400 Red Rose Ln 16-2685 (a)GENERAL CONSTRUCTION NOTES: CHAPTERS AND SECTIONS REFER TO F.B.G.R - 5TH EDITION (2014) NOTE: ANY DIMENSIONS AND/OR CALLOUT5 WITHIN THIS SET OF DRAWINGS REFERENCING LUMBER SIXES OR WALL THICKNE55 ARE TO BE CONSIDERED "NOMINAL DIMEN51ON5" ' OCCUPANCY AND CONSTRUCTION TYPE: THI5 UNIT HAS AN R3 OCCUPANCY AND BUILDING TYPE V -B CLASSIFICATION, LOT 30 TH,ORNBROOKE 50 S CEILING CONSTRUCTION: I. THE GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND ITS ATTIC AREA BY NOT LE55 THAN 1/2 INCH (12.1 mm) GYPSUM BOARD APPLIED TO THE GARAGE SIDE. GARAGES BENEATH HABITABLE ROOMS SHALL BE SEPARATED FROM ALL HABITABLE ROOMS ABOVE BY NOT LE55 THAN 5/8 INCH (15.9 mm) TYPE "X" GYPSUM BOARD OR EQUIVALENT, WHERE THE SEPARATION 15 A FLOOR -CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE SEPARATION SHALL ALSO BE PROTECTED BY NOT LE65 THAN 1/2 INCH (12.1 mm) GYPSUM BOARD OR EQUIVALENT IN ACCORSTANTON 2055 ELEVATION ME MEDITERRANEANDANCE WITH F.B.C.R. 5TH EDITION (2014) 8102.3.5. EXTERIOR FINISHES: INSTALLATION OF EXTERIOR LATHING AND FRAMING APPLICATION REQUIREMENTS TO BE PER F.B.C.R. - 5TH EDITION (2014) 81103.6.1 AND A5TM C 1063. ALL LATH AND LATH ATTACHMENTS SHALL BE OF CORROSION -RESISTANT MATERIAL. EXPANDED METAL OR WOVEN WIRE LATH SHALL BE ATTACHED WITH 1112 INCH II GAUGE NAILS HAVING A 1/16 INCH HEAD, OR 1/8 INCH LONG 16 GAUGE STAPLES 5PAGED NO MORE THAN 6 INCHES, OR AS OTHERW15E APPROVED. THICKNESS OF TEXTURED FIN15H OVER FRAME APPLICATION TO BE GARAGE RIGHT PER F.B.C.R. - 5TH EDITION (2014) 8103,6.2 AND ASTM C 926. PER RB.C.R. 5TH EDITION (2014) 8103.62.1 WEEP 5CREED5 SHALL BE A MINIMUM NO. 2b GALVANIZED SHEET GAUGE CORRO51ON-RE515TANT WEEP SCREED OR PLASTIC WEEP SCREED WITH A MINIMUM VERTICAL ATTACHMENT FLANGE OF 3.1/2 INCHES SHALL BE PROVIDED AT OR BELOW THE PLATE LINE ON EXTERIOR STUD WALLS IN ACCORDANCE WITH ASTM G 926. THE WEEP SCREED SHALL BE PLACED A MINIMUM OF 4 INCHES ABOVE THE EARTH OR 2 INCHES A50VE PAVED AREAS. THE WEATHER RESISTANT BARRIER SHALL LAP THE ATTACHMENT FLANGE. THE EXTERIOR LATH SHALL COVER AND TERMINATE ON THE ATTACHMENT FLANGE OF THE WEEP SCREED. PER F.B.C.R 5TH EDITION (2014) R103.6.3 WATER RE515TIVE BARRIERS INSTALLED OVER WOOD BASED SHEATHING SHALL INCLUDE A WATER RESISTIVE VAPOR PERMEABLE BARRIER EQUIVALENT TO 2 LAYERS OF GRADE D PAPER. STUCCO APPLICATION AND CURING PER F.B,C.R, 5TH EDITION (2014) 8103.6.5 OR IN ACCORDANCE WITH A5TM C 926. TAYLOR MORRISON STUCCO CONTROL JOINTS: STUCCO CONTROL JOINTS TO BE INSTALLED PER A5TM G 1063-06 (1,11,4.1 THRU 1.11.4.4) AT FRAMED WALLS TO DELINEATE: AREAS NOT MORE THAN 144 5.F. AND DELINEATE AREAS NOT MORE THAT 100 5.F. FOR HORIZONTAL APPLICATIONS. DISTANCE BETWEEN CONTROL JOINTS SHALL NOT EXCEED IS FT, IN EITHER DIRECTION OR A LENGTH -TO -WIDTH RATIO OF 2 1/2 TO 1. A CONTROL JOINT SHALL BE INSTALLED WHERE CEILING FRAMING OR FURRING CHANGE DIRECTION, AND WHERE EXPANSION JOINT OCCURS IN BASE EXTERIOR WALL. WALL OR PARTITION HEIGHT DOOR FRAMES SHALL BE CONSIDERED AS CONTROL JOINTS. EGRE55: I. EACH BEDROOM MUST HAVE ONE WINDOW THAT COMPLIES WITH EGRE55 CODES, IF THERE IS NO ACCESS TO EXTERIOR THROUGH A DOOR THE WINDOW MUST HAVE A MAXIMUM THORNBROOKE 50's OPENING HEIGHT OF 44" ABOVE FINISH FLOOR LINE OF THAT PARTICULAR ROOM. COMMUNITY SPECIFIC FLASHING: I. FLASHING SHALL BE INSTALLED AT WALL AND ROOF INTERSECTIONS, DECK AND WALL INTERSECTIONS, AT GUTTERS, AT ALL CHANGES IN ROOF SLOPE OR DIRECTION, AND AROUND STANDARD SPECIFICATIONS REDRAW NOTES PLAN REVISIONS DRAWING INDEX 2.APROVEDC y 2. APPROVED C0880510N-RESISTANT FLASHING SHALL BE APPLIED SHINGLE FASHION IN SUCH A MANNER A5 TO PREVENT ENTRY OF WATER INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE BUILDING STRUCTURAL FRAMING COMPONENTS. THE FLASHING SHALL EXTEND TO THE SURFACE OF THE EXTERIOR WALL FINISH. APPROVED CORRO5ION-RE515TANT FLASHING SHALL BE INSTALLED AT ALL REQUIRED LOCATIONS PER R103,8, 9-14-16 CREATED OT 5 CMC AN FOR LOT 30 IN COV - GENERAL NOTES, INDEX, SPECIFICATIONS WINDOW INSTALLATION: STEM WALL FOOTING, ALUMINUM OVER 2x6 SUB FASCIA, RE EDL PE PL I. WINDOWS SHALL BE INSTALLED AND FLASHED IN ACCORDANCE WITH THE MANUFACTURERS WRITTEN INSTALLATION INSTRUCTIONS. WRITTEN INSTALLATION INSTRUCTIONS SHALL BE SHINGLE ROOF, ELECTRIC NEAT, 50 GAL. W.N., 150 AMP THORNBROOKE 50'5 ELEVATION 1 SLAB INTERFACE PLAN PROVIDED BY THE MANUFACTURER FOR EACH WINDOW, 5ERVICE/PANEL BOX, 6-8 DOORS THROUGHOUT, PAINTED "ME. -MEDITERRANEAN" GARAGE RIGHT W/ /� i KNEE WALLS, ELECTRIC RANGE, PAVER DRIVE AND LEAD PLAN OPTIONS INCLUDING: NICHE AT FOYER, 2/`11 -FLOOR PLAN N®TES DWELLING / GARAGE OPENIN65: WALK, PAVER ENTRY, AND ACRYLIC AT LANAI, TRAY CEILING AT MA5TER SUITE, THE OPENING BETWEEN THE GARAGE AND LIVING AREA SHALL BE EQUIPPED WITH SOLID WOOD DOORS NOT LE55 THAN 13/8 IN THICKNESS, SOLID CORE (S.C.) OR HONEYCOMB 2A2- F L00 R PLAN DIMENSIONS GORE STEEL DOORS NOT LE55 THAN 13/8" THICK, OR 20 MINUTE FIRE RATED DOORS EQUIPPED WITH ASELF-CLOSING DEVICE. INTERCONNECT IN WALL WIRE CHA5E TUBE, UNDER -CABINET LIGHTING AT KITCHEN (ONLY), FLOOD ZONE REQUIREMENTS: ADDITIONAL OUTLET IN NON=WET AREA, (12) 3A1 - FRONT ELEVATION PLAN MEETS OR EXCEEDS FEMA FLOOD FINISHED GARAGE FLOOR ELEVATION, ADDITIONAL RECE55ED CANS, AND (5) 3A2 ELEVATIONS ROOF PLAN BUILDING SECTION ASPHALT SHINGLES (IF APPLICABLE) - CEILING FAN PRE -WIRES, I, WIND RESISTANCE OF ASPHALT SHINGLES. -ASPHALT SHINGLES SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 89052.6 AND 89052.6.1, 11 ----"^ 2 ASPHALT SHINGLES SHALL ONLY BE USED ON ROOF SLOPES OF TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2.12) OR GREATER FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN • JOB NUMBER 26002.219 CAD FILE NAME LOT 30 TB ISSUED 09-14-16 REMISED 3A3 -FLASHING DETAILS 12 UNITS HORIZONTAL (2:12) AND LE55 THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL (4:12), TWO LAYERS OF UNDERLAYMENT COMPLYING WITH A5TM D 226, TYPE I OR TYPE 11, x ca w r A5TM D 4869, TYPE II OR TYPE IV OR A5TM D 615115 REQUIRED IN ACCORDANCE WITH SECTION 89052.1. FOR ROOF SLOPES FROM FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL C 3A4 - FLASHING DETAILS (4:12) AND GREATER, ONE LAYER OF UNDERLAYMENT COMPLYING WITH ASTM D 226, TYPE II, ASTM D 4869, TYPE IV OR ASTM p 615115 REQUIRED )N ACCORDANCE WITH SECTION RW52.1. DESIGN GPOVP 0 -' L50 STATE STREET EAST 4A - ELECTRICAL PLAN CLAY AND CONCRETE TILE (IF APPLICABLE) 813.925.1800 FAX WWW.DAVISBEW&COM THE INSTALLATION OF CLAY AND CONCRETE TILE PER F.B.C.R, - 5TH EDITION (2014) R905.3 SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS, OR a EST. 1994 RECOMMENDATIONS OF FRSA/TRI FLORIDA NIGH WIND CONCRETE AND CLAY ROOF TILE INSTALLATION MANUAL, FIFTH EDITION WHERE THE VASE) 15 DETERMINED IN ACCORDANCE WITH SECTION R3012.13 OR THE RECOMMENDATIONS OF RAS 118,119 OR 120, REQUIRED UNDERLAYMENT PER F.B.CR. - 5TH EDITION (2014) 8905.33 SHALL CONFORM WITH A5TM D 226, TYPE 11; 45TM 1)2626, TYPE 11; OR A5TM D 1910 OR A5TM D 6380, CLA56 M MINERAL SURFACED ROLL ROOFING AND SHALL BE INSTALLED IN ACCORDANCE WITH-FR5A/TRI FLORIDA HIGH >:=.J Cm WIND CONCRETE AND CLAY ROOF TILE INSTALLATION MANUAL, FIFTH EDITION WHERE THE VASE) 15 DETERMINED IN ACCORDANCE WITH SECTION R3012.13 OR THE RMM,MENDATIONS 6 5'OU.. OF RAS 118,119 OR 120, 00 CHIMNEY HEIGHT REQUIREMENTS (IF APPLICABLE) 1, WHEN STANDARD OR OPTIONAL FIREPLACE 15 TO BE INSTALLED THE CHIMNEY MUST EXTEND 34" PAST THE HIGHER POINT WHERE IT EXTENDS THROUGH THE ROOF AND MUST BE ogCo 24" NIGHER THAN THE ROOF OR RIDGE THAT 1510'-0" AWAY OR CLOSER, E Fr_,, TUB AND 5HOWER AREAS: I. CEMENT, FIBER -CEMENT, OR GLA55 MAT GYPSUM BOARD (NO GREEN BOARD ALLOWED) IN COMPLIANCE WITH ASTM 01288, C1325, OR CI118 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS SHALL BE USED AS BACKERS FOR WALL TILE IN TUB AND SHOWER AREAS, AND WALL PANELS IN SHOWER AREAS, co TERMITE PROTECTION: o Z��� I. PENETRATION. PROTECTIVE SLEEVES AROUND PIPING PENETRATING CONCRETE SLAB -ON -GRADE FLOORS SHALL NOT BE OF CELLUL05E CONTAINING MATERIALS. IF 501L TREATMENT 15 USED FOR SUBTERRANEAN TERMITE PROTECTION, THE SLEEVE SHALL HAVE A MAXIMUM WALL THICKNESS OF 0.010 INCH, AND BE SEALED WITHIN THE SLAB U51NG A R,ECOID COPY NON -CORROSIVE CLAMPING DEVICE TO ELIMINATE THE ANNULAR SPACE BETWEEN THE PIPE AND THE SLEEVE. NO TERIMITICIDE5 SHALL BE APPLIED IN51DE THE SLEEVE. 2. PROTECTION AGAINST DECAY AND TERMITES. - CONDENSATE LINES, IRRIGATION / SPRINKLER 5Y5TEM RISERS FOR SPRAY HEADS, AND ROOF DOWNSPOUTS SHALL D15CHARGE AT LEAST I FOOT (305 mm) AWAY FROM THE STRUCTURE 51DEWALL, WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR SPLASH BLOCKS, GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 mm) HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON A ROOF ABOVE ANOTHER ROOF. MECHANICAL AND HVAC: I. ENERGY CALCULATIONS FOR HEATING AND COOLING CAPACITIES SHALL BE FURNISHED BY THE GENERAL CONTRACTOR AS AN ATTACHMENT TO THI5 PLAN SET AT THE TIME OF APPLICATION FOR PERMIT, 2. MECHANICAL APPLIANCES SHALL BE ACCE561BLE FOR INSPECTION, SERVICE, REPAIR, AND REPLACEMENT WITHOUT REMOVING PERMANENT CONSTRUCTION, OTHER APPLIANCES, REVIEWED FOR CODE COMPLIANCE OR ANY OTHER PIPING OR DUCTS NOT CONNECTED TO THE APPLIANCE BEING INSPECTED, SERVICED, REPAIRED, OR REPLACED. A LEVEL WORKING SPACE AT LEAST 30 INCHES (162 mm) DEEP ANp 30 INCHES (162 mm) WIDE SHALL BE PROVIDED IN FRONT OF THE CONTROL SIDE TO SERVICE AN APPLIANCE. PLANS EXAMINER 3. DUCTS IN THE GARAGE AND DUCTS PENETRATING THE WALLS OR CEILINGS SEPARATING THE DWELLING FROM THE GARAGE SHALL BE CONSTRUCTED OF A MIN. 126 GAUGE (0.48 mm) SHEET STEEL OR OTHER APPROVED MATERIAL AND SHALL HAVE NO OPENINGS INTO THE GARAGE. DATE 4 FOUNDATIONS AND SUPPORTS FOR OUTDOOR MECHANICAL SYSTEMS SHALL BE RAISED AT LEAST 3 INCHES (16 mm) ABOVE THE FIN15HED GRADE AND SHALL AL50 CONFORM TO • JOB NUMBER 26002.219 CAD FILE NAME LOT 30 TB ISSUED 09-14-16 REMISED x ca w r C 0 0 too DESIGN GPOVP 0 -' L50 STATE STREET EAST OLDSMA& FLORIDA 34677 813. 925. 1300 TEL 813.925.1800 FAX WWW.DAVISBEW&COM TAMPA • DENVER a EST. 1994 N M 0 d .r 6 >:=.J Cm 6 5'OU.. 00 0� aJ�o ogCo E Fr_,, rm Cm O _ co o Z��� • JOB NUMBER 26002.219 CAD FILE NAME LOT 30 TB ISSUED 09-14-16 REMISED u a. co asp ,. C= ' [ co, CZ M (9f) 81.1 ti erT cD � tt®®'®� Z^ ®�® •®• C) Lr)m w 4:/ U- A••p W s Q`T:C0 e: 0 De J Wtwo• z + 00,00 09 +. 1 0 �ta01111 1�°° ` t W z M THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. ®IVISIO�1 5, AUXILIARY DRAIN PAN, CATEGORY IV CONDENSING APPLIANCES SHALL BE PROVIDED WITH AN AUXILIARY DRAIN PAN WHERE DAMAGE TO ANY BUILDING COMPONENT WILL >= /SNF®R® B19 OCCUR AS A RESULT OF STOPPAGE IN THE CONDENSATE DRAIN PIPING SYSTEM, THESE PANS SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE PROVISIONS OF A PERMIT ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED WITH THE WORK AND NOT AS SECTIONS M14113. AUTHORITY TO VIOLATE, CANCEL, ALTER OR SET 0 ASIDE ANY OF THE PROVISIONS OF THE TECHNICAL EXHAU5T FANS AND VENTING: CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT (.OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY MECHANICAL EXHAUST SYSTEM SHALL BE D15CHARGEID TO THE OUTDOORS. AIR SHALL NOT BE EXHAUSTED INTO AN ATTIC, THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A CORRECTION OF ERRORS IN PLANS, SOFFIT, RIDGE VENT OR CRAWL SPACE, CONSTRUCTION OR VIOLATIONS OF THIS CODE 2. EXHAUST AIR FROM BATH ROOMS AND TOILET ROOMS SHALL NOT BE RECIRCULATED WITHIN A RESIDENCE OR TO ANOTHER DWELLING UNIT AND SHALL BE EXHAUSTED DIRECTLY • TO THE OUTDOORS. EXHAUST AIR FROM BATHROOMS AND TOILET ROOMS SHALL NOT DISCHARGE INTO AN ATTIC, CRAWL SPACE, OR OTHER AREAS IN51DE THE BUILDING. 3. DUCT LENGTH. THE MAXIMUM LENGTH OF A CLOTHES DRYER EXHAUST DUCT SHALL NOT EXCEED 35 FEET FROM THE DRYER LOCATION TO THE WALL OR ROOF TERMINATION. THE 0 • COMP'A.C'TION, TEST MAXIMUM LENGTH OF THE DUCT SHALL BE REDUCED 2.5 FEET (162 mm) FOR EACH 45 DEGREE (0.19 RAD) BEND AND 5 FEET (1524 mm) FOR EACH W DEGREE 0.6 RAD) BEND. THE REQUIRED MAXIMUM LENGTH OF THE EXHAUST DUCT DOES NOT INCLUDE THE TRANSITION DUCT. EXCEPTION - WHERE A CLOTHES DRYER 5005TER FAN IS INSTALLED AND LISTED AND 2055 i'desults to be Verified LABELED FOR THE APPLICATION, THE MAXIMUM LENGTH OF THE EXHAUST DUCT, INCLUDING ANY TRANSITION DUCT, SHALL BE PERMITTED TO BE IN ACCORDANCE WITH THE BOOSTER • at Slab Inspection FAN MANUFACTURER'S INSTALLATION INSTRUCTIONS. WHERE A CLOTHES DRYER BOOSTER FAN 15 INSTALLED AND NOT READILY ACCE5515LE FROM THE ROOM IN WHICH THE DRYER 15 LOCATED, A PERMANENT IDENTIFYING LABEL SHALL BE PLACED ADJACENT TO WHERE THE EXHAUST DUCT ENTERS THE WALL. THE LABEL SHALL BEAR THE WORDS "THI5 DRYER EXHAUST SYSTEM 15 EQUIPPED WITH A REMOTELY LOCATED BOOSTER FAN." TITLE e C 4. PROVIDE LOUVER DEVICES AT INTAKE AND EXHAUST LOCATIONS IN ACCORDANCE WITH AMCA STANDARD 550 IN F$C, COVER SHEET `# 1 6 — 2 6 85 GENERAL NOTES ATTENTION GENERAL CONTRACTOR / BUILDER: _ @�\LDINC ° 155UANCE OF PLANS FROM THI5 DRAFTER'S OFFICE SHALL NOT RELIEVE THE BUILDER OF RE5PON51BILITY TO REVIEW AND VERIFY ALL NOTES, DIMENSIONS, AND ADHERENCE TO APPLICABLE BUILDING CODES PRIOR TO COMMENCEMENT OF ANY CONSTRUCTION. ANY D15CREPANCY OF ERROR IN NOTES, DIMENSIONS, OR ADHERENCE TO APPLICABLE BUILDING - iS AIN r,"0RD CODES SHALL BE BROUGHT TO THE ATTENTION OF THE DRAFTER'S OFFICE FOR CORRECTION BEFORE COMMENCEMENT OF ANY CONSTRUCTION CORRECTION / REVISIONS. ANY REVISIONS OR CHANGES, NOT RELATED TO THE CORRECTION OF ERRORS THAT ARE MADE AFTER THE FINAL PLANS HAVE BEEN COMPLETED SHALL BE SUBJECT TO ADDITIONAL FEES. IF ANY MODIFICATIONS ARE MADE TO THESE PLANS BY ANY OTHER PARTY OTHER THAN THE DRAFTER'S OFFICE„ THE DRAFTER SHALL NOT BE HELD RESPONSIBLE. • SHEET • REV. 10-14-2015 r DAVIS BEWS DESIGN GPOVP L50 STATE STREET EAST OLDSMA& FLORIDA 34677 813. 925. 1300 TEL 813.925.1800 FAX WWW.DAVISBEW&COM TAMPA • DENVER a EST. 1994 u a. co asp ,. C= ' [ co, CZ M (9f) 81.1 ti erT cD � tt®®'®� Z^ ®�® •®• C) Lr)m w 4:/ U- A••p W s Q`T:C0 e: 0 De J Wtwo• z + 00,00 09 +. 1 0 �ta01111 1�°° ` t W z M THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. ®IVISIO�1 5, AUXILIARY DRAIN PAN, CATEGORY IV CONDENSING APPLIANCES SHALL BE PROVIDED WITH AN AUXILIARY DRAIN PAN WHERE DAMAGE TO ANY BUILDING COMPONENT WILL >= /SNF®R® B19 OCCUR AS A RESULT OF STOPPAGE IN THE CONDENSATE DRAIN PIPING SYSTEM, THESE PANS SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE PROVISIONS OF A PERMIT ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED WITH THE WORK AND NOT AS SECTIONS M14113. AUTHORITY TO VIOLATE, CANCEL, ALTER OR SET 0 ASIDE ANY OF THE PROVISIONS OF THE TECHNICAL EXHAU5T FANS AND VENTING: CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT (.OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY MECHANICAL EXHAUST SYSTEM SHALL BE D15CHARGEID TO THE OUTDOORS. AIR SHALL NOT BE EXHAUSTED INTO AN ATTIC, THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A CORRECTION OF ERRORS IN PLANS, SOFFIT, RIDGE VENT OR CRAWL SPACE, CONSTRUCTION OR VIOLATIONS OF THIS CODE 2. EXHAUST AIR FROM BATH ROOMS AND TOILET ROOMS SHALL NOT BE RECIRCULATED WITHIN A RESIDENCE OR TO ANOTHER DWELLING UNIT AND SHALL BE EXHAUSTED DIRECTLY • TO THE OUTDOORS. EXHAUST AIR FROM BATHROOMS AND TOILET ROOMS SHALL NOT DISCHARGE INTO AN ATTIC, CRAWL SPACE, OR OTHER AREAS IN51DE THE BUILDING. 3. DUCT LENGTH. THE MAXIMUM LENGTH OF A CLOTHES DRYER EXHAUST DUCT SHALL NOT EXCEED 35 FEET FROM THE DRYER LOCATION TO THE WALL OR ROOF TERMINATION. THE 0 • COMP'A.C'TION, TEST MAXIMUM LENGTH OF THE DUCT SHALL BE REDUCED 2.5 FEET (162 mm) FOR EACH 45 DEGREE (0.19 RAD) BEND AND 5 FEET (1524 mm) FOR EACH W DEGREE 0.6 RAD) BEND. THE REQUIRED MAXIMUM LENGTH OF THE EXHAUST DUCT DOES NOT INCLUDE THE TRANSITION DUCT. EXCEPTION - WHERE A CLOTHES DRYER 5005TER FAN IS INSTALLED AND LISTED AND 2055 i'desults to be Verified LABELED FOR THE APPLICATION, THE MAXIMUM LENGTH OF THE EXHAUST DUCT, INCLUDING ANY TRANSITION DUCT, SHALL BE PERMITTED TO BE IN ACCORDANCE WITH THE BOOSTER • at Slab Inspection FAN MANUFACTURER'S INSTALLATION INSTRUCTIONS. WHERE A CLOTHES DRYER BOOSTER FAN 15 INSTALLED AND NOT READILY ACCE5515LE FROM THE ROOM IN WHICH THE DRYER 15 LOCATED, A PERMANENT IDENTIFYING LABEL SHALL BE PLACED ADJACENT TO WHERE THE EXHAUST DUCT ENTERS THE WALL. THE LABEL SHALL BEAR THE WORDS "THI5 DRYER EXHAUST SYSTEM 15 EQUIPPED WITH A REMOTELY LOCATED BOOSTER FAN." TITLE e C 4. PROVIDE LOUVER DEVICES AT INTAKE AND EXHAUST LOCATIONS IN ACCORDANCE WITH AMCA STANDARD 550 IN F$C, COVER SHEET `# 1 6 — 2 6 85 GENERAL NOTES ATTENTION GENERAL CONTRACTOR / BUILDER: _ @�\LDINC ° 155UANCE OF PLANS FROM THI5 DRAFTER'S OFFICE SHALL NOT RELIEVE THE BUILDER OF RE5PON51BILITY TO REVIEW AND VERIFY ALL NOTES, DIMENSIONS, AND ADHERENCE TO APPLICABLE BUILDING CODES PRIOR TO COMMENCEMENT OF ANY CONSTRUCTION. ANY D15CREPANCY OF ERROR IN NOTES, DIMENSIONS, OR ADHERENCE TO APPLICABLE BUILDING - iS AIN r,"0RD CODES SHALL BE BROUGHT TO THE ATTENTION OF THE DRAFTER'S OFFICE FOR CORRECTION BEFORE COMMENCEMENT OF ANY CONSTRUCTION CORRECTION / REVISIONS. ANY REVISIONS OR CHANGES, NOT RELATED TO THE CORRECTION OF ERRORS THAT ARE MADE AFTER THE FINAL PLANS HAVE BEEN COMPLETED SHALL BE SUBJECT TO ADDITIONAL FEES. IF ANY MODIFICATIONS ARE MADE TO THESE PLANS BY ANY OTHER PARTY OTHER THAN THE DRAFTER'S OFFICE„ THE DRAFTER SHALL NOT BE HELD RESPONSIBLE. • SHEET • REV. 10-14-2015 6 6 40'-0" 224" A/C PAD I' 4" 20'-6" (VERIFY LOCATION) PAVER DRIVE / LEADWALK 5'-4" 2'-4" 16'-0" 2'-4" SLAB INTERFACE PLAN STANTON -M) ELEVATION "ME - EDITERRANEAN" M SCALE: 1/4" -- 1'4' - co G.C. VERIFY ACRYLIC DAVIS BEWS DESIGN GPOVP 3/4" P.Y.C. „ CONDEN5ATION 4 P.V.C. / to 0 -�� FST. 1994 0 ON LANAI DRAIN m N ' IIAA v+~ $ $„ 5Y PLUMBEREm ■L NyJT ELEVATION 6 3 L' • 00 J T O 06C0 u_c) 1 1/2" REGE55 FOR 5.G.D. N N N to 0}'(p N ti — N N 4 o�0 ZE v ZLN ELEVATION AT 0'-0" (A55UMED) 7/ / IGx� I ��I 1--� 24'-2,. 10'-2" 2' 0" 2'-8" 2'-0" 1'-11" 3' 0" 3' 10" 2' 5" TU GARDEN aLLI / \� p.W. _ -� (�A.� `AV. — — — — — — --- � 1 I� 5HOWER I ELEVATION PROVIDE WATER LINE FOR ICE MAKER O 0'-4" ISI — — — — — o�lll I �I SII III I II � I� �IL__JUI 20'-4" II v - adl N N Q AA 3G2 `r N 20'-5" I I � � III � I ISI I 0 Cl InI L—J III w I L J 50 GAL. W.N. A5V. ELEVATION \ _ 01-411 cn �C n _ (T7 e ELEVATION N (004" PAVERS ELEVATION (-) 0'-4" LL �! HATCHING INDIGATE5 8"x8"x16" 5TANDARD 13'-4" 6'-0" 8" 19'-4" GONG. SLK. TYP. g 8" Q 811 ELEVATION 4ELEVATION ELEVATION o e M tlJ CO N N Ir 11/2" RECESS FOR GAR. DR. s' PAVER DRIVE / LEADWALK 5'-4" 2'-4" 16'-0" 2'-4" SLAB INTERFACE PLAN STANTON -M) ELEVATION "ME - EDITERRANEAN" M SCALE: 1/4" -- 1'4' JOB NUMBER 26002.219• CAD FILE NAME LOT 30 T9 ISSUED 09-14-16 REVISED K w DAVIS BEWS DESIGN GPOVP r/ to 0 -�� FST. 1994 0 c� N ' IIAA v+~ oof�m ■L NyJT 6 3 L' • 00 J T O 06C0 u_c) N to 0}'(p N ti 4 o�0 ZE v JOB NUMBER 26002.219• CAD FILE NAME LOT 30 T9 ISSUED 09-14-16 REVISED ITLE • SLAB INTERFACE PLAN n • SHEET • DAVIS BEWS DESIGN GPOVP 150 STATE STREET EAST OLDWAR, FLORIDA 34677 813. 925. 1300 TEL 813.925.1800 FAX W W W.DAVISBEWS-COM TAMPA •DENVER -�� FST. 1994 ITLE • SLAB INTERFACE PLAN n • SHEET • ALL EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL COMPLY WITH 8310 PER RB.C.R. - 5TH EDITION (2014). NICHE NICHE e l-) 4" e NICHE DETAIL - ASCALE: 1/4" - 411 3'-611x3'-6" T.O.M. A/C PAD TO4M 3 - 25 5H. 81.411 (VERIFY 9' 4" HD. AT S' -ml' LOCATION) A.F,F, * EGRE55 BOTTOMJj OF LINTEL G.G. VERIFY ACRYLIC 4 8'-011 AFF. LANAI ON LANAI 9'-4` FLAT CLG. 22'-0"x8'-0" 104" FLAT CLG. 1 9'-4" PLT. HT. 1 MASTER SUITE 1 16'- 8"x12'-10" 1 T.O.M. I 10'-0" TRAY CLG. 9'-411 FLUSH FRAME 9-06-0 ?EMP. S.G.p. I TO FURRING T25H.D.AT 81-011 I ? o " FROM 8R6'�TO 9'.O FAMILY ROOM 19'-0"x13'-4" 0 0 - VAULTED CLG. o 2 - R/5 '9 2 - R/5 2.96:12 12' 0" 13bx22 — I - ? — — — — — SLOPE CLG, o I ACG ATTIC 2.96:12 A/H E55 — — 9 411I VAULT a 1 91-411 Cir �e� CLG. 1 a CLG. l J SEE TUB DECK KNEE 1'8x6 8 �FRAMING DETAIL IITII WALL 6� ��� ON THIS SHEET M. BATH 20" H. GARDEN 0- 4211 H. 8'_411 TUB DECK TUB '09 - - — — — .4 9'11 CC z COUNTERTOP CLG. z \ GLG. /39' 34" N. KNEE WALL a UNDER VANITY ti n 7T / \ \ a o \ w 0 \ sTILE �CD LAV. 1 VENT MICRO Z Pib'�f W.G. SHOWER To EXTERIOR �K 'sa / FURR OUT I WALL FOR TUB/ TILE 5HELF z KITCHEN I I 5.01$ TUB SHOWER 1 TURD EK o I VAULTED CLG. I 1 12'-0" CLG. 0 1 iiBATH 2 l 1 ARCH- am BEDROOM 2 1 01 III TO 9'-011FRM a,6 if EDI 11'-0"x10'-2" 1 I - Lc II I I — — — =1`? r-� 9'-4" FLAT CLG. _lu IL Lu 121011 p1411 U �Q->F Q 2,96:12 VINYL CPT, I CLG GLG` vauLr BRKFST. 