312 W 1 St 00-2816 Plans interior remodel Federal Trust BankCITY OF SANFORD FIRE DEPARTMENT 300 N. Park Ave. Sanford, FL 32771 (407) 302-1022 (407) 330-5677 FAX Plans Review Sheet Date: 6/12/00 Business Address: 312 W. I" St. Oce. Ch. 27 Business Name: Federal Trust Bank Ph. (407) 645-1201 Contractor: Fla. Concepts (Dick Corbet) Ph. (727) 447-6776 Reviewed [ I Reviewed with comment [ X ] Rejected [ f Reviewed by: H. A. "Pete" Tucker, Fire Protection Inspector Comment: Alarm System components to be field verified as to location to be tied into existing system, as per NFPA 72 1.1 Application — Interior remodel, 3,000 sf. 1.2 Mixed — N/A 1.3 Special Definitions — N/N 1.4 Classification of Occupancy — Business 1.5 Classification of Hazard of Contents — Ordinary 1.6 Minimum Construction — N/R 2.2 Means of Egress Components — O.K. 2.3 Capacity of Egress — O.K. 2.4 Number of Exits — O.K. 2.5 Arrangement of Egress — O.K. 2.6 Travel Distance — O.K. 2.7 Discharge from Exits — O.K. 2.8 Illumination of Means of Egress — O.K.; will field verify 2.9 Emergency Lighting — O.K.; will field verify 2.10 Marking of Means of Egress — O.K. 2.11 Special Features — O.K. 3.1 Protection of Vertical Openings — N/N S 4� 3.2 Protection from Hazards — N/N 3.3 Interior Finish — Class "B" 3.4 Detection, Alarm and Communications Systems — see comments, (NFPA 72 3.5 Extinguishing Requirements —as per NFPA 10 3.6 Corridors - - 4 Special Provisions - 5 Building Services 5.1 Utilities 5.2 HVAC 5.3 Elevators, Escalators, Conveyors (4A-47) 5.4 Rubbish Chutes, Incinerators, and Laundry Chutes Sanford City Code — Chapter 9 Fire Sprinklers: N/A to remodel Monitoring: N/A to remodel Other: NFPA 1 3-5.1 Fire Lanes — Required if building is more than 150' from street; exception: building has fire sprinkler system. 3-6.1 Key Box — N/A to remodel 3-7.1 Bldg. Address Number Posted and Legible — Required; will field verify r7 2 i FtII 0 � > FW ELICAL _ECrR FARM AND AL SYSTEM.- POWE R -FIRE E-2 ."UGHIING, IF:1 SPE�.-,11FICA11ONS . . . E RIS EK D SC IIIITE$ II 0 11 I Fill F5 T 7 I T HF -E.,CLEANING AND .'EN5URE,�'THAT: Ols R jq�':OVLeRSE L; C -'A,T F TO 'F I NA L�� I �t,THE�, F:;5PON5(5IWTY'�*OF TH[;L �N IQ E; 'T I 0 N AL" 'IR ) 5 �:A R e M P0 N T A I N E Q 1 DUPING� CON AL H E, _:k� DOPTEC)�.E.0 (7:,R A C U5515 T H 5 N �6 �TA A 10 N A N 13 T R U Ce AN TCH. rA II NG'::;JW R I 50 I Q, T I Q K. - U NT Q AL' �AIR, PA j 'Al NTA[N NP A 4 NTR CTOR,WREf C> u C H 0 P A M 0 5. R, A Q I Z=PIEQ' 5 Y 0 WN A V t�,T,,T H E . F,e V IF 1.� 15 c TIP 's,u . 7rERM 'TO' :QWNER MAIN iINA7IQN Hl� B S - A N T 14 .4 L Y H A� -ACE F U D E A '�5 FOR CARE ��ANQ T I T He:,:,A EQ WMr.NT_�Q tR F PH R AND"LINSTRUC JR1, C P 5TfR U OT "ARE 4 6 Q 0 5 Q F T C Q N 1) I :T[QNE 0 R� DE Y FQR r N N, I -T 'r "' 'L L �L' � I , , , I � . I _ rN b, .