYPE :8in.CONC.N/W BLK 4758.206 55349.95 ----------------------------------- West 401.4 4 .15 TYPE :8in.CONC.N/W BLK 22531.8 55349.95 WALL SUB TOTAL DOORS-------------- --------------------- LOSS/BTUH GAIN/BTUH 2227.77 1806.3 1770.45 574.2 2227.77 722.52 6225.99 3103.02 -- ------------------------------------------------------- DOOR FACES AREA R -VALUE U -VALUE LOSS/BTUH GAIN/BTUH South 21 n/a .26 945 87.36 TYPE :STEEL CEILINGS -------------------------------- AREA R -VALUE TYPE :WD TRUSS W/VENT. ATTIC WITH STANDARD CEILING ROOF COLOR: DARK 1797 19 FLOORS---------------------------------- SLAB PERIMETER 124 0 ---------------------------------------- STRUCTURAL SUB TOTALS ---------------------------------------- OTHER SENSIBLE GAINS PEOPLE 94 FLOUR/LIGHTING 360 Watts ICAND/LIGHTING 2200 it INTERNAL GAINS VENTILATION 705 CFM ROOM SENSIBLE DUCT LOSS & GAIN TOTAL SENSIBLE ----------------------------------------- LATENT GAINS PEOPLE VENTILATION TOTAL LOAD ----------------------------------- U-VALUE LOSS/BTUH GAIN/BTUH .05 3324.45 5480.85 ------------------------------------ .81 4017.6 000.00 ------------------------------------ 22045.39 14403.14 ------------------------------------ N/A 20210 N/A 1244.63 N/A 6914.6 N/A 3000 -- ------------------------------------------------------- DOOR FACES AREA R -VALUE U -VALUE LOSS/BTUH GAIN/BTUH South 21 n/a .26 945 87.36 TYPE :STEEL CEILINGS -------------------------------- AREA R -VALUE TYPE :WD TRUSS W/VENT. ATTIC WITH STANDARD CEILING ROOF COLOR: DARK 1797 19 FLOORS---------------------------------- SLAB PERIMETER 124 0 ---------------------------------------- STRUCTURAL SUB TOTALS ---------------------------------------- OTHER SENSIBLE GAINS PEOPLE 94 FLOUR/LIGHTING 360 Watts ICAND/LIGHTING 2200 it INTERNAL GAINS VENTILATION 705 CFM ROOM SENSIBLE DUCT LOSS & GAIN TOTAL SENSIBLE ----------------------------------------- LATENT GAINS PEOPLE VENTILATION TOTAL LOAD ----------------------------------- U-VALUE LOSS/BTUH GAIN/BTUH .05 3324.45 5480.85 ------------------------------------ .81 4017.6 000.00 ------------------------------------ 22045.39 14403.14 ------------------------------------ N/A 20210 N/A 1244.63 N/A 6914.6 N/A 3000 26085 13705.2 48130.39 59477.57 7219.559 4758.206 55349.95 ----------------------------------- 64235.78 N/A 9870 N/A 22531.8 55349.95 96637.58 OUTSIDE AIR CALCULATION - per ASHRAE 62-89 ,Table 2 Assembly 94 people cfm = 7.5 94 people x 7.5 cfm = 705 cfm usage less than 3 hours per day TOTALS 705 cfm 705 cfm required 705 cfm provided *****************************************************************************