N-Master(c)
COMMERCIAL HEAT LOSS / GAIN
Based on ACCA MANUAL N
MANUAL N Copyrighted (c) 1988 by ACCA
Project name : M.P. Room
- Kitchen
Address : 1512 West
13th Place
City/State : Sanford
Owner :
Builder :
HVAC contr.: Barnes Htg
-----------------------------------------------------------------
& Ac
COOLING PARAMETERS
---------------------------------------------------------------------
Geographical Location ---->
----------------------------------------------------------------------
State FLORIDA City :
Sanford
North Latitude / Elevation
I 28 o / 14 Ft.
Above Sea Level
Relaltive Humidity
I 50
Grains / Lb.(inside)
I 63
Outdoor Dry Buld (Deg Fra)
I 93 o
Outdoor Wet Bulb (Deg Fra)
I 76 o
Indoor Dry Bulb (Deg Fo)
I 75 o
Indoor Wet Bulb (Deg Fra)
61.3 o
Outdoor Humidity Ratio
I 110
Daily Range
I 16 o
Peak Load Time
I 1200 Hours
Temperature Differance (Td)(Deg Fo) I 18 o
Cooling Load Td Correction (Deg Fra) I 30(+)
----------------- ----------------------------------------------------------
HEATING SUMMARY
COOLING SUMMARY
TOTAL LOSS : 23778.31
TOTAL SENSIBLE
44038.86
LATENT GAINS
17423.96
TOTAL GAIN :
61462.82
--------------------------------------------------------------------
SENSIBLE OVERSIZE @ 20%
8807.771
------------------------------------------------------------------------
HVAC Equipment
Heating
Manufacturer
Htg System lOkw 34.1 MBTU
COP/HSPF 1
-------------------------------------------------------------------------
Cooling
Clg System 5 Ton 60.0 MBTU
(S) EER 10
Air Handler Vert @ cfm
------------------------------------------------------------------------
HTG AIR FLOW FACTOR = .093538 CLG AIR FLOW FACTOR = .050505
ZONE CFM = 584.2336 ZONE CFM = 2224.182
SENSIBLE HEAT RATIO = .72
PLANS REVIEWED
CITY OF SANFORD
GLASS _SOLAR --------------------------------------------------------------
TYPE GLASS FACES
AREA
Sc
U -VALUE
LOSS/BTUH
GAIN/BTUH
SINGLE CLEAR East
33
1
1221
1947
SINGLE CLEAR West
49
1
1813
1813
GLASS _CONDUCTION ----------------------------------------------------------
SINGLE CLEAR
33
1
366
356.02
SINGLE CLEAR
49
1
542
527.22
WALLS-----------------------------------------------------------------------
WA.LL FACES
AREA
R -VALUE
U -VALUE
LOSS/BTUH
GAIN/BTUH
North
319
4
.15
1770.45
478.5
TYPE :8in.CONC.N/W BLK
East
311
4
.15
1726.05
1399.5
TYPE :8in.CONC.N/W BLK
West
111.7
4
.15
619.93
201.06
TYPE :8in.CONC.N/W BLK
WALL SUB TOTAL
4116.43
2079.06
DOORS-----------------------------------------------------------------------
DOOR FACES
AREA
R -VALUE
U -VALUE
LOSS/BTUH
GAIN/BTUH
North
21
n/a
.26
945
87.36
TYPE :STEEL
CEILINGS--------------------------------------------------------------------
AREA
R -VALUE
U -VALUE
LOSS/BTUH
GAIN/BTUH
TYPE :WD TRUSS W/VENT.
ATTIC
WITH STANDARD CEILING
ROOF COLOR: DARK
857
19
.05
1585.45
2613.85
FLOORS----------------------------------------------------------------------
SLAB PERIMETER
----------------------------------------------------------------------------
81.17
0
.81
2629.908
000.00
STRUCTURAL SUB TOTALS
----------------------------------------------------------------------------
13239.79
9443.94
OTHER SENSIBLE GAINS
PEOPLE
40
N/A
11000
FLOUR/LIGHTING
1280
Watts
N/A
4425.34
ICAND/LIGHTING
0 "
N/A
0
INTERNAL GAINS
N/A
12000
VENTILATION
300 CFM
7437
3907.44
ROOM SENSIBLE
20676.79
40776.72
DUCT LOSS & GAIN
3101.519
3262.137
TOTAL SENSIBLE
----------------------------------------------------------------------------
23778.31
44038.86
LATENT GAINS
PEOPLE
N/A
11000
VENTILATION
N/A
6423.96
TOTAL LOAD
23778.31
61462.82
OUTSIDE AIR CALCULATION - per ASHRAE 62-89 ,Table 2
Assembly
40 people
cfm = 7.5
40 people x 7.5 cfm = 300 cfm
usage less than 3 hours per day
TOTALS
300 cfm
300 cfm required
300 cfm provided
*************************************************************************
N-Master(c)
COMMERCIAL HEAT LOSS / GAIN
Based on ACCA MANUAL N
MANUAL N Copyrighted (c) 1988 by ACCA