� , 1; N C -' "AL ' M PROY EME NT 'NATLIRE- � ONTE T,5 RAL,,L�'rj K C U Q E M AN U F A T ' T H EL M A I N-T g. N A N C E 0 R 'A L L-�- "A e N I Q A R C; H T--'� P I- F 0, R T H, E:' r� R 10 IN E 5 A Q ST R I OR F OL R I N 7 F `TION N IR ON; ;,�BT!AR,T PL'-' OPE RA AN d, E M A 1 T'F: T T T 5 H fE ­T I 0 N,�� T Y P E-� C ON tVA I 141A 5LF_ H N N T 5 �v l5ee ..;j:�REpAREa' �T 'y IA N E UJL tq�(:j T F PEC f E, L CA E FI L T Q, R H jA� 1; L - P E R F Q. R A A A0 J5 M �IN L Ei N V e L�.' r E R I; 4) H -A N4 Qr N5. "T E R P.Q R A'U'(� T. A� C , Q I, 5 t 1 5) T, Y TTi R R O 6. 5, I�R ALL, H 5 H A EX A NE�� THE�-;�!:`ARJE ��7 O' -4 T I N G A, of� A'l 'T R A5 Ic 5 H V AG, U T R I 15 rz. F f U �5' H T FifA T; H I F I N I S,H �N K tt�, f� N_ 'T T< NO, W A L L ��,C_ 5j L5 TE DeTE,RMI� F, A R C HI T E C "AN T I N:,G A E A M IN F; 1, T! 10K R. E N 0 VA T I Q N5 7 9 E ,A N -C N Q 0 U15,, "A RE H:,, H e,' I M N, F, 0 �T 0 N T I VERIFYI '�:SAA V E 0 F Kc - Q R k :�UNIT$ _R 5S, H,E 1� 00., JAM 'AL L. K IN ,U C E D '6 R-4` A' 0 0c I'A N7 A t--D R 4 T �, 0 5,e': 5 0 OR:,1NIFOR -TION AT H N Q, 'AT L- W O -T'Q 'C 'Rb OR A Sl N G.L N O�, Q N EN RR M'Z) I1� , 0 N T H V W (UHe A P P R 0 V, R­:,97HER, Q Al-IF.:,L, Il A T F; �l u Q & MATIQN:� T F �,,Q Is T� "I R NO �F RLOTECTI U.N 8 Fl�,R > /A N, IQ Q 4f '5 T� tr�F $0 ­T F 'T A f T, TH, fO N 17 A T1 N MA 6 I TH W 5T . 0 7R A IW.. O N E� A L A 5 R OLI T H 15,,� N ACT r IQ ,,A C Ello" AM e T AH R'01�LED, E ��'A 9 TRACTOR'��5 nl� THE IV T U fl Q. R �T 0,7 T H T 5 H, A 4 - , Q - T HE FE R'r= C4�. ARI�A5,:,j0" T I-Y INC 0 t L IQ N -5 N [R F R CON _0 T R A-� TQ 10 N, Q N E M I� H. lq I- --T 0 N 01 T I t? N r IU. IitiIIIT AR F.4 F rz 5 P r `�'AN -TH r :A 9,jN 5 N 113 * 0 ,RDINA7 .6 L L " ?,�R "d Y,,' THER -',C T 'A PR p H E N wf�: Tx� T. I ­ L � - I- 1.11 .1 WHICH PF-RFOR, N C E 'Q F- "'T IJOR K' R U CT eK T M5' "A K I KC ttt0 N 408, F No y Jr Ok 'KA, 1�4 ,, r"A WIX W, 07 '7 Vl�-, io yr Yy V& IN ll IN a EF P -El% I = NFU O -i. ,NGIN, A QT 1EXCEE skawavve sm—y-y" on-r-, YOM' P90 -SINCF�C05T-��,DOE$K. OR wools J00 Rut Soo . . . . . . . . . . . . . . . -00 yy AW PA",,`,T 9 TIAWN&V WX W 020 rot.. J D1000.fCJ fu�t IV V1J1I lHt 51It ANU FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND SATISFY THEMSELVES AS TO THE NATURE AID SCOPE OF WORK. THE SUBMISSION OF A BID WILL BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERI WHICH COULD HAVE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED. ALL EXISTING CIRCUITS TO REMAIN SHALL BE RECONNECTED WHETHER INDICATED OR NOT ON PROJECT DOCUMENTS. NEW AND EXISTING CIRCUIT DESIGNATIONS MAY NOT REPRESENT ACTUAI FIELD CONDITIONS. THEY ARE INTENDED FOR REFERENCE ONLY. COORDINATE WITH