1 1 Q 10'-10'x8'-8" 2.96:12 I 112'-011 121-0" CLG. VAULTED CLG. 5L E+ CLG. I I ARCH AA 1 I FROM 8'I 6" 2-6x6.8 TO 9'-0" 3C2 ARCH FROM 641 TO 91-011 1-64-8 W w z _ — _ _ _ mz:y 5 5H. BEDROOM 3 m11'-0"x10'-0" ARCH 6,ru 0-y1z 1 9'-4" FLAT CLG. FROM 81-61 1 ARCH o 0 0 TO 9'-0" FROM 811- 611 Q [ I_ 9 4 UTIL. 1 TO 9'-0 1 CLG.Lu a 1cn 1 0�l �o � 121-011 BOX EN L DINING 12'-0"x11'-6" CLG. o cp 9'-4" FLAT CLG. g1-411 121-011 INSULATE CLG. CLG. WALLS 50 GAL. --p '- W.N. a v V NOTE: �1J ALL INTERIOR ANGLED WALLS 1 �{ X68 LL, ARE AT 45' (UN.O.) L — — — — _ 54"x2211 z ATTIC ACCE55 DEN 12'-0"x11'-6" e 9'-4" FLAT CLG. � z GARAGE o 19'-4"x22'-0" FLUSH FRAMEENTRY PAVERS 8'-0" PLT. HT. TO FURRING LINE OF GARAGE DOOR IN OPEN P051TION a Q T.O.M. I-----------_---------� O 121-011 121-m" CLG, I 1 A.F.F. - - - - 2- 1/2 35 5H. 1 HD. AT 6'41 1 1 U T.O.M. T.O.M. I I O ARCHED HDR LIVING 2055 TYPICAL MASONRY G,41RAGE 4(oQ WINDOW SCHEDULE LANAI 17& WINDOW WIDTHS ENTRY 4(o S.F. 2011 2111 3111 5311 u H TAMPA • DENVER EST. 1994 WINDOW CALL -OUTS �. LSNLL • L �_ r � T 00 J O o�co -5. ( 26" �,CW E � 12 5H 1/2 32 5H 22 5H 32 5H 0 p Z_�v = 3 013 5H 1/2 33 5H 23 5H 33 5H J p 51" 14 5H 1/2 34 5H 24 5H 34 5H z 63" 0 15 5H 1/2 35 5H 25 5H 35 5H Z_ 12" 16 5H 1/2 36 5H 26 5H 36 5H G.C. VERIFY MASONRY OFENING5 FOR ALL WINXI JS, cLu n WINDOW 5IZE5 ANP INSTALLATION MAY VARY PER O MANUFACTURER AND 5PECIFICATION5. z REFER TO FLOOR RLAN5 FOR STYLE OF WINDOW J5E1) (51NGLE HUNG -5H, CA5EMENT- C5MT, OR FIXED GLA55- F.G.) ALL EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL COMPLY WITH 8310 PER RB.C.R. - 5TH EDITION (2014). NICHE NICHE e l-) 4" e NICHE DETAIL - ASCALE: 1/4" - 411 3'-611x3'-6" T.O.M. A/C PAD TO4M 3 - 25 5H. 81.411 (VERIFY 9' 4" HD. AT S' -ml' LOCATION) A.F,F, * EGRE55 BOTTOMJj OF LINTEL G.G. VERIFY ACRYLIC 4 8'-011 AFF. LANAI ON LANAI 9'-4` FLAT CLG. 22'-0"x8'-0" 104" FLAT CLG. 1 9'-4" PLT. HT. 1 MASTER SUITE 1 16'- 8"x12'-10" 1 T.O.M. I 10'-0" TRAY CLG. 9'-411 FLUSH FRAME 9-06-0 ?EMP. S.G.p. I TO FURRING T25H.D.AT 81-011 I ? o " FROM 8R6'�TO 9'.O FAMILY ROOM 19'-0"x13'-4" 0 0 - VAULTED CLG. o 2 - R/5 '9 2 - R/5 2.96:12 12' 0" 13bx22 — I - ? — — — — — SLOPE CLG, o I ACG ATTIC 2.96:12 A/H E55 — — 9 411I VAULT a 1 91-411 Cir �e� CLG. 1 a CLG. l J SEE TUB DECK KNEE 1'8x6 8 �FRAMING DETAIL IITII WALL 6� ��� ON THIS SHEET M. BATH 20" H. GARDEN 0- 4211 H. 8'_411 TUB DECK TUB '09 - - — — — .4 9'11 CC z COUNTERTOP CLG. z \ GLG. /39' 34" N. KNEE WALL a UNDER VANITY ti n 7T / \ \ a o \ w 0 \ sTILE �CD LAV. 1 VENT MICRO Z Pib'�f W.G. SHOWER To EXTERIOR �K 'sa / FURR OUT I WALL FOR TUB/ TILE 5HELF z KITCHEN I I 5.01$ TUB SHOWER 1 TURD EK o I VAULTED CLG. I 1 12'-0" CLG. 0 1 iiBATH 2 l 1 ARCH- am BEDROOM 2 1 01 III TO 9'-011FRM a,6 if EDI 11'-0"x10'-2" 1 I - Lc II I I — — — =1`? r-� 9'-4" FLAT CLG. _lu IL Lu 121011 p1411 U �Q->F Q 2,96:12 VINYL CPT, I CLG GLG` vauLr BRKFST. 1 1 Q 10'-10'x8'-8" 2.96:12 I 112'-011 121-0" CLG. VAULTED CLG. 5L E+ CLG. I I ARCH AA 1 I FROM 8'I 6" 2-6x6.8 TO 9'-0" 3C2 ARCH FROM 641 TO 91-011 1-64-8 W w z _ — _ _ _ mz:y 5 5H. BEDROOM 3 m11'-0"x10'-0" ARCH 6,ru 0-y1z 1 9'-4" FLAT CLG. FROM 81-61 1 ARCH o 0 0 TO 9'-0" FROM 811- 611 Q [ I_ 9 4 UTIL. 1 TO 9'-0 1 CLG.Lu a 1cn 1 0�l �o � 121-011 BOX EN L DINING 12'-0"x11'-6" CLG. o cp 9'-4" FLAT CLG. g1-411 121-011 INSULATE CLG. CLG. WALLS 50 GAL. --p '- W.N. a v V NOTE: �1J ALL INTERIOR ANGLED WALLS 1 �{ X68 LL, ARE AT 45' (UN.O.) L — — — — _ 54"x2211 z ATTIC ACCE55 DEN 12'-0"x11'-6" e 9'-4" FLAT CLG. � z GARAGE o 19'-4"x22'-0" FLUSH FRAMEENTRY PAVERS 8'-0" PLT. HT. TO FURRING LINE OF GARAGE DOOR IN OPEN P051TION a Q T.O.M. I-----------_---------� O 121-011 121-m" CLG, I 1 A.F.F. - - - - 2- 1/2 35 5H. 1 HD. AT 6'41 1 1 U T.O.M. T.O.M. I I O ARCHED HDR LIVING 2055 5.F. G,41RAGE 4(oQ 5.F. LANAI 17& 5.F. ENTRY 4(o S.F. TQTAI 5Q. FT. 2737 S.F. 16-0x1-0 O.H. GARAGE DOOR I 9 411 (5EE ELEVATION) 9 4 A.F.F. A.F.F. PAVER DRIVE / LEADWALK REFER TO SHEET 25 FOR FLOOR PLAN W/ DIMEN51ON5 HATCHING LEGEND [7= IN5ULATE WALL FLOOR PLAN NOTES STANTON (TM) ELEVATION "ME - M EDITERRANEAN 11 SCALE: 1/4" - 11-0" • JOB NUMBER 26002.219• CAD FILE NAME LOT 30 TB ISSUED 09-14-16 REWSED K m w s J TO DAVIS BEWS 0 h� DESIGN GROUP N� 150 STATE STREET EAST OLDSMAR, FLORIDA 39677 Mrn 813. 925.1800 FAX W W W.DAVLSBEWS.COM TAMPA • DENVER EST. 1994 >_ 3J� �. LSNLL • L �_ r � T 00 J O o�co -5. �,CW E � .c = .— 0 °o1 0 p Z_�v • JOB NUMBER 26002.219• CAD FILE NAME LOT 30 TB ISSUED 09-14-16 REWSED • TI TLE • FLOOR PLAN NOTES DETAILS s DAVIS BEWS DESIGN GROUP 150 STATE STREET EAST OLDSMAR, FLORIDA 39677 813.925.1300 TEL 813. 925.1800 FAX W W W.DAVLSBEWS.COM TAMPA • DENVER EST. 1994 • TI TLE • FLOOR PLAN NOTES DETAILS eiv:uw FLOOR PLAN DIMENSIONS STANTON (TM) ELEVATION "ME - MEDITERRANEAN" SCALE: 1/4" :1'-0" • • DAVIS BEWS DESIGN GROUP 20'-8.. 150 STATE STREET EAST OLDSMAR, FLORIDA 39677 813.925.1300 TEL 813. 925.1800 FAX W W WDAVLSBEWS.COM TAN PA • DENVER x m C 0too N J y60MNh _ ISM tl, =JM LL e O C =T~ J V � LANAI -- --- _o�co LLL w0 I L �}iN a+ p CO ror �+ MASTER V-4" M.O. 3' 0° SUITE fTYPJ = I2'.6' FAMILY ROOM a LIN J N N I 3'-8" m 3'-2" 2'-5" 3'-2" "• 2'-5" 5'-0° 6'-4" - 3' 11/2" 2'-2 1/2" M. BATH co m O 5I N m O C2, V O KITCHEN F # — -in I I I L N — I III 1'-2° IIIS BATH I BEDROOM 2 I I III ► --- 2 2' 8" Q? - I? a 1. 6.. 1'-6"I r BRKFST. I Q 0" o v v Ti - m II 6 0 I -6 5 0 16 0 4 I 2'-5" Iz' 0" «, - -r11111— BEDROOM 3 1 5 -0 J 6'-4" 2'-8"F_ —,DINING CUTIL r 5 4" 9' 6" V -UD" v Si, 20'-0" N DEN GARAGE — CV N I' 4" 3'-4" M.O. 1'-4" ENTRY -----------------, r--- I I I I 13'-4" 6'-0" 811 811 � I I I I n% oz. N cl� N 5'-4" 8" 5'-4" REFER TO SHEET 2A FOR FLOOR PLAN 11'4" 214" 4'-8" 8" W/ NOTES 14'-0" 5'-4" 2'-4" 16'-0" M.O. 2'-4" 264" 40'-0" FLOOR PLAN DIMENSIONS STANTON (TM) ELEVATION "ME - MEDITERRANEAN" SCALE: 1/4" :1'-0" 14 JOB NUMBER 26002.219 CAD FILE NAME LOT 30 TB ISSUED 09-14-16 REMISED • • DAVIS BEWS DESIGN GROUP 150 STATE STREET EAST OLDSMAR, FLORIDA 39677 813.925.1300 TEL 813. 925.1800 FAX W W WDAVLSBEWS.COM TAN PA • DENVER x m C 0too N J y60MNh ISM N y =JM LL e O C =T~ J V � _o�co LLL w0 L �}iN a+ p CO ror �+ oN ZV2° 14 JOB NUMBER 26002.219 CAD FILE NAME LOT 30 TB ISSUED 09-14-16 REMISED e ca �0 un N ® ano co Z cL W C) Lr)��+,rr'Illalllo r' �, W'w'a'me 4C 00 ' s e , ,• • • �,( aee o �®��OI111111 W z ISL. (y) 1 0 F�m >mJ 2055 • TI TLE • FLOOR PLAN DIMENSIONS II 2A2 DAVIS BEWS DESIGN GROUP 150 STATE STREET EAST OLDSMAR, FLORIDA 39677 813.925.1300 TEL 813. 925.1800 FAX W W WDAVLSBEWS.COM TAN PA • DENVER EST. 1994 � e ca �0 un N ® ano co Z cL W C) Lr)��+,rr'Illalllo r' �, W'w'a'me 4C 00 ' s e , ,• • • �,( aee o �®��OI111111 W z ISL. (y) 1 0 F�m >mJ 2055 • TI TLE • FLOOR PLAN DIMENSIONS II 2A2 ;.t.t e ca �0 un N ® ano co Z cL W C) Lr)��+,rr'Illalllo r' �, W'w'a'me 4C 00 ' s e , ,• • • �,( aee o �®��OI111111 W z ISL. (y) 1 0 F�m >mJ 2055 • TI TLE • FLOOR PLAN DIMENSIONS II 2A2 1112" THICK SAND FIN15H KEYSTONE IIF APPLICABLE) RA15ED 5AND FIN15H TEXTURED BANDING NOTE: z TH15 DETAIL 5HOW5 THE TYPICAL THICKNE55 OF ALL RA15ED TEXTURED FIN15H BANDING Q AND 5AND FINISHED KEY5TONE5 (WHERE x y APPLICABLE) IF THICKNE55 15 TO BE DIFFERENT IT WILL BE CALLED OUT AT SPECIFIC KEYNOTE CALL -OUT z * * * * * * * * IN5TALLATION OF EXTERIOR LATHING AND FRAMING APPLICATION REQUIREMENT5 TO BE PER F.B.C.R. - 5TH 3/4° EDITION (2014) R103.6.1 AIND A5TM C 1063. THICK THICKNE55 OF TEXTURED FIN15H OVER FRAME APPLICATION TO BE PER F.B.C.R. - 5TH EDITION (2014) R103h.2 AND A5TM C 926. * * * * * * * * TYP. CROSS-SECTION OF RAISED TEXTURED FINISH BANDING AND / OR SAND FINISH KEYSTONE 5CALE: 3" = 1'-0" CLEAR OPENING NEIGPT5 IN DWELLING UNITS, WHERE THE OPENING OF AN OPERABLE WINDOW 15 LOCATED MORE THAN 12 INCHE5 ABOVE THE FINI5HED GRADE OR 5URFACE BELOW, THE LOWEST PART OF THE CLEAR OPENING OF THE WINDOW 5HALL BE A MINIMUM OF 24 INCHE5 ABOVE THE FINI5HED FLOOR OF THE ROOM IN WHICH THE WINDOW 15 LOCATED. OPERABLE 5ECTION5 OF WINDOW5 5HALL NOT PERMIT OPENING5 THAT ALLOW PA55AGE OF A 4 INCH DIAMETER 5PHERE WHERE SUCH OPENING5 ARE LOCATED WITHIN 24 INCHE5 OF THE FIN15HED FLOOR PER F.B.C. 2010 RE51DENTIAL CODE 8612.2 WINDOW FALL PREVENTION DEVICES AND WINDOW GUARD5, WHERE PROVIDED, 5HALL COMPLY WITH THE REQUIREMENTS OF A5TM F 2090 PER F.B.C. 2010 RESIDENTIAL CODE 8612.3 t., � 0 1/2" 3 11/2" 8" 8" SEGMENTED DECORATIVE CROWN 31-0 COPED BANDING DETAIL MOLDING DETAIL ENTRY F.G. DETAIL SCALE: 1/2" - 1411 SCALE: 1/2": 14" SCALE: 112": 14" SHINGLE 12 LSNINGLE a 6 ROOF 7 I'-0" GROWN ROOF MOULDING 12 (5EE DETAIL) a 6 o� 12 = 6 12 12 Q6 6 T.O.M. BEYOND_ 5TUCCo _ PLT. HT. S" SEGMENTED FINISH - - SADDLE LSNINGLE SHINGLE COPED BANDING 2' 0" ROOF ROOF - (TYP.) G.C. VERIFY T.O.M. _ a, FA5CIA CALL -OUT (TYPICAL) b- TEXTURED FINISH to 8" 5EGMENTED COPED BANDING ❑ ❑ ❑ ❑ ❑ ❑ (rYP) �k FIN150--00 L RLINE4-1 Tl� k lf�;] 7� 71 GRADE LINE ALIGN TOP OF (ASSUMED) BANDING W. BOTT OF WINDOW FRONT ELEVATION 5CALE: 1/4" - I'-0" REFER TO COVER 5HEET GENERAL NOTE5FOR ROOFING UNDERLAYMENT REQUIREMENT5 FOR ROOF PITCHE5 LE55 THAN 4:12 * * * * * T.O.M. BEYOND T.O.M. - 8" 5EGMENTED COPED BANDING (TYP.) v TEXTURED �ro FIN15H FINI51­1 FLOOR LINE • JOB NUMBER 26002.219 CAD FILE NAME LOT 30 TB ISSUED 09-14-16 REVISED r x ro w DAVIS BEWS DESIGN GROVP U 00 EST. 1994 J �W O i N ti 'Ae v, 00 04 `. >_; JM LL Lm 0 00 ro= aJ�ti � o°o E .c } N 0. m n Z520 • JOB NUMBER 26002.219 CAD FILE NAME LOT 30 TB ISSUED 09-14-16 REVISED r ELEVATION "ME - MEDITERRANEAN" • TITLE • FRONT ELEVATION DETAILS II 3C1 II DAVIS BEWS DESIGN GROVP 150 STATE STREET EAST OLDSMAR, FLORIDA 34677 813.92.5.1300 TEL 813. 925.1800 FAX W W W.DAVLSBEWS.COM TAMPA •DENVER EST. 1994 ELEVATION "ME - MEDITERRANEAN" • TITLE • FRONT ELEVATION DETAILS II 3C1 II - --------------------- ----------------- I � I I v ll I 1 ------------------------ i 1 1 ROOF VENT i REQUIREMENTS HATCHING INDICATES G.C. VERIFY THAT 110.61 5Q. IN. i OF VENTILATION THROUGH UPPER RECESS IN TRUSSES FOR 2/3 OF ROOF 15 REQUIRED. TRAY GLG. BELOW rTYPJ VERIFY QUANTITY OF ROOF VENTS REQUIRED, PER MANUFACTURER'5 SPECIFICATIONS OF NET FREE AREA PER VENT. i Lu AA r . �. I 4e I I I L KNEE !! WALL ROOF PLAN. 5CALE: 1/8" : I'-0" REFER TO COVER SHEET GENERAL NOTES FOR ROOFING UNDERLAYMENT REQUIREMENTS FOR ROOF PITCHE5 LE65 THAN 4:12 11/2" THICK SAND FIN15H KEYSTONE - (IF APPLICABLE) RA15ED SAND FINISH TEXTURED BANDING 3/4" THICK TYP. CROSS-SECTION OF RAISED TEXTURED FINISH BANDING AND / OR SAND FINISH KEYSTONE 5CALE: 3" = 1'-0" GLEAR OPENING HEIGHTS IN DWELLING UNIT5, WHERE THE OPENING OF AN OPERABLE WINDOW IS LOCATED MORE THAN 12 INCHES ABOVE THE FINISHED GRADE OR SURFACE BELOW, THE LOWEST PART OF THE CLEAR OPENING OF THE WINDOW SHALL BE A MINIMUM OF 24 INCHES ABOVE THE FINI5HED FLOOR OF THE ROOM IN WHICH THE WINDOW IS LOCATED. OPERABLE 5ECTION5 OF WINDOWS SHALL NOT PERMIT OPENINGS THAT ALLOW PASSAGE OF A 4 INCH DIAMETER SPHERE WHERE SUCH OPENINGS ARE LOCATED WITHIN 24 INCHES OF THE FINISHED FLOOR PER F.B.C. 2010 RESIDENTIAL CODE R612.2 WINDOW FALL PREVENTION DEVICES AND WINDOW GUARDS, WHERE PROVIDED, SHALL COMPLY WITH THE REQUIREMENT5 OF A5TM F 2090 PER F.B.C. 2010 RESIDENTIAL CODE 8612.3 40'-0" (VERIFY W/ TRUSS MANUF.) SECTION AA 5CALE: 1/8" = 14 12 a 6 12 12 �6 6� /SHINGLE ROOF 12 a 6 12 T.O.M. _ T.O.M. Z' d- TEXTUREp FINISH 7 c0 �' cA ❑ FINISH FLOOR LINE _ _ _ _ _ _ _ _ _ _ FIN15H FLOOR LINE GRADE LINE LEFT ELEVATION (A55UMED) SCALE: 1/8" - I'-0" 12 12 E6 6� /SHINGLE ROOF T.O.M. _ T.o.M. _ TEXTURED FINISH L] FIN15H FLOOR LINE x ro DAVIS BEWS DESIGN GROVP i U T No —,=�q EST. 1994 F�- J _0 N I I II II 11 �w N I I L j C4LaM • II ro_ 0 0:9L.0 L._j Oroc0 I I II m �s_� II N 0 I � l� r; I I II KNEE II II II II • ALL i i T SADDLE i `fie II I I II I i I I II I I II I I j \e � II I II I I I II I II J, rJ I I j I I '- I I' 0" TYP. OVERHANG AT HIP ROOF PLAN. 5CALE: 1/8" : I'-0" REFER TO COVER SHEET GENERAL NOTES FOR ROOFING UNDERLAYMENT REQUIREMENTS FOR ROOF PITCHE5 LE65 THAN 4:12 11/2" THICK SAND FIN15H KEYSTONE - (IF APPLICABLE) RA15ED SAND FINISH TEXTURED BANDING 3/4" THICK TYP. CROSS-SECTION OF RAISED TEXTURED FINISH BANDING AND / OR SAND FINISH KEYSTONE 5CALE: 3" = 1'-0" GLEAR OPENING HEIGHTS IN DWELLING UNIT5, WHERE THE OPENING OF AN OPERABLE WINDOW IS LOCATED MORE THAN 12 INCHES ABOVE THE FINISHED GRADE OR SURFACE BELOW, THE LOWEST PART OF THE CLEAR OPENING OF THE WINDOW SHALL BE A MINIMUM OF 24 INCHES ABOVE THE FINI5HED FLOOR OF THE ROOM IN WHICH THE WINDOW IS LOCATED. OPERABLE 5ECTION5 OF WINDOWS SHALL NOT PERMIT OPENINGS THAT ALLOW PASSAGE OF A 4 INCH DIAMETER SPHERE WHERE SUCH OPENINGS ARE LOCATED WITHIN 24 INCHES OF THE FINISHED FLOOR PER F.B.C. 2010 RESIDENTIAL CODE R612.2 WINDOW FALL PREVENTION DEVICES AND WINDOW GUARDS, WHERE PROVIDED, SHALL COMPLY WITH THE REQUIREMENT5 OF A5TM F 2090 PER F.B.C. 2010 RESIDENTIAL CODE 8612.3 40'-0" (VERIFY W/ TRUSS MANUF.) SECTION AA 5CALE: 1/8" = 14 12 a 6 12 12 �6 6� /SHINGLE ROOF 12 a 6 12 T.O.M. _ T.O.M. Z' d- TEXTUREp FINISH 7 c0 �' cA ❑ FINISH FLOOR LINE _ _ _ _ _ _ _ _ _ _ FIN15H FLOOR LINE GRADE LINE LEFT ELEVATION (A55UMED) SCALE: 1/8" - I'-0" 12 12 E6 6� /SHINGLE ROOF T.O.M. _ T.o.M. _ TEXTURED FINISH L] FIN15H FLOOR LINE GRADE LINE (455UMED) REAR ELEVATION SCALE: I/8" = I'-0" ZIP FIN15H FLOOR LINE 12 12 6 6 ----SHINGLE 12 ROOF 6 /HINGLE STUCCO ROOF 12 �—SHINGLE FIN15H 6 � ROOF --r T.O.M. T.OM. _ T.O.M. 2' 0" - ❑ ❑v TYP. TEXTURED Q TEXTURED cO RETURN * * FIN15H7 TEMP. FIN15H 7 AT 51DE5 FINISH FLOOR LINE FINISH FLOOR LINE GRADE LINE (ASSUMED) RIGHT ELEVATION 5CALE: 1/8" - 1'-0" x ro DAVIS BEWS DESIGN GROVP i U T No —,=�q EST. 1994 F�- GRADE LINE (455UMED) REAR ELEVATION SCALE: I/8" = I'-0" ZIP FIN15H FLOOR LINE 12 12 6 6 ----SHINGLE 12 ROOF 6 /HINGLE STUCCO ROOF 12 �—SHINGLE FIN15H 6 � ROOF --r T.O.M. T.OM. _ T.O.M. 2' 0" - ❑ ❑v TYP. TEXTURED Q TEXTURED cO RETURN * * FIN15H7 TEMP. FIN15H 7 AT 51DE5 FINISH FLOOR LINE FINISH FLOOR LINE GRADE LINE (ASSUMED) RIGHT ELEVATION 5CALE: 1/8" - 1'-0" • JOB NUMBER 26002.219• CAD FILE NAME LOT 30 TB ISSUED 09-14-16 x ro DAVIS BEWS DESIGN GROVP U T No —,=�q EST. 1994 F�- J _0 N 0 c) �w N j C4LaM • ro_ 0 0:9L.0 L._j Oroc0 m �s_� N 0 � l� r; 0 4 Z • JOB NUMBER 26002.219• CAD FILE NAME LOT 30 TB ISSUED 09-14-16 0 0 00® Z CD W C -J ti 01 9 _j ®®®®IIII►Il/ ' ca Z¢�. SW o, -,,: •/ V sig C' •• ��,��f�� •• 'I�0 �•••• R << ee 0 C) z V rvj cem 0>= 0J • 2055 0 SHEET ELEVATION "ME - MEDITERRANEAN" 3C2 DAVIS BEWS DESIGN GROVP 150 STATE STREET EAST OLDSMAR, FLORIDA 34677 813.925.1300 TEL 813. 925.1800 FAX W W W.DAVLSBEWS.COM TAMPA • nENVF_R_ —,=�q EST. 1994 F�- 0 0 00® Z CD W C -J ti 01 9 _j ®®®®IIII►Il/ ' ca Z¢�. SW o, -,,: •/ V sig C' •• ��,��f�� •• 'I�0 �•••• R << ee 0 C) z V rvj cem 0>= 0J • 2055 0 SHEET ELEVATION "ME - MEDITERRANEAN" 3C2 �^ BUILDING WRAP TO GO OVER FLASHING FLASHING TO BE FLEXIBLE SELF ADHESIVE TYPE (MIN 6" WIDE) PRECAST LINTEL TYPICAL FLASHING AT PRECAST OF MATERIAL PER :VATIONS WITH APPROVED DERLAYMENT (REFER TO VER SHEET) =-ENGINEERED ROOF JSSES AT 24" O.C. RRICANE STRAP PER OF FRAMING PLAN gk BRG. HGT. IM. DRIP EDGE . FASCIA JTED ALUM. SOFFIT :.ATH & EXT. FINISH NDOW FLASHING AS REQ'D WINDOW TRIM L. ADER TYPICAL WINDOW AND SLIDING GLASS DOOR "Z" FLASHING DETAIL FLASHING WOODEN SIDING SILL PLATE SEE NOTE #2 WALL SHEATHING NOTES: 1. FLASHING TO BE FLEXIBLE SELF-ADHESIVE TYPE (MIN. 6" WIDE) 2. REMOVE WEATHER RESISTIVE BARRIER FROM TOP OF WINDOW SILL PLATE 3. INSTALL SILL FLASHING AS SHOWN ABOVE 4. INSTALL FLASHING AROUND REMAINING WINDOW UNIT 5. WEATHER RESISTIVE BARRIER TO FORM WATER SHEDDING LAPS TYPICAL FLASHING DETAIL AT SILL. PLATE TIE-IN WITH WEATHER RESISTIVE BARRIER: 1. INTEGRATE INSTALLATION OF WEATHER RESISTIVE BARRIER WITH FLASHING TO FORM WATER SHEDDING LAPS 2. SCORE & FOLD WEATHER RESISTIVE BARRIER ABOVE HEADER TO ALLOW FOR FLASHING INSTALLATION 4. INSTALL HEAD FLASHING UNDER WEATHER RESISTIVE BARRIER 5. FOLD WEATHER RESISTIVE BARRIER BACK OVER HEAD FLASHING AND SEAL WITH WEATHER RESISTIVE BARRIER TAPE FLASHING LAPPING DOWN OVER RIM JOIST AND UP WALL BY 6" WATERPROOF MEMBRANE Mel 15/32 O.S.B. SHEATHING i DAVIS BEWS DESIGN GROVP BUILDING WRAP BEYOND PROVIDE SELF ADHERED Z - EST. 1994 0 J t, FLASHING UNDER S.G.D. AS (4) 1/4" X 4" LAG SCREWS 1 RUBBER MEMBRANE BEYOND SHOWN, PROVIDE 4" 4' BEAD OF �= 6>;JCO I' 1 SPACED EVENLY @ 24" O.C. MAX CONST. ADHESIVE TO BE APPLIED - 0� 0ca a i CAULK/SEALANT OR SOLDER UNDER THRESHOLD OF DOOR USP HTA20 STRAP 1 BETWEEN PAN FLASHING AND RETURN UP JAMB 6". USE 0 EA. JOIST L AND DECK FLASHING. LIQUID NAIL BRAND OR EQUALI i EXTERIOR FINISH WATER PROOF CAULKING 1 PER BUILDER CEMENT PLASTER 1 FINISH TYPICAL DOOR FLASHING AT BALCONY 1 � � PROVIDE SELF ADHERED wF�Ty FOLD UP WEATHER FLASHING- RESISTIVE LSCURE TEMPORARILY LAPPING DOWN OVER RIM JOIST AND UP WALL BY 6" WATERPROOF MEMBRANE Mel 1) WEATHER RESISTIVE BARRIER CORNER PATCH FLASHING NOTES: 1. FLASHING TO BE FLEXIBLE SELF-ADHESIVE TYPE (MIN. 6" WIDE) 2. INSTALL FLASHING IN ORDER AS SHOWN BY NUMBERS 3. MECHANICALLY FASTEN AS NECESSARY TYPICAL SLIDING GLASS DOOR FLASHING DETAIL FOLD UP WEATHER RESISTIVE MECHANICALLY FASTEN AS WEATHER BARRIER & TEMPORARILY SECURE NECESSARY IN CORNERS RESISTIVE THROUGH FLASHING BARRIER i i WEATHER i EXTERIOR RESISTIVE SHEATHING 1 BARRIER TAPE / SILL PLATE 2 (ASSEMBLED FLASHING 1 WINDOW) 2 i FLASHING FLASHING DO NOT FLASH OVER BOTTOM NAILING FLANGE HEAD FLASHING TIE-IN INSTRUCTIONS: NOTES: 1. CUT, FOLD UP & TEMPORARILY SECURE WEATHER RESISTIVE 1. FLASHING TO BE FLEXIBLE SELF-ADHESIVE TYPE (MIN. 6" WIDE) BARRIER ABOVE HEADER TO ALLOW FOR FLASHING 2. REMOVE WEATHER RESISTIVE BARRIER FROM TOP OF WINDOW INSTALLATION SILL PLATE 2. INSTALL HEAD FLASHING UNDER 3. INSTALL FLASHING IN ORDER AS SHOWN BY NUMBERS WEATHER RESISTIVE BARRIER 4. INSTALL FLASHING AND WEATHER RESISTIVE 3. FOLD WEATHER RESISTIVE BARRIER TO FORM WATER SHEDDING LAPS BARRIER BACK OVER HEAD FLASHING AND SEAL WITH TAPE TYPICAL WINDOW FLASHING DETAIL PROVIDE SELF ADHERED FLASHING LAPPING DOWN OVER RIM JOIST AND UP WALL BY 6" 2X4'S @ 16" O.C. BRG EXT WALL FLASHING TO EXTEND 36" 7/16" O.S.B. SHEATHING - BUILDING WRAP BEYOND FLASHING. CEMENT PLASTER STOP WATERPROOF MEMBRANE j I I 20" FLOOR TRUSS I I I I I I I I I I I SEE STRUCTURAL FOR CONNECTORS �24" FLOOR TRUSS SEESTRUCTURAL 8' CMU BLOCK TYPICAL FLASHING AT BALCONY EXTERIOR FINISH PER BUILDER PROVIDE FLASHING BOOT AT POSTS WATERPROOF MEMBRANE 7/16" O.S.B. SHEATHING FLASHING. 2X8 TRIM BOARD STUCCO "J" MOLD 7/16" O.S.B. SHEATHING TEXTURED CEMENT PLASTER FINISH WALL COVERING 2014 FBRC SECTION R703 EXTERIOR COVERING EXTERIOR WALLS SHALL PROVIDE THE BUILDING WITH A WEATHER -RESISTANT EXTERIOR WALL ENVELOPE. THE EXTERIOR WALL ENVELOPE SHALL INCLUDE FLASHING AS DESCRIBED IN SECTION R703.8. THE EXTERIOR WALL ENVELOPE SHALL BE DESIGNED AND CONSTRUCTED IN A MANNER THAT PREVENTS THE ACCUMULATION OF WATER WITHIN THE WALL ASSEMBLY BY PROVIDING A WATER -RESISTIVE BARRIER BEHIND THE EXTERIOR VENEER AS REQUIRED BY SECTION R703.2 AND A MEANS OF DRAINING TO THE EXTERIOR WALL THAT ENTERS THE ASSEMBLY. PROTECTION AGAINST CONDENSATION IN THE EXTERIOR WALL ASSEMBLY SHALL BE PROVIDED IN ACCORDANCE WITH SECTION R702.7 OF THE CODE. R703.2 WATER -RESISTIVE BARRIER 00 ONE LAYER OF APPROVED WEATHER -RESISTANT MATERIAL, FREE FROM HOLES AND BREAKS, COMPLYING WITH .. ® z ASTM D 226 FOR TYPE 1 APPROVED WATER -RESISTIVE BARRIER SHALL BE APPLIED OVER STUDS OR SHEATHING OF, ALL EXTERIOR WALLS. SUCH MATERIAL SHALL BE APPLIED HORIZONTALLY, WITH THE UPPER LAYER LAPPED OVER co � -r THE LOWER LAYER NOT LESS THAN 2 INCHES (51 MM). WHERE JOINTS OCCUR, MATERIAL SHALL BE LAPPED NOT LESSJl�) THAN 6 INCHES (152 MM). THE APPROVED MATERIAL SHALL BE CONTINUOUS TO THE TOP OF WALLS AND ®®i,® TERMINATED AT PENETRATIONS AND BUILDING APPENDAGES IN A MANNER TO MEET THE REQUIREMENTS OF THE �` 0,°��; •®•°°•° `'��� EXTERIOR WALL ENVELOPE AS DESCRIBED IN SECTION R703.1. ujj 52 O :`LL1 R703.8 FLASHING a z co �-� APPROVED CORROSION -RESISTANT FLASHING SHALL BE APPLIED SHINGLE -FASHION IN A MANNER TO PREVENT•���`�: ENTRY OF WATER INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE BUILDING STRUCTURAL FRAMING °°°••.•••° `1�` COMPONENTS. SELF -ADHERED MEMBRANES USED AS FLASHING SHALL COMPLY WITH AAMA 711. ALL EXTERIOR ,1111111 ;, FENESTRATION PRODUCTS SHALL BE SEALED AT THE JUNCTURE WITH THE BUILDING WALL WITH A SEALANT; COMPLYING WITH AAMA 800 OR ASTM C 920 CLASS 25 GRADE NS OR GREATER FOR PROPER JOINT EXPANSION AND CONTRACTION, ASTM C 1281, AAMA 812, OR OTHER APPROVED STANDARD AS APPROPRIATE FOR THE TYPE OF SEALANT. THE FLASHING SHALL EXTEND TO THE SURFACE OF THE EXTERIOR WALL FINISH. APPROVED n CORROSION -RESISTANT FLASHINGS SHALL BE INSTALLED AT ALL OF THE FOLLOWING LOCATIONS:a 1. EXTERIOR WINDOW AND DOOR OPENINGS. FLASHING AT EXTERIOR WINDOW AND DOOR OPENINGS SHALL EXTEND r 0 GS L A S TO THE SURFACE OF THE EXTERIOR WALL FINISH OR TO THE WATER -RESISTIVE BARRIER FOR SUBSEQUENT DRAINAGE. FLASHING AT EXTERIOR WINDOW AND DOOR OPENINGS SHALL BE INSTALLED IN ACCORDANCE WITH ONE OR MORE OF THE FOLLOWING OR OTHER APPROVED METHOD: 1.1 THE FENESTRATION MANUFACTURER'S INSTALLATION AND FLASHING INSTRUCTIONS, OR FOR APPLICATIONS NOT ADDRESSED IN THE FENESTRATION MANUFACTURER'S, IN ACCORDANCE WITH THE FLASHING MANUFACTURER'S INSTRUCTIONS. WHERE FLASHING INSTRUCTIONS ARE NOT PROVIDED, PAN FLASHING SHALL BE INSTALLED AT THE SILL OF EXTERIOR WINDOWS AND DOOR OPENINGS. PAN FLASHING SHALL BE SEALED OR SLOPED IN SUCH A MANNER AS TO DIRECT WATER TO THE SURFACE OF THE EXTERIOR WALL FINISH OR TO THE WATER -RESISTIVE BARRIER FOR SUBSEQUENT DRAINAGE. OPENINGS USING PAN FLASHING SHALL ALSO INCORPORATE FLASHING OR PROTECTION AT THE HEAD AND SIDES. 