--------------------------------------------
Project name : Office Chior
Address : 1512 West 13th Place
City/State : Sanford
Owner
Builder
HVAC contr.: Barnes Htg & Ac
----------------------------------------------------
COOLING PARAMETERS
--------------------------------------------------
Geographical Location ----> State FLORIDA City : Sanford
-------------------
-------------------
North Latitude / Elevation 28 o / 14 Ft. Above Sea Level
Relaltive Humidity 50 o
Grains / Lb.(inside) 63
Outdoor Dry Buld (Deg Fo) 93 o
Outdoor Wet Bulb (Deg Fo) 76 o
Indoor Dry Bulb (Deg Fo) 75 o
Indoor Wet Bulb (Deg Fo) 61.3 o
Outdoor Humidity Ratio 110
Daily Range 16 o
Peak Load Time 1200 Hours
Temperature Differance (Td)(Deg Fo) 18 o
Cooling Load Td Correction (Deg Fo) 30(+)
------------------------------------------------------
HEATING SUMMARY COOLING SUMMARY
TOTAL LOSS : 14845.81 TOTAL SENSIBLE 18628.66
LATENT GAINS 6204.6
TOTAL GAIN : 24833.26
SENSIBLE OVERSIZE @ 20% 3725.732
--------------------------------------------------------
HVAC Equipment
----------------------------------------------------------
Heating
Manufacturer
Htg System 5kw 17.1 MBTU
COP/HSPF 1
----------------------------------------------------------
Cooling
Clq System 4.0 Ton 48.0 MBTU
(S) EER 10
Air Handler Vert @ cfm
---------------------------------------------------------
HTG AIR FLOW FACTOR = .063374 CLG AIR FLOW FACTOR = .050505
ZONE CFM = 364.7619 ZONE CFM '= 940.8405
SENSIBLE HEAT RATIO = .75
GLASS ------------NON INSTALLED ----------------------------------------------
---------------------------------------------WALLSWALL
WALLS
WALLFACES
AREA
R -VALUE
U -VALUE
LOSS/BTUH
GAIN/BTUH
East
119
4
.15
660.45
535.5
TYPE :8in.CONC.N/W BLK
West
340
4
.15
1887
612
TYPE :8in.CONC.N/W BLK
WALL SUB TOTAL :
2547.45
1147.5
DOORS
DOOR FACES
AREA
R -VALUE
U -VALUE
LOSS/BTUH
GAIN/BTUH
East
21
n/a
.26
945
87.36
TYPE :STEEL
CEILINGS--------------------------------------------------------------------
AREA
R -VALUE
U -VALUE
LOSS/BTUH
GAIN/BTUH
TYPE :WD TRUSS W/VENT.
ATTIC
WITH STANDARD CEILING
ROOF COLOR: DARK
678
19
.05
1254.3
2067.9
FLOORS
SLAB PERIMETER
-----------------------------------------------------------
48
0
.81
1555.2
000.00
STRUCTURAL SUB TOTALS
------------------------------------------------------------
7914.4
3329.02
OTHER SENSIBLE GAINS
PEOPLE
18
N/A
3870
FLOUR/LIGHTING
1280 Watts
N/A
4425.34
ICAND/LIGHTING
0 TY
N/A
0
INTERNAL GAINS
N/A
3000
VENTILATION
135 CFM
4995
2624.4
ROOM SENSIBLE
12909.4
17248.76
DUCT LOSS & GAIN
1936.41
1379.901
TOTAL SENSIBLE
-------------------------------------------------------------
14845.81
18628.66
LATENT GAINS
PEOPLE
N/A
1890
VENTILATION
N/A
4314.6
TOTAL LOAD
14845.81
24833.26
OUTSIDE AIR CALCULATION - per ASHRAE 62-89 ,Table 2
Offices
18 people
cfm = 7.5
18 people x 7.5 cfm = 135 cfm
usage less than 3 hours per day
TOTALS
135 cfm
135 cfm required
135 cfm provided
N-Master(c)
COMMERCIAL HEAT LOSS / GAIN
Based on ACCA MANUAL N
MANUAL N Copyrighted (c) 1988 by ACCA
------------------------------------------------------------------
Project name Sanctuary - R.R.'s
Address 1512 West 13th Place
City/State : Sanford
Owner f
Builder
HVAC contr.: Barnes Htg & Ac
--------------------------------------------------------------------
COOLING PARAMETERS
--------------------------------------------------------------------
Geographical Location ----> State FLORIDA City : Sanford
-------------------------------------------------------------------
North Latitude / Elevation 28 o / 14 Ft. Above Sea Level
Relaltive Humidity 50
Grains / Lb.(inside) 63
Outdoor Dry Buld (Deg Fra) 93 o
Outdoor Wet Bulb (Deg Fo) 76 o
Indoor Dry Bulb (Deg Fra) 75 o
Indoor Wet Bulb (Deg Fo) 61.3 o
Outdoor Humidity Ratio 110
Daily Range 16 o
Peak Load Time 1200 Hours
Temperature Differance (Td)(Deg Fo) 18 o
Cooling Load Td Correction (Deg Fo) 30(+)