OTHER TRADES FOR ITEMS IN THEIR SCOPE OF WORK WHT('H wni II n RF(]I ITRF' r7I.r7r TDTr'AI %A/r)Dv (nTcr nKwC'rnrTCU l /nrr nnir��r. I ll eyp N a� c 4-J C_ (a c co I 0 0 0 Cu 0 Ln Ln IN a ro ELECTRICAL SPECIFICATIONS 1. MATERIALS AND INSTALLATION, AS A MINIMUM, ARE TO CONFORM WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE, THE LATEST EDITION OF N.F.P.A., AND THE LATEST EDITIONS OF THE LOCAL CODES AND ORDINANCES, INCLUDING ALL AMENDMENTS TO THE N.E.C. EQUIPMENT, WHERE APPLICABLE, WILL BE LISTED WITH THE UNDERWRITERS LABORATORIES, INC. QUALITY AND WORKMANSHIP ESTABLISHED BY DRAWINGS AND SPECIFICATIONS ARE NOT TO BE REDUCED BY THE ABOVE MENTIONED CODES. 2. BIDDERS ARE TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND t, SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. THE SUBMISSION OF A BID WILL BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT, OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED. 3. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST-CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM IS TO BE FULLY OPERABLE AND ACCEPTANCE OF THIS SYSTEM BY THE ENGINEER/ARCHITECT MUST BE A CONDITION OF THE SUB CONTRACT. 4. ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION. 5. CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE. 6. CORRECTION OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL CHARGE AND TO INCLUDE REPLACEMENT OR REPAIR, OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 7. ALL REQUIRED INSURANCE TO BE PROVIDED FOR PROTECTION AGAINST PUBLIC LIABILITY OF PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 8. CONTRACTOR TO PAY FOR ALL PERMITS, FEES INSPECTIONS AND TESTINGS. 9. ELECTRICAL INSTALLATION TO MEET ALL STANDARD REQUIREMENTS OF LOCAL POWER AND TELEPHONE COMPANIES. ELECTRICAL CONTRACTOR SHALL CONTACT LOCAL POWER AND TELEPHONE COMPANIES PRIOR TO START OF CONSTRUCTION. 10. ALL WIRING SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED, MINIMUM WIRE SIZE SHALL BE J12 AWG, EXCLUDING CONTROL WIRING. ALL CONDUCTORS SHALL BE COPPER WITH THWN/THHN INSULATION. CONDUCTORS #10 AND SMALLER MAY BE SOLID; ALL THOSE #8 AND LARGER TO BE STRANDED. 11. ALL UNDERGROUND RACEWAYS SHALL BE MINIMUM 3/4% GALVANIZED RIGID STEEL CONDUIT OR SCHEDULE 40 PVC. ALL OTHER RACEWAYS TO COMPLY WITH GOVERNING CODES. WHERE RIGID STEEL IS USED, IT SHALL BE COMPLETELY COATED WITH AN ALKALI AND RUST RESISTANT BITUMASTIC PAINT, KOPPER NO. 50, AND THREADS SHALL BE COATED WITH ZINC CHROMATE. RIGID STEEL SHALL ALSO BE USED WHEN CONDUIT IS EXPOSED TO EXTERIOR ENVIRONMENT SUCH AS EXTERIOR OF BUILDING OR WHERE IT IS EXPOSED AND SUBJECT TO DAMAGE, INSIDE OF BUILDING. 12. OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCATIONS, AND BE OF SPECIAL CONSTRUCTION FOR OTHER CLASSIFIED AREAS. ALL BOXES SHALL BE RECESSED (FLUSH) IN WALLS OR CEILINGS WHENEVER POSSIBLE, 13. DISCONNECT SWITCHES SHALL BE N.P. RATED, GENERAL DUTY, QUICK -MAKE; QUICK -BREAK TYPE. ENCLOSURES SHALL BE AS REQUIRED BY N.E.C. AND LOCATION (WEATHERPROOF, EXPLOSION PROOF, ETC.). ENGRAVED LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSTALLED ON ALL DISCONNECT SWITCHES, CONTACTORS AND STARTERS. 13.1. ALL FUSES FOR SAFETY SWITCHES SHALL BE DUAL ELEMENT, CARTRIDGE TYPE. FUSES SHALL BE THOSE MANUFACTURED BY EITHER BUSSMAN OR LITTLEFUSE. THE CONTRACTOR SHALL FURNISH TO THE OWNER ONE SPARE FUSE FOR EACH SIZE AND TYPE OF FUSE INSTALLED. FUSES 600 AMPS OR LESS SHALL BE CLASS RK1, TYPICAL UNLESS OTHERWISE NOTED. FUSES OVER 600 AMPS SHALL BE CLASS L. 14. ALL GENERAL PURPOSE SWITCHES AND RECEPTACLES SHALL BE THE PRODUCT OF A SINGLE MANUFACTURER. CATALOG NUMBERS LISTED ARE LEVITON: HOWEVER, COMPARABLE DEVICES BY PASS & SEYMOUR, BRYANT, OR ARROW HART WILL BE ACCEPTED. COLOR OF DEVICES AND PLATES SHALL BE DICTATED BY ARCHITECT/OWNER. A. SWITCHES: LEVITON JCSB1-20I B. RECEPTACLES: LEVITON #BR20-I C. COVER PLATES: SMOOTH PLASTIC NOTE: ALL OTHER REQUIRED DEVICES SHALL MATCH IN COLOR AND STYLE. 15. ALL RACEWAYS AND PIPES, SPACED IN OR Ti1ROUGH ANY CONCRETE SLAB, SHALL BE SPACED A MINIMUM OF THREE TIMES THE DIAMETER OF THE LARGEST RACEWAY. 16. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM, AND PROVIDE ALL NECESSARY DEVICES AND COMPONENTS FOR EQUIPMENT BE PLACED IN PROPER WORKING ORDER. 17. A SEPARATE, GREEN TYPE THW COPPER GROUND CONDUCTOR SHALL BE RUN FROM GROUND LUG OF EACH GROUNDED RECEPTACLE TO AN APPROVED CONNECTION INSIDE THE ENCLOSING STEEL OUTLET BOX. DEVICE MOUNTING SCREWS SHALL NOT BE CONSIDERED AN APPROVED GROUND. A SEPARATE GROUND CONDUCTOR SHALL BE INSTALLED IN EVERY CONDUIT AND RACEWAY AND SECURELY BONDED IN AN APPROVED GROUNDING TERMINAL AT BOTH ENDS OF THE RUN. THE GROUNDING CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE 250-95 OF THE N.E.C. CONTRACTOR SHALL SIZE CONDUIT TO ACCOMMODATE ADDITIONAL CONDUCTOR. 18. LOAD DATA IS BASED ON INFORMATION GIVEN ENGINEER AT THE TIME OF DESIGN. VERIFY ALL EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING. 19. CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES. THE CONTRACTOR IS TO PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS. 20. FURNISH AND INSTALL DISCONNECT SWITCHES, WIRING, AND CONNECTIONS ON AIR CONDITIONING SYSTEM AS SHOWN ON PLANS. ELECTRICAL CONTRACTOR SHALL VERIFY AND COORDINATE WITH MECHANICAL CONTRACTOR REGARDING SUPPLY AND INSTALLATION OF ALL REQUIRED CONTROLS. 