1.2 IN ACCORDANCE WITH THE FLASHING DESIGN OR METHOD OF A REGISTERED DESIGN PROFESSIONAL. M 1.3 IN ACCORDANCE WITH OTHER APPROVED METHODS. 0' 1.4 IN ACCORDANCE WITH FMA/HAMA 100, FMA/AAMA 200, FMA/WDMA 250„ OR FMA/AAMA/WDMA 300. 2. AT THE INTERSECTION OF CHIMNEYS OR OTHER MASONRY CONSTRUCTION WITH FRAME OR STUCCO WALLS WITH >m PROJECTING LIPS ON BOTH SIDES UNDER STUCCO COPINGS. 3. UNDER AND AT THE ENDS OF MASONRY, WOOD OR METAL COPINGS AND SILLS. 4. CONTINUOUSLY ABOVE ALL PROJECTING WOOD TRIM. • 5. WHERE EXTERIOR PORCHES, DECKS OR STAIRS ATTACH TO A WALL OR FLOOR ASSEMBLY OF WOOD -FRAME • CONSTRUCTION. 2055 6. AT WALL AND ROOF INTERSECTIONS. • TI TLE • 7. AT BUILT-IN GUTTERS. FLASHING DETAILS ° • x P i DAVIS BEWS DESIGN GROVP Lo Cir 0 2X12 #2 SYP CONT LEDGER W/ - EST. 1994 0 J t, (4) 1/4" X 4" LAG SCREWS - / d �= 6>;JCO SPACED EVENLY @ 24" O.C. MAX � L �0• - 0� 0ca a (EA. FLOOR TRUSS) � -''O0 o@Co USP HTA20 STRAP cm .c ; N o . cD 0 EA. JOIST L 41 Z520 TEXTURED CEMENT PLASTER FINISH TYPICAL DOOR FLASHING AT BALCONY EXTERIOR SHEATHING wF�Ty FOLD UP WEATHER RESISTIVE LSCURE TEMPORARILY 1) WEATHER RESISTIVE BARRIER CORNER PATCH FLASHING NOTES: 1. FLASHING TO BE FLEXIBLE SELF-ADHESIVE TYPE (MIN. 6" WIDE) 2. INSTALL FLASHING IN ORDER AS SHOWN BY NUMBERS 3. MECHANICALLY FASTEN AS NECESSARY TYPICAL SLIDING GLASS DOOR FLASHING DETAIL FOLD UP WEATHER RESISTIVE MECHANICALLY FASTEN AS WEATHER BARRIER & TEMPORARILY SECURE NECESSARY IN CORNERS RESISTIVE THROUGH FLASHING BARRIER i i WEATHER i EXTERIOR RESISTIVE SHEATHING 1 BARRIER TAPE / SILL PLATE 2 (ASSEMBLED FLASHING 1 WINDOW) 2 i FLASHING FLASHING DO NOT FLASH OVER BOTTOM NAILING FLANGE HEAD FLASHING TIE-IN INSTRUCTIONS: NOTES: 1. CUT, FOLD UP & TEMPORARILY SECURE WEATHER RESISTIVE 1. FLASHING TO BE FLEXIBLE SELF-ADHESIVE TYPE (MIN. 6" WIDE) BARRIER ABOVE HEADER TO ALLOW FOR FLASHING 2. REMOVE WEATHER RESISTIVE BARRIER FROM TOP OF WINDOW INSTALLATION SILL PLATE 2. INSTALL HEAD FLASHING UNDER 3. INSTALL FLASHING IN ORDER AS SHOWN BY NUMBERS WEATHER RESISTIVE BARRIER 4. INSTALL FLASHING AND WEATHER RESISTIVE 3. FOLD WEATHER RESISTIVE BARRIER TO FORM WATER SHEDDING LAPS BARRIER BACK OVER HEAD FLASHING AND SEAL WITH TAPE TYPICAL WINDOW FLASHING DETAIL PROVIDE SELF ADHERED FLASHING LAPPING DOWN OVER RIM JOIST AND UP WALL BY 6" 2X4'S @ 16" O.C. BRG EXT WALL FLASHING TO EXTEND 36" 7/16" O.S.B. SHEATHING - BUILDING WRAP BEYOND FLASHING. CEMENT PLASTER STOP WATERPROOF MEMBRANE j I I 20" FLOOR TRUSS I I I I I I I I I I I SEE STRUCTURAL FOR CONNECTORS �24" FLOOR TRUSS SEESTRUCTURAL 8' CMU BLOCK TYPICAL FLASHING AT BALCONY EXTERIOR FINISH PER BUILDER PROVIDE FLASHING BOOT AT POSTS WATERPROOF MEMBRANE 7/16" O.S.B. SHEATHING FLASHING. 2X8 TRIM BOARD STUCCO "J" MOLD 7/16" O.S.B. SHEATHING TEXTURED CEMENT PLASTER FINISH WALL COVERING 2014 FBRC SECTION R703 EXTERIOR COVERING EXTERIOR WALLS SHALL PROVIDE THE BUILDING WITH A WEATHER -RESISTANT EXTERIOR WALL ENVELOPE. THE EXTERIOR WALL ENVELOPE SHALL INCLUDE FLASHING AS DESCRIBED IN SECTION R703.8. THE EXTERIOR WALL ENVELOPE SHALL BE DESIGNED AND CONSTRUCTED IN A MANNER THAT PREVENTS THE ACCUMULATION OF WATER WITHIN THE WALL ASSEMBLY BY PROVIDING A WATER -RESISTIVE BARRIER BEHIND THE EXTERIOR VENEER AS REQUIRED BY SECTION R703.2 AND A MEANS OF DRAINING TO THE EXTERIOR WALL THAT ENTERS THE ASSEMBLY. PROTECTION AGAINST CONDENSATION IN THE EXTERIOR WALL ASSEMBLY SHALL BE PROVIDED IN ACCORDANCE WITH SECTION R702.7 OF THE CODE. R703.2 WATER -RESISTIVE BARRIER 00 ONE LAYER OF APPROVED WEATHER -RESISTANT MATERIAL, FREE FROM HOLES AND BREAKS, COMPLYING WITH .. ® z ASTM D 226 FOR TYPE 1 APPROVED WATER -RESISTIVE BARRIER SHALL BE APPLIED OVER STUDS OR SHEATHING OF, ALL EXTERIOR WALLS. SUCH MATERIAL SHALL BE APPLIED HORIZONTALLY, WITH THE UPPER LAYER LAPPED OVER co � -r THE LOWER LAYER NOT LESS THAN 2 INCHES (51 MM). WHERE JOINTS OCCUR, MATERIAL SHALL BE LAPPED NOT LESSJl�) THAN 6 INCHES (152 MM). THE APPROVED MATERIAL SHALL BE CONTINUOUS TO THE TOP OF WALLS AND ®®i,® TERMINATED AT PENETRATIONS AND BUILDING APPENDAGES IN A MANNER TO MEET THE REQUIREMENTS OF THE �` 0,°��; •®•°°•° `'��� EXTERIOR WALL ENVELOPE AS DESCRIBED IN SECTION R703.1. ujj 52 O :`LL1 R703.8 FLASHING a z co �-� APPROVED CORROSION -RESISTANT FLASHING SHALL BE APPLIED SHINGLE -FASHION IN A MANNER TO PREVENT•���`�: ENTRY OF WATER INTO THE WALL CAVITY OR PENETRATION OF WATER TO THE BUILDING STRUCTURAL FRAMING °°°••.•••° `1�` COMPONENTS. SELF -ADHERED MEMBRANES USED AS FLASHING SHALL COMPLY WITH AAMA 711. ALL EXTERIOR ,1111111 ;, FENESTRATION PRODUCTS SHALL BE SEALED AT THE JUNCTURE WITH THE BUILDING WALL WITH A SEALANT; COMPLYING WITH AAMA 800 OR ASTM C 920 CLASS 25 GRADE NS OR GREATER FOR PROPER JOINT EXPANSION AND CONTRACTION, ASTM C 1281, AAMA 812, OR OTHER APPROVED STANDARD AS APPROPRIATE FOR THE TYPE OF SEALANT. THE FLASHING SHALL EXTEND TO THE SURFACE OF THE EXTERIOR WALL FINISH. APPROVED n CORROSION -RESISTANT FLASHINGS SHALL BE INSTALLED AT ALL OF THE FOLLOWING LOCATIONS:a 1. EXTERIOR WINDOW AND DOOR OPENINGS. FLASHING AT EXTERIOR WINDOW AND DOOR OPENINGS SHALL EXTEND r 0 GS L A S TO THE SURFACE OF THE EXTERIOR WALL FINISH OR TO THE WATER -RESISTIVE BARRIER FOR SUBSEQUENT DRAINAGE. FLASHING AT EXTERIOR WINDOW AND DOOR OPENINGS SHALL BE INSTALLED IN ACCORDANCE WITH ONE OR MORE OF THE FOLLOWING OR OTHER APPROVED METHOD: 1.1 THE FENESTRATION MANUFACTURER'S INSTALLATION AND FLASHING INSTRUCTIONS, OR FOR APPLICATIONS NOT ADDRESSED IN THE FENESTRATION MANUFACTURER'S, IN ACCORDANCE WITH THE FLASHING MANUFACTURER'S INSTRUCTIONS. WHERE FLASHING INSTRUCTIONS ARE NOT PROVIDED, PAN FLASHING SHALL BE INSTALLED AT THE SILL OF EXTERIOR WINDOWS AND DOOR OPENINGS. PAN FLASHING SHALL BE SEALED OR SLOPED IN SUCH A MANNER AS TO DIRECT WATER TO THE SURFACE OF THE EXTERIOR WALL FINISH OR TO THE WATER -RESISTIVE BARRIER FOR SUBSEQUENT DRAINAGE. OPENINGS USING PAN FLASHING SHALL ALSO INCORPORATE FLASHING OR PROTECTION AT THE HEAD AND SIDES. 1.2 IN ACCORDANCE WITH THE FLASHING DESIGN OR METHOD OF A REGISTERED DESIGN PROFESSIONAL. M 1.3 IN ACCORDANCE WITH OTHER APPROVED METHODS. 0' 1.4 IN ACCORDANCE WITH FMA/HAMA 100, FMA/AAMA 200, FMA/WDMA 250„ OR FMA/AAMA/WDMA 300. 2. AT THE INTERSECTION OF CHIMNEYS OR OTHER MASONRY CONSTRUCTION WITH FRAME OR STUCCO WALLS WITH >m PROJECTING LIPS ON BOTH SIDES UNDER STUCCO COPINGS. 3. UNDER AND AT THE ENDS OF MASONRY, WOOD OR METAL COPINGS AND SILLS. 4. CONTINUOUSLY ABOVE ALL PROJECTING WOOD TRIM. • 5. WHERE EXTERIOR PORCHES, DECKS OR STAIRS ATTACH TO A WALL OR FLOOR ASSEMBLY OF WOOD -FRAME • CONSTRUCTION. 2055 6. AT WALL AND ROOF INTERSECTIONS. • TI TLE • 7. AT BUILT-IN GUTTERS. FLASHING DETAILS ° ° J08 NUMBER 26002.219° CAD FILE NAME LOT 30 TB ISSUED 09-14-16 REVISED • x P i DAVIS BEWS DESIGN GROVP Lo Cir 0 TAMPA • DENVER.. - EST. 1994 0 J t, N � - / d �= 6>;JCO � L �0• 0� 0ca a -''O0 o@Co 3�E� L cm .c ; N o . cD 0 41 Z520 ° J08 NUMBER 26002.219° CAD FILE NAME LOT 30 TB ISSUED 09-14-16 REVISED FLASHING DETAILS N.T.5. • SHEET • i DAVIS BEWS DESIGN GROVP 150 STATE STREET FAST OLDSMW FLORIDA 39677 813.925.1300 TEL 813. 925.1800 FAX W W W.DAVISBEWS.COM TAMPA • DENVER.. - EST. 1994 FLASHING DETAILS N.T.5. • SHEET • 5HEATHING TEXTURE FIN15H COAT BROWN COAT 5CRATCH COAT 5ELF-FURRING LATH TWO LAYER5 WRB WEEP 5CREED TERMINATE 5ELF ADHE5IVE FLA5HING AT LOWER N05E OF M.WU1.5, 5ELF ADHE5IVE FLA5HING M45ONRY BLOCK WALL WEEP SCREED AT MID -WALL MASONRY TO WOOD DETAIL EXTERIOR SHEATHING REFER TO TECHNICAL / LETTER ON CHEMICAL / COMPATIBILITY SELF -ADHERED FLASHING WEATHER RESISTIVE A CONT. GALV. "L" - WINDOW UNIT 150 STATE STREET EAST OLDSM I , FLORIDA 34677 813. 925. 1300 TEL 813. 925.1800 FAX W W W.DAVISBEWS.COM TAMPA • DENVER BARRIER r? _ / DOOR ROUGH OPENING \ SPECIFICATIONS OVER ROOF ROOF MATERIAL PER SLOPE SHINGLES W/ TAR ELEVATIONS WITH APPROVED NOTE: THIS DETAIL IS REQUIRED 0.3 inin WOOD FRAME CONSTR. AT ALL VERTICAL WALL INTERSECTIONS COVER SHEET) (0.6 cm :3 300 .5 cm) SELF -ADHERED FLASHING - 3/4"-1" BEAD OF CONSTR. PRE-ENGINEERED ROOF BY LAPPING DOWN - ADHESIVE TO BE APPLIED UNDER SELF -ADHERED FLASHING OVER RIM JOIST AND UPTHRESHOLD OF DOOR AND RETURN �' WALL BY 6 IN. :J/- UP JAMB 6". USE LIQUID NAIL BRAND OR EQUAL WEATHER PROOF CAULKING EXTERIOR 0) CEMT. FIN. SELF -ADHERED FLASHING BUILDING PAPER SEAL TOPS OF JOISTS WIRE LATH 1 UNDER DECKING SUBFLOOR (SEE DETAIL WP07) RIM JOIST V SELF -ADHERED FLASHING SELF -ADHERED FLASHING EXTERIOR DOOR WITH DECK - SECTION A CEMT. FINISH SILL/ POTSHELF/ CHIMNEY SHOULDER EXTERIOR MECHANICALLY FASTEN IF RUBBERIZED RUBBERIZED ASPHALT - 3/4" -1" BEAD OF CONSTR. SHEATHING SELF-ADHEREDINSTALL NEEDED IN CORNERS ,ADHESIVE ADHESIVE TO BE APPLIED UNDER FLASHING JAMB& HEAD THROUGH SELF -ADHERED ASPHALT ADHESIVE THRESHOLD OF DOOR AND RETURN FLASHING, SEE FLASHING SELF -ADHERED FLASHING ` UP JAMB 6". USE LIQUID NAIL BRAND FLANGED WINDOW OR EQUAL WEATHER PROOF CAULKING r SECTION -A (SEE DETAIL WP02) SELF -ADHERED FLASHING. / NAILING FLANGE SELF -ADHERED — FLASHING DO NOT FLASH OVER i / SEAL TOPS OF JOISTS BOTTOM NAILING UNDER DECKING FLANGE (SEE DETAIL WP07) SELF -ADHERED FLASHING HALF ROUND WINDOW MAI I LIUMATUlKit' SCORED -- RELEASE PAPER SELF -ADHERED FLASHING, (BEFORE FOLDING, SCORE EXTEND A MINIMUM 6" RELEASE PAPER TO EXPOSE VERTICALLY FROM ADHESIVE AS SHOWN) BOTTOM OF THRESHOLD O i O, "INSTALL SELF -ADHERED FLASHING IN ORDER AS SHOWN BY NUMBERS ** INSTALL FLASHING AND WEATHER RESISTIVE BARRIER TO FORM WATER SHEDDING LAPS SELF -ADHERED FLASHING SELF -ADHERED FLASHING EXTERIOR DOOR WITH DECK INSIDE CORNER ASPHALT SEALANT: wry 1. v. EXTEND MIN. OF 6" j FLASHINGNG PER TEXTURED, PAIN'''"^ OUTSIDE OF FLASHING j MANUFACTURES EXTER. WALL FIP SPECIFICATIONS ROOF CRICKET: / MIN: 3:12 SLOPE CRICKET AS (REQUIRED AT PLASTER STOP SPECIFIED ALL LEVEL VALLEY VERTICAL WALL BEAUTY STRIF BY PLAN LOCATIONS) AT ENTRY SHINGLE OVE FLASHING W/ DIVERTER FLASHING MY/ys DRIP EDGE FASCIA FIGURE 1: FLASHING INSTALLATION TEXTURED, PAINTED EXTERIOR WALL FINISH HOLD EXTERIOR °`°'`rr�'°. FINISH 2" ABOVE r °y ROOF FFLASHING CAULKING FIGURE 2: WALL FINISH ASPHALT SEALANT: EXTEND MIN. 6" ABOVE FLASHING 6 TO 12" PER PLAN 6"HIGH SPECS. DIVERTER FLASHING e GALV. 'L' FLASHING TYPICAL. ROOFING FELT DRIP EDGE FASCIA FIGURE 3: CORNER DETAIL ASPHALT BASED SEALANT APPLIED BEHIND FLASHING AND EXTENDING A MINIMUM OF 6" ABOVE VERTICAL RISE OF FLASHING AT KNEEWALL SEALANT HIND DETAILS TRUSSES AT 24" O.C. BEAUTY STRIP ROOF SHINGLE OVER FLASHING W/ TAR FLASHING INSTALLATION /CONT. GALV. "L" WHERE ROOF MEETS VERTICAL WALL / FLASHING PER MANUFACTURES i' SPECIFICATIONS OVER ROOF SHINGLES W/ TAR — SHINGLE PER �E CONTRACT R�0 RpoF METAL DRIP EDGE TO q� rsti �.. BE UNDER T,S F9 /� UNDERLAYMENT AT Tq�✓ C+ROC�s ROOF EAVES — O O / '. � 9 �q< \ RpoF TYPICAL ROOF TO �OA- ooRoo �5�� WALL FLASHING DETAIL �gTti/0 5�N q�N ppuRs� 3R° GpV�pp�Rg� \ gE 9 1s� GO - RAKE METAL DRIP EDGE TO BE OVER EAVES LINE VALLEY BY CENTERING 36" WIDE UNDERLAYMENT AT --14" _ �\ CERTAINTEED WINTERGUARD GABLE ENDS FIRST STARTER SHINGLE WATERPROOFING SHINGLE 7 %- UNDERLAYMENT OR EQUIVALENT EXTEND THE SHINGLES OVER DIRECTLY TO DECK. THE RAKE AND EAVES ABOUT SAVE 7" PIECES 1/2" IF DRIP EDGE IS USED, OR j TO USE IN 5TH ABOUT 3/4" IF NO DRIP EDGE IS COURSE USED. EMBED EACH SHINGLE IN A 2" DO NOT NAIL WITHIN 6" OF ---_f- WIDE STRIP OF ASPHALT VALLEY CENTERLINE RAGING CEMENT. ,., CUT 2" DIAGONALLY OFF UPPER CORNER OF TRIMMED SHINGLE i . - CUT SHINGLES 2" BACK FROM VALLEY CENTERLINE FIGURE 4: VALLEY DETAIL CEMENT PLASTER IN — ACCORDANCE WITH ASTMC926 OVER WOOD 2ND FLOOR / CEMENT PLASTER OVER BLOCK 1 ST FLOOR NOTE: \\ THE BUILDING PAPER AND METAL LATH MUST BE INSTALLED OVER THE TOP 7/8" CEMENT PLASTER IN ACCORDANCE WITH ASTMC926 APPROVED WEATHER -RESISTANT MATERIAL W/ METAL LATH IN ACCORDANCE WITH ASTMC1063 BUILDING PAPER 7/16" O.S.B. SHEATHING METAL FLASHING 31/2" UNPERFORATED FLANGE 7/8" WEEP SCREED MAINTAIN BOTTOM OF WEEP SCREED 11/2" TO 2" ABOVE ROOF SHEATHING SLAB OPTIONAL DETAIL WEEP SCREED DETAIL SCALE: NOT TO SCALE )UBLE JOIST 3 2 AM BELOW 7/8" CEMENT PLASTER IN ACCORDANCE WITH ASTMC926 APPROVED WEATHER -RESISTANT MATERIAL W/ METAL LATH IN ACCORDANCE. WITH ASTMC1063 BUILDING PAPER 7/16" O.S.B. SHEATHING KEEP TOP EDGE OF WEEP SCREED 2" BELOW TOP OF BLOCK VULCUM CAULK BOTTOM JOINT ONLY METAL FLASHING 3-1/2" UNPERFORATED FLANGE 7/8" WEEP SCREED 1/2" CEMENTITIOUS DECORATIVE FINISH ALL INSIDE AND OUTSIDE CORNER WILL NEED TO BE MITER CUTAND CAULKED ALL BUTT JOINTS NEED TO BE EMBEDDEDIN SEALANT USING VULCUM CAULK FOR ALL — 1/2" CEMENT PLASTER FINISH 2 1/2" PERFORATED FLANGE 1/2" WEEP SCREED INSTALL BOTTOM EDGE OF WEEP SCREED 1" BELOW FINISH FLOOR SELF -ADHERED - FLASHING PATCH SELF -ADHERED FLASHING THESE DETAILS ARE GENERIC AND MEANT TO SHOW GENERAL FLASHING AND FLASHING DETAILS WATERPROOFING METHODS TO BE USED. N.T.5. CONT. GALV. "L" - x m w 150 STATE STREET EAST OLDSM I , FLORIDA 34677 813. 925. 1300 TEL 813. 925.1800 FAX W W W.DAVISBEWS.COM TAMPA • DENVER FLASHING PER r? _ / MANUFACTURES \ SPECIFICATIONS OVER ROOF ROOF MATERIAL PER SHINGLES W/ TAR ELEVATIONS WITH APPROVED NOTE: THIS DETAIL IS REQUIRED UNDERLAYMENT (REFER TO AT ALL VERTICAL WALL INTERSECTIONS COVER SHEET) WITH ROOF VALLEYS & ROOF CRICKETS. PRE-ENGINEERED ROOF ASPHALT BASED SEALANT APPLIED BEHIND FLASHING AND EXTENDING A MINIMUM OF 6" ABOVE VERTICAL RISE OF FLASHING AT KNEEWALL SEALANT HIND DETAILS TRUSSES AT 24" O.C. BEAUTY STRIP ROOF SHINGLE OVER FLASHING W/ TAR FLASHING INSTALLATION /CONT. GALV. "L" WHERE ROOF MEETS VERTICAL WALL / FLASHING PER MANUFACTURES i' SPECIFICATIONS OVER ROOF SHINGLES W/ TAR — SHINGLE PER �E CONTRACT R�0 RpoF METAL DRIP EDGE TO q� rsti �.. BE UNDER T,S F9 /� UNDERLAYMENT AT Tq�✓ C+ROC�s ROOF EAVES — O O / '. � 9 �q< \ RpoF TYPICAL ROOF TO �OA- ooRoo �5�� WALL FLASHING DETAIL �gTti/0 5�N q�N ppuRs� 3R° GpV�pp�Rg� \ gE 9 1s� GO - RAKE METAL DRIP EDGE TO BE OVER EAVES LINE VALLEY BY CENTERING 36" WIDE UNDERLAYMENT AT --14" _ �\ CERTAINTEED WINTERGUARD GABLE ENDS FIRST STARTER SHINGLE WATERPROOFING SHINGLE 7 %- UNDERLAYMENT OR EQUIVALENT EXTEND THE SHINGLES OVER DIRECTLY TO DECK. THE RAKE AND EAVES ABOUT SAVE 7" PIECES 1/2" IF DRIP EDGE IS USED, OR j TO USE IN 5TH ABOUT 3/4" IF NO DRIP EDGE IS COURSE USED. EMBED EACH SHINGLE IN A 2" DO NOT NAIL WITHIN 6" OF ---_f- WIDE STRIP OF ASPHALT VALLEY CENTERLINE RAGING CEMENT. ,., CUT 2" DIAGONALLY OFF UPPER CORNER OF TRIMMED SHINGLE i . - CUT SHINGLES 2" BACK FROM VALLEY CENTERLINE FIGURE 4: VALLEY DETAIL CEMENT PLASTER IN — ACCORDANCE WITH ASTMC926 OVER WOOD 2ND FLOOR / CEMENT PLASTER OVER BLOCK 1 ST FLOOR NOTE: \\ THE BUILDING PAPER AND METAL LATH MUST BE INSTALLED OVER THE TOP 7/8" CEMENT PLASTER IN ACCORDANCE WITH ASTMC926 APPROVED WEATHER -RESISTANT MATERIAL W/ METAL LATH IN ACCORDANCE WITH ASTMC1063 BUILDING PAPER 7/16" O.S.B. SHEATHING METAL FLASHING 31/2" UNPERFORATED FLANGE 7/8" WEEP SCREED MAINTAIN BOTTOM OF WEEP SCREED 11/2" TO 2" ABOVE ROOF SHEATHING SLAB OPTIONAL DETAIL WEEP SCREED DETAIL SCALE: NOT TO SCALE )UBLE JOIST 3 2 AM BELOW 7/8" CEMENT PLASTER IN ACCORDANCE WITH ASTMC926 APPROVED WEATHER -RESISTANT MATERIAL W/ METAL LATH IN ACCORDANCE. WITH ASTMC1063 BUILDING PAPER 7/16" O.S.B. SHEATHING KEEP TOP EDGE OF WEEP SCREED 2" BELOW TOP OF BLOCK VULCUM CAULK BOTTOM JOINT ONLY METAL FLASHING 3-1/2" UNPERFORATED FLANGE 7/8" WEEP SCREED 1/2" CEMENTITIOUS DECORATIVE FINISH ALL INSIDE AND OUTSIDE CORNER WILL NEED TO BE MITER CUTAND CAULKED ALL BUTT JOINTS NEED TO BE EMBEDDEDIN SEALANT USING VULCUM CAULK FOR ALL — 1/2" CEMENT PLASTER FINISH 2 1/2" PERFORATED FLANGE 1/2" WEEP SCREED INSTALL BOTTOM EDGE OF WEEP SCREED 1" BELOW FINISH FLOOR SELF -ADHERED - FLASHING PATCH SELF -ADHERED FLASHING THESE DETAILS ARE GENERIC AND MEANT TO SHOW GENERAL FLASHING AND FLASHING DETAILS WATERPROOFING METHODS TO BE USED. N.T.5. JOB NUMBER 26002.219 CAD FILE NAME LOT 30 TB ISSUED 09-14-16 REVISED x m w 150 STATE STREET EAST OLDSM I , FLORIDA 34677 813. 925. 1300 TEL 813. 925.1800 FAX W W W.DAVISBEWS.COM TAMPA • DENVER 6 L L 00 E6' J r0 N' do r ON0rn m N d ? ;JM °�L'• C oro Co 0 +_+ N 6. o tp `o�n�n 2-�° JOB NUMBER 26002.219 CAD FILE NAME LOT 30 TB ISSUED 09-14-16 REVISED uj V) rco00 cue CD® ®z OL Lu r_ Lr)®�IIAI1911 / cn m J u - 16Y, b ®`, m �l aCoQ- ., 14 Ie ®a 1h�111 z CD 0 M 1 2055 • TITLE • FLASHING DETAILS • SHEET • wwr. 3 DAVIS BEWS DESIGN GROVP 150 STATE STREET EAST OLDSM I , FLORIDA 34677 813. 925. 1300 TEL 813. 925.1800 FAX W W W.DAVISBEWS.COM TAMPA • DENVER EST. 1994 uj V) rco00 cue CD® ®z OL Lu r_ Lr)®�IIAI1911 / cn m J u - 16Y, b ®`, m �l aCoQ- ., 14 Ie ®a 1h�111 z CD 0 M 1 2055 • TITLE • FLASHING DETAILS • SHEET • MICROWAVE OUTLET +14" OPT. OPT, COACH COACH LIGHTING LIGHTING ELECTRICAL PLAN STANTON (TM) ELEVATION "ME - W.P. Gpl ELEC. METER W.P. G.F.I. MEDITERRANEAN if 4/0 ALU. CABLE ELECTfRICAL <E�- NOTES - COMBO - SQUARE D =L 09-14-16 REVISED 014 AND 012 COPPER TO 1. PROVIDE AND INSTALL GROUND FAULT CIRCUIT-INTER;WPTER6 (GRI.) AS INDICATE[) INSIDE LIGHTS AND OUTLETS DUPLEX CONVENIENCE OUTLET PANE $10 COPPER TO EXHAUST FAN ON PLANS OR AS ITEM NO, 4 AND 513ELOW INDICATES. UNDERGROUND DUPLEX OUTLET ABOVE CONTER SERVICE BY EXHAUST FAN/LIGHT COMBINATION POWER COMPANY Kkpl WEATHERPROOF DUPLEX OUTLET AL50 SERVICE TO BE BONDED ELECTRIC DOOR OPERATOR (OPTIONAL) 2. UNLESS OTHERWISE INDICATED, INSTALL SWITCHES AND RECEPTACLES AT THE ELECTRICAL RISER DIAGRAM NOTE: - FOLLOWING HEIGHTS ABOVE FIN15HEID FLOOR: SHALL GROUND FAULT INTERRUPTER DUPLEX OUTLET ELEC. CODE, LOCAL CODES, AND THE LOCAL POWER COMPANY. CHIMES (OPTIONAL) SWITCHES .... 4211 HALF -SWITCHED DUPLEX OUTLET Ei PU51413UTTON SWITCH (OPTIONAL) OUTLETS .... 14" LLA O�) SPECIAL PURPOSE OUTLET CARBON MONOXIDE DETECTOR TELEPHONE ... 1411 (UNLESS A5v COUNTERTOP) to TELEV1510K. 1411 DUPLEX OUTLET IN FLOOR 0 z SMOKE DETECTOR le 220 VOLT OUTLET SMOKE / CARBON MONO. COMBO DETECTOR 3. ALL SMOKE DETECTORS SHALL BE WARDWIRED INTO AN ELECTRICAL POWER $ WALL 6WITCW TELEPHONE (OPTIONAL) SOURCE AND SHALL BE EQUIPPED WITH A MONITORED BATTERY BACKUP. PROVIDE AND INSTALL LOCALLY CERTIFIED SMOKE DETECTORS. 13 THREE-WAY SWITCH M TELEV15ION (OPTIONAL) 14 FOUR-WAY SWITCH THEW06TAT 4. ALL 15A AND 20A RECEPTACLES IN SLEEPING ROOMS, FAMILY ROOMS, DINING ID DIMMER SWITCH ELECTRIC METER ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, SUNROOM5, RECREATION ROOMS, CLOSETS, HALLWAYS, AND 51MILAR AREAS WILL REQUIRE A COMBINATION TYPE A.F.C.I. CEILING MOUNTED INCANDESCENT LIGHT FIXTURE ELECTRIC PANEL DEVICE AND TAMPER -PROOF RECEPTACLES PER N.E.C. 2011406.12 AND 406,13 WALL MOUNTED INCANDESCENT LIGHT FIXTURE DISCONNECT SWITCH KCE66ED INCANDESCENT L16HT FIXTURE SPEAKER (OPTIONAL) 5. ALL 15A AND 20A 120V FECEPTACLES LOCATED IN THE GARAGE AND UTILITY ROOMS SHALL BE GP.Cl PROTECTED (G.F.P. LIGHT FIXTURE WITH FULL CHAIN /> ROLIGH-IN FOR OPT. CEILING FAN TRACK LIGHT </ \> 6. IT 15 THE RESPONSIBILITY OF THE LICENSED ELECTRICIAN TO ENSURE THAT ALL FLUORESCENT LIGHT FIXTURE CEILING MOUNTED INCANDESCENT LIGHT FIXTURE W1 ELECTRICAL WOW 15 IN FULL COMPLIANCE WITH N.F.P.4, 10, N.EC. 2011, F.BC.R. - 5TH ROUGH -IN FOR OPT. CEILING PAN EDITION (2014), AND ALL APPLICABLE LOCAL STANDARDS, CODES, AND ORDINANCES. 1. EVERY BUILDING HAVING A FO5SIL-FUEL-BURNING HEATER OR APPLIANCE, FIREPLACE, OR AN ATTACHED GARAGE SHALL WAVE AN OPERATIONAL CAR13ON MONOXIDE DETECTOR INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. 8. ALARM$ SHALL RECEIVE THEIR PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING 15 SERVED FROM THE LOCAL POWER UTILITY. 6UCW ALAW5 SHALL HAVE BATTERY BACKUP. COMBINATION 5MOKE/GAR50N MONOXIDE ALARMS SHALL 13E L16TED OR LABELED BY A NATIO44LY RECOGNIZED TESTING LABORATORY. MICROWAVE OUTLET +14" OPT. OPT, COACH COACH LIGHTING LIGHTING ELECTRICAL PLAN STANTON (TM) ELEVATION "ME - W.P. Gpl ELEC. METER W.P. G.F.I. MEDITERRANEAN if 4/0 ALU. CABLE MAIN DISCONNECT A/C DISC. FTYPF'. COMBO - SQUARE D =L 09-14-16 REVISED 014 AND 012 COPPER TO REFER TO FLOOR PLAN FOR NOTED MAIN DISC. INSIDE LIGHTS AND OUTLETS AMPS. REQUIRED PANE $10 COPPER TO WATER HEATER UNDERGROUND 08 COPPER TO RANGE SERVICE BY POWER COMPANY 04 COPPER TO �/V' GROUND ROD AL50 SERVICE TO BE BONDED TO FOOTING STEEL ELECTRICAL RISER DIAGRAM NOTE: - ELECTRICAL MATERIALS AND INSTALLATION$ SHALL COMPLY W1 APPLICABLE PROVISIONS OF THE NATIONAL ELEC. CODE, LOCAL CODES, AND THE LOCAL POWER COMPANY. MICROWAVE OUTLET +14" OPT. OPT, COACH COACH LIGHTING LIGHTING ELECTRICAL PLAN STANTON (TM) ELEVATION "ME - W.P. Gpl ELEC. METER W.P. G.F.I. MEDITERRANEAN if JOB NUMBER 26002.219 CAD FILE NAME x ca ISSUED 09-14-16 REVISED oo 0 -1 0 -i t., —m co 60 0 o cq j cm J) 00 0 2 c o 3�E LLA O�) IN 0 to 4-0 0 z le JOB NUMBER 26002.219 CAD FILE NAME LOT JO TB ISSUED 09-14-16 REVISED EST. 1994 (A om C) Ln 0 0 z 0 V) F�q 0 C) 0 >= 2LO 5:5 TI TLE ELECTRICAL PLAN SHEET 4 DAVIS BEWS DESIGN GROVP L50 STATE STREET FAST OUXWAR, FLORMA 34677 813. 