-------------------------------------------------------------------------
HEATING SUMMARY COOLING SUMMARY
TOTAL LOSS : 55349.95 TOTAL SENSIBLE 64235.78
LATENT GAINS 32401.8
TOTAL GAIN : 96637.58
SENSIBLE OVERSIZE @ 200 12847.16
----------------------------------------------------------------------------
HVAC Equipment
---------------------------------------------------------------------=------
Heating
Manufacturer
Htg System (2) 10kw 34.1 MBTU
COP/HSPF 1
----------------------------------------------------------------------------
Cooling
Clg System (2) 5 ton 60.0 MBTU
(S) EER 10
Air Handler Vert @ cfm
----------------------------------------------------------------------------
HTG AIR FLOW FACTOR = .058613 CLG AIR FLOW FACTOR = .050505
ZONE CFM = 1359.95 ZONE CFM = 3244.228
SENSIBLE HEAT RATIO = .66
GLASS_SOLAR ---------------------------------------------------------------
TYPE GLASS FACES
AREA Sc U -VALUE LOSS/BTUH GAIN/BTUH
SINGLE CLEAR East 48.6 1 1798.2 2867.4
SINGLE CLEAR West 48.6 1 1798.2 1798.2
GLASS _CONDUCTION ----------------------------------------------------------
SINGLE CLEAR 48.6 1 537.6 522.94
SINGLE CLEAR 48.6 1 537.6 522.94
WALLS---------------------------------------
WALL FACES
AREA
R -VALUE U -VALUE
East
401.4
4 .15
TYPE :8in.CONC.N/W BLK
3000
26085
South
319
4 .15
TYPE :8in.CONC.N/W BLK
4758.206
55349.95
-----------------------------------
West
401.4
4 .15
TYPE :8in.CONC.N/W BLK
22531.8
55349.95
WALL SUB TOTAL
DOORS--------------
---------------------
LOSS/BTUH GAIN/BTUH
2227.77 1806.3
1770.45 574.2
2227.77 722.52
6225.99 3103.02
--
-------------------------------------------------------
DOOR FACES AREA R -VALUE U -VALUE LOSS/BTUH GAIN/BTUH
South 21 n/a .26 945 87.36
TYPE :STEEL
CEILINGS --------------------------------
AREA R -VALUE
TYPE :WD TRUSS W/VENT. ATTIC
WITH STANDARD CEILING
ROOF COLOR: DARK 1797 19
FLOORS----------------------------------
SLAB PERIMETER 124 0
----------------------------------------
STRUCTURAL SUB TOTALS
----------------------------------------
OTHER SENSIBLE GAINS
PEOPLE 94
FLOUR/LIGHTING 360 Watts
ICAND/LIGHTING 2200 it
INTERNAL GAINS
VENTILATION 705 CFM
ROOM SENSIBLE
DUCT LOSS & GAIN
TOTAL SENSIBLE
-----------------------------------------
LATENT GAINS
PEOPLE
VENTILATION
TOTAL LOAD
-----------------------------------
U-VALUE LOSS/BTUH GAIN/BTUH
.05 3324.45 5480.85
------------------------------------
.81 4017.6 000.00
------------------------------------
22045.39 14403.14
------------------------------------
N/A
20210
N/A
1244.63
N/A
6914.6
N/A
3000
--
-------------------------------------------------------
DOOR FACES AREA R -VALUE U -VALUE LOSS/BTUH GAIN/BTUH
South 21 n/a .26 945 87.36
TYPE :STEEL
CEILINGS --------------------------------
AREA R -VALUE
TYPE :WD TRUSS W/VENT. ATTIC
WITH STANDARD CEILING
ROOF COLOR: DARK 1797 19
FLOORS----------------------------------
SLAB PERIMETER 124 0
----------------------------------------
STRUCTURAL SUB TOTALS
----------------------------------------
OTHER SENSIBLE GAINS
PEOPLE 94
FLOUR/LIGHTING 360 Watts
ICAND/LIGHTING 2200 it
INTERNAL GAINS
VENTILATION 705 CFM
ROOM SENSIBLE
DUCT LOSS & GAIN
TOTAL SENSIBLE
-----------------------------------------
LATENT GAINS
PEOPLE
VENTILATION
TOTAL LOAD
-----------------------------------
U-VALUE LOSS/BTUH GAIN/BTUH
.05 3324.45 5480.85
------------------------------------
.81 4017.6 000.00
------------------------------------
22045.39 14403.14
------------------------------------
N/A
20210
N/A
1244.63
N/A
6914.6
N/A
3000
26085
13705.2
48130.39
59477.57
7219.559
4758.206
55349.95
-----------------------------------
64235.78
N/A
9870
N/A
22531.8
55349.95
96637.58
OUTSIDE AIR CALCULATION - per ASHRAE 62-89 ,Table 2
Assembly
94 people
cfm = 7.5
94 people x 7.5 cfm = 705 cfm
usage less than 3 hours per day
TOTALS
705 cfm
705 cfm required
705 cfm provided
*****************************************************************************