21. ALL FLUORESCENT AND H.I.D. LIGHTING FIXTURES SHALL BE FUSED, AS REQUIRED BY LOCAL CODE ONLY. 22.TANDEM AND HALF -SPACE CIRCUIT BREAKERS SHALL NOT BE USED. 23. TYPEWRITTEN CIRCUIT INDEX SHALL BE AFFIXED TO INSIDE SURFACE OF EACH PANELBOARD DOOR, CLEARLY INDICATING AREA AND TYPE OF LOAD SERVED BY EACH BRANCH CIRCUIT PROTECTIVE DEVICE, INCLUDING SPARES. HAND PRINTED WILL NOT BE ACCEPTED. 24.ENGRAVED, LAMINATED PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSTALLED ON ALL PANELS AND SWITCHGEAR. PLATES SHALL BE AFFIXED TO FRONT OF PANELS, INDICATING PANEL NAME, VOLTAGE AND AMPERAGE. 25. ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY, EMT, RIGID GALVANIZED CONDUIT OF SCHEDULE 40 P.V.C. TYPE 'NM', 'MC', ELECTRICAL NON-METALLIC TUBING, & FLEXIBLE METAL CONDUIT MAY BE USED FOR RESIDENTIAL TYPE BRANCH CIRCUITING. MAXIMUM NUMBER OF 120 VOLT CIRCUITS ALLOWED IN A COMMON CONDUIT SHALL BE SIX (6). THE CONTRACTOR SHALL STRICTLY CONFORM TO THE N.E.C. REQUIREMENTS OF DERATING FOR CONDUCTOR AMPACITY AND CONDUIT FILL. ELECTRICAL CONTRACTOR SHALL VERIFY W/ LOCAL AUTHORITIES PRIOR TO SUBMITTING BID. 25.1. CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: 208V SYSTEM _MOV SYSTEM PHASE SEQUENCE NEUTRAL - WHITE NEUTRAL - WHITE ABC, TOP TO BOTTOM PHASE A - BLACK PHASE A - BROWN LEFT TO RIGHT, FRONT PHASE B - RED PHASE B - ORANGE TO BACK PHASE C - BLUE PHASE C - YELLOW GRD.CON - GREEN GRD.CON - GREEN 26. CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL CONDUIT PENETRATIONS MADE THROUGH FIRE RATED WALLS, CEILINGS, SLABS, ETC. PENETRATION SEALS SHALL BE PER U.L. ASSEMBLY STANDARDS. 27. CONTRACTOR SHALL PROVIDE SHOP DRAWING SUBMITTALS FOR LIGHT FIXTURES, SWITCHGEAR, WIRING DEVICES, EMERGENCY GENERATOR/TRANSFER EQUIPMENT, AND ALL SYSTEMS (FIRE ALARM, SECURITY, ETC.) PROVIDE TWO (2) COPIES, TEN (10) DAYS PRIOR TO BID DATE FOR ENGINEER'S APPROVAL TO SUBMIT. ENGINEER'S APPROVAL OF THE PRIOR APPROVAL PACKAGE WILL BE CONSIDERED PRELIMINARY. FINAL APPROVAL WILL BE CONTINGENT UPON REVIEW OF FINAL SHOP DRAWINGS. ALL PROPOSED ALTERNATES MUST BE INDUSTRY STANDARD EQUALS TO THE ITEMS SPECIFIED AS THE BASIS OF DESIGN; HOWEVER, IF THE ITEMS ARE NOT CONSIDERED EQUAL BY THE ENGINEER, IT SHALL BE DISAPPROVED FOR FINAL SUBMITTAL. IF ELECTRICAL CONTRACTOR/ GENERAL CONTRACTOR DOES NOT SUBMIT SHOP DRAWINGS TO ELECTRICAL ENGINEER FOR ITEMS LISTED ABOVE, ELECTRICAL ENGINEER WILL NOT BE RESPONSIBLE FOR ANY, AND OR OMISSIONS OR ERRORS DUE TO SHOP DRAWINGS NOT SUBMITTED. SHOP DRAWINGS WILL ONLY BE REVIEWED TWICE AS PART OF THIS CONTRACT. ADDITIONAL SHOP DRAWING REVIEWS SHALL BE INVOICED AT 185.00 PER HOUR, BILLABLE TO THE SUB -CONTRACTOR, C.O.D. 28. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF CONTRACT DRAWINGS AT JOB SITE WITH COLORED MARKINGS INDICATING PROGRESS OF WORK. THIS SET OF CONTRACT DRAWINGS IS TO BE SEPARATE FROM AND IN ADDITION TO CONTRACTOR'S CONSTRUCTION SET. EVERY UNIT OF EQUIPMENT, DEVICE, CONDUIT AND WIRE IS 'TO MARKED WHEN INSTALLED. USE SREEN TO INDICATE INSTALLATION AS SHOWN ON DRAWINGS AND USE EM TO INDICATE FIELD CHANGES. UPON COMPLETION OF WORK, THIS SET OF CONTRACT DRAWINGS IS TO BE TURNED OVER TO, AND BECOME PROPERTY OF THE ARCHITECT. 29. THE OWNER RESERVES THE RIGHT TO REVISE THE DRAWING FROM TIME TO TIME TO INDICATE CHANGES IN THE WORK. WHEN REVISED DRAWING ARE ISSUED, THE CONTRACTOR SHALL EVALUATE THE CHANGES PROMPTLY. BEFORE INSTALLATION OF ANY ITEM OR PERFORMANCE OF THE WORK INDICATED BY THE REVISED DRAWINGS, THE CONTRACTOR SHALL NOTIFY THE OWNER IN WRITING THAT THE REVISED DRAWINGS INVOLVE AN ADDITION OR DEDUCTION OF A SPECIFIC AMOUNT OF MONEY TO THE CONTRACT PRICE. THE CONTRACTOR SHALL NOT PROCEED WITH THE REVISED WORK WITHOUT PRIOR WRITTEN APPROVAL BY THE OWNER OF THE COST OF THE REVISED WORK. 30. IF ELECTRICAL CONTRACTOR HAS QUESTIONS, OR IN THEIR OPINION FINDS OMISSIONS OR ERRORS ON ELECTRICAL DOCUMENTS, IT IS THEIR RESPONSIBILITY TO BRING THIS TO THE ATTENTION OF THE ELECTRICAL ENGINEER/ARCHITECT/OWNER IMMEDIATELY. IF ELECTRICAL CONTRACTOR PROCEEDS WITH Aa CHANGES TO THE CONTRACT DOCUMENTS WITHOUT WRITTEN PRIOR APPROVAL FROM THE ELECTRICAL ENGINEER/ARCHITECT/OWNER WILL NOT BE COMPENSATED; , 10 1 FLUSH MOUNTED PANEL "A" w/ ISOL. GROUND (EXISTING) MAIN BKR — 1 '120/208V,, 30, 4W. SQUARE-D TYPE "NQOD", 10,000 AIC (INTEGRATED) MAIN LUGS 225A POLE NO. TRIP AMP BKR POLE WIRE GND WIRE COND SERVES LOAD V.A. POLE NO. TRIP AMP BKR POLE WIRE GND WIRE COND SERVES A B 0 C 0 1 20 1 2#12 1 ##12 1/2" PLUGMOLU 1}5 75 18.0- 360r /-600 `too; q 2<LF) 360- 54CJ 360 _ J40 540 360 /1000 -840 , -c524-0 `> 360 2 20 1 2#12 1 #12 1 /2" QUAD RECEPTACLE ' 72C .� J0C1 .�Fa � < 500 1040-> < 3 20 1 2##12 1 ¢#12 1 /2" ROOF TOP RECEPTACLE 4 20 1 2#12 1 #"1 2 1/2" QUAD RECEPTACLE c- a 20 1 2##12 l�#12 / 1,2" RECEPTACLES C � ' 0 1 ? 2#i2 1#12 1/2" T C F•ECEF Pr�CLE� 7 20 1 2##12 1#12 1/2" RECEPTACLES ` 8 20 1 2#12 1#12 1/2" -rELLER 9 20 1 2#12 1 # 12 1 /2" WORKROOM 10 20 1 2#12 1 #12 1/2" BANK DISPLAY 1 I 20 1 2#12 1 #121 /2" -rELEPt-1ON j 12 2Q 1 2##12. 1360 :j#12 1/2" WORKROOM 13 20 1 2#12 -1 #12 1/2" REFRIGERA 1OR 14' 20 1 2#12 1 #12 1/2" RECEPTACLES 15 20 1 2#12 2 1 #12 1, 2 ' '„ PR.[id rER 16 20 1 2##12 1 ##12 1, 2" LIGHTING 17 20 1 2#12 1 {#12 1/2" COPIER > 18 20 1 2#12 1 #12 1 /2" LIGHTIt tG 19 21 23 .30 3 4,r'#1 U 1 #1 Q 1 /2" SURGE SUPPRESSOR 20 100 3 3#3 1 #8 1 1 /4" RJU-'I (HEA r) 22 ;2 r 25 20 1 1 2#12 1#12 1/2" SERVER 26 20 1 2#12 11/12 1/2" LIGHrI11G 27 ?