925.1300 TEL 813 . 92-5 . 1800 FAX YVV-/W.E)AVlSBEVVS.00M TAMPA 9 E>Eal�� EST. 1994 (A om C) Ln 0 0 z 0 V) F�q 0 C) 0 >= 2LO 5:5 TI TLE ELECTRICAL PLAN SHEET 4 GENERAL NOTES MEEA COATINGS FOR USE VffH PRESSURE IRFATED WOOD #5 25 00 IT IS THE BUILDER'S RESPONSIBILITY TO ENSURE THAT ALL METAL CONNECTORS, 30" FOUNDATIONS METAL FASTENERS, ANCHORS, AND NAILS ARE THE APPROPRIATE MATERIAL PLANE PERMANENT BRACING REQUIREMENTS. SOIL TO BE COMPACTED TO AT LEAST 95% UNDER SLABS AND UNDER FOOTINGS AND/OR HAVE THE APPROPRIATE COATING FOR USE WITH THE DIFFERENT TYPES -PERMANENT 2x4 SPF #2 (MIN.) CONT. LATERAL TRUSS BOTTOM CHORD BRACING PERPENDICULAR OF MAX. DRY DENSITY AS DETERMINED BY ASTM- 1557 (MODIFIED PROCTOR) OF PRESSURE TREATED WOODS, AS PER THE FOLLOWING GUIDELINES. 1. WOOD TREATED WITH DOT SODIUM BORATE(SBX): CONNECTORS SHALL BE A MINIMUM TO TRUSS SPAN AT 15'-O"O.C. MAX W/IN TRUSS SPAN OR PER TRUSS DESIGN DRAWINGS. ATTACH MINIMUM BEARING CAPACITY 2000 1PSF G50 ZINC COATING W/ (2) 16d NAILS AT EACH TRUSS. OVERLAP BRACING AT LEAST ONE TRUSS SPACE (24") PLUS 6" TERMITE TREATMENT 2. WOOD TREATED WITH ACQ-C OR ACQ-D (CARBONATE) OR OTHER BORATE MIN PAST BOTTOM CHORD. THE SOIL UNDER THIS STRUCTURE SHALL BE TREATED FOR THE PREVENTION OF (NON -DOT) TREATMENTS: CONNECTORS SHALL BE A MINIMUM 0185 ZINC COATING. -INSTALL PERMANENT 2x CONTINUOUS LATERAL BRACE (CLB) ACROSS TRUSS WEBS AS INDICATED SUBTERRANEAN TERMITES, OR A PERIMITER TREATMENT (BORACARE MAY BE USED, 3. FOR ALL OTHER COMBINATIONS FOLLOW THE RECOMMENDATIONS OF THE ON TRUSS SHOP DRAWINGS & BCSI-B3. IN ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE FL_dRIDA DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES. PRESERVATIVE WOOD TREATER. ("T"BRACING MAY BE USED I.L.O. PEMANENT CLB IF IT EXTENDS MIN. 90% OF THE TRUSS WEB CAST IN PLACE CONCRffE 4. STAINLESS STEEL CONNECTORS AND FASTENERS MAYBE USED WITH ALL TYPES OF (SEE WEB REINFORCEMENT TABLE WITHIN BCSI-B3). 13. PRESSURE TREATED WOOD. -AT RAISED HEEL TRUSSES, 2x4 SYP #2 (MIN.) AT TOP AND BOTTOM OF HEEL W/ (2) 12d 1. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS PREFABRICATED WOOD TRUSSES TOENAILS REQ'D. EXT. SHEATHING MUST BE ATTACHED TO RAISED HEEL TRUSS AND INDICATED OF 2500 PSI, A SLUMP OF 4" PLUS OR MINUS 1", AND HAVE 2 TO 4% AIR 1, ALL PREFABRICATED WOOD TRUSSES SHALL BE SECURELY FASTENED TO THEIR BLOCKING. ALTERNATE IF HEEL HEIGHT IS LESS THAN 12"TALL: 2x4 SYP #2 BEHIND THE TRUSS ENTRAINMENT, AND A MAXIMUM WATER/CEMENT RATIO OF 0.58. SUPPORTING WALLS OR BEAMS WITH HURRICANE CLIPS OR ANCHORS.UPLIFT SHOES, TYP U.N.O. 2. ALL REINFORCING STEEL SHALL BE NEW DOMESTIC DEFORMED BILLET STEEL CONNECTORS SUCH AS HURRICANE CLIPS, TRUSS ANCHORS AND ANCHOR BOLTS ARE ONLY BE USED FOR RISERS & TREADS ILO 2x12'S CONFORMING TO ASTM A-615 GRADE 40. REQUIRED ON MEMBERS IN WALLS THAT ARE EXPOSED TO UPLIFT OR LATERAL FORCES. WOOD TREATMENT AND TO SELECT APPROPRIATE CONNECTOR THAT RESIST CORROSION. 3. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185 FOR 6x6xWl.4xWl.4 INTERIOR LOAD BEARING WALLS ARE NOT ALWAYS EXPOSED TO UPLIFT FORCES, THE 5. OMITTED J -BOLT WWF SHALL BE LAPPED AT LEAST 6" & CONTAIN AT LEAST ONE CROSS WIRE MEMBERS OF THESE WALLS WOULD NOT NEED TO HAVE CONNECTORS APPLIED. PLEASE 8. ALL EXPOSED WOOD OR WOOD IN CONTACT WITH EARTH, CONCRETE OR MASONRY IS TO WITHIN THE 6".FIBERMIX OF EQUAL SPECIFICATIONS MAY BE USED IN LIEU OF WWF. COORDINATE WITH THE TRUSS ENGINEER FOR THE LOCATION OF THESE WALLS AND -1/2%6" SIMPSON TITEN HD THREADED ANCHORS W/ LBP1/2 WASHER MAY BE 4. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH "THE BUILDING CODE STRUCTURAL PLANS FOR MORE INFO. SEAT PLATES SHALL BE PROVIDED AT BEARING LOCATIONS W/OUT WOODEN TOP PLATES. REQUIREMENTS FOR REINFORCED, CONCRETE" ACI 318 LATEST EDITION, AND 2. TRUSSES SHALL BE DESIGNED BY MWFRS METHODOLOGY FOR LONG SPAN TRUSSES TO 7. MORTAR JOINTS "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS," ACI 301. DETERMINE UPLIFT AND REACTION VALUES. MEMBER AND PLATE DESIGN TO BE CALCULATED ALL ENG. LUMBER IS TO HAVE THE MIN. DESIGN VALUES BELOW: 5. HORIZONTAL FOOTING BARS SHALL BE BENT MIN. 12 BAR DIAMETERS (EXCLUDING BY COMPONENTS AND CLADDING METHOD U.N.NO. BY TRUSS ENGINEER OF RECORD - FOR HEAD JOINTS GREATER THAN 3/4", GROUT FILL CELL IN BLOCK AFFECTED ON R301.2.1.2 OF THE RESIDENTIAL CODE FOR SPECIFICATION 3. PREFABRICATED WOOD TRUSSES SHALL BE DESIGNED IN ACCORDANCE WITH THE LATEST Fb 2500 Fb 3000 Fb 2200 BEND) AROUND CORNERS OR CORNER BARS WITH MIN. 24" LAP EXCLUDING BEND EDITION OF ANSI TPI 1. 1st TWO COURSES FROM FOUNDATION HAVE HEAD JOINTS WHICH FALL WITHIN THE AT EACH END SHALL BE PROVIDED. 4. BRIDGING FOR PRE-ENGINEERED TRUSSES SHALL BE AS REQ'D BY TRUSS MANU. U.N.O. Fc 3000 Fc 2100 Fc J_ = 900 900 Fc 450 6. MINIMUM LAP SPLICES ON ALL REINFORCING BARS SHALL BE 48 BAR DIAMETERS. 5. TRUSS ELEVATIONS AND SECTIONS ARE FOR GENERAL CONFIGURATION OF STRUCTUM STEEL 7. SLAB ON GRADE, REINFORCEMENT SHALL BE SUPPORTED IN PLACE FROM THE TRUSSES ONLY. WEB MEMBERS ARE NOT SHOWN, BUT SHALL BE DESIGNED BY 1. MATERIAL SPECIFICATIONS: WIDE FLANGE SECTIONS: ASTM A992, GRADE 50, CENTER TO UPPER 1/3 OF THE' SLAB. TRUSS MANUFACTURER IN ACCORDANCE WITH THE DESIGN LOADS. Fy=50 KSI TUBE STEEL (HSS): ASTM A500, GRADE B, Fy = 46 KSI PIPE STEEL: BOLTS AND IIHIRE�QED RODS TRUSS DESIGN LOADS : ASTM A53, TYPE E OR S, Fy = 35 KSI ALL OTHER STRUCTURAL & MISC. STEEL: 1. ALL BOLTS & THREADED RODS TO BE ASTM A307 OR BETTER (U.N.O.) TOP CHORD: Lr = 16 PSF A36 Fy=36 KSI. STEEL BOLTS LESS THAN ONE -HALF-INCH (12.7 mm) DIAMETER DL = 7 PSF (SHINGLE TYPE ROOF COVER) 2. STRUCTURAL CONNECTIONS: ALL STRUCTURAL BOLTS TO BE A325N U.N.O. ALL 2. USED AS FASTENERS FOR PRESSURE PRESERVATIVE -TREATED WOOD SHALL DL = 15 PSF (LIGHT WEIGHT CLAY TILE ROOF COVER) A325N BOLTS SHALL BE BROUGHT TO A "SNUG -TIGHT" CONDITION , AS DEFINED BE OF HOT -DIPPED ZINC COATED GALVANIZED STEEL, STAINLESS STEEL, DL = 14 PSF (TRUSS OVERBUILD) IN THE SPECIFICATION. SLIP CRITICAL (SC) BOLTS MUST BE FULLY TENSIONED SILICON BRONZE OR COPPER. FASTENERS SHALL BE IN ACCORDANCE WITH BOTTOM CHORD: OIL = 5 PSF PER SPECIFICATION STRUCTURAL BOLTS SMALLER THAN 5/8" DIA. TO BE A307 ASTM A 153. FASTENERS OTHER THAN NAILS AND TIMBER RIVETS SHALL BE MINIMUM FLOOR DESIGN LIVE LOADS: 3. PERMITTED TO BE OF MECHANICALLY DEPOSITED ZINC -COATED STEEL WITH A) FLOORS = 40 PSF THREADED ROD SHALL CONFORM TO A36 OR A307 ANCHOR BOLTS SHALL COATING WEIGHTS IN ACCORDANCE WITH ASTM B 695, CLASS 55, MINIMUM. B) BALCONIES = 60 PSF / 100 PSF (WHEN BALCONY EXCEEDS 100 SID FT) CONFORM TO ASTM F1554 ALL BOLTS CAST IN CONCRETE: ASTM A36 OR ASTM MMONRY WALL CONSTRUCTION C)DECKS = 40 PSF A-307 SHOP AND FIELD WELDS: E70XX ELECTRODES STEEL REINFORCEMENT 1. HOLLOW LOAD BEARING UNITS SHALL BE NORMAL WEIGHT, GRADE N, TYPE 2, D) STAIRS = 40 PSF SHOP DRAWINGS TO BE PROVIDED TO ENGINEER OF RECORD BEFORE FABRICATION FOR REVIEW AND APPROVAL. WELDED CONNECTIONS: ELECTRODES - CONFORMING TO ASTM C90, WITH A MINIMUM NET COMPRESSIVE STRENGTH OF E)BONUS ROOM/GAME ROOMS = 60 PSF U.N.O. E70XX UNO (LOW HYDROGEN). FILLET WELDS SHALL BE Y16" LINO. 2000 PSI (f'm = 1900 PSI) MINIMUM FLOOR DESIGN DEAD LOADS: A) FLOORS = 15 PSF 3. SUBMIT SHOP DRAWINGS INDICATING ALL SHOP AND ERECTION DETAILS 2. MORTAR SHALL BE TYPE M OR S, CONFORMING TO ASTM C270 B)BALCONIES = 15 PSF INCLUDING PROFILES, SIZES, SPACING, AND LOCATIONS OF STRUCTURAL 3. HEAD MORTAR JOINTS AT PRECAST WINDOW SILLS TO BE NO MORE THAN 1". GENERAL LOADING: MEMBERS, CONNECTION ATTACHMENTS, FASTENERS, LOAD, AND TOLERANCES. 4. COARSE GROUT SHALL CONFORM TO ASTM C476 WITH A MAXIMUM AGGREGATE SIZE ATTIC WITHOUT STORAGE = 10 PSF 4. STRUCTURAL STEEL SHALL RECEIVE SHOP COAT OF PRIMER (COLOR AS DIRECTED OF 3/8" AND A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI. ATTIC WITH LIMITED STORAGE = 20 PSF BY ARCHITECT) EXCEPT FOR AREAS WHICH WILL RECEIVE SPRAY -ON FIRE 5. VERT. REINF. SHALL BE AS NOTED ON THE DRAWINGS WITH CELLS FILLED WITH GUARDRAILS / HANDRAILS = 200 LB POINT LOAD / 50 PSF PROTECTION. COARSE GROUT AND GRADE 40 STEEL. REINFORCEMENT SHALL BE PLACED IN THE GUARDRAILS IN -FILL COMPONENTS = 50 PSF 5. A CERTIFIED TESTING AGENCY SHALL BE ENGAGED TO PERFORM INDUSTRY CENTER OF THE MASONRY CELL WITH MIN 1/2" CLEARANCE TO INSIDE FACE. GENERAL TRUSS BRACING & BLOCKING REQUIREMENTS STANDARD INSPECTIONS TO ENSURE CONFORMANCE WITH PLANS AND 6. VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION AT THE TOP & BOTTOM & -ADDIT'L BRACING & BLOCKING PER BCSI-1 & TRUSS MANUFACTURER'S DRAWINGS SPECIFICATIONS (IF PROVIDED). SUBMIT REPORTS TO ARCHITECT AND ENGINEER. AT A MAX. SPACING OF 8'-0" U.N.O. -G.C. TO PROVIDE MIN 2x SYP #2 BLOCKING BETWEEN TRUSSES TO COMPLY W/ APA 7. REINFORCING STEEL SHALL BE LAPPED PER TABLE BELOW U.N.O. ON DRAWINGS. RECOMMENDATIONS FOR MIN. 7/16"OSB SHEATHING REBAR SIZE MIN. LAP SPLICE LENGTH #5 25 00 #6 30" #7 35" -MIN 2x SYP #2 BLOCKING REQ'D ALONGSIDE TRUSS TOP CHORD 0 ROOF HIP/RIDGE TO PREVENT SHEATHING SPAN FROM EXCEEDING 2FT (NOT REQ'D IF SHEATHING SPAN IS LESS THAN 2FT). BLOCKING TO TRUSS TOP CHORD w/ (2) 12d NAILS 0 12"O.C. MAX & 4"FROM EA. END. NOTE: PLYWOOD EDGES 0 HIP CORNERS REQ. MIN 2x4 SYP #2 BLOCKING wl (3) 12d TOENAILS EA. END. -TRUSS "X"BRACING: MIN 2x4 SYP #2 AT ANGLE APPROX. 45' FROM VERT. TO EA. TRUSS MEMBER w/ (3) 12d NAILS. SPACE "X"BRACING ALONG TRUSS SPAN 0 10'-O"MAX AND EQUALLY .. 11 1 11 ULLL VVIIM LIIHER RODDING UIN rLNUIL VIDRAIUR IV LI'43URL rRUrLR %,VPIk.1Rr_ I- VLKI. KUNNINU MUM IUr IV DUHUM AUKVZZ MAA 4 IKU33IL3, inu,4 ouiivm iv ivr vy/ kf) Izu SPAUILU MUM tNU ur 1111.133. A DINAWNU IV aIAKI LV -L) MAA rK%jm ri nir uir%uLm Arqu / un 8. HOOKS AT THE TOP & BOTTOM OF VERT. REINF. BARS TO BOND COURSE & (4) BAYS AFTER GABLE END BRACING. SEE BCSI-B3 SECTIONS 1, 2 AND 3 FOR ADDITIONAL ROOF 1. WOOD CONSTRUCTION SHALL CONFORM TO THE NFPA "NATIONAL DESIGN FOOTING TO BE NO LESS THAN 12 BAR DIAMETERS EXCLUDING BEND PLANE PERMANENT BRACING REQUIREMENTS. 9. EXPANSION TYPE ANCHORS ARE NOT TO BE USED IN BOND COURSE. EMBEDDED -PERMANENT 2x4 SPF #2 (MIN.) CONT. LATERAL TRUSS BOTTOM CHORD BRACING PERPENDICULAR STRUCTURAL WOOD FRAMING MEMBERS. (I.E. BLOCKING OR GABLE END BRACING), HEID ANCHORS OR EPDXY FASTENED STUDS SHALL BE USED. TO TRUSS SPAN AT 15'-O"O.C. MAX W/IN TRUSS SPAN OR PER TRUSS DESIGN DRAWINGS. ATTACH 10. MASONRY ROUGH OPENING TOLERANCES - 1/4" TO + 1/2" W/ (2) 16d NAILS AT EACH TRUSS. OVERLAP BRACING AT LEAST ONE TRUSS SPACE (24") PLUS 6" 11. PROVIDE GROUT STOPS BELOW BOND BEAM. PLASTIC SCREEN, METAL LATH STRIP MIN PAST BOTTOM CHORD. FILLED HOLE EPDXY TO BE SIMPSON STRONG TIE EPDXY OR EQUIVALENT. OR CAVITY CAPS MAY BE USED TO PREVENT THE FLOW OF GROUT INTO CELLS -INSTALL PERMANENT 2x CONTINUOUS LATERAL BRACE (CLB) ACROSS TRUSS WEBS AS INDICATED SUPPORTS OF A BUILDING OR OTHER STRUCTURE & ARE EXPOSED TO WEATHER BELOW. THE USE OF FELT PAPER AS A STOP IS PROHIBITED. ON TRUSS SHOP DRAWINGS & BCSI-B3. 12. TEMPORARY BRACING AND SHORING OF WALL TO PROVIDE STABILITY DURING ("T"BRACING MAY BE USED I.L.O. PEMANENT CLB IF IT EXTENDS MIN. 90% OF THE TRUSS WEB PRESERVATIVE -TREATED WOOD. CONSTRUCTION SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR (SEE WEB REINFORCEMENT TABLE WITHIN BCSI-B3). 13. DO NOT APPLY UNIFORM LOADS TO MASONRY WALLS FOR (3) DAYS AND NO -AT RAISED HEEL TRUSSES, 2x4 SYP #2 (MIN.) AT TOP AND BOTTOM OF HEEL W/ (2) 12d RESPONSIBILITY OF THE CONTRACTOR & TO BE DESIGNED AND DETAILED BY OTHERS. CONCENTRATED LOADS FOR (7) DAYS. PER CODE ACI 318 LATEST EDITION 5.11.1 TOENAILS REQ'D. EXT. SHEATHING MUST BE ATTACHED TO RAISED HEEL TRUSS AND INDICATED 14. DURING CONCRETE POURS, THE CONTRACTOR TO ADEQUATELY VIBRATE THE FILLED BLOCKING. ALTERNATE IF HEEL HEIGHT IS LESS THAN 12"TALL: 2x4 SYP #2 BEHIND THE TRUSS 1" IN DIA FOR PLUMBING LINES, ETC. SHALL BE REPAIRED WITH SIMPSON HSS2 STUD T SHOES, TYP U.N.O. ULLL VVIIM LIIHER RODDING UIN rLNUIL VIDRAIUR IV LI'43URL rRUrLR %,VPIk.1Rr_ I- VLKI. KUNNINU MUM IUr IV DUHUM AUKVZZ MAA 4 IKU33IL3, inu,4 ouiivm iv ivr vy/ kf) Izu CONSOLIDATION. NAILS AT EACH TRUSS MEMBER (DIAGONAL BRACING) WOOD CONSTRUCnON DIAGONAL BRACING REQUIRED AT CLB PER BCSI-83. 1. WOOD CONSTRUCTION SHALL CONFORM TO THE NFPA "NATIONAL DESIGN 6. THE TRUSS MANUFACTURER SHALL DETERMINE ALL SPANS, WORKING POINTS, BEARING SPECIFICATION FOR WOOD CONSTRUCTION", LATEST EDITION.(NDS) POINTS, AND SIMILAR CONDITIONS. TRUSS SHOP DRAWINGS SHALL SHOW ALL TRUSSES, ALL 2. ALL EXTERIOR WOOD STUD WALLS, BEARING WALLS. SHEAR WALLS AND MISC. BRACING MEMBERS, AND ALL TRUSS TO TRUSS HANGERS. STRUCTURAL WOOD FRAMING MEMBERS. (I.E. BLOCKING OR GABLE END BRACING), HEID REPAIR NOTES SHALL BE SPRUCE- PINE -FIR OR EQUIVALENT. NO. 2 GRADE SHALL BE USED 1. OMITTED REBAR REGARDLESS OF SPECIES. U.N.O. ON FRAMING PLANS OR DETAILS DRILL A 3/4" DIAMETER HOLE MIN. 6" DEEP AT THE LOCATION OF THE OMITTED 3. FIELD -CUT ENDS, NOTCHES AND DRILLED HOLES OF PRESERVATIVE -TREATED WOOD REBAR, AND INSTALL VERTICAL REBAR (SIZE AS NOTED ON PLAN) INTO EPDXY SHALL BE TREATED IN THE FIELD IN ACCORDANCE WITH AWPA M4. FILLED HOLE EPDXY TO BE SIMPSON STRONG TIE EPDXY OR EQUIVALENT. 4. THE PORTIONS OF GLUED -LAMINATED TIMBERS THAT FORM THE STRUCTURAL FOLLOW MANUFACTURE'S INSTRUCTIONS. ASSURE THAT ALL DUST AND DEBRIS SUPPORTS OF A BUILDING OR OTHER STRUCTURE & ARE EXPOSED TO WEATHER FROM DRILLING ARE REMOVED FROM HOLE BY USING COMPRESSED AIR PRIOR TO & NOT PROTECTED BY A ROOF, EAVE OR SIMILAR COVERING SHALL BE PRESSURE APPLYING EPDXY. ALLOW EPDXY TO CURE TO MANUFACTURER'S TREATED w/ PRESERVATIVE, OR BE MANUFACTURED FROM NATURALLY DURABLE OR SPECIFICATIONS, THEN FILL CELL IN THE NORMAL WAY DURING BONDBEAM POUR. PRESERVATIVE -TREATED WOOD. USE 30" MIN. LAP SPLICE. HOOKS AT TOP OF BAR TO BE MIN. 12 BAR 5. ALL LUMBER SPECRED ON DRAWING ARE INTENDED FOR DRY USE ONLY (MOISTURE DIAMETERS(EXCLUDING BEND). CONTENT 19% OR LESS), U.N.O. ALL WATERPROOFING & FIRE SAFETY SYSTEMS ARE THE 2. STRAPS /CONNECTOR SUBSTITUTION RESPONSIBILITY OF THE CONTRACTOR & TO BE DESIGNED AND DETAILED BY OTHERS. MAY SUBSTITUTE STRAPS/CONNECTORS w/STRAPS/CONNECTORS OF EQUAL OR 6. ANY WOOD FRAME INTERIOR BEARING WALL STUDS THAT HAVE HOLES IN THE CENTER GREATER UPLIFT & LATERAL RESISTANCE VALUES IN FIELD WITHOUT VERIFICATION, OR THE STUD UP TO 1" DIA. SHALL HAVE STUD PROTECTION SHEILDS. ALL HOLES OVER PROVIDED ALL MANUFACTURES INSTALLATION INSTRUCTIONS ARE FOLLOWED. 1" IN DIA FOR PLUMBING LINES, ETC. SHALL BE REPAIRED WITH SIMPSON HSS2 STUD 3. STAIR CONSTRUCTION SHOES, TYP U.N.O. 2X12'S MAY BE USED ILO TIMBERSTRANDS FOR STAIR STRINGERS RIM BOARDS MAY 7. MANY OF THE NEW PRESSURE TREATED WOODS USE CHEMICALS THAT ARE CORROSIVE BE USED FOR RISERS & TREADS ILO 2x12'S TO STEEL. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE TYPE OF 4. METAL STUD SUBSTITUTION WOOD TREATMENT AND TO SELECT APPROPRIATE CONNECTOR THAT RESIST CORROSION. WOOD STUDS MAY BE SUBSTITUTED OF METAL STUDS IN NON -LOAD BEARING WALLS FOR EXAMPLE. ACQ-C, ACQ-D, CBA -A OR CA -B REQUIRE HOT -DIPPED GALVANIZED OR 5. OMITTED J -BOLT STAINLESS STEEL FASTENERS. DOR SODIUM BORATE (SBX) DOES NOT. -1/2" ALL THREAD w/ WASHERS MAY BE USED ILO 1/2" J -BOLTS W/ WASHER 8. ALL EXPOSED WOOD OR WOOD IN CONTACT WITH EARTH, CONCRETE OR MASONRY IS TO DRILL & EPDXY w/ SIMPSON SET EPDXY 0 5" MIN EMBED. BE PRESSURE TREATED. -1/2%6" SIMPSON TITEN HD THREADED ANCHORS W/ LBP1/2 WASHER MAY BE 9. UNTREATED WOOD SHALL NOT IBE IN DIRECT CONTACT WITH CONCRETE OR MASONRY. USED ILO 1/2" J -BOLT. SEAT PLATES SHALL BE PROVIDED AT BEARING LOCATIONS W/OUT WOODEN TOP PLATES. 6. TAPCON FASTENERS MAY BE USED ILO SIMPSON TITENS 10. SEE PLAN FOR STUD PACK & BEAM NAILING PATTERNS 7. MORTAR JOINTS ENCINEERED WMPER -FOR BED JOINTS 1/2" TO I", GROUT FILL CELLS IN BLOCK AFFECTED (NO VERT. ALL ENG. LUMBER IS TO HAVE THE MIN. DESIGN VALUES BELOW: REINF. REQUIRED) COLUMNS BEAMS STUDS E = 1,800,000 lb/in' U.N-O. E = 2,000,000 lb/in' U.N.O. E = 1,500,000 lb/in' U.N.O. - FOR HEAD JOINTS GREATER THAN 3/4", GROUT FILL CELL IN BLOCK AFFECTED ON R301.2.1.2 OF THE RESIDENTIAL CODE FOR SPECIFICATION EITHER SIDE OF JOINT. PROVIDE (1) #5 VERT. REINF. IN EACH CELL CONT. PER PLAN. Fb 2500 Fb 3000 Fb 2200 ** EXCEPTION: IF TIE BEAM COURSE AND ADJACENT TWO COURSES BELOW, AS WELL AS Ff 1500 Ft 1700 Ft 1500 1st TWO COURSES FROM FOUNDATION HAVE HEAD JOINTS WHICH FALL WITHIN THE Fc 3000 SPECIFIED TOLERANCES, THE ADDED VERTICAL REINFORCEMENT IS NOT REQUIRED TO BE Fc 3000 Fc 2100 Fc J_ = 900 900 Fc 450 EPDXIED INTO TIE BEAM OR FOOTING Fc 8. FOR BLOCKS NOT STAGGERED, GROUT FILL CELL EA. SIDE OF JOINT AND PROVIDE Fv = 285 Fv 285 Fv 150 (1) #5 VERT. REINF. IN EACH CELL, CONT. PER PLAN. WOOD BEARING SURFACES ARE TO BE SYP#2 OR BETTER END GRAIN 9. OVERHANGING CMU WALL CONDITION U.N.O. -FOR CMU OVERHANGING FOUNDATION UP TO 1/2", NO FIX IS REQ'D POUR TIEBEAM AND CEIIUNG CONSTRUCTION VERTICAL CELLS PER PLAN. 1. USE 1/2" CEILING OR SAG RESISTANT BOARD FOR 24"O.C. FRAMING U.N.O. -FOR CMU OVERHANGING FOUNDATION FROM OVER 1/2" TO 1-1/2", GROUT FILL THE 2. 5/8" F'Y' GYPSUM BOARD SHALL BE USED ON CEILING IN GARAGE WHEN FIRST THREE COURSES IN THE WALL ALONG AREA AFFECTED AS WELL AS TIE BEAM AND LIVING SPACE IS ABOVE THE GARAGE. VERTICAL CELLS PER PLAN UNDER STAR PROTECnON -FOR CMU OVERHANGING FOUNDATION FROM OVER 1-1/2", CONTACT ENGINEER OF 1. ENCLOSED ACCESSIBLE SPACE UNDER STAIRS SHALL HAVE WALLS, UNDER STAIR SURFACE RECORD FOR APPLICABLE REPAIRS. & ANY SOFFITS PROTECTED ON THE ENCLOSED SIDE w/ 1/2"(12.7MM) GYP. B.D. DESIGN PRESSURES WIND DESIGN LOAD INFORMATION WIND SPEED (ULTIMATE) 139 mph WIND SPEED (ALLOWABLE) 108 mph WIND EXPOSURE B RISK CATEGORY 11 BUILDING TYPE V B ENCLOSURE CLASSIFICATION ENCLOSED INTERNAL PRESSURE COEFFICIENT +/- 0.18 EFFECTIVE WIND WIND PRESSURE AND SUCTION (PSF) AREA (SQ FEET) VALUE DENOTES PRESSURE FOUNDATION DETAILS VALUE DENOTES SUCTION AREA SD3 GENERAL DETAILS 10 (+)21.2 (+)21.2 �-)22.9 20 (+)20.2 __��28.3 + )20.2 �-)22.0 �-)26.4 (+)19.0 (+)19.0 50 (-)20.8 H23.9 100 1 .0 �1 (+)18.0 119.8 H22.0 .1 GARAGE DOORS W-010 x 70-0$0 161-Ols x V-0" __T+7718.4 (+7 _177 (-) 20.9 19.7 WIND PRESSURE/ SUCTION DIAGRAM 5 5 4 4 5 5 STANDARD DESIGN PRESSURE NOTES 1 . ASCE 7-10 WALL DESIGN ALLOWABLE COMPONENTS AND CLADDING WIND PRESSURES AND SUCTIONS PER FLORIDA BUILDING CODE 5th EDITION (2014). WIND SPEED IS BASED ON LINEAR INTERPOLATION FOR THIS SITE. 2. MEAN ROOF HEIGHT FOR A TYPICAL SINGLE STORY HOME IS 15FT, 2 STORY HOME IS 30FT 3. MULTIPLY THE ABOVE PRESSURES BY 1.67 TO GET ULTIMATE WIND PRESSURES. 4. "a" = END ZONE IS ONLY W/IN 5'-0" OF ALL EXTERIOR BUILDING CORNERS. 5. INDICATED PRESSURES CAN BE INTERPOLATED FOR OTHER DOOR SIZES, OTHERWISE USE LOAD ASSOCIATED WITH THE LOWER EFFECTIVE AREAS. 6. DESIGNATED AREAS WHERE THE ULTIMATE WIND SPEED IS 140 MPH OR GREATER IS CONSIDERED TO BE IN THE WIND -BOURNE DEBRIS AREA. OPENING PROTECTION REQUIRED. REFER TO SECTION R301.2.1.2 OF THE RESIDENTIAL CODE FOR SPECIFICATION REQUIREMENTS OF THE USE OF WOOD STRUCTURAL PANELS. REFER TO TABLE R301.2.1.2 FOR ATTACHMENT SPECIFICATIONS INDEX OF DRAWINGS SHEET SHEET TITLE S1 STRUCTURAL NOTES S2 FOUNDATION PLAN S3 DOWEL PLACEMENT PLAN S4 ROOF FRAMING PLAN S4.1 NOTES & CONNECTOR LEGEND S5 LINTEL PLAN SD1 FOUNDATION DETAILS SD2 GENERAL DETAILS SD3 GENERAL DETAILS SD4 GENERAL DETAILS MASTER UPDATES NUMBER DATE DESCRIPTION INTIALS 1 5/7/2015 1 CREATED ELEV. FC, NC, ME, & NCII w/ GARAGE OPTIONS, OPT BED 4 JEA tA u IVIII'Slurk ul- 1 IVIN 0 0 c� z u c 0 .2 < z Cos 0 W Q w z c) 0 Lu Z 0 1 E z 8 0 A LL z c) (6 0 0 w z z 8 < 0 0 UIL) :s ct) 0 F � III �j Z Z =) U) �- z OE < < Z 0 0 uo- � Oz. CTJL- C) C6 � C'4 Co LL LU C"4 < a Lu 0 0 z 0 F- LU Lu U) ri uj z 00 z z < 0 0 c) _j u w) LLF Fx La cm 0 0 0 0 Z uj Lu w 5 a 0 0 0 STRUCTURAL ENG: BED DRAFTING: -STRUCT: TVV QC CHECK: IVIB JOB No. TIVI - 2153124 SCALE: AS INDICATED DATE: 09.15.2016 si LLJ z 0 a F_ I I D_ ry d. � w .10 M rf T.d uj 0) to 00 s C=) ...... 0* Fj Ld 00 Z 004c, 0) LL. co o :2! w Uj OD a- 3, Lu 0: Z 00 *"5 0 z 0 6*0 0 611 0 00 im U - ///#In" it AAI f)" FOUNDATION PLAN b rl- (1) #5 @ TOP, BOTTOM & MID -HEIGHT OF COLUMN FILLED CELL FOUNDATION NOTES: uj 1. PROVIDE MIN. 6 MIL. APPROVED VAPOR BARRIER. ALL JOINTS TO BE LAPPED MIN. 6" AND SEALED. < 2. PROVIDE 3-1/2" 300OPSI CONC. SLAB W/ 6x6xWl.4xWl.4 WELDED WIRE MESH PLACED AT MID DEPTH ON 6 MIL. VAPOR BARRIER ON COMPACTED FILL (FIBER MESH MAY BE USED ILO WWM, WHEN FIBER MESH. MEETS OR EXCEEDS SPECIFICATIONS SET FORTH IN CURRENT CODE EDITION. 3. VERT. #5 BAR TO BE HOOKED AT TOP & BOTTOM (FTG. & TIE BEAM ENDS) W/MIN. 12 BAR DIAMETER LEGS EXCLUDING BEND @ EA. END. LAP SPLICES SHALL BE NO LESS THAN 25". 4. CONSULT W/MAN. SPECIFICATIONS PRIOR TO POURING OR z RECESSING DOOR SILLS. 0 5. EXTERIOR SLABS SHALL SLOPE 1/8" PER FOOT AWAY FROM HOUSE. I 6. CONTROL JOINTS (IF SHOWN) ARE NOT REQUIRED BY CODE BUT ARE SUGGESTED (ESPECIALLY WHEN USING FIBER REINF. CONC.) CONTROL JOINTS TO BE SAW CUT A DEPTH OF 1/4" OF THE THICKNESS OF THE SLAB. FILL CUT W/APPROVED JOINT MATERIAL OR 4= Ljj USE ALTERNATE APPROVED METHOD. w 7. MECHANICAL EQUIP. LOCATIONS WILL BE DETERMINED BY COMMUNITY & COUNTY CODES. 8. FOUNDATIONS AND SUPPORTS FOR OUTDOOR MECHANICAL SYSTEMS SHALL BE RAISED AT LEAST 3" ABOVE THE FINISHED GRADE AND SHALL ALSO CONFORM TO THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. 9. NO WOOD STAKES PERMITTED IN FOUNDATION. w 10, PENDING SITE CONDITIONS, FOUNDATION MAY HAVE TO BE STEPPED DOWN. SEE SHEET SD1 FOR ADDITIONAL INFORMATION. GC TO DETERMINE STEP LOCATIONS IF REQUIRED 11. SEE TYPICAL DETAIL ON LINTEL PLAN FOR REQUIRED STEEL BENDS N0111111jill, to AND LAP SPLICE. SEE DTL MF09 AND MI`10 ON SD1 FOR STANDARD N"I % * N� // V- ui CS FOOTING STEP DOWN AND CORNER INFORMATION. C"j a- 000 o 00 00 a 4k, 12. ANY EQUIPMENT AND/OR APPLIANCES HAVING AN IGNITION SOURCE 4-0. ci SHALL BE ELEVATED A MIN OF 18". CONTRACTOR TO PROVIDE SUCH CO 0 00, a* _j Z z ui -1 PLATFORM w/ EITHER MASONRY OR WOOD CONSTRUCTION Ere b �0 it 00 Z .Lu 0 13. ASSUMED ALLOWABLE SOIL BEARING PRESSURE AFTER 0 11 .,: (:) - W Ld 0 * --,- -Z" < COMPACTION: 2000 PSF (SEE SOILS REPORT AND SPECIFICATIONS 00 0 4z z FOR COMPACTION REQUIREMENTS). IF SOIL CONDITIONS IN THE 00' PROJECT DO NOT MEET OR EXCEED THE CAPACITY, THE GENERAL 0 CONTRACTOR SHALL CONTACT THE ENGINEER PRIOR TO _j m u_ FOUNDATION POUR FOR VERIFICATION OF FOUNDATION DESIGN. SOIL TO BE FREE OF ORGANIC MATERIAL AND COHESIVE SOILS, COMPACTED IN 12" LIFTS TO AT LEAST 95% OF MAX. DRY DENSITY AS DETERMINED BY ASTM - 1557 (MODIFIED PROCTOR). THE FOUNDATION SIZES INDICATED ON THE FOUNDATION PLAN HAS BEEN DESIGNED FOR A MINIMUM SOIL BEARING CAPACITY OF 2000 u PSF. 0 14. PENDING SITE CONDITIONS, IF STEMWALL IS REQUIRED, G.C. TO 14� DETERMINE REQUIRED COURSES FOR STEMWALL FOUNDATION. SEE 0 cy) STEMWALL CHART ON SD1 FOR REQUIRED REINFORCEMENT AND c� FOOTING S�IZES PENDING DEPTH OF STEMWALL. U I I C) 6 z FOOTING SCHEDULE u r_ 0 .2 > 12"xl2"xl2" do w/ #5's EQUALLY SPACED EA. �7, WAY MIN. 2" HORIZ. CLEARANCE BETWEEN MIN (2) # 5 E.W. BARS & 3" MIN. COVER TO EDGE OF CONC. d, 24"x24"xl2" dp w/ #5's EQUALLY SPACED EA. _1I 0 WAY MIN. 2" HORIZ. CLEARANCE BETWEEN MIN (3) # 5 E.W. z BARS & 3" MIN. COVER TO EDGE OF CONC. 0 28"x28"xl 2" dp w/ #5's EQUALLY SPACED EA. OEM= WAY MIN. 2" HORIZ. CLEARANCE BETWEEN MIN (4) # 5 E.W. BARS & 3" MIN. COVER TO EDGE OF CONC. 30"x3O"xl 2" dp w/ #5's EQUALLY SPACED EA. WAY MIN. 2" HORIZ. CLEARANCE BETWEEN MIN (4) # 5 E.W. BARS & 3" MIN. COVER TO EDGE OF CONC. 32"x32"xl 2" dp w/ #5's EQUALLY SPACED EA. WAY MIN. 2" HORIZ. CLEARANCE BETWEEN MIN (5) # 5 E.W. z BARS & 3" MIN. COVER TO EDGE OF CONC. < 36"x36"xl 2" dp w/ #5's EQUALLY SPACED EA. WAY MIN. 2" HORIZ. CLEARANCE BETWEEN MIN (5) # 5 E.W. (D BARS & 3" MIN. COVER TO EDGE OF CONC. U) C-) W 42"x42"xl 2" dp w/ #5's EQUALLY SPACED EA. WAY MIN. 2" HORIZ. CLEARANCE BETWEEN MIN (6) # 5 E.W. Z 06 U) - C'4 W 0 LU m E z ll�_ BARS & 3" MIN. COVER TO EDGE OF CONC. I-_ U) _j 8 0 (D < z 0') 48"x48"xl 2" dp w/ #5's EQUALLY SPACED EA. 0 - WAY MIN. 2" HORIZ. CLEARANCE BETWEEN MIN (7) # 5 E.W. Z (.) p �; 0 (D w uj Z BARS & 3" MIN. COVER TO EDGE OF CONC. 0 - I.- - _j co a � z w 54"44"xI6" dp w/#5's EQUALLY SPACED EA. < 0 0 0- = (0 -- WAY MIN. 2" HORIZ. CLEARANCE BETWEEN MIN (8) # 5 E.W. < (n a i_- � w w Z Z :) U) I'- z E BARS & 3" MIN. COVER TO EDGE OF CONC. < < ZO 60"x6O"xl6" dp w/#5's EQUALLY SPACED EA. 0 0 w I � 0 U, z (.5 0 20- 0 WAY MIN. 2" HORIZ. CLEARANCE BETWEEN MIN (9) # 5 E.W. (N BARS & 3" MIN. COVER TO EDGE OF CONC. < IN U- C14 < w z 0 _j SYMBOLSLEGEND 0 0 F- UEM INDICATES GROUT FILLED CELL WITH (1) VERT. #5 CONT. FTG. w TO TIE BEAM (8'-0" O.C. MAX U.N.O.). w INDICATES GROUT FILLED CELL WITH (2) VERT. #5 CONT. FTG. U) TO TIE BEAM. 0 INDICATES GROUT FILLED CELL WITH NO REINFORCEMENT. INDICATES 45' CORNER BLOCK GROUT FILLED WITH (2) VERT. #5 CONT. FT.G TO TIE BEAM. Lj Lu z 00 z z 8 - La Ld BOTTOM & (1) #5 @ TOP, (1) CONT. #5 FROM Lo MID -HEIGHT OF 4 0 COLUMN TIE BEAM 0 C4 0 _---------TO FOOTING 0 ow _j Z Lu _j UJ w A --) >. a 0 MASONRY WALL 0 0 REINFORCING PER 1',' 2 PLAN(TYP). CL STRUCTURAL ENG: BED DRAFTING: -STRUCT: TW --------------- -H QC CHECK: MB OEM TM - 2153124 JOB No. SCALE: AS INDICATED SECTION VIEW DATE: 09.15.2016 PLAN VIEW MASONRY COLUMN TIE IN 3/4"=11-011 S2 J01 J02 J03 J04 NOTE: THIS TRUSS TO BE (2) PLY FOR TILE LOADING i L R27 R11 T— LO 010 co C%j (0 r— C) R27 R11 (D Z w E05 TOENAIL VALLEY TRUSS SIM. R27 w z -1 5 TO EA. R 11 TRUSS USING (3) CO -L- 1 -1 R11 D 16d NAILS 0 U) o- n -n < BW2 -, E2 �- --6,= R27 TO� @ 8'-0"' —n- u - R11 0 N 0 R27 < Li n- ll, 0 \R11 FO Lu co R28 D > x 0 0 uj= \R11 @ 0 Z3 R11 R29 u- 'R25C F1 R23 R30 I I Q*R25C D z LID R24 J02 CD 1 A 11`1��VF1 J10 �SDZ) R26 FO J03 �INV— 1 J01I I Lff L ROOF FRAMING PLAN_ 1/4"=11-011 NOTE: SEE PAGE S4.1 FOR NOTES AND CONNECTOR LEGEND WALLLEGEND w 8'-0" T.O.M. = 9'-4" T.O.M. c) 12'-0" T. 0. M. = INTERIOR/EXTERIOR BEARING WALLS VERIFY HGT. W/ ARCHITECTURAL PLAN U.N.O. z 0 CL Lr- uj co O'Dell Ld 00 It —j z LL 0 O'D b co w Fr: Q --:1 < 0: uj < z 00 0 m LL 0 c� u EI al, C) z u 0 Q 0 z0 Z z 0 C/) Lij q 06 w 0 w E Z I- U) 8 (D OZ z Up: z 0 00:0 U) � -p a (0 R z 0 < 0 0 cf) In F- m, w �j Z Z D U) F- Z OE < < ZO 0 w LL 0 OR 01 ll-� 1:6 <t u- w 04 w 04 < u- N Z 0 0 0 0 ui w r U) rUH I Lu z 00 z z F- 0 0 U) -i W) Lu W) 04 0 0 0 0 -1 Z Lij I w w 5 5.00 0 0 3: STRUCTURALENG: BED bw-fING: -STRUCT: TW -.- ... ......................... . . ... . . . . ...... ...... QC CHECK: MB JOB No. TM - 2153124 ..... . ....... ..... --- ---------- ...... SCALE: AS INDICATED DATE: 09,15.2016 S4 BEARING WOOD WALL SCHEDULE TAG F�.; STUD L LUMBER CONNECTION & FASTENERS UPLIFT CAP. BLOCKING TOP BOTTOM 16d SPACING SPECIES (pl� NAILING NOTES r __. 1611 SPF (3)12d TOENAILS (3)12d TOENAILS NO UPLIFT MID -SPAN ON MASONRY: SIMP. META16 1611 SPF 1/2" THREADED ROD @ 48" O.C. ADJUST AS REQ'D TO MISS STUDS 1160 pIf MID -SPAN <�> 16" SPF 1/2" THREADED ROD @ 48" O.C. ADJUST AS REQ'D TO MISS STUDS 1160 plf 1 gd. PT. TO MASONRY: SIMP. HU410 OR HUC410 w/(10)10d 1211 SPF (3) 12d TOENAILS (3) 12d TOENAILS NO UPLIFT MID -SPAN 7"x7" LVL COLUMN. 12" SPF 1/2" THREADED ROD @ 48" O.C. ADJUST AS REQ'D TO MISS STUDS 1160 pIf MID -SPAN 1. NAIL ALL BUILT-UP STUDS PER DTL. WF08/SD4. 12" SPF 1/2" THREADED ROD @ 48" O.C. ADJUST AS REQ'D TO MISS STUDS 1160 pli 3rd. PT. 7" EMBEDMENT 16" SYP (3) 12d TOENAILS (3) 12d TOENAILS NO UPLIFT MID -SPAN 5. SEE STRUCTURAL COVER SHEET FOR LVL SPECIFICATIONS. 16" SYP 1/2" THREADED ROD @ 48" O.C. ADJUST AS REQ'D TO MISS STUDS 1160 pif MID -SPAN 1 16" SY P 1/2" THREADED ROD @ 48" O.C. ADJUST AS REQ'D TO MISS STUDS 1160 pif -ird. PT. 3 F6] 12" SYP (3) 12d TOENAILS (3) 12d TOENAILS NO UPLIFT MID -SPAN TOPOST: SIMP.HTS20ORLSTA18 12" SYP 1/2" THREADED ROD @ 48" O.C. ADJUST AS REQ'D TO MISS STUDS 1160 pIf MID -SPAN 860 12" SYP 1/2" THREADED ROD @ 48" O.C. ADJUST AS REQ'D TO MISS STUDS 1160 plf ird PT. 3 STANDARD BEARING WALL W/THREADED ROD NOTES 1 . VERIFY w/PLAN FOR WALL SIZE. ASSUME 2x4 STUDS U.N.O. 2. ALL LUMBER TO BE EITHER SPIF #2 OR SYP #2 U.N.O. (CAN BE SUBBED WITH OUT REVIEW) ALWAYS NAIL STUDS TO TOP AND BOTTOM PLATE W/ (3) 12d TOENAILS 3. IF BEARING WALL IS NOT CALLED OUT CONTACT E.O.R. 4. IF "BW" CALLED OUT ON 2nd FLR. SEE PLAN FOR STUD TO STUD CONNECTIONS. 5. ATTACH ALL STUDS TOP AND BOTTOM W/ (3) 12d TOENAILS. 6. MID OR 1/3 PT BLOCKING TO BE 2x W/ (2) 12d TOENIALS EACH END. 7. Y2" THREADED ROD w/ MIN 6" EMBED (OR 6" PAST STEP DOWN) wl SIMPSON SET EPDXY. SEE ABOVE FOR SPACING. CENTERED Win TOP PLATE, FOLLOW SIMPSON INSTRUCTIONS FOR INSTALLATION OF ROD AT BASE. NUT AND 2"x2"x1/4" WASHER @ TOP. THREADED ROD TO -BE PLACED 6" AWAY FROM ANY STRUCTURAL COLUMN UNLESS PLANS INDICATE CONNECTIONS. 8. 2x P.T. PLATE AT BASE OF BRG.WALL W/ THREADED ROD. NO ADDIT'L BASE CONNECTIONS TO THE FOUNDATION ARE REQ'D IF B RG. WALL IS INDICATED WITH BW1, BW4, BW7, & BW10. THESE WALLS ARE ONLY SUPPORTING THE FLOOR LOAD AND DO NOT HAVE UPLIFT, THE STUDS ARE TOENAILED/ ENDNAILED TO THE PLATE AND THE 2X BASE PLATE CAN BE ATTACHED WITH HARD CASED GUN NAILS & THE ANCHOR BOLT ATTACHMENT INDICATED IN BEARING WALL SCHEDULE IS NOT REQ'D. 9. AT SHEAR WALL LOCATIONS ONLY: NUT & WASHER @ BASE OF THREADED ROD ARE REQ'D. SEE PLAN FOR ADDIT'L SHEARWALL INFO. AND DETAILS. 10. FOR BEARING WALL TO MASONRY CONNECTION SEE DETAIL MD03/SD2 U.N.O. ON PLAN. 11. AT HEADER LOCATIONS WITHIN BEARING WALLS SEE DETAIL WF09/SD3 U.N.O. ON PLAN. 12. COLUMNS Win BEARING WALLS w/ UPLIFT THAT DO NOT SHOW A BASE CONNECTION: CONTRACTOR TO INSTALL THREADED ROD Win 6" OF COL. (MIN CENTER TO CENTER SPACING OF THREADED ROD IS 8") 13. IF PLUMBING IS TO BE RUN THROUGH BEARING WALL, CONTACT EOR FOR FURTHER REVIEW. 14. AT NON-BEARING WALL LOCATIONS 2x4 SPF#2 STUDS @ 24"o.c. MAX. ARE ADEQUATE. AT NON-BEARING HEADERS USE (2)2x4 FLAT w/(3)12d TOENAILS EA. SIDE AND CRIPPLES AT 24"o.c. AT 2 -STORY OPEN AREAS INSTALL NON-BEARING WALL STUDS @16"o.c. A SINGLE BASE PLATE (P.T. IF AGAINST CONCRETE) AND SINGLE TOP PLATE ARE ADEQUATE LEAVE A 11'GAIP FROM TRUSS TO TOP PLATE AND ATTACH USING 4 EITHER (2)12d TOENAILS OR SIMPSON DTC CLIP. ATTACH BASE PLATE w/ EITHER GUN NAILS @32"o.c. OR (2)12d NAILS TO EACH FLOOR TRUSS. 1111 �1111 111 11 '!Ij COLUMN SCHEDULE <3> (2)2X4 SPF #2 BUILT UP STUD COLUMN 8d (3)2X4 SPF #2 BUILT UP STUD COLUMN 10d (4)2X4 SPF #2 BUILT UP STUD COLUMN 12d (2)2X6 SPF #2 BUILT UP STUD COLUMN 16d (3)2X6 SPF #2 BUILT UP STUD COLUMN 8d RINIG SHANK (2)2X8 SPF #2 BUILT UP STUD COLUMN NAILING NOTES (3)2X8 SPF #2 BUILT UP STUD COLUMN <8> (3)2X4 SYP #2 BUILT UP STUD COLUMN 2. CONNECTORS MAY USE DIFFERENT NAIL LENGTHS. MINIMUM NAIL (2)2X6 SYP #2 BUILT UP STUD COLUMN ADEQUATE AS LONG AS IT DOES NOT EXTEND THRU THE MEMBER IT'S (2)2X8 SYP #2 BUILT UP STUD COLUMN ON MASONRY: SIMP. META16 44 SYP #2 POST (2)2x12 #2 SYP w/21" FLITCH PLATE 6x6 SYP #2 POST <8> 8x8 SYP #2 POST <�> 3-1/2"x3-1/2" LVL COLUMN. <s> 3-1/2"x5-1/4" LVL COLUMN.. B2x10 3-1/2"x7" LVL COLUMN. TO MASONRY: SIMP. HU410 OR HUC410 w/(10)10d 3-1/2"x9-1/2" LVL COLUMN. (2)ply 1900 5-1/4"x5-1/4" LVL COLUMN. H 1 OA w/(1 8)1 Od x 1 -1" NAI LS OR 2 5-1/4"x7" LVL COLUMN. H10A 1015 7"x7" LVL COLUMN. 31 F 3 1/2" X 11 7/8" LVL COLUMN FRAME TO FRAME 5 1/4" X 9 1/2" LVL COLUMN STANDARD COLUMN NOTES 1. NAIL ALL BUILT-UP STUDS PER DTL. WF08/SD4. 2. ALL POST/ LVL COLUMNS IN EXTERIOR CONDITION SHOULD BE P.T. OR WOLMANIZED. 3. CONTRACTOR TO USE ABU BASE CONNECTORS @ SPF/SYP SOLID POSTS. AT EXTERIOR CONDITIONS 4x4: ABU44 w/(12)16d NAILS & �" EPDXY ANCHOR w/MIN. 8 7" EMBEDMENT 6x6: ABU66 w/(12)16d NAILS & �" EPDXY ANCHOR w/MIN. 7" EMIBEDMENT 8x8: ABU88 w/(l 8)16d NAILS & (2)f�" EPDXY ANCHORS wl 8 MIN. 7" EMBEDMENT 4. POST/LVL INSTALLED WITHIN BRG. WALL TO BE WITHIN TOP AND BASE PILATE U.N.O. ON PLANS. 5. SEE STRUCTURAL COVER SHEET FOR LVL SPECIFICATIONS. NAIL SCHEDULE STANDARD NAIL GENERAL DIAMETER/ LENGTH 8d .131 " x 2-1" 2 10d .148" x 3" 12d .148" x 3-1" 4 16d .162" x 31" 2 8d RINIG SHANK .113" x 22" NAILING NOTES 1. CONTRACTOR MAY USE A DIFFERENT NAIL THEN INDICATED AS LONG AS IT MEETS OR EXCEEDS THE DIAMETER AND LENGTH INDICATED. 2. CONNECTORS MAY USE DIFFERENT NAIL LENGTHS. MINIMUM NAIL LENGTH PER CONNECTOR IS REQ. IF LONGER NAIL IS USED IT IS ADEQUATE AS LONG AS IT DOES NOT EXTEND THRU THE MEMBER IT'S BEING ATTACHED TO. CONNECTOR SCHEDULE TAG BEAM SIZE CONNECTIONS VALUES VALUES TAG SIMPSON CONNECTOR TYPE SPF(Ib) SYP(Ib) (2)2x8 #2 SYP META16 w/(7) 10dxll" NAILS OR 2 B2x8 WITH 1/2" FLITCH w/(6)10d NAILS & (14)"'x23' 4 4 F-11 M ETA20 w/(7) 1 Od x 111' NAILS 2 FRAME TO CMU 1450 1450 ON MASONRY: SIMP. META16 (2)META16 OR (2)META20 (2)2x12 #2 SYP w/21" FLITCH PLATE TOPOST: SIMP.HTS20ORLSTA18 Ifl (1)ply TRUSS (110)1 Od x 1-21" NAILS FRAME TO CMU (1)ply 1985 (1)ply 1985 B2x10 (2)ply TRUSS (12) 16d x li" NAILS 2 TO MASONRY: SIMP. HU410 OR HUC410 w/(10)10d (2)ply 1900 (2)ply 1900 NAILS & (18)"'x23" TAPCONS 4 4 H 1 OA w/(1 8)1 Od x 1 -1" NAI LS OR 2 H10A 1015 H 1 OA 1340 31 F (2)ply TRUSS H I OA -2 w/(l 8) 1 Od x 11" NAILS 2 FRAME TO FRAME H10A-2 1070 H 1 OA -2 1245 H5.5x1 1.25 HTS20 w/(24)1 Od x 1 i" NAILS 2 (10) 10d NAILS B2x12 WITH 1/2" FLITCH TO MASONRY: SIMP. HU410 OR HUC410 w/(10)10d (AT EXT LOCATIONS INCLUDE (3)12d TOENAILS) FRAME TO FRAME 1245 1450 PLATE BETWEEN PLIES ON MASONRY: SIMP. META16 HEADER SUPPORT # JACKS/KINGS REQ'D. @ OPENING (2)HTS20 w/(24)10d x 112" NAILS TOPOST: SIMP.HTS20ORLSTA18 JACKS @ EA. END KINGS @ EA. END TOBEAM: SIMP.HUC410w/(18)16d& 1 1 (AT EXT LOCATIONS INCLUDE (3)12d TOENAILS) FRAME TO FRAME 2490 2900 F6] H2.5A wl(l 0)8d FRAME TO FRAME 535 600 MTS 12 w/(1 4)1 Od x 1 "' NAI LS 2 TOPOST: SIMP.HTS20ORLSTA18 TOBEAM: SIMP.HUC410w/(18)16d& (AT EXT LOCATIONS INCLUDE (3)12d TOENAILS) FRAME TO FRAME 860 1000 ElMGT TO MASONRY: SIMP. HU41 0 OR HUC41 0 w/(1 0)1 Od w/(22)10d �" EPDXY ANCHOR w/SIMP. SET EPDXY MIN. 8 FRAME TO CMU 3140 3140 ON MASONRY: SI MP . META16 7" EMBEDMENT TOPOST: SIMP.HTS20ORLSTA118 1fl 8. HTT4 w/(1 8)16d x 21" NAILS & " EPDXY ANCHOR w/SIMP. 2 FRAME TO CMU 3640 4235 B3.5x16 SET EPDXY MIN. 7" EMBEDMENT TO MASONRY: SIMP. HU41 0 OR HUC41 0 w/(1 0)1 Od NAILS & (18)-l"X22" TAPCONS 4 4 HGT-2 w/(16)10d NAILS w/g3" EPDXY ANCHOR w/SIMP. SET TO POST: (2) SIMP. HTS20 OR LSTA18 11-01 ON MASONRY: (2) SIMP. META16 B5.25x16 FRAME TO CMU 6280 6280 NAIL TOGETHER USING (3) ROWS OF 12d NAILS EPDXY MIN. 5" EMBEDMENT @ 6" O.C. EACH SIDE TO POST: (2) SIMP. HTS20 OR LSTA18 HTSM 16 w/(8)1 Od NAILS & (4) -1"x 2-1" TAPCONS 4 4 FRAME TO CMU 1020 1175 LSTA 18 W/(l 4)1 Od NAILS HEADER TO STUDS 1110 1235 I (2)LSTA18 w/(14)10d NAILS HEADER TO STUDS 2220 2470 OF BEAM LSTA18 w/(14)10d NAILS CENTERED EACH STUD STUDS TO BEAM/GT 833plf 928plf F15] LSTA24 w/(1 8)1 Od NAILS CENTERED EACH STUD STUDS TO BEAM/GT 1235 1235 EMSTC28 w/(36)16d SINKERS CENTERED STUDS TO BEAM/GT 2980 3455 F17] MSTC40 w/ (52) 16d SINKERS CENTERED STUDS TO BEAM/GT 4305 4745 LTT20B w/(10) 1 Od NAILS & �'EPDXY ANCHOR w/SIMP. SET 8 Efl EPDXY MIN. 7" EMBEDMENT MIN. 7"EMBED.-AT LVL/PL COLUMN TO FTG. OR 1290 1300 COLUMNS USE (18)#10xl2l" SID SCREWS INSTEAD OF NAILS CMU HTT4 w/(1 8) 16d x 21" NAILS w481" EPDXY ANCHOR w/SIMP. 2 ESET EPDXY MIN. 7" EMBED. -AT LVL/PL COLUMNS USE COLUMN TO FTG. 3640 4235 (1*)#10x1!" SID SCREWS INSTEAD PF NAILS 2 (3)HTS20 w/(24)1 Od x 1 -1" NAILS 2 (AT EXT LOCATIONS INCLUDE (3)12d TOENAILS) FRAME TO FRAME 3735 4350 F 211 MSTCM40 W/ (14) 16d SINKERS AND (10) 1/4"x2-1/4" TITENS FRAME TO CMU 2420 2800 F 22] SIMPSON HGUS 5.50/10 W/ (63) 16d NAILS GIRDER TO COLJ BEAM 9100 4095 F2 HUC210-2 HEADER TO CMU wl (18) 1/4"x2-3/4" SIMPSON GRAVITY:5085 GRAVITY:5085 3] TITENS & (10) 1 Od NAILS FRAME TO CMU UPLIFT:1810 UPLIFT:1810 R24 HUS26 TO LEDGER W/(14)16d NAILS AND TO TRUSS 1335 1550 W/(6)16d NAILS FRAME TO FRAME F25] HUSC210-2 W/(8)16d NAILS TO BEAM AND (8)16d NAILS TO FRAME TO FRAME GRAVITY:2125 GRAVITY -2125 COLUMN UPLIFT:3290 UPLIFT:3290 LTT20B w/(10) 10d NAILS & �'EPDXY ANCHOR w/SIMP. SET 8 FRAME TO CMU 1290 1300 I EPDXY MIN. 7" EMBED. I STANDARD CONNECTOR NOTES ALL TRUSS/BEAM TO MASONRY CONNECTIONS TO BE SIMP. META16, U.N.O. ON PLAN AT FLOOR TRUSSES PARALLEL TO MASONRY WALLS CONNECT w/SIMP. META16 @ 24"o.c. OR �32"o.c. VERIFY w/ TRUSS SHOP DRAWINGS FOR VERTICAL SPACING WITHIN FLOOR TRUSS. (IF SITTING ON FRAME WALL USE SIMP. LSTA18(14) @ 24"o.c. OR 32"o.c.) CONNECT ALL CONTINUOUS RIM BOARDS TO TOP OF MASONRY W/SIMP. META16, @ 32"o.c. MAX. AND (2) AT EACH CORNER. 2. ALL TRUSS/BEAM TO FRAME CONNECTIONS TO BE SIMP. H10A FOR SINGLE PLY, OR HIOA-2 FOR 2 -PLY U.N.O. ON PLAN 3. CONNECT ALL TYPICAL HIP JACKS (CORNER JACKS) TO FRAME USING SIMP. H2.5A CONNECTOR. IF UPLIFT EXCEEDS 5351bs USE (2) H2.5A CONNECTORS. 4. CONNECT ALL INTERIOR FLOOR TRUSSESMOISTS TO INTERIOR BRG. WALLS USING (3)12d TOENAILS, 5. ALL TRUSS TO TRUSS CONNECTIONS TO BE SPECIFIED BY TRUSS MANUFACTURER, U.N.O. ON PLAN. 6. MISSED LINTEL STRAPS: CONTRACTOR TO INSTALL SIMP. HTSM16 @ EACH MISSED META16 STRAP LOCATION. IF DOUBLE META16 @ A 2 -PLY OR 1 -PLY TRUSS IS MISSED, USE (2)HTSM16 STRAPS. IF UPLIFT IS HIGHER THEN 2100lbs, CONTACT E.O.R. FOR FURTHER REVIEW. STANDARD HEADER NOTES 1. VERIFY w/PLAN FOR CORRECT LENGTH OF HEADER REQ'D. SIZE INDICATED ON PLAN IS MINIMUM REQ'D. PER LOCATION. LARGER HEADER MAY BE INSTALLED w/OUT APPROVAL FROM E.O.R. 2. ALL HEADER JACKS/KINGS TO MATCH WALL LUMBER GRADE U.N.C. ON PLAN. ATTACH STUDS TOGETHER FOLLOWING DTL. WF08/SD4. 3. NAIL HEADER PLIES (INCLUDING LVLs) TOGETHER USING (2) ROWS OF 10d NAILS @ 12"o.c. ONE SIDE. MIN. 2" FROM TOP AND BOTTOM. USE (3) ROWS IF HEADER IS 2x10 OR LARGER. TOP -LOADED HEADERS ONLY. CONTACT E.O.R. IF MEMBERS BUCKET INTO HEADER 4. NAIL KING STUDS TO HEADER w/(3) 10d TOENAILS PER SIDE IN ADDITION TO NAILING PER HEADER SCHEDULE. 5. IF MORE THEN (1)KING IS REQ'D. AS PER HEADER SUPPORT TABLE, GC TO INSTALL REQ'D. NAILS FROM 1st KING INTO HEADER THEN ATTACH ADDIT'L KING PER DTL. WF08/SD4. OTHERWISE, CONTACT E.O.R. FOR REQ'D. WOOD SCREWS. 6. IF HEADER IS NOT SPECIFIED CONTACT E.O.R. 7. SEE STRUCTURAL COVER SHEET FOR LVL SPECIFICATIONS. 8. SEE DTL. WF09/SD3 FOR IST FLOOR HEADER CONSTRUCTION AND CONNECTIONS AT 2 STORY CONDITIONS. SEE 2ND FLOOR NOTES FOR MORE INFO. BEAM SCHEDULE TAG BEAM SIZE CONNECTIONS H2x6 (2)2x6 #2 SYP w/2"' FLITCH PLATE TOPOST: SIMP.HTS20ORLSTA18 TW TOBEAM: SIMP. HUC48w/(14)16d NAILS H2x8 (2)2x8 #2 SYP TO MASONRY: SIMP. HU48 OR HUC48 B2x8 WITH 1/2" FLITCH w/(6)10d NAILS & (14)"'x23' 4 4 H2x10 PLATE TAPCONS - ----------- . ......... __1 - 09.15.2016 ON MASONRY: SIMP. META16 H2x12 (2)2x12 #2 SYP w/21" FLITCH PLATE TOPOST: SIMP.HTS20ORLSTA18 TOBEAM: SIMP.HUC410w/(18)16d& H3.5x5.5 (2)2xl 0 #2 SYP (10) 10d NAILS B2x10 WITH 1/2" FLITCH TO MASONRY: SIMP. HU410 OR HUC410 w/(10)10d H3.5x7.25 PLATE NAILS & (18)"'x23" TAPCONS 4 4 ON MASONRY: SIMP. META16 H3.5x9.25 (2)1.75"x9.25" LVL TOPOST: SIMP.HTS20ORLSTA118 TOBEAM: SIMP.HUC410w/(18)16d& H5.5x1 1.25 (2)2x12 #2 SYP (10) 10d NAILS B2x12 WITH 1/2" FLITCH TO MASONRY: SIMP. HU410 OR HUC410 w/(10)10d H3x12 PLATE NAILS & (11 8)1"x22" TAPCONS 4 4 PLATE BETWEEN PLIES ON MASONRY: SIMP. META16 HEADER SUPPORT # JACKS/KINGS REQ'D. @ OPENING OPENING SIZE TOPOST: SIMP.HTS20ORLSTA18 JACKS @ EA. END KINGS @ EA. END TOBEAM: SIMP.HUC410w/(18)16d& 1 1 (10) 10d NAILS B3.5x1 1.25 (2)1.75"xl 1.25" LVL TO MASONRY: SIMP. HU410 OR HUC410 w/(10)10d NAILS & (1 8)-i"x22" TAPCONS 4 4 ON MASONRY: SIMP. META16 TOPOST: SIMP.HTS20ORLSTA18 TOBEAM: SIMP.HUC410w/(18)16d& (10) 1 Od NAILS B3.5x1 1.875 (2)1.75"xl 1.875" LVL TO MASONRY: SIMP. HU41 0 OR HUC41 0 w/(1 0)1 Od NAILS & (18)1"x23" TAPCONS 4 4 ON MASONRY: SI MP . META16 TOPOST: SIMP.HTS20ORLSTA118 TOBEAM: SIMP.HUC410w/(18)16d& (10) 1 Od NAILS B3.5x16 (2) 1.75"x 16" LVL TO MASONRY: SIMP. HU41 0 OR HUC41 0 w/(1 0)1 Od NAILS & (18)-l"X22" TAPCONS 4 4 ON MASONRY: SIMP. META16 TO POST: (2) SIMP. HTS20 OR LSTA18 ON MASONRY: (2) SIMP. META16 B5.25x16 (3) 1.75"x16" LVL NAIL TOGETHER USING (3) ROWS OF 12d NAILS @ 6" O.C. EACH SIDE TO POST: (2) SIMP. HTS20 OR LSTA18 ON MASONRY: (2) SIMP. META16 B3.5x2O (2) 1.75"x2O" LVL * U.N.O. NAIL TOGETHER USING (3) ROWS OF 12d I I NAILS @ 6" O.C. EACH SIDE STANDARD BEAM NOTES 1. NAIL ALL (2) 2x BEAMS TOGETHER USING (2) ROWS OF 12d NAILS @ 12"o.c. (TYP. ONE SIDE) USE 3 ROWS WHEN 2x10 OR LARGER. MIN. 2" FROM TOP AND BOTTOM OF BEAM NAIL ALL LVL BEAMS TOGETHER USING (3) ROWS OF 12d NAILS @ 6"o.c. (TYP. ONE SIDE) MIN. 2" FROM TOP AND BOTTOM OF BEAM 2. VERIFY w/PLAN CORRECT LENGTH OF BEAM REQ'D. (MIN. 4" BRG. EA. END) 3. SEE PLAN FOR TOP OR BOTTOM OF BEAM INDICATIONS. 4. BEAMS ARE NOT TO BE DRILLED OR NOTCHED IN ANY WAY WITHOUT WRITTEN APPROVAL FROM THE E.O.R. 5. SEE STRUCTURAL COVER SHEET FOR LVL SPECIFICATIONS HEADER SCHEDULE TAG HEADER FASTENERS H2x6 (2)2x6 #2 SYP w/2"' FLITCH PLATE ATTACH KING STUD TO HEADER w/(6) TW 16d NAILS H2x8 (2)2x8 #2 SYP w/21" FLITCH PLATE ATTACH KING STUD TO HEADER w/(8) TM - 2153124 16d NAILS H2x10 '2)2xl 0 #2 SYP w/1" FLITCH PLATE ATTACH KING STUD TO HEADER w/(1 0) - ----------- . ......... __1 - 09.15.2016 16d NAILS H2x12 (2)2x12 #2 SYP w/21" FLITCH PLATE ATTACH KING STUD TO HEADER wl(10) 16d NAILS H3.5x5.5 (2)1.75"x5.5" LVL ATTACH KING STUD TO HEADER w/(6) 16d NAILS H3.5x7.25 (2)1.75"x7.25" LVL ATTACH KING STUD TO HEADER w/(8) 16d NAILS H3.5x9.25 (2)1.75"x9.25" LVL ATTACH KING STUD TO HEADER w/(10) 16d NAILS H5.5x1 1.25 (3)1.75"xl 1.25" LVL ATTACH KING STUD TO HEADER w/(12) 16d NAILS H3x12 (3) 2xl 2 #2 SYP w/ I" FLITCH 2 ATTACH KING STUD TO HEADER w/(10) PLATE BETWEEN PLIES 16d NAILS HEADER SUPPORT # JACKS/KINGS REQ'D. @ OPENING OPENING SIZE SEE PLAN FOR WALL WIDTH JACKS @ EA. END KINGS @ EA. END V-0" TO 3'- 11 " 1 1 4'-0" TO V-10" 2 2 ROOF NOTES: 1 . THE ROOF PLAN DEPICTED IS NOT INTENDED TO SERVE AS A TRUSS DESIGN. 2. TOP PLATE HEIGHTS VARY. SEE BUILDING SECTIONS, WALL SECTIONS AND ELEVATIONS FOR BEARING HEIGHTS. 