_0 1 3#/12 2j 12 1 /2" RECEPTS (f?PA 11h,115 28 20 1 3#12 2##12 1 /2" � -� RECEP 1a (RM 116,117,1'18) 29 20 1 RECEP r5 (RPr1 120,1211) , 30 20 1 RECEPTS (RM 1 18) -S4Q 540 31 20 1 3##12 2##12 1;�2" RECEPTS (FOv1 103,112,113) 32 20 1 3#12 2#12 1/2 " RECEPTS (COMP./WK. STA. 1,2) 540 54Q 3.3 20 1 RECEPTS (RN1 102,103,105) 34 20 1 RECEPTS (V.P. OPS/OPS MGR.) 360 35 20 1 3#12 2#12 1/2" RECEPTS (TREAS./ACCTG. SUPV.) 36 - 1 - - - SPACE ONLY 37 20 1 RECEPTS (WIRE/WK. STA. 1,2) 38 - 1 - - - SPACE ONLY 39 1 - - SPACE ONLY 40 - 1 - - - SPACE ONLY _ 41 - 1 - - - SPACE ONLY 42 - 1 - - - SPACE ONLY \ CONNECTED V.A. PER PHASE 16280 14170 14320 rONNECTED AMPS PER PHASE 136 118 119 IG - ISOLATED GROUND CIRCUIT ELECTRICAL LEGEND rim F-1 FLUORESCENT LIGHT FIXTURE, LETTER INDICATES TYPE QB INCANDESCENT OR HID LIGHT FIXTURE, LETTER INDICATES TYPE FO C WALL BRACKET LIGHT FIXTURE, LETTER INDICATES TYPE *0 EXIT LIGHT (ARROW INDICATES DIRECTION) BATTERY POWERED EMERGENCY LIGHT S. SINGLE POLE SWITCH, LOWER CASE LETTER INDICATES. LIGHT CONTROLLED, MOUNT 48" A.F.F. U.O.N. S2 DOUBLE POLE SWITCH, MOUNT 48" A.F.F. U.O.N. S3 THREE-WAY SWITCH, MOUNT 48" A.F.F. U.O.N. 0 DIMMER SWITCH, WATTS AS NOTED, MOUNT 48" A.F.F. U.O.N. S M MOTOR RATED SWITCH DUPLEX RECEPTACLE, MOUNT 18" A.F.F. U.O.N. DUPLEX RECEPTACLE, MOUNT ABOVE COUNTER HEIGHT U.O.N. QUADRAPLEX RECEPTACLE, MOUNT 18" A.F.F. U.O.N. @5 30A 10, 25OV. RECEPTACLE, AMPS AS NOTED, MOUNT 18" A.F.F. U.O.N. Q FLOOR MOUNTED DUPLEX RECEPTACLE JQ JUNCTION BOX (FLUSH MOUNT IN FINISHED AREAS U.O.N.) DEVICE AS NOTED LIGHTING OR POWER PANELBOARD CONDUIT CONCEALED IN WALL OR ABOVE CEILING WITH 2 #12, 1 #12 E.G. CONDUCTORS IN 1/2" CONDUIT MIN. U.O.N. ® COMBINATION TELEPHONE/DATA OUTLET. PROVIDE 3/4" C. WITH PULL -CORD STUBBED INTO CEILING SPACE WITH INSULATED BUSHING. MOUNT 18" A.F.F. U.O.N. ABBREVIATIONS EG EQUIPMENT GROUND NIL NIGHT LIGHT IG ISOLATED GROUND C/T CURRENT TRANSFORMER WP WEATHERPROOF EX EXISTING DEVICE EWH ELECTRIC WATER HEATER AFF ABOVE FINISH FLOOR EWC ELECTRIC WATER COOLER AFG ABOVE FINISH GRADE E/F-EF EXHAUST FAN U.O.N. UNLESS OTHERWISE NOTED A/H-AHU AIR HANDLING UNIT N.T.S. NOT TO SCALE ACC-CU CONDENSING UNIT EC EMPTY CONDUIT RTU ROOF TOP UNIT NOTE: MOUNTING HEIGHTS NOTED ARE TO CENTERLINE OF DEVICE SHOWN. U.O.N. (NOT ALL SYMBOLS MAY BE USED FOR A PARTICULAR PROJECT) / IG IG IG IG IG IG IG FLUSH MOUNTED 120/208V., 30, 4W. PANEL Opp" (EXISTING) SQUARE 'D' TYPE "NQOD", 10,000 A.I.C. (INTEGRATED) MAIN BKR — MAIN LUGS 225A POLE NO. TRIP AMP BKR POLE WIRE GND WIRE COND SERVES LOAD V.A. POLE NO. TRIP AMP BKR POLE WIRE GND WIRE COND SERVES A 0 B 0 C 0 1 20 1 < RECEPTS (LOUNGE/RM ) 900 1000 < 720 -360 I��oU > 900 .