3. TRUSS SPACING SHALL BE 24" O.C. MAX. UNLESS OTHERWISE NOTED. CONVENTIONAL FRAMING SHALL BE 16" O.C. MAX. OR AS OTHERWISE NOTED. 4. FRAME WALLS UP TO UNDERSIDE OF ROOF TRUSSES AT ALL NON-BEARING WALLS AND AT VOLUME AREA UNLESS NOTED OTHERWISE. STUDS CAN BE 24" O.C. W/ SINGLE TOP AND P.T. BASE PLATE LEAVE 1 1/2" GAP FROM TOP PLATE TO TRUSS BOTTOM CHORD. CONNECT TRUSS TO NON-BEARING WALL w/ SIMPSON DTC OR (2) 12d TOENAILS. 5. ALIGN TRUSSES AND HAND FRAMING SO ALL GYPSUM WALL BOARD WILL BE CONTINUOUS FROM FLOOR TO CEILING. 6. TRUSS MANUFACTURER TO INSURE DESIGN CONSIDERATION TO THE FOLLOWING ADDITIONAL LOADS: A) ALL CEILING HUNG SOFFITS AND SOFFITS WITH CABINETS AS SHOWN ON PLANS. B) ATTIC LOCATED HVAC; UNITS AS SHOWN ON PLANS. 7. REFER TO MANUFACTURER SPECIFICATIONS FOR INSTALLATION REQUIREMENTS OF ALL HARDWARE BEFORE INSTALLATION. 8. GC REQ'D TO PROVIDE PERMANENT BRACING/ BLOCKING PER BCSI 1 (CURRENT EDITION). SEE COVER SHEET NOTES FOR MORE INFO & STANDARD DETAILS IN THIS DRAWING SET FOR ADDITIONAL BRACING/ BLOCKING INFO. 9. ALL TRUSS -TO -TRUSS CONNECTORS ARE TO BE PROVIDED BY TRUSS SUPPLIER. THIS INCLUDES BUT IS NOT LIMITED TO PIGGY BACK TRUSSES AND VALLEY TRUSSES 10. USE 5/8" TYPE X GYPSUM BOARD ON CEILING IN GARAGE WHEN LIVING SPACE IS ABOVE THE GARAGE. 11. IF ROOF TRUSS LAYOUT DEPICTS TRUSS LABELS OR ID'S, THIS LAYOUT HAS BEEN PROVIDED BY A TRUSS COMPANY TO USE FOR THE DESIGN OF THIS PROJECT. OTHERWISE AN ENGINEERED LAYOUT HAS BEEN DETERMINED BUT PRIOR TO CONSTRUCTION OR TRUSS FABRICATION, FINAL TRUSS LAYOUT AND TRUSS SHOP DRAWS ARE TO BE SUBMITTED TO ENGINEER OF RECORD (E.O.R.) FOR REVIEW AND APPROVAL. AT THIS TIME THE E.O.R. RESERVES THE RIGHT TO REVISE THE PLAN AS REQUIRED PER THE REVIEW OF THE FINAL TRUSS LAYOUT AND TRUSS SHOP DRAWS, ADDITIONAL FEE'S MAY APPLY. STARTING CONSTRUCTION OR TRUSS FABRICATION PRIOR TO THIS REVIEW IS NOT ADVISED, AND THE E.O.R. IS NOT RESPONSIBLE FOR ADDITIONAL COSTS DUE TO REVISIONS OF THE PLAN. IF CONVENTIONAL FRAMING IS SHOWN, NO TRUSS APPROVAL IS REQUIRED, UNLESS LAYOUT IS REVISED W/OUT WRITTEN APPROVAL FROM MCD. 12. IF DESIGN DOCUMENTS INDICATE THAT AN A/C UNIT IS TO BE RECESSED INTO THE ROOF SYSTEM, THE TRUSS SUPPLIER IS TO COORDINATE WITH THE DESIGNER AND BUILDER TO DETERMINE THE REQUIRED SIZE. (2) 751b MIN POINT LOAD SHOULD BE ADDED TO EITHER THE TOP OF BOTTOM CHORD OF THE TRUSS IN THE AFFECTED AREAS. THIS LOAD SHOULD BE INDICATED ON THE TRUSS SHOP DRAWINGS. CONNECTIONS OF THE A/C UNIT TO THE TRUSSES SHOULD BE SUPPLIED BY EITHER THE CONTRACTOR OR A/C SUPPLIER. SEE TB01/SD2 FOR MORE INFORMATION. BUILDER NOTE: IF THE TRUSS LAYOUT SHOWN DOES NOT MATCH THE TRUSS MANUFACTURERS LAYOUT -1 --- STOP ---- AND CALL THE ENGINEER OF RECORD PRIOR TO PLACEMENT OF ANY TRUSSES NAILING SCHEDULE: ROOFS: ROOF SHEATHING TO BE 15/32" OSB (WITH SHINGLE), 5/8" OR 19/32" OSB (WITH TILE) FASTENING WITHIN 4'-0" OF EAVES TO BE 4" O.C. AT ALL SUPPORTED EDGES AND 6" O.C. IN FIELD. FOR ALL OTHER AREAS NAIL @ 6" O.C. AT ALL SUPPORTED EDGES AND 6" O.C. IN FIELD. SHEATHING TO BE PLACED WITH LONG DIMENSION PERPENDICULAR TO SUPPORTS (TRUSSES). PROVIDE PLY CLIPS AT ALL UNSUPPORTED ROOF SHEATHING JOINTS EXCEPT AT PITCH CHANGE LOCATIONS. PLY CLIPS TO BE SPACED NO MORE THAN 24" O.C. GABLE ENDS: ALL SHEATHING TO BE MIN. 15132" O.S.B. AND SHALL BE NAILED (1) ROW @ 3" O.C. AT TOP PLATE AND (1) ROW AT BOTTOM PLATE OF WALL, 6" O.C. ALL OTHER EDGES AND 6" IN FIELD. BLOCKING SHALL BE PLACED AT ALL SHEATHING JOINTS. EXTERIOR WALLS: SEE WF10/SD4 FOR MORE INFO. NAILS: NAILS USED IN ROOF SHEATHING APPLICATIONS SHALL BE 8d RING SHANK NAILS. ALL OTHER SHEATHING APPLICATIONS SHALL BE 8d, 8d RING OR SPIRAL SHANK, HAND OR GUN DRIVEN NAILS. GUN DRIVEN NAILS SHALL HAVE HEAD SIZE EQUIVALENT TO HAND DRIVEN NAILS. FASTENERS FOR PRESERV- ATIVELY TREATED WOOD SHALL BE HOT -DIPPED ZINC -COATED GALVANIZED STEEL, STAINLESS STEEL, SILICON BRONZE OR COPPER. THE COATING WEIGHTS SHALL BE IN ACCORDANCE WITH ASTM A 153. APA SHEATHING NOTE: 24/16 SPAN RATED SHEATHING REQUIRES BLOCKING AT ALL UNSUPPORTED PANEL EDGES AT HIP LOCATIONS. BLOCKING TO BE 2X4 ATTACHED AT EACH END WITH (3) 10d TOENAILS. FLOOR FRAMING NOTES GENERAL NOTES 1. FLOOR JOIST/TRUSS HANGERS SUPPLIED & ENGINEERED BY FLOOR JOIST/TRUSS CO. 2. REFER TO TRUSS MANU. DRAWINGS FOR TRUSS DESIGNATIONS. 3. GENERAL FLOORING FINISHES ARE ACCEPTABLE. IF LIGHTWEIGHT CONCRETE OR SELF LEVELING CONCRETE IS REQ. CONTACT E.O.R. ALONG WITH TRUSS CO. TO VERIFY FLOOR TRUSS DESIGN. NAILING SCHEDULE FLOOR SHEATHING TO BE & PLYWOOD OR OSI3 (U.N.0), WITH LONG DIMENSION PERPENDICULAR TO SUPPORT (FLOOR TRUSSES). NAILS: NAILS USED IN ALL FLOORING APPLICATIONS SHALL BE 8d, 8d RING OR SPIRAL SHANK, HAND OR GUN DRIVEN NAILS. GUN DRIVEN NAILS SHALL HAVE HEAD SIZE EQUIVALENT TO HAND DRIVEN NAILS, SPACING SHALL BE 6" ON EDGES AND 12" IN FIELD. NOTES: 1. FLOOR JOIST/ TRUSS MANUFACTURER SHALL COORDINATE LOCATIONS OF ALL MECHANICAL CHASES AND PLUMBING TO AVOID CONFLICT. 2. ALL JOIST TO JOIST OR TRUSS TO TRUSS CONNECTIONS SHALL BE SPECIFIED BY THE MANUFACTURER. 3. G.C./BUILDER SEE ARCHITECTURAL DRAWINGS FOR ROUGH OPENING LOCATIONS AND ADDITIONAL INFORMATION REQ. FOR DOOR AND WINDOW INSTALLATION ALONG WITH DIMENSTIONS NOT SHOWN HERE. I I NOTES & CONNECTOR LEGEND 1/4"=11-011 w z 0 d. U) w Tic I I lilt,, * c) LL 00 0 F0 z co c; < 0 z < 01 0 m U - u 0 cn !91 0 4-� 0 co 01", CN u 6 0 z u r_ 0 .2 z u < z rn S0�) 6) z 0 z 0 U) q w -J w o6 Lu 0 w m E z 1-_ C/) _j z 0 < �u- z z z C) r- I u� 0 0 0 00 U) wz!�m U) �Z- E2 .- r -- w CL . 0 n < 0 0 0) sn (/) 0 :c 2 .. a 1--'_ Lu w 0 Z Z 0 �) I'- Z E < < ZO ui 0 ,, -�Oxf 06 0 m C6 3: of 04 C14 CD Lu LL W 04 _j Z 0 w 0 I-- u o i ILLI 7: Z W r_"N 0 Lj Lu z 0 C) M z z < 0 F_ 0 co co W) uj Lo 04 0 0 0 0 Z UJ W W N5 0 0 o 0 m STRUCTURALENG: BED DRAFTING: -STRUCT: TW QC CHECK: 11 ---- ----- - --------- MB JOB No. TM - 2153124 SCALE: AS INDICATED DATE: - ----------- . ......... __1 - 09.15.2016 S4.1 CONTRACTOR TO VERIFY AT CORNERS PRECAST "U" METAL LATH OR WIRE SCREEN THE GROUT IS LEVEL PROVIDE LINTEL W/ 3000 OVER COURSES NOT Ri WITH TOP OF BLOCK FOR STANDARD #5 psi CONC. PER TO BE FILLED. (SHEET METAL PROPER TRUSS/ FLOOR HOOK BAR. LAP LINTEL PLAN. IF & PAPER FELT PROHIBITED) SYSTEM BEARING (MIN 3") OTHER BARS INTO REBAR IS .,:.,.LINTEL PER PLAN z w 0 w z 0 U) CORNER AS li INDICATED IN 10" HOOK LINTEL, #5 TO BE HOOKED INTO SIDE VERTICALS �4. 41' 4 '4 iiiiiiiiiii� .. 4 A . .... IF. ii;.— 96— F -- U) '4 A 4 0 A u_ < z 4 44' 4 < .4 04 .. A z w w 4 BOTTOM STEEL IN LINTEL IF V) INDICATE - SHOULD HOOK INTO VERTICAL CELLS 4 44 ROUGH OPENING PER PLAN 4. 4 TYPICAL MASONRY CONSTRUCTION SCALE: 3/4" = V-10" SEE PLAN FOR TOP OF WALL AND LINTEL INFO GRADE40 GRADE60 BAR SIZE BEND 0 LENGTH LAP SPLICE BEND 0 r LAP SPLICE "Alf NON A M TYPI AL SHEAR WALL SEGMENT .,:.,.LINTEL PER PLAN . A 17/8 41/4 7 15 21/4 �i 7 4_ 18 #4 21/2 55/8 91/2 A 3 55/8 121/2 24 #5 31/8 TYPICAL MASONRY CONSTRUCTION SCALE: 3/4" = V-10" SEE PLAN FOR TOP OF WALL AND LINTEL INFO GRADE40 GRADE60 BAR SIZE BEND 0 LENGTH LAP SPLICE BEND 0 LENGTH LAP SPLICE "Alf NON -SHEAR WALLAT OPENING M TYPI AL SHEAR WALL SEGMENT .,:.,.LINTEL PER PLAN . A 17/8 41/4 7 15 21/4 �i 7 91/4 18 #4 TYPICAL MASONRY CONSTRUCTION SCALE: 3/4" = V-10" LINTEL W/ TRANSOM DETAIL SCALE: 3/4" = T-0" REQ'D LAP SPLICE, EMBEDMENT, AND HOOKED REINF. STEEL (INCHES) SEE PLAN FOR TOP OF WALL AND LINTEL INFO GRADE40 GRADE60 BAR SIZE BEND 0 LENGTH LAP SPLICE BEND 0 LENGTH LAP SPLICE "Alf 111311 11C., M "Alf "B" "C" .,:.,.LINTEL PER PLAN . A 17/8 41/4 7 15 21/4 �i 7 91/4 18 #4 21/2 55/8 91/2 1 20 3 55/8 121/2 24 #5 31/8 7 TRANSOM OPENING 25 33/4 7 151/2 30 �/FRAME INFILL AR011i 33/4 81/16 14 30 41/2 81/16 181/2 WINDOW BY BUILDER #7 43/8 9 13/16 16 1/2 SEE FOUNDATION 51/4 913/16 213/4 SEE WF01/SD3 FOR PLAN FOR FILLED CELL INFO. MIN. (1) IS Rii MORE INFO ON EITH ER SIDE U.N.O. I'LFIRSTPLY2X8TO (2) 2X8 SYP#2 P.T. HEADER TUR NED SIDEWAYS. MASONRY WALL W/ DOOR OR WINDOW OPENING �4;; SIMPSON HU28 HANGER @ MAX. OPENING 3 FT EA. END. W/ (6) 1/4"x 2-314" TAPCONS INTO MASONRY & (4) 1 Od X 1 1/2" NAILS INTO HEADER. 2ND PLY TO IST PLY W/ 10d STAGGERED @ 6" O.C. LINTEL W/ TRANSOM DETAIL SCALE: 3/4" = T-0" REQ'D LAP SPLICE, EMBEDMENT, AND HOOKED REINF. STEEL (INCHES) GRADE40 GRADE60 BAR SIZE BEND 0 LENGTH LAP SPLICE BEND 0 LENGTH LAP SPLICE "Alf 111311 11C., "Di" "Alf "B" "C" "D" #3 17/8 41/4 7 15 21/4 41/4 91/4 18 #4 21/2 55/8 91/2 1 20 3 55/8 121/2 24 #5 31/8 7 113/4 25 33/4 7 151/2 30 #6 33/4 81/16 14 30 41/2 81/16 181/2 36 #7 43/8 9 13/16 16 1/2 35 51/4 913/16 213/4 42 4 4 id 4f C) + co �A A LAP SPLICE EMBEDDED 4DO8 REBAR SPLICE DETAIL SCALE: 3/4" = T-0" #3 = 2 Y2" #4 = 2 Y2" #5 = 2 Y2" #6 = 3" #7 = 3 Y2" TYPICAL TRUSS ANCHOR PER PLAN PROVIDE SCREEN WHEN BLOCK BELOW IS NOT REQUIRED TO BE FILLED STANDARD 90 DEGREE HOOK TYP. BOND BEAM 8" x 8" x 16" K.O. LINTEL BLOCK FILL w/ 3000 psi CONIC. w/ (1) #5 DIA. REBAR STD. 90 DEGREE ANGLE 3000 psi CONIC. w/ (1) #5 DIA. REBAR 8" x 8" x 16" CMU U.N.O. INDICATES FILLED CELL FROM FTG. TO TIE BEAM w/ (1) #5 BAR W/ 3000 psi CONC. SEE Mli FOR LAP INFO. rM%_)V1L)r_ %,Lr -MINI UU 1 �W_ FILLED CELL AND REBAR (TYP). MORTAR JOINTS SHOULD NOT BE CUT SEE FOUNDATION FOR FOOTING 20'-8" V C? zo S ].%J.IVI. I.%a.IvI. 9'4" 8'-0" PRECAST LINTEL LOAD TABLE GENERAL CONCRETE LINTEL SCHEDULE LOADS LISTED BELOW HAVE BEEN CALCULATED OR COMPILED FROM DATA FROM THE FOLLOWING APPROVED LINTEL MANUFACTURERS: APPROVED MAN. CAST -CRETE, QUALITY PRECAST CO., AND LOTTS CONCRETE CASTE -CRETE, QUALITY, AND LOTTS w STANDARD LINTELS STANDARD LINTEL NOTES cl CLEAROPENING 8"UNFILLED 8F8-1B/8F8-0B8F16-1B/8F16-0B 8F24-1B/8F24-0B 81`32-113/15F32-013 1. AREAS OF BLOCK ABV. MASONRY OPENINGS ARE TO BE GROUTED SOLID TO TIE BEAM. 11-611 2231 3069/3069 6113/6113 8974/8974 10000 / 10000 2. (1) #5 REBAR IN TIE BEAM IS TO BE CONT. THRUOUT INCLUDING ABV, MASONRY OPENINGS. U.N.O. ... .. ..... 2'-2" 1783 3069/3069 6113/5163 8974/8054 10000 / 10000 21-8" 1343 2693/2561 6113/3820 8974/5961 10000/8107 3. ALL STANDARD LINTELS TO HAVE MIN. 4" BEARING EA, END. ALL RECESSED LINTELS TO HAVE MIN. T-2" 1217 2165/1969 6113/2931 8672/4576 10000/6224 8" BEARING EA. END 3-4' 1006 1663/1349 5365/1999 7342/3123 10000/4249 4. LINTEL MIN. DEPTHS ARE CALLED OUT ON LINTEL PLAN. IF DEEPER LINTEL INSTALLED THAN 4'-0" 860 1651 /1349 5365/1999 7342/3123 10000/4249 INDICATED ON PLAN, THE STRENGTH OF THE LINTEL INCREASES AND IS APPROVED WITHOUT 4'-6" 710 1423/1105 4360/1631 6036/2549 8328/3470 ENGINEERING LETTER. IF A SMALLER LINTEL IS INSTALLED CONTACT EOR FOR APPROVAL. z 6-2" 570 1232/1232 3480/2580 8360/3586 8825/4592 0 6-2" 488 991 /991 2661 /2143 5681/2698 6472/3685 5. 11 ANY LINTEL DEEPER THAN 32" HAS BEEN VERIFIED TO WORK AS A MIN. 32" FOR THE LOAD T -O" 416 752/699 1843/1625 3486/2602 6390/3302 CONDITIONS. ANY LINTEL GREATER THAN 32" HAS A GREATER CAPACITY AND THEREFORE IS 8'-0" 354 726/699 1843/1625 3486/2255 6205/2885 ADEQUATE FOR THE LOADS. 9'-2" 315 618/535 1533/1247 2781 /1946 4754/2489 6. G.C. TO VERIFY ALL LINTEL DIMS IN FIELD WITH WINDOW R.O. SPECIFICATIONS ON PLAN. DIMS C) 101-01, '4 U) 292 567/454 1366/1277 2423/1770 4006/2263 SHOWN ON LINTEL PLAN ARE CLEAR SPAN AND USED TO VERIFY DESIGN OF LINTEL ONLY. VERIFY ui 101-8" 277 492/352 1254/1132 2193/1567 3552/2003 WITH WINDOW/DOCR SUPPLIER SPECIFICATIONS AND COORDINATE WITH EOR AS li 1 V-2" 255 471 /352 1075/1075 1838/1567 2883/2003 7. LINTELS SHOULD BE SHORED UP DURING CONSTRUCTION AS REQUIRED PER THE LINTEL 12'-0" 239 418/297 1075/1045 1838/1446 2883/1848 SUPPLIER SPECS. MCD IS NOT RESPONSIBLE FOR CONSTRUCTION MEANS AND METHODS 12'-8" 0 369/261 1002/984 1697/1361 2630/1738 13'41' 0 328/0 1234/0 1779/0 2662/0 14'-0" 0 292/0 1160/0 1660/0 2439/0 16'-0" 0 284/0 950/0 1379/0 1997/0 MATERIALS - ------ - - - 181-01, 0 211/0 750/0 1177/0 1676/0 18'-8" 0 142/0 598/0 1114/0 1468/0 1. f c PRECAST LI INTELS 3500 PSI. w 20'-0" 0 180/0 598/0 1024/0 1441/0 2. fc PRESTRESSED LINTELS = 6000 psi. 20'-8" 0 145/0 550/0 981 /0 1376/0 3. GROUTED PER ASTM C476 fg = 3000 psi W/ MAXIMUM 3/8" AGGREGATE AND 8" TO 11" SLUMP. 22'-8" 0 1 824/0 1147/0 4. CONCRETE MASONRY UNITS (CMU) PER ASTM C90 W/ MINIMUM NET AREA COMPRESSIVE RECESSED LINTELS -FILLED 0) STRENGTH = 1900 PSI. c:) w m CLEAR OPENING 8111 B/811i 8R14 -113/811i 811113/8111 -,t 2'-4" 1694/1694 3725/3280 5499/5421 5. REBAR PER ASTM A615 GRADE 60. PRESTRESSING STRAND PER ASTM A416 GRADE 00 z, L'i Oill 2'-8" 1425/1425 3343/3280 4933/4933 6. 270 LOW RELAXATION. 7/32 WIRE PER ASTM A51 0, v 6 T-01' 1230/1230 2769/2769 4085/4085 AA. _j Z T-4" 1081 /920 2769/1716 4085/2839 LINTEL DESIGNATION SCHEDULE < (j 001 uj 0 _j 4'-4" 846/833 2121/1716 3127/2839 z 0 ch uj < 5'-4" 664/572 1761/1761 2595/2595 LINTEL F = FILLED WITH GROUT u) Z MARK U = UNFILLED R = RECESSED 64" 526/434 1539/1539 1329/2267 REQUIREMENTS QUANTITY OF #5 REBAR @ Ole 0 T-4" 480/322 1334/1334 1964/1552 BOTTOM OF LINTEL CAVITY 0� _j 8RF6-1B/1T 8'4" 415/235 1152/1152 1694/1552 1 8F16-1B/1T 8F8-1B/1T QUANTITY OF #5 REBAR AT TOP 1) FOR HEADER DEPTHS DEEPER THAN 32", USE VALUES FOR 32" DEEP HEADER 2) FOR HEADER DEPTHS NOT LISTED ON CHART, USE THE VALUES FOR THE NEXT DEPTH DOWN. 8RF14-1B/1T NOMINAL HEIGHT (D 8F16-1B/1T NOMINAL WIDTH 0 TYPE DESIGNATION 8RF14-0B/1T cf) 8F16-0B/1T 1-1/2" CLEAR u 6 i B/1 T z < w Tr— wif u c: 0 #5 REBAR AT TOP MIN. (1) li .0 8F20-0B/1T cu < < C.M.U. z L) z 8RF22-1B/1T GROUT u') '60 L) z #5 REBAR AT BOTTOM OF LINTEL < 8F24-1B/1T z (0 CAVITY NR 8RF22-0B/1T BOTTOM REINFORCING PROVIDED 0 7-5/8" ACTUAL IN LINTEL (VARIES) 8F24-0B/1T 8" NOMINAL WIDTH 8RF30-1B/1T FILLED ii B/1 T 1-1/2" CLEAR 8RF30-OB/IT _j (D < uj 3: #5 REBAR AT TOP MIN. (1) li z 8F32 -li 0 _j I CD < < C.M.U. U) C) = z t; r1_ 8F38 -1 B/1 T 00 � w 0 ;B z in 10 & Z z 6 C6 Lu 0 w E 8F1 2 -1 B/1 T z 1.) 8 (D CO!, < (D < Z U- 0) 6 BOTTOM REINFORCING PROVIDED L) 'i �-:.g 8F40 -0B/1T Z Coco= 0 7-5/8" ACTUAL IN LINTEL (VARIES) w I Z!� _j u) Iz- 8F8 -0B/1T 8" NOMINAL WIDTH < 0 0 0 U) UNFILLED V) W W 0 Z Z Du)�-z E < < ZO I � 0 0 0 2 0 cn SAFE LOAD TABLE NOTES c, <t w c\1 U- C14 ui z 0 1. ALL VALUES BASED ON MINIMUM 4" NOMINAL BEARING. EXCEPTION: SAFE LOADS FOR UNFILLED LINTELS MUST BE REDUCED BY 20% IF BEARING LENGTH IS LESS THAN 6-1/211. SAFE LOADS FOR ALL 0 RECESSED LINTELS BASED ON 4" NOMINAL BEARING. 2. 0 = NOT RATED. uj 3. SAFE LOADS ARE TOTAL SUPERIMPOSED ALLOWABLE LOAD ON THE SECTION SPECIFIED. LLJ 4. SAFE LOADS BASED ON GRADE 40, GRADE 60 MAY BE USED WITHOUT WRITTEN APPROVAL FROM EOR 0'! 5. ADDITIONAL LATERAL LOAD CAPACITY CAN BE OBTAINED BY THE DESIGNER BY PROVIDING ADDIONAL REINFORCED MASONRY ABOVE THE PRECAST LINTEL. 6. ONE #7 REBAR MAY BE SUBSTITUTED FOR TWO #5 REBARS IN 8" LINTELS ONLY. -00, 7. THE DESIGNER MAY EVALUATE CONCENTRATED LOADS FROM THE SAFE LOAD TABLES BY CALCULATING THE MAXIMUM RESISTING MOMENT AND SHEAR AT D -AWAY FROM THE FACE OF SUPPORT. 8. FOR COMPOSITE LINTEL HEIGHTS NOT SHOWN, USE SAFE LOAD FROM NEXT LOWER i 9. ALL SAFE LOADS IN UNITS OF POUNDS PER LINEAR FOOT. LLJ 0? N 1 2 04 z 00 z z < 8— F_ 0 co) cf) Ill Lj In �ii 0 0 0 C4 0 Z Uj j LU W 11111 5: a 0 LINTEL PLAN STANDARD 90' HOOK STANDARD 180* HOOK DATE: 09.15.2016 S5 STRUCTURAL ENG: BED DRAFTING: -8TRUCT: TW QC CHECK: MB JOB No. TM - 2153124 SCALE: AS INDICATED STANDARD 90' HOOK STANDARD 180* HOOK DATE: 09.15.2016 S5 (1) #5 FROM FTG. TO (1) #5 FROM FTG. TO IF BRIG. WALL ABOVE- HOLD BRIG WALL BACK 2x BRIG WALL PER 2x BRIG WALL PER w TIE BEAM SPLICE TO TIE BEAM SPLICE TO 1/2" J -BOLT W/ MIN. 6" SO GYP FINISH IS PLAN AND BEARING PLAN AND BEARING F- 4 < BE MIN. 25" GROUT BE MIN. 25" GROUT PAST DEEPEST STEP FLUSH w/ FOUNDATION WALL SCHEDULE WALLSCHEDULE CELL SOLID CELL SOLID REQ'D MIN 4" BELOW MASONRY WALL MASONRY WALL ---------------------------------- - w CONIC. SLAB PER (1) #5 CONT. w/ 1-1/2" SEE PLAN SEE PLAN FOUNDATION PLAN COVER TYP. 10 e, 11-1 /2" COVER TYP. CONIC. SLAB PER 2 1/4" 1 U) FOUNDATION PLAN CONC. SLAB PER CONCRETE SLAB PER CONCRETE SLAB PER w CONCRETE SLAB PER U) FOUNDATION PLAN w uj I FOUNDATION PLAN < FOUNDATION PLAN z z 00 2x FIT SILL PLATE 2x P.T. SILL PLATE A _j 0- 0- -- FOUNDATION PLAN .11 § 0_ Lu :� w VARIES w CL m w w SEE PLAN U) 4. 4: 4 4, 4 4 IA 00 4 .. 0 00 U 44 ,4' 1 4 �q GRADE GRADE z i� w 4 4, -45' 0 0 co 1=7 14 75 < _=�l I F z 0? LLJ < > 7 A -d 400j 10 c) 0 0 M-1 b LL_ 4 — . — I U -,--F - I rr U) t 4 co co LCO w 4 8" 81, 0, 6" (2) #5 BARS CONT. (2) #5 BARS CONT. w > ui C, 4 — 74 ;4 4 4�- 18�­: 1�4 F� W/ 3" COVER TYP. C V FILL @ 95% STANDARD CLEAN COMPACTED 0 (2) #5 BARS CONT. W/ CLEAN COMPACTED :J 'C:1 ED W/ 3" COVER TYP. CLEAN COMPACTED CLEAN COMPACTED 13� rAv H CLEAN COMPACT 0 3" 8" FILL @ 95% STANDARD (2) #5 BARS CONT. w/ 3" FILL @ 95% STAND FILL @ 95% STANDARD V-4" DENSITY FILL @ 95% STANDARD COVER TYP.; AT ilk COVER TYP.; AT ARID Ir— 1-4- DENSITY ___70p DENSITY (2) #5 BARS CONT. w/ 31. cy) 2 -STORY COND. (3) #5 DENSITY 2 -STORY COND. (3) #5 DENSITY COVER TYP.; AT CLEAN COMPACTED BARS REQ'D & FTG TO BARS REQ'D & FTG TO WHERE 2ND STORY OCCURS, FTG WHERE 2ND STORY OCCURS, FTG 2 -STORY COND. (3) #5 FILL @ 95% STANDARD BE 20" WIDE BE 20" WIDE 1 11 SHALL BE lt-4" WIDE w/(3) #5 BARS RApq PFr),n P. FTnTn DENSITY Orl/ALL Dr– 1-14 VVIUr_ WkO) *0 DMRO BE 20" WIDE TYPICAL GARAGE CURB FOOTING AFO�- NON-BEARING SLAB STEP DOWN AFO�\ DOUBLE STEP FOOTING 16F':nl TY ICAL EXTERIOR FOOTING 16FO 3/4"=V-0" 3/4"=V-0" 3/4"=V-0 OPT. MASONRY CURB @ ELEV. 0'4' w/ (1) #5 VERIFY W/ DETAILS FOR REQ'D CONT. BAR STEEL AT 2 STORY LOCATIONS SLOPED GROUT TO DRAIN OPTIONAL CURB BY BUILDER MIN. 24" BEFORE 7 CONIC. SLAB PER 8"x`12" THICKENED ANOTHER STEP CONIC. SLAB PER FOUNDATION PLAN SLAB w/ (1) #5 CONT. FOUNDATION PLAN w/ 3" COVER TYP. Lu 61 In 4 GRADE �A Lu �4: 4, U) alm won immin mum ui co Lu 0 womb mom w 14 ;2� U) s o:4 23, ao 4- 4. w mom .N w 4 4 w 0 1 7. "o WINE L w F1 ... A > #5 CONT. W/ 3" 0 (2) #5 CONT. W/ 3'� 7— MIN. COVER TYP. V-4" (2) #5 BARS CONT. W/ 3" COVER TYP. COVER TYP. (2) #5 BENT BARS W/ CLEAN COMPACTED MIN. 25" LAP SPLICE WHERE 2ND STORY OCCURS, FTG FILL @ 95% STANDARD DENSITY SHALL BE V-4" WIDE w/(3) #5 BARS FOOTING a, SHOWER AT MASONRY OFOk THICKENED EDGE 3/4"=V-0" 1\� 3/4"=11_011 FILLED CELL PER PLAN WOOD POST PER PLAN u Z"�— FOR SIZE AND BASE 4" CONNECTION TOP COURSE TO BE GARAGE CHAIR BLOCKS. ENTIRE BASE TO BE FILLED SOLID TOP VIEW CORNER SEE E.LEVATION CONIC. SLAB PER CMU BASE w/ (1) #5 FOUNDATION PLAN GARAGE WALL VERTICAL @ EACH 0MC: M D 3/4"=11-011 8" CMU - FINISH PER ELEV. CONC. SLAB PER FOUNDATION PLAN FINISH FLOOR PENETRATING PIPE 'GRADE 4 4: 11EE PVC SLEEVE MIN. FOOTING PER PLAN DIAMETER TO BE 2 CLEAN COMPACTED PIPE SIZES LARGER FILL @ 95% STANDARD THAN THE PENETRATING PIPE (SIDE VIEW) DENSITY (MF14� TYPICAL FOUNDATION PENETRATIONS 3/4"= 1 1-01, (FRONT VIEW) 3/4"=11-0" TYPICAL STEP FOOTING DETAIL NOT USED TOP (2) #5 x 4'-0" — CENTERED AT PIPE 8" C.M.U. FINISH PER PENETRATION ELEV. FINISH FLOOR PENETRATING PIPE 3/4"= 1 1-0.1 PVC OR SCH40 SLEEVE LOOP TIE (TYP.) 4 44 < I C? FOOTING PER PLAN SEE FDN N FOR SI PVC SLEEVE PIPE VERTICAL THRU FDN 3/4"=11-01. ui BEARING SLAB STEP DOWN AFO FOOTING AT INTERIOR BEARING c4j 3/4"=V-0" 3/4"=1 =j 00 oo -0 y 6 L U. A -It z 0 VERIFY W/ DETAILS FOR REQ'D LIJ :w STEEL AT 2 STORY LOCATIONS Lu _u < 0: z w J 6 ui < lk -Z z MASONRY WALL 4. < SEE PLAN 0 _j ca LL TIE BEAM MIN. 25" SLOPE CONIC. SLAB PER (1) #5 FROM FTG. TO FOUNDATION PLAN #5 CONT. PER MFG SPLICE GROUT CELL REINFORCEMENT SEE A, SOLID PER PLANS J FOUNDATION PLAN 4 FOR QUANTITY 0 _r -..q THRESHOLD PER MFG — — — --- — won #5 x 25" x 25" CORNER 4 A m 4. 4 0 BaIR, ONE FOR EA. U) .4 Lu HORIZONTAL CONIC. SLAB PER I. It — V_ w 4 14 REBAR, TYP. U.N.O. FOUNDATION PLAN 0 A z — — — — — --- — co FE1 I 1EH1 I C6 u 0 1'' 1.1 1 1 (2) #5 BARS CONT. —7-77'"' TYPICAL CORNER BAR DETAIL (TOP VIEW) 3/4"= 1 1-01, TOP (2) #5 x 4'-0" PVC OR SCH 40 SLEEVE CENTERED AT PI P PENETRATION SLOPE VV/,j I-uvt:m I Y t-.; �C_v 4' 2 -STORY CONDITION PER MFG (3) #5 BARS w/ 20" . . . . . . . . . SLOPE EXT. SURFACE u 6vv_ 0 WIDE FOOTING < OR GRADE 1/4" PER CLEAN COMPACTED �71 FOOT AWAY FROM FILL @ 95% STANDARD 0 BUILDING DENSITY ELASTOMERIC JOINT FILLER EXTERIOR DOOR POURED SILL fi_Fl�� FOOTING AT INTERIOR BEARING WITH CMU NOT USED 3/4"=V-011 3/4"=11-011 BEYOND _j �7xz cn PLAN FOR BASE SIZ'E < (v Z (D (D q ui Lu b ;z P 06 0 DRIVEWAY BY SEE FOUNDATION FOR 0 0 P: cd z I— F- 0 � (D 0c) w z BUILDER- CONCRETE PAD SIZE w It- 0 2 �z " 0 0 : s ,4' — U) OR PAVERS z Z U) �— Z E < < Lu Z 0 < CONIC. SLAB OR u- 3: 0 1: 0 Mo- C/i < 77 uj > LU A.. PAVERS PER PL A�7 z Z 0 0 ui w 0 W CLEAN COMPACTED LL 77 FILL @ 95% STANDARD 1 14-11 DENSITY L_ L 8,, 8" x 8" THICKENED 3" COVER TYP. CLEAN COMPACTED 7 4 l� lo EDGE W/ (1) #5 CONT. FILL @ 95% STANDARD 1.6 11"— 177 -7�'.j,_ DENSITY w THICKENED EDGE 0 GARAGE DOOR /MF1 �\ FOOTING (M. ENTRY MASONRY COLUMN 3/4"=11-011 8" CMU - FINISH PER ELEV. CONC. SLAB PER FOUNDATION PLAN FINISH FLOOR PENETRATING PIPE 'GRADE 4 4: 11EE PVC SLEEVE MIN. FOOTING PER PLAN DIAMETER TO BE 2 CLEAN COMPACTED PIPE SIZES LARGER FILL @ 95% STANDARD THAN THE PENETRATING PIPE (SIDE VIEW) DENSITY (MF14� TYPICAL FOUNDATION PENETRATIONS 3/4"= 1 1-01, (FRONT VIEW) 3/4"=11-0" TYPICAL STEP FOOTING DETAIL NOT USED TOP (2) #5 x 4'-0" — CENTERED AT PIPE 8" C.M.U. FINISH PER PENETRATION ELEV. FINISH FLOOR PENETRATING PIPE 3/4"= 1 1-0.1 PVC OR SCH40 SLEEVE LOOP TIE (TYP.) 4 44 < I C? FOOTING PER PLAN SEE FDN N FOR SI PVC SLEEVE PIPE VERTICAL THRU FDN 3/4"=11-01. ui BEARING SLAB STEP DOWN AFO FOOTING AT INTERIOR BEARING c4j 3/4"=V-0" 3/4"=1 =j 00 oo -0 y 6 L U. A -It z 0 VERIFY W/ DETAILS FOR REQ'D LIJ :w STEEL AT 2 STORY LOCATIONS Lu _u < 0: z w J 6 ui < lk -Z z MASONRY WALL 4. < SEE PLAN 0 _j ca LL TIE BEAM MIN. 25" SLOPE CONIC. SLAB PER (1) #5 FROM FTG. TO FOUNDATION PLAN #5 CONT. PER MFG SPLICE GROUT CELL REINFORCEMENT SEE A, SOLID PER PLANS J FOUNDATION PLAN 4 FOR QUANTITY 0 _r -..q THRESHOLD PER MFG — — — --- — won #5 x 25" x 25" CORNER 4 A m 4. 4 0 BaIR, ONE FOR EA. U) .4 Lu HORIZONTAL CONIC. SLAB PER I. It — V_ w 4 14 REBAR, TYP. U.N.O. FOUNDATION PLAN 0 A z — — — — — --- — co FE1 I 1EH1 I C6 u 0 1'' 1.1 1 1 (2) #5 BARS CONT. —7-77'"' TYPICAL CORNER BAR DETAIL (TOP VIEW) 3/4"= 1 1-01, TOP (2) #5 x 4'-0" PVC OR SCH 40 SLEEVE CENTERED AT PI P PENETRATION SLOPE VV/,j I-uvt:m I Y t-.; �C_v 4' 2 -STORY CONDITION PER MFG (3) #5 BARS w/ 20" . . . . . . . . . SLOPE EXT. SURFACE u 6vv_ 0 WIDE FOOTING < OR GRADE 1/4" PER CLEAN COMPACTED �71 FOOT AWAY FROM FILL @ 95% STANDARD 0 BUILDING DENSITY ELASTOMERIC JOINT FILLER EXTERIOR DOOR POURED SILL fi_Fl�� FOOTING AT INTERIOR BEARING WITH CMU NOT USED 3/4"=V-011 3/4"=11-011 C0 _j cn < Z (D (D q ui Lu b ;z P 06 V) 0 Lu C\1 uj z �_ I I.- E z U) -,j 8 z 0 0 P: cd z F- 0 � (D 0c) w z 0 w It- 0 2 �z " 0 0 : s U) Uj L�j z Z U) �— Z E < < Lu Z 0 < 0 C) u- 3: 0 1: 0 Mo- C/i < 0 04 t] uj c*4 < LL 0 CN w z Z 0 0 w 0 W LL w 2 z 0 C) z z < F - 0 0 _j to LLF 04 0 0 0 2 w .. m ow -1 Z w 5 _j ui > 00 M 0 0 m Q� 2 F- STRUCTURALENG: BED DRAFTING: -STRUCT: TW QC CHECK: -- --------- . ...... MB . JOB No. TM - 2153124 SCALE: . .... ...... . AS INDICATED DATE: 09.15.2016 SD1 PRECAST LINTEL PER PLAN MASONRY WALL SEE PLAN 2x8 W/ (2) 16d TOE NAILS EA. END 2x SPF CONT. BLOCKING ATTACH TO 7/16" OSB W/ (2) 8d NAILS 7/16" OSI3 EA. SIDE, W/ 6d NAILS @ 16" O.C. TO SIDE & TOP NAILER 2x BUCK PER MD04 THIS SHEET 1/2"=l'-0" 1\� NOTE: CUT BACK 2x8 - P.T, @ TOP TO ALLOW CONT. 2x4 BLOCKING AROUND CURVE. MIN. q 2 TAPCON ANCHORS PPR 9YA K ARCH WINDOW FRAMING DETAILS PRE-ENGINEEF TRUSSES PER 24" 0. C. MAX. TYP. TRUSS T( CONNECTION I CONNECTION I EXT. SHEATHIP ATTACHED PEI NAILING SCHEI FROM TOP OF KNEEWALLTO OR SP2 CLIPS AND SP1 CLIP%' BASE ARE REC 2x BLOCKING MIN 2x4 STUDE O/C 2x P.T. PLATE 1/2" x 8" A.B. 01 HID @ 32" O.C. FROM EA. END ON BASE PLA7 TOP KNOCK 01 COURSE W/ (1: CONT. fiF'� KNEEWALL ABOVE MASONRY WALL 3/4"=l .-011 1/2"=11-011 LINTEL (SEE PLAN) 7/16" O.S.B. EA. SID[ 2x BLK'G. TO O.S.B. ARCH PER ELEV (2) - 8d EACH END END PROVIDE STANDARD ROOF SHEATHING FOR STRAP HEADER (SEE PLAI` CONT. ROOF SHEATHING NAIL PER PLAN 7/16" O.S.B. EA, SID[ 2x6xl2 P.T, CENTER SEE PLAN FOR WALL ,gkARCH (2) - 8d EACH END END VIEW w/ WOOD BELOW AND CONNECT w/ HTS20 @ 32" O.C. '/16" OSB W/ (2) 8d PRE-ENGINEERED ROOF TRUSS PER PLAN BELOW 2x4'X'BRACE ACROSS 2x PLATES OVER ROOF DECK PER VALLEY U) HOOK WALL TO BOTTOM OF DOUBLE TOP PLATE BUILDER FRAME SIMPSON H3, H4, OR H5 @ EA. END OF TRUSS OR BUCK FRAMING INF 0 NAILS COMMON TRUSS PER PLAN OR CONV. FRAMING w/ BEAM. ATTACHED PER STRUCTURAL SHEATHING PER PLAN AND ROOF NAILING SCHEDULE FINISH PER ARCHSFIN BETWEEN TRUSSES CURVED ROOF TRUSSES PER PLAN OR CURVED TOENAILED TO RAFTERS w/ (2) LAYERS 3/4" CDX SHEATHING Lu NAILED @ 6" O.C. STAGGERED NOTE: SEE ARCH ELEVATION FOR FRONT WINDOW OPENING IF REQ'D 1/4"= 1 1-01, NOTE: ROOF SHE,ATHING MUST BE APPLIED AND FASTENED TO BASE TRUSS PER PLANS BEFORE DORMER FRAMING IS INSTALLED. STANDARD TRUSS – TRUSS PER PLAN BOTTOM CHORD DOUBLE TOP PLATE TBD BY BUILDER J PLAN 5. ADDITIONAL WOOD BUCK MATERIAL MAY BE FASTENED TO 2x BUCK w/ (2) u 7- PRECAST LINTEL OR ROWS OF 8d NAILS @ 16" O.C. FASTEN WINDOW TO 2x PER WIN. MANU.'S CENTERED KNOCK OUT COURSE BOTTOM OF WALL. 7.. ATTACHED PER U) co Iz- Cc: PRE-ENG.TRUSS PER .j < NAILING SCHEDULE U) (D THREADED ROD PER PLAN / BEARING WALL OTHERWISE SP2 CLIPS z Z E < < zo 1 � 0 . I BUILDER FRAME MASONRY WALL AT TOP AND SP1 CLIPS w C) (1) #5 IN TIE BEAM PER ARCHS AT BASE ARE REQ'D z 0 SCHEDULE. ONLY w CNI < 04 0 SEE FRAMING PLAN 8 go _j Z 0 FOR CONNECTION (1) #5 BAR IN PRECAST INFO REQUIRED WHEN INDICATED SEE ELEVATION LLJ Ly TOP OF MASONRY LINTEL ON SEE ARCH PLANS FOR OVERHANGINFO Ir GARAGE WALL SCHEDULE. MIN 6" TYP. SINGLE TIE -BEAM W/ (1) #5 CONT. (2) #5's VERTICAL IN GROUT SOLID BEYOND FROM END OF WALL (n uj GROUT FILLED CELL 2 MASONRY WALL. U) W z LLI WINDOW PER 0 FLOOR PLAN z w z z 0 2x6 P.T. BUCK EACH 53 T-1 0 (j) PRECAST CONC. OR W Lo LLI SIDE OF OPENING BLOCKING PER BRG FE LO TYP. @ ALL WINDOWS ENTIRE COLUMN TO CL CMD WALL SCHEDULE 0 EXT FINISH PER PLAN w BE GROUT FILLED Lu Lu w :D (5) 3/8" DIA. J -BOLT W/ u 0 Z uj _j uj 01 w U.N.O. U) UJ >. 0 0 5-1/2" EMBED. AT EA. ELEV 0'-0" '--)W AI VERT REINF. BEYOND (1) #5 VERT ICAL IN (D < DOOR BRACKET, EA. BASE PLATE BED DRAFTIIN�__ - MASONRY WALL PER GROUT FILLED CELL (IF C/) < PLAN SIDE OF DOOR. CONNECTION PER BRG MB JOB No. TM - 2153124 --- SCALE: AS INDICATED REQ'D PER PLAN) 00 (D 09.15.2016 PROVIDE 1-1/2" x 3/16" WALLSCHEDULE 0 uj co > THICK WASHER W/ EA. NOTE: SEE MD08 ON ANCHOR. (1 st BOLT TO f LINTEL PLAN FOR BE 8" MAX. ABV. CURB, ADDIT'L REBAR INFO REST EQ. SPACED -24" O.C.) PT BASE PLATE fiDOI)I VERTICAL REINFORCEMENT DETAIL 6�4 GARAGE BUCK DETAIL BEARING/ SHEARWALL CONNECTION TO CMU PRECAST LINTEL PER PLAN MASONRY WALL SEE PLAN 2x8 W/ (2) 16d TOE NAILS EA. END 2x SPF CONT. BLOCKING ATTACH TO 7/16" OSB W/ (2) 8d NAILS 7/16" OSI3 EA. SIDE, W/ 6d NAILS @ 16" O.C. TO SIDE & TOP NAILER 2x BUCK PER MD04 THIS SHEET 1/2"=l'-0" 1\� NOTE: CUT BACK 2x8 - P.T, @ TOP TO ALLOW CONT. 2x4 BLOCKING AROUND CURVE. MIN. q 2 TAPCON ANCHORS PPR 9YA K ARCH WINDOW FRAMING DETAILS PRE-ENGINEEF TRUSSES PER 24" 0. C. MAX. TYP. TRUSS T( CONNECTION I CONNECTION I EXT. SHEATHIP ATTACHED PEI NAILING SCHEI FROM TOP OF KNEEWALLTO OR SP2 CLIPS AND SP1 CLIP%' BASE ARE REC 2x BLOCKING MIN 2x4 STUDE O/C 2x P.T. PLATE 1/2" x 8" A.B. 01 HID @ 32" O.C. FROM EA. END ON BASE PLA7 TOP KNOCK 01 COURSE W/ (1: CONT. fiF'� KNEEWALL ABOVE MASONRY WALL 3/4"=l .-011 1/2"=11-011 LINTEL (SEE PLAN) 7/16" O.S.B. EA. SID[ 2x BLK'G. TO O.S.B. ARCH PER ELEV (2) - 8d EACH END END VIEW w/ CMU ROOF SHEATHING FOR STRAP HEADER (SEE PLAI` CONT. ROOF SHEATHING NAIL PER PLAN 7/16" O.S.B. EA, SID[ PER ELEV 2x BLK'G. TO O.S.B. ,gkARCH (2) - 8d EACH END END VIEW w/ WOOD 6FO1� DORMER FRAMING DETAIL 1 It =1 1-01, 3/4"=11-011 OC:C= TVO]f'Al UC:Ar-%C:D 'RAMING DETAILS FOR \DDITONAL NFORMATION HEADER CAN BE EITHER UPSET OR )OWNSET) !x W/ (2) 16d TOE NAILS EACH END 3) 16d COMMON JAILS (TYP.) IF REQ'D, PROVIDE CLOSURE WALL w/ SINGLE TOP AND BASE PLATE w/ (2) 16d NAILS TO TRUSS. STUDS @ 24" O.C. & EXT, SHEATHING INSTALLED PER NAILING PATTERN CRICKET AS REQUIRED MAIN SPAN ROOF TRUSS UPLIFT CONNECTOR (SEE SCHEDULE) MASONRY WALL PER PLAN (2) 2x TOP PLATE TYPICAL TIE BEAM w/ 3000 psi CONC. w/(l) #5 REBAR CONT. STID HOOK 2x P.T. STUD TYPICAL FILLED CELL w/ 3000 psi CONC. w/(l) #5 REBAR VERT. VERIFY w/ PLAN FOR REQ'D LOCATIONS CMU WALL PER PLAN (4) EQ. SPACED 2" TITEN HD ANCHORS w/ MIN. 1 "' EMBED. FOR 4 HOLLOW BLOCK OR 3 -"'EMBED. FOR SOLID 2 BLK. MAX. 6" FROM TOP & BOTTOM OR "' x 4" TITENS wl WASHERS 6" FROM TOP AND BOTTOM AND 12" O.C. OTHERWISE. NOTE: THIS DETAIL APPLIES TO THE FOLLOWING CONDITIONS: (1) EXTERIOR FRAME WALL TO CMU (2) INTERIOR FRAME SHEAR WALL TO CMU (3) INTERIOR LOAD BEARING FRAME WALL TO CMU WALL. SEE BEARING WALL SCHEDULE FOR SHEATHING PER PLAN TYP. TRUSS TO FRAME CONNECTION PER STD. CONNECTOR NOTES FRAME OUT TO BLOCK EDGE AS REQ'D 2x BUCK DETAIL (2) 2x TOP PLATE (2) 2x PLATE !x4 SPF CONT. 2x STUDS @ 16" O.C. FOR KNEE WALL CHORD WITH (4) 1 Od LSTA18 @ 32" O.C. STUD TO PRE -ENG TRUSS, SLIT MIN, 2x4 SPF #2 KNEE WALL WITH STUDS @ 16" O.C. W/ ROOF SHEATHING FOR STRAP 3LOCKING ATTACH TO CONT. ROOF SHEATHING NAIL PER PLAN SCAB IN EACH TRUSS PROVIDE 2x4 BLOCKING w/(2)16d NAILS EACH END STRUCTURAL TO TOP CHORDS OF TRUSSES BELOW WHEN SHEATHING ON BOTH BOTTOM PLATE DOES NOT LINE UP ABOVE TRUSS (3) 10d NAILS TYPICAL BELOW AND CONNECT w/ HTS20 @ 32" O.C. '/16" OSB W/ (2) 8d PRE-ENGINEERED ROOF TRUSS PER PLAN BELOW 2x4'X'BRACE ACROSS 2x PLATES OVER ROOF DECK PER VALLEY SIDES FROM TOP OF FRAMING DETAIL I WALL TO BOTTOM OF DOUBLE TOP PLATE BUILDER FRAME SIMPSON H3, H4, OR H5 @ EA. END OF TRUSS OR '/16" OSB EACH SIDE, RAFTER NAILS COMMON TRUSS PER PLAN OR CONV. FRAMING w/ BEAM. ATTACHED PER STRUCTURAL SHEATHING PER PLAN AND ROOF NAILING SCHEDULE FINISH PER ARCHSFIN BETWEEN TRUSSES CURVED ROOF TRUSSES PER PLAN OR CURVED TOENAILED TO RAFTERS w/ (2) LAYERS 3/4" CDX SHEATHING DOUBLE TOP PLATE w/ NAILED @ 6" O.C. STAGGERED NOTE: SEE ARCH ELEVATION FOR FRONT WINDOW OPENING IF REQ'D 1/4"= 1 1-01, NOTE: ROOF SHE,ATHING MUST BE APPLIED AND FASTENED TO BASE TRUSS PER PLANS BEFORE DORMER FRAMING IS INSTALLED. (2) 2x TOP PLATE TYPICAL TIE BEAM w/ 3000 psi CONC. w/(l) #5 REBAR CONT. STID HOOK 2x P.T. STUD TYPICAL FILLED CELL w/ 3000 psi CONC. w/(l) #5 REBAR VERT. VERIFY w/ PLAN FOR REQ'D LOCATIONS CMU WALL PER PLAN (4) EQ. SPACED 2" TITEN HD ANCHORS w/ MIN. 1 "' EMBED. FOR 4 HOLLOW BLOCK OR 3 -"'EMBED. FOR SOLID 2 BLK. MAX. 6" FROM TOP & BOTTOM OR "' x 4" TITENS wl WASHERS 6" FROM TOP AND BOTTOM AND 12" O.C. OTHERWISE. NOTE: THIS DETAIL APPLIES TO THE FOLLOWING CONDITIONS: (1) EXTERIOR FRAME WALL TO CMU (2) INTERIOR FRAME SHEAR WALL TO CMU (3) INTERIOR LOAD BEARING FRAME WALL TO CMU WALL. SEE BEARING WALL SCHEDULE FOR SHEATHING PER PLAN TYP. TRUSS TO FRAME CONNECTION PER STD. CONNECTOR NOTES FRAME OUT TO BLOCK EDGE AS REQ'D 2x BUCK DETAIL (2) 2x TOP PLATE (2) 2x PLATE !x4 SPF CONT. MIN. 2x4 SPF #2 KNEE --------- WALL WITH STUDS @ 161, O.C. W/ CHORD WITH (4) 1 Od (2) 2x #2 SYP SEE PLAN MIN, 2x4 SPF #2 KNEE WALL WITH STUDS @ 16" O.C. W/ 2x4 #2 SYP BLOCKINC. 3LOCKING ATTACH TO STRUCTURAL SCAB IN EACH TRUSS FOR BEAM SIZE STRUCTURAL SUPPLIED BY A/C SHEATHING ON BOTH COMPANY (3) 10d NAILS TYPICAL SHEATHING ON BOTH '/16" OSB W/ (2) 8d SIDES FROM TOP OF 2x4'X'BRACE ACROSS END SIDES FROM TOP OF JAILS WALL TO BOTTOM OF BUILDER FRAME WALL TO BOTTOM OF '/16" OSB EACH SIDE, BEAM. ATTACHED PER NAILS RADIUS AS REQ'D BEAM. ATTACHED PER N/ 6d NAILS @ 16" O.C. NAILING SCHEDULE LAP W/ (2) 16d NAILS BETWEEN TRUSSES NAILING SCHEDULE FO SIDE & TOP NAILER OTHERWISE SP2 CLIPS N BUCKS, AT TOP AND SP1 CLIPS AT BASE ARE REQUIRED KNEEWALL AT DOWNSET BEAM fiFO NAIL SCAB TO TOP IF A/C IS SUSPENDED CHORD WITH (4) 1 Od FROM TOP CHORD (2' NAILS 2x4 #2 SYP BLOCKINC. ADD 2x4 VERTICAL REQ'D @ TOP CHORC SCAB IN EACH TRUSS ATTACHMENTS IF NO WEB IS PRESENT SUPPLIED BY A/C ENDS AND 16" O.C. MAX. TAPCONS TO BE 1 1/2" MIN. FROM EDGE OF BUCK COMPANY (3) 10d NAILS TYPICAL 2. AT EACH TRUSS 2x4'X'BRACE ACROSS END LENGTH OF SHEARWALL NAIL SCAB TO TOP 2x4 #2 SYP RAT RUIN CHORD WITH (3) 10d TOP AND BOTTOM MI NAILS (2) BAYS PAST A/C L) LOCATION. MIN (3) BA 2x4 BLOCKING LAP W/ (2) 16d NAILS BETWEEN TRUSSES TO EACH TRUSS. TYF TOENAILED TO EACH SIDE DOUBLE TOP PLATE w/ 4. 1 Od NAILS @ 4" 0. C. _j cl STANDARD TRUSS – TRUSS PER PLAN BOTTOM CHORD DOUBLE TOP PLATE TBD BY BUILDER FRAMED WALL PER PLAN 5. 3/4"=11-0" PRE -CAST LINTEL PER uj PLAN I-_ (2) 2x PT BUCKS w/ 1/2" O.S.B. BETWEEN IF DBL. NAILER IS USED, USE 1/4" x 4-1/2" TAPCONS; SEE NOTES I FASTEN PT 2x NAILER ATTACHMENT REQUIREMENTS SIZE TAPCONS SPACING # ROWS 2x6 3/16" x 3" 121, O_C� 9 2x8 3/16" x 3" 1 12" O.C. 2 TO MASONRY NOTES: 1/2" x 8" ANCHOR BOLT (2) 2x #2 SYP SEE PLAN 1. 2x PT BUCKS/NAILERS SHALL EXTEND BEYOND INT. FACE OF WINDOW, OR TITEN HD @ 32" FASTEN BUCK TO MASONRY W/ (1) ROW OF 3/16"X4" TAPCONS 6"FROM z ENDS AND 16" O.C. MAX. TAPCONS TO BE 1 1/2" MIN. FROM EDGE OF BUCK O.C. & 6" FROM EACH 0 2. BUCKS LESS THAN 2x TO BE FASTENED W/CUT NAILS OR EQUIVALENT, I-_ END STRUCTURAL CONNECTION OF WINDOW TO STRUCTURE BY OTHERS IN CL THIS CASE. 0� x L) < BUCKED OPENING, USE (3) ROWS OF 10d x 3" NAILS STAGGERED @ 12" U) U) O.C, @ EACH SUCCESSIVE BUCK 2x PT BOTTOM W 4. MIXING OF lx AND 2x BUCKS SHALL BE PERMITTED FOR THE SAME _j cl (1) 2x OR (2) 2x BUCK OPENING IF WINDOW MANUFACTURER AND PLAN REQUIREMENTS Cl ci z TBD BY BUILDER (FASTENING) ARE MET SHEATHING FROM of 5. ADDITIONAL WOOD BUCK MATERIAL MAY BE FASTENED TO 2x BUCK w/ (2) u (D PRECAST LINTEL OR ROWS OF 8d NAILS @ 16" O.C. FASTEN WINDOW TO 2x PER WIN. MANU.'S SPECS KNOCK OUT COURSE BOTTOM OF WALL. 1/2"=11-0" — SHEATHING PER PLAN — TYP. TRUSS TO FRAME CONNECTION PER STD. CONNECTOR NOTES — FRAME OUT TO BLOCK EDGE AS REQ'D KNEEWALL AT UPSET BEAM PERP. SHEARWALL CONNECTION TO TRUSS A/C IN TRUSSES 3/4"=l'-0" 1\�� PRE -MANUFACTURED CHIMNEY CAP TOP OF CHIMNEY MIN 2'-0" ABOVE A POINT WITH IN 1 U-0" OF THE NEAREST ROOF (1) SPH4 EVERY OTHER STUD TO DOUBLE TOP PLATE 2x4 VERTICAL @ 24" 0. C. MAX. w/ (4) 1 Od NAILS TO BOTTOM CHORD & (3) 10d NAIL� TO TOP CHORD; NOTE IF WALL HEIGHT IS BETWEEN 4FT & 8FT, USE 2x6 SYP #2 STUD� GALVANIZED FLASHIN 2x4 BLOCKING W/ (2) 16d COMMONS END NAILED TO VERTICAL 2x4's 3/4"=l.-011 CHIMNEY FRAMING DETAIL 3/4"=11-0" m 4211111 . w cl) % % so — , 0, 0 % .; �Y,! % 00 STRUCTURAL v- ? 4�, u� �e 6 SHEATHING : co _j z OZ , 0 p1l. T CO3 .:Z - W:LU CD < TYP TRUSS TO FRAME (5 < 0: z 0 CO J0 NNECTION PER 6 uj STD. CONNECTOR z 0 NOTES < >- 0 FRAME OUT TO BLOCK X _j EDGE 11111 m U- (2) 2x TOP PLATE 3/4"=l'-0" ROOF SHEATHING ATTACH PER NAILING SCHEDULE STANDARD TRUSS TOP CHORD VARIES TRUSS WEBS NOT SHOWN FOR CLARITY 2x4 #2 SYP CROSS BRACING (AT 45') W/ (3) 12d NAILS TO RAT RUNS. TYP EACH SIDE CONDENSATE DISPOSAL BY A/C SUPPLIER CONNECTION TO BE SUPPLIED BY A/C COMPANY (2) 2x4 #2 SYP BLOCKING W/ SIMPSON RE, ELEV A34 OR LUS24-2 EACH FOR O.H. -*ED FLUE PER MANUF. SPECS W/ 2" MIN. CLEAR BETWEEN FLUE &FRAME GALVANIZED FLASHING EXT. SHEATHING ATTACHED PER NAILING SCHEID. 2x4 FRAMED CRICKET W/ GALVANIZED FLASHING (4) 16d COMMONS NAILED @ EACH END CONC. SLAB - SEE FOUNDATION 2x4 BLOCKING W/ (2) PLAN FOR MORE INFO 16d COMMONS END NAILED TO VERTICAL 2x4's SEE FOUNDATION DETAILS FOR FTG INFO TRUSS PER PLAN 3/4"=1-4' 1/2" x 8" ANCHOR BOLT (2) 2x #2 SYP SEE PLAN OR TITEN HD @ 32" 0 (2) 2x #2 SYP SEE PLAN O.C. & 6" FROM EACH FOR BEAM SIZE (ONLY FOR BEAM SIZE END IF OPENING PROVIDED 4-� PER PLAN) 0 (y) < MIN. 2x4 SPF #2 KNEE U) c� 2x PT BOTTOM WALL w/ STUDS @ 16" u C) _j PLATE O.C. w/ STRUCTURAL uj ci z u W 0 LU m E z �- �- 8 '� SHEATHING FROM of u c u (D PRECAST LINTEL OR TOP OF WALL TO KNOCK OUT COURSE BOTTOM OF WALL. 7.. ATTACHED PER U) co Iz- Cc: PRE-ENG.TRUSS PER .j < NAILING SCHEDULE U) (D PLAN, 24" O.C. MAX OTHERWISE SP2 CLIPS z Z E < < zo 1 � 0 . I BUILDER FRAME MASONRY WALL AT TOP AND SP1 CLIPS w C) RADIUS AS REQ'D PER ARCHS AT BASE ARE REQ'D z 0 w CNI < 04 0 SEE FRAMING PLAN 8 go _j 3/4"=l'-0" ROOF SHEATHING ATTACH PER NAILING SCHEDULE STANDARD TRUSS TOP CHORD VARIES TRUSS WEBS NOT SHOWN FOR CLARITY 2x4 #2 SYP CROSS BRACING (AT 45') W/ (3) 12d NAILS TO RAT RUNS. TYP EACH SIDE CONDENSATE DISPOSAL BY A/C SUPPLIER CONNECTION TO BE SUPPLIED BY A/C COMPANY (2) 2x4 #2 SYP BLOCKING W/ SIMPSON RE, ELEV A34 OR LUS24-2 EACH FOR O.H. -*ED FLUE PER MANUF. SPECS W/ 2" MIN. CLEAR BETWEEN FLUE &FRAME GALVANIZED FLASHING EXT. SHEATHING ATTACHED PER NAILING SCHEID. 2x4 FRAMED CRICKET W/ GALVANIZED FLASHING (4) 16d COMMONS NAILED @ EACH END CONC. SLAB - SEE FOUNDATION 2x4 BLOCKING W/ (2) PLAN FOR MORE INFO 16d COMMONS END NAILED TO VERTICAL 2x4's SEE FOUNDATION DETAILS FOR FTG INFO TRUSS PER PLAN 3/4"=1-4' z (D < U) 0 UJ _j uj u W 0 LU m E z �- �- 8 '� 0 (D < z u- �' m 5 9 Wi z —..E- 0 F- 0 0 00:�:! w z !� - F- _j U) co Iz- Cc: PRE-ENG.TRUSS PER .j < U) 0 m uj w PLAN, 24" O.C. MAX 0 Z E < < zo 1 � 0 . I ROOFING MATERIAL w C) 0 �- a' (6 :tz N PER ARCHS c:0 Lu z w CNI < 04 0 SEE FRAMING PLAN 8 go _j Z 0 FOR CONNECTION INFO SEE ELEVATION LLJ Ly TOP OF MASONRY SEE ARCH PLANS FOR OVERHANGINFO TYP. SINGLE TIE -BEAM W/ (1) #5 CONT. GROUT SOLID uj 2 U) W z WINDOW PER 0 FLOOR PLAN z < z 0 53 0 (j) PRECAST CONC. OR W Lo LLI POWERS STEEL SILL FE LO TYP. @ ALL WINDOWS 0 0 C4 0 0 EXT FINISH PER PLAN w u 0 Z uj _j uj 01 w MAIN FLOOR 3 0 >. 0 0 ELEV 0'-0" '--)W VERT REINF. BEYOND STRUCTURALENG: BED DRAFTIIN�__ - MASONRY WALL PER -STRUCT: TW ------ - ------ PLAN QC CHECK: MB JOB No. TM - 2153124 --- SCALE: AS INDICATED -- ---------- - -------- DATE: 09.15.2016 TYPICAL ONE STORY CMU WALL SECTION 3/4"=11-011 SD2 SIMPSON HGAl 0 @ 48" O.C. A SHEATHING NOT REQ'D v TO BE CONT. @ THE TRANSITION FROM BEAM TO GABLE SIMPSON HGA10 @ 48" O.C. SHEATHING NOT REQ'D TO BE CONT @ THE TRANSITION FROM WALL TO GABLE NOTE: ALL GABLE BRACING IS TO BE SYP#2 OR BETTER 2x4 BLOCKING @ EA. x TRUSS TRUSS TRUSS BOT. CHORD PLAN SPAN 2'-0") w/ (2) 16d 2'-0" MAX. DOUBLE 2x TOP PLATE 1/2" J -BOLTS w/ rsTRONGBACK W/ (2) 2x4 BRACE TRUSS PER PLAN FASTEN SIDE WALL PT 2x8 PLT., CANT. FOR WASHERS (MIN. 7" BEAM PER PLAN SHEATHING PER PLAN. DTC CLIP, (2) 8d NAILS CLG. NAILING SURFACE EMBED) MIN. 6" FROM 2x4 SYP #2 BRACING @ (5) 16d NAILS BRACE OUTLOOKER EACH END AND 32" O.C. TO BLOCKING (2)16dTOENAILS Lu EXT. SHEATHING; MAX. ATTACHMENT w/ (3) 1 Od SIMPSON H10A SIMPSON H10A ATTACH PER PLAN HOLD WALL 3-1/2" FASTEN CONV. 2x DIAGONAL TO BEAM DIAGONAL TO TOP ATTACH W/ (2) 1 Od : END PROVIDE 16d NAILS PLATE FHING FASTEN STD CONDITION @ FRAME WALL DOUBLE TOP PLATE BEAM CONNECTION FRAME WALL CONNECTION 2x TOP PLATE TO 2x4 LEDGER W/ (2) 10d CONTRACTOR TO FIELD VERIFY WHICH CONDITION IS REQUIRED. CONTACT EOR FOR ADDITIONAL INFO AS REQ'D A SIMPSON A23 @ EACH A35 DIAGONAL TO 2x4 BLOCKING @ EA. NO BRACE REQUIRED \V BRACE TO PLATE TRUSS BOT. CHORD PLAN SPAN 2'-0") w/ (2) 16d 2'-0" MAX. 3 1/4" HOLD 1/2" J -BOLTS w/ rsTRONGBACK W/ (2) 2x4 BRACE TRUSS PER PLAN META16 AT 24" O.C. PT 2x8 PLT., CANT. FOR WASHERS (MIN. 7" 11 '-0" O.H. DTC CLIP, (2) 8d NAILS CLG. NAILING SURFACE EMBED) MIN. 6" FROM 2x4 SYP #2 BRACING @ W INTO BLOCKING, (4) 8d OUTLOOKER EACH END AND 32" O.C. 24" O.C. FOR FALSE BM (2)16dTOENAILS Lu SIMPSON H2.5(TYP.) MAX. ATTACHMENT w/ (3) 1 Od U_) 24" O.C. uj T HOLD WALL 3-1/2" FASTEN CONV. 2x TOENAILS EA. END ATTACH W/ (2) 1 Od : END PROVIDE 16d NAILS m ED FHING FASTEN STD CONDITION @ FRAME WALL DOUBLE TOP PLATE GABLE END TRUSS TO � i-; 5 2x TOP PLATE TO 2x4 LEDGER W/ (2) 10d PLT.@12" O.C. MAX. Ji r y U GABLE END W/ 16d NAILS @ EACH WEB No/ A REQ'D. MIN (1) JACK & U) < CID NAILS @ 6" O.C. I --- EXTERIOR SHEATHING. (1) KING STUD w/ SIMPS. 0 2: FRAMING FOR FALSE ___z L ATTACH PER PLAN CMU WALL OR LINTEL--------___. Z '4, " �.. HGA10KT @ 32" O.C. BEAM, IF REQ'D w/ (3) FROM TOP OF WALL BELOW 10d NAILS @ EA. TRUSS Lu ujsl TO BOTTOM CONNECTION BRACE U) -I 2x8 #2 SPF STUDS AT SHEATHING PER PLAN TIE BEAM COURSE w/ (1) 2x4 STUDS @ 24" O.C. w/ 16" O.C. 1/2" x 8" J -BOLT @ 32" #5 CONT. SINGLE BASE & TOP -4 O.C. AND 6" FROM EA. PLATE w/ PLYWOOD FALSE BM PER PLAN 2x8 #2 SYP PT. BASE END w/ NUT & WASHER MASONRY WALL OR SHEATHING COVERING IF REQ'D PLATE W/ 1/2" x 8" CMU WALL CONNECTION CLEAR SPAN CONNECTION ANCHOR BOLT OR 'NOTE: REFER TO DETAIL GE02 THIS PAGE FOR GABLE BRACING*** GABLE END @ FLAT CEILING CONNECTIONS 2x4 OUTLOOKER @ 24" O.C. MAX. w/ (2) 16d END NAILS TO TRUSS TRUSS PER PLAN ----I NOTE: PROVIDE ADDIT'L BLOCKING AS REQ'D PER HIB -91 & TRUSS MANU.'S DRAWINGS; CEILING GYP. BID. IS NOT A DIAPHRAGM l'-9" MAX. VARIES 11 li RAKED DOUBLE TOP PLATE CEILING NAILER AS I REQ D 2x8 #2 SPF STUDS @ 16" O.C. TYP. 2x8 #2 SYP PT BASE PLATE CMU WALL PER PLAN - GABLE END @ VAULTED CEILING 3/4"= 1 1-01, cr wig W -...Pd mr! 0 FIELD FRAMED VALLEY DETAIL 1/2"=11-0" 2x4 BLOCKS, (2)16d NAILS @ EA. END. BLOCK ADJ BAYS @ EA. DIAG. AS SHOWN. FASTEN ROOF SHEATHING TO BLOCKS W/ 8d NAILS @ 6" O.C. (4) BAYS MIN (1) BAY AFTER BRACE IS REQ'D) PROVIDE 2x4 BRACE - TO EA. ADJ. DIAG. FASTEN TO DIAG. w/(2) 16d NAILS. I I GABLE BRACING @ 48" O.C. NOT REG'D 6' FROM EAVES GABLE BRACING CHART 3/4"=11-0" GABLE BRACING 2x4 BLOCKING @ EA. NO BRACE REQUIRED OUTLOOKER (MAX. ROOF SHEATHING PER ROOF SHEATHING PLAN SPAN 2'-0") w/ (2) 16d 2'-0" MAX. STRONGBACK W/ (1) 2x4 BRACE END NAILS EA. END 2x4 OUTLOOKER @ 24" O.C. MAX. w/ (2) 16d END NAILS TO TRUSS TRUSS PER PLAN ----I NOTE: PROVIDE ADDIT'L BLOCKING AS REQ'D PER HIB -91 & TRUSS MANU.'S DRAWINGS; CEILING GYP. BID. IS NOT A DIAPHRAGM l'-9" MAX. VARIES 11 li RAKED DOUBLE TOP PLATE CEILING NAILER AS I REQ D 2x8 #2 SPF STUDS @ 16" O.C. TYP. 2x8 #2 SYP PT BASE PLATE CMU WALL PER PLAN - GABLE END @ VAULTED CEILING 3/4"= 1 1-01, cr wig W -...Pd mr! 0 FIELD FRAMED VALLEY DETAIL 1/2"=11-0" 2x4 BLOCKS, (2)16d NAILS @ EA. END. BLOCK ADJ BAYS @ EA. DIAG. AS SHOWN. FASTEN ROOF SHEATHING TO BLOCKS W/ 8d NAILS @ 6" O.C. (4) BAYS MIN (1) BAY AFTER BRACE IS REQ'D) PROVIDE 2x4 BRACE - TO EA. ADJ. DIAG. FASTEN TO DIAG. w/(2) 16d NAILS. I I GABLE BRACING @ 48" O.C. NOT REG'D 6' FROM EAVES GABLE BRACING CHART H GABLE BRACING UP TO 4'-8" NO BRACE REQUIRED 4'-8" < H T-0" (1) 2x4 BRACE T-0" < H 9'-4" (2) 2x4 BRACE (SEE SECTION A -A) 9'-4" < H:. -S14' -O" STRONGBACK W/ (1) 2x4 BRACE 14'-0" < H!El 8'-8" rsTRONGBACK W/ (2) 2x4 BRACE 2x4 BRACE IF REQ'D WHERE O.H. IS > V-0", DROP GABLES wl OUTLOOKERS @ 24" O.C. l' -O" MAX PLYOOD CANT. O.H. 2x4 BLOCKS, (2) 16d TO RUN BACK TO 1 ST COMMON SEE ELEV. FOR NAILS @ EA. END. TRUSS WITH (3) 12d TOENAILS. O.H. SIZE BLOCK ADJ. BAYS CC CONNECT TO DROP GABLE WITH EA.DIAG. AS SHOWr H2.5 CLIP, MAX 2'-0" O.H. FASTEN ROOF SHEATHING TO LI BLOCKS w/8d NAILS I I z @ 6" O.C. SEE GABLE -- CONNECTION DETAIL FOR REO'D CONNECTIONS 2x4 ATTACHED TO EA. GABLE 2x4 BRACE WITH (2) 10d NAILS SEE CHART. 