> i` 1500 680 > 1120 900 -�_TC) 2 20 1 4##12 1##12 1/ 2" REFRIGERATOR 3 20 1 RECEPTS HALL/RM ( ) 4 20 1 MICROWAVE 1000 > 1540 154U 1 120- i1>zo ` ' 780 -5h� - < 2fJ I z##12 1##12 1/2" FtECFr''rS (FZPA 114,115) > ° 20 1 COFFEE 7 20 1 RECEPTS (RM 120,121) 8 20 I '�,�12 1 #12 1/2" FAX 9 20 1 4#12 1 ##12 1/2" LIGHTS (OPS MGR.,VP/WK. STA.) 10 20 1 COPIER 11 20 1 LIGHTS (TREAS./ACCTG./COMP.) r 12 20 1 3'12 �� i 12 �# 1 � /`„ LIGHTS (HALL 1) 13 20 1 LIGHTS (FILES) `' 14 20 1 LIGHTS (RM '102.,103,106) 1400 14-5 15 20 1 i##12 1##12 /` 1, 2" LIGHTS (FUTURE OFFICES) 16 20 1 3}#12 1##12 ii.2„ LIGHTS (RM '112,1 13,116) 17 20 1 2##12 1##12 1/2" LIGHTS (RM 114,115,120,121) 18 20 1 LIGHTS (PM 117,118) 19 20 1 3##12 1 ##12 1 / 1" LIGHTS (VAULT) { 20 20 1 3#12 1 #12 1/2" RECEPTS (RN1 116,117, 118) 540 < 1900 21 20 1 LIGFITS (FILE/DEAD SrUR.) 22 20 1 RECEPTS (RM 118) 23 20 1 2j#12 1;#12 1/2" VAULT RECEPTS ,24 20 i 2#t12 1 #12 1 j 2" RECEPTS (RM '112,113,'114) 25 20 1 3#12 1#12 1/2" RECEPTS (V.P. OPS/OPS MGR.) 26 20 1 3#12 1#12 1/2 RECEPTS (TREAS./ACCTG. SUPV.) 27 20 1 RECEPTS (COMP.) 20 1 RECEPTS MIS ( /WIRE) 108� 29 - 1 - - - SPACE ONLY N32 - 1 - - - SPACE ONLY _ 31 - 1 - - - SPACE ONLY - 1 - - - SPACE ONLY _ 33 - 1 - - - SPACE ONLY 34 - 1 - - - SPACE ONLY _ 35 - 1 - - - SPACE ONLY 36 - 1 - - - SPACE ONLY _ 37 - 1 - - - SPACE ONLY 38 - 1 - - - SPACE ONLY _ 39 - 1 - - - SPACE ONLY 40 - 1 - - - SPACE ONLY _ 41 - 1 - - - SPACE ONLY 42 - 1 - - - SPACE ONLY CONNECTED V.A. PER PHASE 9755 10260 8840 J CONNECTED AMPS PER PHASE 81 86 74 EXISTING 2500 AMP MAIN SWITCHBOARD r--------------------------------------------n I I r---------r----a----r------------ i 1 I I PANEL I I I I I I I I "f7" I I I I I I I I I I I I I (EX.) i I I L_J I I I I I I I 1 I I I L_J I I I I I I I I I I I I I I I 1 I I I I I L L 1 1 L L J J 1 j L------------------------- I I I L-----------------Sj § - - - - - - - PARTIAL O RISER DIAGRAM N.T.S. TOTAL CONNECTED LOAD (NEW): 6.1 KW @ 120/208V-30, 4W = 17 AMPS 1 1 EXISTING 200 AMP FEEDERS,;; ca PANEL co Cl X 61 ( TVSS 1 M r, H 1ro1 & Associates, Inc.. TING ENGINEERS �ray Street :Tampa, Florida 33609 _ el • ,+?8'13) 287-2719 Fax: (813) 287-5704 , 3 3 � v \'4 PLAPIS' cay C;r off rr" -FINAL MUST MEET FL,R1DA ACCESSIBILITY CODES MUST MEET FLORID Y:I" C E:NLERGY CODES ff GRY of Sanford Model Codes in effact: Standard BUilding Code 1997 ed. Standard PlUmbing Code 1997 ed. Standard Mechanical Code 1997 ed. National Electrical Code 1906 ed. See City Code AMENDINIEN-rs FL. Accessibility Codes 1997 FL. Energy Code 1997 SANFORD BUILOINO bgffr. THESE PLANS ARE REVIRWE'O ANP 9�C*QiTIONALLY ACCEPTED FOR Pewvirr, A rifflMIT ISSUED SHALL BE CONSTRUED TO OC A LICENSE TO PROCEED WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, ALTER, OR '5ET ASIDE ANY OF THE PROVISIONS OF THE: TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT THE BUILDING DEPT FROM THEREAFTER REQUIRING A.CORREC- -ViQ17J.QF-9RRQR5 ON THE PLANS, CONSTRUCTION nR nTHER VIOLATIONS OF THE CODES. Be PERMIT