10d COMMON NAILS (1) A23 FROM @ 6" O.C. STRONGBACKTO DIAGONAL GABLE VERTICAL 2ND 2x4 BRACE IF REQ'D, SEE CHART A -A GABLE VERTICAL BRACING 2x6 10d COMMON NAILS @ 81, O.C. GABLE END BRACING 3/4"=11-0" PROVIDE 2x BLOCKING FOR NAILING I -X'+ MILIJUNINU IZ) I (2)16d NAILS PLT. TO NAILS, TOENAILED 45' CONT. 2x4 2x4 DIAGONAL BRACE @ 48" O.C. TO 3RD BAY REQ'D w/ STRONGBACK, SEE CHART GABLE BRACING SEE CHART STRONGBACK IF REQ'D PER CHART (5) 16d NAILS BRACE Q TO BLOCKING AF IA T- PROVIDE 2x4 BRACE LLI FHING PER PLAN E O.H. IS > l' -O" END GABLE w/ )OKERS @ 24" TRUSS PER PLAN z 0 RUN BACK TO ROOF SHEATHING 0 )MMON TRUSS %K3 3/16" x 2 3/4" TAPCONS �3) 12d TOENAILS. TO STUD) F ECT TO DROP TRUSS PER PLAN META16 AT 24" O.C. : WITH H2.5 CLIP. @ 24" O.C. W/ (2) 12d 11 '-0" O.H. DTC CLIP, (2) 8d NAILS C) SHEATHING PER PLAN C= W INTO BLOCKING, (4) 8d OUTLOOKER 2x4 (2)16dTOENAILS NAILS INTO TOP PLATE SIMPSON H2.5(TYP.) IS W/ (2) 12d END NAILS U_) 24" O.C. HOLD WALL 3-1/2" FASTEN CONV. 2x @ EACH END ATTACH W/ (2) 1 Od : END DOWNFOR NAILS @ EACH TRUSS FHING FASTEN STD CONDITION @ FRAME WALL DOUBLE TOP PLATE GABLE END TO EA. ADJ. DIAG. PER PLAN > FASTEN TO DIAG.w/(2) w SHEATHING FASTEN SPLICE AS REQ'D w PER PLAN. 16d NAILS. im I I I I I [ I I I I STUD TOP & BOTTOM TRUSS PER PLAN DTC CLIP, (2) 8d NAILS EACH END.AT 24" O.0 ROOF SHEATHING (TYP.) (END NAIL PLTS. (AS SHOWN) %K3 3/16" x 2 3/4" TAPCONS PER PLAN TO STUD) IN CMU. OR SIMPSON TRUSS PER PLAN META16 AT 24" O.C. 2x FASCIA w (2) 16d @ 24" O.C. W/ (2) 12d 11 2x6 (MIN.) PLATE THRU DTC CLIP, (2) 8d NAILS END NAILS @ EA. SHEATHING PER PLAN 2x4 #2 SYP P.T. INTO BLOCKING, (4) 8d OUTLOOKER BLOCKING @ 24" O.C. (2)16dTOENAILS NAILS INTO TOP PLATE SIMPSON H2.5(TYP.) PLAN W/ (2) 12d END NAILS BRACE TO LEDGER HOLD WALL 3-1/2" FASTEN CONV. 2x @ EACH END ATTACH W/ (2) 1 Od VALLEY RAFTER DOWNFOR NAILS @ EACH TRUSS FRAMING (OR PRE -ENG VALLEY TRUSSES) TO STD CONDITION @ FRAME WALL DOUBLE TOP PLATE OUTLOOKER TRUSS PER PLAN %ZII 2x4 LEDGER W/ (2) 10d HEADER PER PLAN IF NAILS @ EACH WEB No/ A REQ'D. MIN (1) JACK & I --- EXTERIOR SHEATHING. (1) KING STUD w/ SIMPS. TRUSS PER PLAN < ATTACH PER PLAN LSTA18 HEADER TO FROM TOP OF WALL STUDS TYP. BASE Lu ujsl TO BOTTOM CONNECTION U) -I 2x8 #2 SPF STUDS AT SHEATHING PER PLAN 16" O.C. 1/2" x 8" J -BOLT @ 32" DTC CLIP, (2) 8d NAILS -4 O.C. AND 6" FROM EA. INTO BLOCKING, (2) MASONRY WALL OR 2x8 #2 SYP PT. BASE END w/ NUT & WASHER MASONRY WALL OR 3/16" x 2 3/4" TAPCONS LINTEL SEE PLAN PLATE W/ 1/2" x 8" MSTAM-24 TYP. EA. LINTEL SEE PLAN IN CMU. OR SIMPSON ANCHOR BOLT OR SIDE OF EA, STUD. META16 TITEN HID @ 32" O.C. & CENTERED BETWEEN 6" FROM EACH END FRAME AND CMU SEE WALL SPLICE DETAIL STD CONDITION @ CMU VAULTED CONDITION @ CMU FOR REQ'D FLASHING 2x8 RIDGE BOARD 2x6 COLLAR TIE HALF WAY UP HEIGHT OF VALLEY. FASTEN w/ (5) 10d COMMON NAILS @ EACH END (TYP.) 2x6 RAFTER TO 2x8 TRUSS PER PLAN RIDGE BOARD W/ A35 ON (1) SIDE OF 'lroul'4 u I u, III/-) ou ILS INTO BLOCKING, 8d NAILS TO TOP \TE TRUSS PER PLAN I I RAFTER & A35 ON ADJ TRUSS PER PLAN DTC CLIP, (2) 8d NAILS RAFTER TO OPP SIDE 7t] INTO BLOCKING, (2) (AS SHOWN) %K3 3/16" x 2 3/4" TAPCONS 2x6's @ 24" O.C, MAX. IN CMU. OR SIMPSON 2x4 SYP #2 BLOCKING, META16 AT 24" O.C. FASTEN SYP OR SPF @ 24" O.C. W/ (2) 12d 11 2x6 (MIN.) PLATE THRU END NAILS @ EACH Fl SHEATHING PER PLAN END. W/ 1/4"x4-1/2" SIMPSON SIDS SCREWS TO TOP WALL SHEATHING PER LAY 2x4 BLOCKING CHORD OF EACH PLAN OVER THE TOP OF THE LINTEL PER PLAN TRUSS BELOW BOTTOM CHORD. FASTEN CONV. 2x 2x WALL, SEE PLAN ATTACH W/ (2) 1 Od VALLEY RAFTER NAILS @ EACH TRUSS FRAMING (OR PRE -ENG VALLEY TRUSSES) TO STD CONDITION @ FRAME WALL AT 24" O.C. BEARING CONDITION a CMU WALL -r" %ZII 2- X r- L/A I E: V V I SIMPSON MTS12 OR LSTA12 & (5) 8d NAILS @ EA. RAFTER TO PLT. fiFNON-BEARING WALL CLIP DETAIL 0 3/4"=11-0" SIMPSON H10A DIAG. TO BLOCKING uj c) (L 't z cl- 00 x w % ;z' v 6 0, LL .6-0. w z CID 0 UJ GABLE BRACING @ 48" PROVIDE 2x BLOCKING 0 Ilk w CD -K < wj 11 0: z 0 L) O.C. MAX. 450 FROM FOR NAILING 0 : 0 cf) Lij < HORIZONTAL (+/- 10') BRACE NOT REQUIRED z 6'FROM EAVES. 0 1 r-11000 r -c -Ill r -l -MIN w -j ca u - SEE PLAN FOR SUPPORT AND TIE 0 �A�� . DOWN OF JACK 7� TRUSSES PROVIDE BLOCKING u BETWEEN TRUSS BAYS 0 @ 48" O.C. FOR FIRST 3 BAYS SEE GABLE WALL PER PLAN CONNECTION DETAIL (FRAME WALL SHOWN; FOR REQ'ID "Ze c� MAY ALSO BE CONNECTIONS MASONRY) 5 r>0 'NOTE: GABLES SPANNING LESS THAN 8'DO NOT REQUIRE BRACING' 0 z u z CA z 0 GABLE END @ FLAT CEILING w/ BOSTON HIP 3/4"=11-0" n -rnM Ml A=: x vj z SEE GEOl/SD3 FOR 8d NAILS @ 4" O.C. (D w C,:" OUTLOOKER OR CONV. FRAME OR < HEADER PER PLAN; SHEATHING VALLEY TRUSSES PER 0 7 SEE HEADER CANTILEVER 06 Lu 0 JJ E PLAN SCHEDULE & NOTES .1-3 8 (D < Z 'u- uj — 0 - -7 cc) FOR ADDT'L INFO. z C) - X co - ­ SIMPSON LSTA12 OR 0 P: 0 uj CO -u:3 U) - 6- - iI a SP4 CONNECTORS @ -j u) 0: �z " IS 8 24"o.c. IF HEADER WITH GABLE TRUSS ::) < 0 0 au) s U) 0 1'- '2 u J w UPLIFT SPAN 4'-6" OR Z Z :) U) I'- z E0 < <Wzo MORE. EXT. SHEATHING; 0 u- 3: 0 z: 13� 0 2 a. ATTACH PER NAILING C) .0 < SCHEID. li -, w 2x DOWNFRAME TO U - DOOR AS REQ'D (2) 16d NAILS TO EA. LU z 0 COMMON TRUSS z w 0 SIMPSON META16 @ uj 32" O.C. GABLE TRUSS uj 1/2" THREADED ROD TO MASONRY. AT MAIN SPAN ROOF -r EA. SIDE OF HEADER WOOD WALL TRUSS (CENTERED w/in TOP LOCATIONS USE UPLIFT CONNECTOR PLATE & 6" FROM JAMB LSTA18 OR MTS12 @ (SEE SCHEDULE) STUDS) w/ MIN 7" 32" O.C. MASONRY WALL EMBED. INTO SLAB SHOWN, SEE PLAN ONLY REQ'D @ BRG FOR WOOD OR WALL W/ UPLIFT MASONRY (G'E�O GABLE END AT VALLEY FRAMING 3/4"=11-0" w HEADER STUDS PER z HEADER SCHEDULE 0 U.N.O. ON PLANS F - z Z 0 0 ATTACH JAMB STUDS cl) W) uj PER WF08/SD4 Lo C4 0 0 0 0 Z uj uj w D T PACZr= 01 ATI= 5 a 0 NOTE: CONTRACTOR TO NAIL lst KING STUD INTO HEADER PER HEADER SCHEID. THEN STRUC TURALENG: BED ATTACH ADDIT'L KINGS AS DRAFTING: REQ'D. SEE SCHEID. FOR -STRUCT: Tvv NUMBER OF KING AND JACK STUDS REQ'D. QC CHECK: MB JOB No. TM - 2153124 SCALE: AS INDICATED nATF=- An irl Onlez TYPICAL HEADER DETAIL NOT USED SD3 NOTE: PIPE OR DUCT W/ 2 ROWS 1 Od @ 3" O.G. PLATE LENGTHS MUST BE AT PENETRATION OF LEAST 8'-0" LONG, TYP. MORE THAN 50% OF TOP PLATE WIDTH INSTALL SIMPSON 2x4 STUDS PER PSPN516Z W/ (12) 16d FRAMING PLAN NAILS TYP. TOP & BOT. DOUBLE 10d @ 3" O.C. TOP SPLICE 2x4 BEYOND AGAINST 2x8 STUDS ATTACH 2x STUDS TO TOP PLATE W/ (4) 16d NAILS ((2) ON EA. SIDE) TYP. AT ALL EXTERIOR ATTACH 2x STUDS TO UUNUI 1 ]U1140 TOP PLATE W/ (4) 16d NOTES: NAILS ((2) ON EA. SIDE) 2x8 STUDS PER TYP. AT ALL EXTERIOR FRAMING PLAN CONDITIONS LEDGER U) < TOP SPLICE BOTTOM SPLICE OVER 2) ALL NAILS PENETRATE AT LEAST 3/4" OF THE THICKNESS OF THE LAST LAMINATION STUD DOUBLE 2x8 TOP NAILING PER PLATE #RT TYPICAL TOP PLATE SPLICE BRG. WALL �_ 0 DOUBLE 2x4 TOP r Lu f= w a: NOTES: PLATE m >- 0 1) ADJACENT NAILS ARE DRIVEN FROM OPPOSITE SIDES OF THE COLUMN LEDGER U) < 11� I -- SEE TRUSS PLAN FOR 2) ALL NAILS PENETRATE AT LEAST 3/4" OF THE THICKNESS OF THE LAST LAMINATION W 07- 0 [--- NAILING PER NAIL TOP PLATE To 3) FOR 5 -PLY, PROVIDE 1/4"DIA. x 5 1/2" LAG SCREWS OR EQUAL (SPACE AS SHOWN FOR 3 -PLY) �_ 0 PROVIDE 2x4 ON TOP I BOTTOM PLATE wl (4) 4) TOLERANCES: ALL DIMENSION TO BE HELD WITHIN 1/4" _111--i OF 2x8 TO BLOCK OUT LAP SPLICE 48" MIN & 10d NAILS 1" EDGE 1 1/2" EDGE FLOOR SYSTEM TOP PLATE ATTACH W/ (2) 10d NAILS O.C. ATTACH PER NAILING -- — — — — — — — Nil U- CUT TO FIT \ PATTERN ON THIS + + ....... X' X' ...... 01 OPENING SIZE ----(D--/ 01 BEYOND SEE PLAN (SOLID BLOCK W/ 2x6) DETAIL 2x12 BOX HDR w/ 2x8's 1 Od x 3" COMMON REMOVED AND REPLACED. IF MORE THAN 50% OF THE SHEATHING IS x x x AR)� EXTERIOR SHEATHING SCHEDULE MAX.; k 1 3/4"=11_011 2x4 #2 SYP CONT. w/ (2) 2x8 #2 SPF VERTICAL TO MASONRY wl 2x6 PT PRE-ENGINEERED NAIL AS SHOWN (5) 1 Od SIMPSON LSTA30 W/ 2x12 w/ 10d X 3" NAILS SYP #2 LEDGER w/ (2) @ 24" O.C. w/ EXT. 2x4 #2 SPF z MEMBER, TYP. (MAX. (22) 10d NAILS (ALL z @ 6" O.C. 2x12 AT z Lu SHEATHING PER BLOCKING @ 24" O.C. 1 1/2" z 12" O�C. CORNER CONDITIONS 1:2) WALL TO PRECAST w/ MIN. 2"EMBED. @ w w/ (2) 16d END NAILS SPACING EXTERIOR SHEATHING STRAP AROUND SIMPSON H3 CLIP LINTEL wl (2)ROWS OF ++ ++, (4) 12d NAILS EACH ui SEE PLAN FOR NAIL PER PLAN TALLER STUD) w w U) 1/4" x 4" TAPCONS @ 2x4 #2 SYP P.T. @ EA.1 TRUSS MEMBER 2x4 SYP #2 LEDGER. CONNECTION (4) 10d NAILS FOR a) 16" O.C. MAX. TRUSS w/ (4) 12d NAI LS c\1 - 1\1 I I x x WALL OR TRUSS, SEE PT POST PER PLAN (2) 1/4" X 41%?" SIMPS. 7 STAGGERED INTO TRUSS & (3) 12d EACH VERTICAL x x 2x BRG WALL, SEE SIDS SCREWS @ 16" MEMBERS ONLY TOENAILS INTO OTHER PLAN SEE WALL CLIP DETAIL PLAN FOR STUD SIZE & TRANSOM BETWEEN TRUSS TRANSOM BETWEEN FOR MORE INFO SPACING. MIN (2) 2x 0; NUT SET IN ADHESIVE SEE FLOOR PLAN FOR LINTELS LINTELS _rrrr 10d x 3" COMM( SIDS SCREWS @ 16" MORE BRG. WALL INFO LINTEL PER PLAN SLOPE AS REQ'D OVERLAP TOP PLATE 10dx3"COMMONOPP LINTEL PER PLAN U.N.O. COMMUNITY SPECS 2x6 #2 SYP P.T. CONT. TO MASONRY w/ 2x4, PT 2x6 #2 SYP P.T. CONT. 2x4 SYP #2 OR 4 PLAN FOR ADDITIONAL SYP #2 LEDGER W1 1/4" wl (2) 1/4" x 3 1/2" AT CORNER SIDE _-N 2x BLOCKING x 2 3/4" TAPCONS @ 12" ROOF TRUSSES @ 24" TAPCONS @ 12" O.C. Z L) 0 0 co w z TAPGONS @ 12" O.C. O.C. SIMPSON LSTA24 EACH O.C. MAX (2) 2x TOP PLATE SIDE VIEW @ BASE OF POST SPACED EVENLY (D SPACED EVENLY DESIGNED FOR STUD 2x8 TO UNDER SIDE OF ATTACH 2x TO VERTICALLY SHINGLE ONLY VERTICALLY (CDO CORNER COLUMN FRAMING 2x BRG WALL, SEE NAIL BOTTOM PLATE z CL U) 2x6 PLAN FOR STUD SIZ , E 2: TRUSS PER PLAN ROWS OF 10d NAILS w 11 < 04 2x8 w/ (2) 1 Od NAILS @ TO CORNER STUD 2x8 w/ (2) 1 Od NAILS @ LLJ SPACING. MIN (2) 2x 00 POCKET SGD 3" O.C. TO EA. 2x6 POCKET SGD EACH VERTICAL POCKET SGID UNDER GIRDER TRUSS SEE PLAN FOR ATTACHMENT BY VERTICAL PACK w/ (4) 1 Od NAILS U) ATTACHMENT BY U.N.O. CONNECTION Lu BUILDER BUILDER (4) 12d NAILS EACH BUILDER fiF 1 SECTION @ DOUBLE BEARING fiFfk STEP (a). — BEARING FRAME WALL HEADER @ POCKET SLIDER w/ TRANSOM FS 0 2� HEADER @ POCKET SLIDER w/ TRANSOM 00 q/A"=1. j)" AND BOTTOM CHORDS 3/4"=V-0" 1/2 "=V-0" 1/2"=V-0" ALONG W/ WEBBING) TOP PLATE TRANSITION 1 Od x 3" COMM( OPP. SIDE v TOP PLATE CORNER TRANSITION (2) 2x4's (2) 2x6's (2) 2x8's (2) 2x COLUMN fi4 TYPICAL BUILT-UP STUD COLUMN DETAIL 2 1/2" EDGE 3/4"= 1 1-01, 1-1/2"=V-0" 2x DBIL TOP PLATE MIN. 15/32" EXP 1 SHEATHING 3/8" SHEATHING PER PLAN BEYOND INSTALLED VERTICALLY. ONAIL SHEATHING AT FRAME WALL BOTTOM PLATE (D AND AT FLOOR TRUSS TOP & BOTTOM PLATES USING 7.z-@ u- z — — — — — — w o (1) ROW OF 8d COMMON NAILS @ 3" O.C. 0 _j W= NAIL SPACING — — — — — – w – -11- 01, 9cd 01, 90 z C) co ni ITCInC: /)\ ') A' A a c( EDGE DISTANCE PER V&AIL --74— INSIDE PLY NAILS NAILED AT 8" O/C STAGGERED, OUTSIDE NAILS NAILED AT 8" O/C. OUTSIDE 2x's (3+) 2x COLUMN ROOF SHEATHING, jjj I-VAIL M I I Ur- r -LM I F_ U011NU kZ-) r-\kJVV\D Ur- OU �,UIVIIVIUIN �q4 �, �,, -2 ��4 "IS? �_, FASTEN PER PLAN U_ T q"c) 0 ROOF SHEATHING, 0 NAILS @ 3" O.C. FASTEN PER PLAN < [-- U) 1/2" / �A / / U))� �u U�� .% Lu w 1/2" —7 O_ T 0 Q NAIL OPENING PERIMETER W1 (2) ROWS OF 8d _11— L D_ Cf) Z OA_ 19 op _1 rr__ 0� u- cl) ox/ COMMON NAILS @ 3" O.C. 0 w WALL SHEATHING SPLICE, SEE SPLICE NAIL INT. W/ 8d COMMON NAILS @ 12" O.C. & NAIL 2x4 FRAMING @ 24" EDGES 6" O.C. U.N.O. ON PLANS A 1/2" 2x4 FRAMING @ 24" O.C. MAX. DETAIL. MAX 1/8" '1 O.C. MAX. OPENING Lu STAGGER ALL VERT, PANEL JOINTS & NAIL VV/ 8d PROVIDE (4) 10d x 3" SPACE BETWEEN Lu DOUBLE NAIL EDGE SPACING 2x SCAB w/ 10d NAILS uj COMMON NAILS @ 3" O.C. NAILS AT JOINT PANELS U) 5_ @ 4" O.C. PROVIDE (4)10d x3" U) U) PLYWOOD SPLICES @ HEADER - NAIL SHEATHING TO EXTERIOR SHEATHING 3 PER -ENG TRUSSES NAILS AT JOINT _j w HEADER W/ 8d COMMON NAILS @ 3" O.C� (2) ROWS @ 2x SCAB w/ 1 Od NAILS TYP. Z) 0 STUD PER PLAN f rAAROUND 2x STUDS BEYOND, u- 0 TOP & BOTTOM @ 4" O.C. C OPE _j SHEATHING SPLICE, TRUSS CONNECTIO PER -ENG TRUSSES 0 < u- VERTICAL MEMBER IF GABLE END PER PLAN 2x FASCIA PER PLAN 2x FASCIA OPENING SEE PLAN FOR MORE w U- (D (2) 8d NAILS @ 3" O.C. TO EACH TRUSS END OR @ BETWEEN EXTERIOR N INFO �- 0 SHEATHING & T _71— — _T1_ r Lu f= w a: co -2 CMU WALL PER PLAN (2) 8d TOE NAILS TO m >- 0 JOINT, MAX. 1/8" GAP LEDGER U) < 11� I -- SEE TRUSS PLAN FOR 2x4 PT LEDGER W/ W 07- 0 [--- NAILING PER 1/4" x4" TAPCONS @ 12" i �_ 0 I— ILJILL I co 0 LL (/) 00 _111--i . =U _IL 0 C\j A_ FLOOR SYSTEM EACH END 0 -- — — — — — — — Nil U- CUT TO FIT \ 2x BOTTOM PLATE + + ....... X' X' ...... 01 OPENING SIZE ----(D--/ 01 BEYOND SEE PLAN 12d NAILS @ EACH END SCREWS @ 16" O.C. 2x12 BOX HDR w/ 2x8's SHEATHING DIAGRAM REMOVED AND REPLACED. IF MORE THAN 50% OF THE SHEATHING IS x x x AR)� EXTERIOR SHEATHING SCHEDULE MAX.; k 1 3/4"=11_011 2x4 #2 SYP CONT. w/ (2) BLOCKING GYPSUM WALLBOARD ROOF SHEATHING, CONNECTION +,/ -1 CMU WALL PER PLAN (2) 8d TOE NAILS TO TRUSS CONNECTION (2) 8d TOENAILS JOINT, MAX. 1/8" GAP LEDGER PER PLAN TO LEDGER SEE TRUSS PLAN FOR 2x4 PT LEDGER W/ BLOCKING @ 24" O.C. 2x4 LEDGER W/ (2) 16d NAILING PER 1/4" x4" TAPCONS @ 12" 2x FRAME WALL PER NAILS @ 16" O.C. SCHEDULE i _v\1 O.C. PLAN ATTACHMENT BY 2x4 BLOCKING PLACED SEE ELEV. FOR SEE ELEV. FOR FLATWISE (2) 16d O.H. SIZE EACH END O.H. SIZE NAILS EACH END SHEATHING SPLICE DETAIL CONDITION @ CMU WALL F1 TYPICAL SCAB OVERHANG CONDITION @ FRAME WALL NOTE: CONTRACTOR TO TAKE CARE AND NOT OVER DRIVE NAILS. IF + + ....... X' X' ...... NAILS ARE OVERDRIVEN, THE ENTIRE SHEET OF SHEATHING IS TO BE @ EACH STUD 12d NAILS @ EACH END SCREWS @ 16" O.C. 2x12 BOX HDR w/ 2x8's REMOVED AND REPLACED. IF MORE THAN 50% OF THE SHEATHING IS x x x 3/4"=11_011 MAX.; OVERDRIVEN, CONTACT EOR FOR REVIEW OF EXTERIOR STUDS SEE ROOF SHEATHING, CONNECTION +,/ -1 + + 2x4 #2 SPF uj 0) PLAN NAIL PER PLAN (2) 2x BUILT-UP COL. BEAM INTO LONG SPAN AS INDICATED ON BEAM SEE TRUSS PLAN FOR SEE TRUSS PLAN FOR BLOCKING @ 24" O.C. Ld SCHEDULE. IF BUCKET IS INSTALLED THE SHORT SPAN DOUBLE TOP PLATE 2x8 w/ (2) 1 Od NAILS @ SIMPS. SIDS SCREWS @ MORE INFO & MORE INFO & w/ (2) 16d END NAILS ATTACHMENT BY 16" O.C. MAX., �� HEADER@ POCKET SLID CONNECTION CONNECTION EACH END TO GABLE END STUDS w/ SIMPSON SP4 OR SP2 2x BLOCKING W/ (2) (2) 2x TOP PLATE (2) 1/4" X 3%." SIMPS. SIDS + + ....... X' X' ...... PT POST PER PLAN @ EACH STUD 12d NAILS @ EACH END SCREWS @ 16" O.C. 2x12 BOX HDR w/ 2x8's + x x x MAX.; LAP BEAM PLYS AND TOP & BOT., 2x8 TO 2x4 #2 SYP CONT. w/ (2) 2x8 #2 SPF VERTICAL TO MASONRY wl 2x6 PT PRE-ENGINEERED NAIL AS SHOWN (5) 1 Od SIMPSON LSTA30 W/ 2x12 w/ 10d X 3" NAILS SYP #2 LEDGER w/ (2) @ 24" O.C. w/ EXT. 2x4 #2 SPF ROOFTRUSS-SEE MEMBER, TYP. (MAX. (22) 10d NAILS (ALL z @ 6" O.C. 2x12 AT 24" O.C.). IF MASONRY, SHEATHING PER BLOCKING @ 24" O.C. FRAMING PLAN FOR 12" O�C. CORNER CONDITIONS 1:2) WALL TO PRECAST w/ MIN. 2"EMBED. @ NAILING SCHEDULE & w/ (2) 16d END NAILS SPACING EXTERIOR SHEATHING STRAP AROUND SIMPSON H3 CLIP LINTEL wl (2)ROWS OF ++ ++, (4) 12d NAILS EACH EACH END SEE PLAN FOR NAIL PER PLAN TALLER STUD) w w U) 1/4" x 4" TAPCONS @ 2x4 #2 SYP P.T. @ EA.1 TRUSS MEMBER 2x4 SYP #2 LEDGER. CONNECTION (4) 10d NAILS FOR a) 16" O.C. MAX. TRUSS w/ (4) 12d NAI LS 2x8 w/ (2) 1 Od NAILS @ - 1\1 I I x x WALL OR TRUSS, SEE PT POST PER PLAN (2) 1/4" X 41%?" SIMPS. 7 STAGGERED INTO TRUSS & (3) 12d EACH VERTICAL x x 2x BRG WALL, SEE SIDS SCREWS @ 16" MEMBERS ONLY TOENAILS INTO OTHER PLAN SEE WALL CLIP DETAIL PLAN FOR STUD SIZE & TRANSOM BETWEEN TRUSS TRANSOM BETWEEN FOR MORE INFO SPACING. MIN (2) 2x 0; NUT SET IN ADHESIVE SEE FLOOR PLAN FOR LINTELS LINTELS _rrrr UNDER GIRDER TRUSS SIDS SCREWS @ 16" MORE BRG. WALL INFO LINTEL PER PLAN SLOPE AS REQ'D LINTEL PER PLAN SLOPE AS REQ'D LINTEL PER PLAN U.N.O. COMMUNITY SPECS 2x6 #2 SYP P.T. CONT. TO MASONRY w/ 2x4, PT 2x6 #2 SYP P.T. CONT. 2x4 SYP #2 OR 4 PLAN FOR ADDITIONAL SYP #2 LEDGER W1 1/4" wl (2) 1/4" x 3 1/2" PRE-ENGINEERED 0- w/ (2) 1/4" x 3 1/2" 2x BLOCKING x 2 3/4" TAPCONS @ 12" ROOF TRUSSES @ 24" TAPCONS @ 12" O.C. Z L) 0 0 co w z TAPGONS @ 12" O.C. O.C. SIMPSON LSTA24 EACH O.C. MAX (2) 2x TOP PLATE SIDE VIEW @ BASE OF POST SPACED EVENLY SIMPSON H3 CLIP SPACED EVENLY DESIGNED FOR STUD 2x8 TO UNDER SIDE OF ATTACH 2x TO VERTICALLY SHINGLE ONLY VERTICALLY (CDO CORNER COLUMN FRAMING 2x BRG WALL, SEE PRE -ENG. ROOF BUILT-UP W/ (2) 2x6 PLAN FOR STUD SIZ , E 2: TRUSS PER PLAN ROWS OF 10d NAILS w 11 < 04 2x8 w/ (2) 1 Od NAILS @ 2x8 w/ (2) 1 Od NAILS @ LLJ SPACING. MIN (2) 2x STAGGERED @ 8" O..C. POCKET SGD 3" O.C. TO EA. 2x6 POCKET SGD EACH VERTICAL POCKET SGID UNDER GIRDER TRUSS SEE PLAN FOR ATTACHMENT BY VERTICAL ATTACHMENT BY ATTACHMENT BY U.N.O. CONNECTION Lu BUILDER BUILDER (4) 12d NAILS EACH BUILDER fiF 1 SECTION @ DOUBLE BEARING fiFfk STEP (a). — BEARING FRAME WALL HEADER @ POCKET SLIDER w/ TRANSOM FS 0 2� HEADER @ POCKET SLIDER w/ TRANSOM ('�S�O3 HEADER @ POCKET SLIDER q/A"=1. j)" AND BOTTOM CHORDS 3/4"=V-0" 1/2 "=V-0" 1/2"=V-0" ALONG W/ WEBBING) 3/4"=1 1-011 LEDGER @ LOW ROOF SEE TRUSS PLAN FOR MORE INFO & ix +/v CONNECTION +,/ -1 + + CONTRACTOR MAY ELECT TO BUCKET SHORT SPAN uj 0) @ 24" O.C. w/ EXT. 2x6 SYP #2 LEDGER. TO SHEATHING PER BEAM INTO LONG SPAN AS INDICATED ON BEAM NAILING SCHEDULE & STUDS w/ (2) 1/4" X 41/2" Ld SCHEDULE. IF BUCKET IS INSTALLED THE SHORT SPAN 2x8 w/ (2) 1 Od NAILS @ SIMPS. SIDS SCREWS @ EACH VERTICAL STRAP IS NOT REQUIRED. ATTACHMENT BY 16" O.C. MAX., �� HEADER@ POCKET SLID FASTEN PER PLAN TO GABLE END STUDS w/ EXTERIOR WALL/TRUSS (2) 1/4" X 3%." SIMPS. SIDS EXT. BEAM PER PLAN PT POST PER PLAN SCREWS @ 16" O.C. MAX.; LAP BEAM PLYS AND 2x4 #2 SYP CONT. w/ (2) TO MASONRY wl 2x6 PT NAIL AS SHOWN (5) 1 Od SYP #2 LEDGER w/ (2) NAILS PER PLY MEMBER, TYP. (MAX. 1/4" x 2 3/4" TAPCONS AT 24" O.C.). IF MASONRY, EXT. BEAM PER PLAN o ce) 12 12" O�C. 1:2) w/ MIN. 2"EMBED. @ �SEE PLAN � i �i:� u �b HTS20 CLIP FROM SIMPSON H3 CLIP POST TO BEAM TRUSS PER PLAN SHEATHING PER PLAN PLAN VIEW @ TOP OF POST 2x4 SYP #2 LEDGER. (4) 10d NAILS FOR a) TO STUDS OR BEAM w/ o WALL OR TRUSS, SEE PT POST PER PLAN (2) 1/4" X 41%?" SIMPS. 7 CONV. FRAMED ABU POST BASE PER SIDS SCREWS @ 16" MEMBERS ONLY PLAN O.C. MAX.; 5/8" THREADED ROD W/ END STUDS TO GABLE END STUDS 0; NUT SET IN ADHESIVE wl (2) 1/4" X 31/2" SIMPS. 4'-0" MAX. _rrrr SIDS SCREWS @ 16" FASCIA PER O.C. MAX.; < COMMUNITY SPECS SEE FOUNDATION TO MASONRY w/ 2x4, PT — 0,� 0 (6 , — 'c' - LU 0 LU E 2x4 SYP #2 OR 4 PLAN FOR ADDITIONAL SYP #2 LEDGER W1 1/4" PRE-ENGINEERED INFO x 2 3/4" TAPCONS @ 12" ROOF TRUSSES @ 24" Z L) 0 0 co w z O.C. O.C. MAX F - — z w 0 < 0 SIDE VIEW @ BASE OF POST SIMPSON H3 CLIP _j DESIGNED FOR 2x8 TO UNDER SIDE OF L.- w w 0 Z in �- z E Z < <wzo SHINGLE ONLY ROOF SHEATHING (CDO CORNER COLUMN FRAMING ce (SD�01 TYPICAL SHED ROOF DETAIL 3/4"=1 1-011 LEDGER @ LOW ROOF SEE TRUSS PLAN FOR 1/2"=V-011 10d x 3" 10d x 3" OPP. SIDE kNCE PER z 0 F_ ry W III MORE INFO & ix +/v CONNECTION +,/ -1 + + 2x8 #2 SPF VERTICAL uj 0) @ 24" O.C. w/ EXT. LINTEL PER PLAN SHEATHING PER NAILING SCHEDULE & (4) 12d NAILS EACH Ld TRUSS MEMBER 2x8 w/ (2) 1 Od NAILS @ z 0— le 6 EACH VERTICAL POCKET SGID ATTACHMENT BY BUILDER �� HEADER@ POCKET SLID 1/2"=V-011 10d x 3" 10d x 3" OPP. SIDE kNCE PER z 0 F_ ry W III C:D uj 0) Ld z 0— le 6 Z, _j Z . % Am, < b ROOF SHEATHING, u 0 FASTEN PER PLAN To uj < uj 0: Z 0 0, 'j: z Z < 0 in LL 2x4 #2 SYP CONT. w/ (2) 16d COMMON NAILS EA. STUD OR TRUSS 0 MEMBER, TYP. (MAX. 24" O.C.). IF MASONRY, o ce) USE (2) 1/4" TAPCONS 1:2) w/ MIN. 2"EMBED. @ � i �i:� u �b 24" O,C. 0 z u 0 TRUSS PER PLAN a) WOOD/MASONRY o WALL OR TRUSS, SEE 0 PLAN (TRUSS SHOWN) U) z < U) 0 LLj - Ip C:) — 0,� 0 (6 , — 'c' - LU 0 LU E uj C.6 z �_ F- C/) _j 8 <Z 2 Z L) 0 0 co w z F - — z w 0 < 0 _j o tao : s 2x8 TO UNDER SIDE OF L.- w w 0 Z in �- z E Z < <wzo ROOF SHEATHING ce LL 3: 0 0 0� 0 c\1 uj w 11 < 04 LLJ LL z 00 2x8 #2 SPF VERTICAL z 0 @ 24" O.C. w/ EXT. w SHEATHING PER NAILING SCHEDULE & Lu (4) 12d NAILS EACH LL1 TRUSS MEMBER (TOP r AND BOTTOM CHORDS U) ALONG W/ WEBBING) 2x8 wl (2) 1 Od NAILS @ EACH VERTICAL R w 2 N z 00 �— M z �_ Z 0 0 c) cl) Lo Lu LID 0 C14 0 0 0 wo- Z W -1 w M J >.00 0 <ox STRUCTURALENG: DRAFTING: -STRUCT: TW QC CHECK: MB JOB No. TM - 2153124 SCALE: AS INDICATED DATE: 09.15.2016 SD4 RECORD COPY #16-2685 4co &b &% Uwe