312 W 1 St 02-1928 Canopyz Q m Z z �J �I Y z Q m ;n Z J z m 0 D Q J z z :n HEIGHT REQUIREMENTS FOR WALL -MOUNTED DEVICES 1. EACH MANUAL FIRE ALARM BOX SHALL BE SECURELY MOUNTED. THE OPERABLE PART FOR EACH MANUAL FIRE ALARM BOX SHALL NOT BE MORE THAN 48" (1.37 M) ABOVE FLOOR LEVEL. 2. WHERE CEILING HEIGHTS ALLOW, WALL -MOUNTED APPLIANCES SHALL HAVE THEIR BOTTOMS AT 80" A.F.F. 3. WALL -MOUNTED VISUAL APPLIANCES SHALL BE MOUNTED 80 IN. (2 M) FROM THE BOTTOM OF THE DEVICE TO THE FINISHED FLOOR. 4. WHERE COMBINATION AUDIBLE/VISIBLE APPLIANCES ARE INSTALLED, THE LOCATION OF THE INSTALLED APPLIANCE SHALL BE DETERMINED BY VISIBLE APPLIANCES. CONTROL PANEL ±70" BELL HORN/STROBE JO SIGN 1-- � SIGN 2 MANUAL RELEASE �j ABORT I L- J f 48" +80" I STROBE I Y7SIGN 3 OUTSIDE HAZARD HEIGHT OF DEVICES DETAIL (CLEAN AGENT). N.T.S. First Alarm United Fire Protection 1-888-822-5544 SIGN #1 CAUTION When Light Is Flashing Agent Has Discharged United Fire Protection 1-888-822-5544 SIGN #3 Second Alarm Discharge countdown Initiated United Fire Protection 1-888-822-5544 SIGN #2 KEEP DOUR CLOSED AREA PROTECTED By FM-200 SYSTEM United Firs Protection 1-888-822-5544 DOOR SIGN NODE PRESSURE 0 190 psi 1 185 psi 2 168 psi 3 150 psi 4 143 psi TANK INFORMATION TANK CAPACITY: 601bs TANK- DIAMETER: 10.75" HEIGHT TO PORT: 28" PORT SIZE: 1" NOZZLE PART # SIZE DRILL DIAMETER NOZZLE AREA 1 FLOW ORIENTATION E1 —N1 80-062-1850 3/4" 0.1850 in. 0.2957 sq in 57 lbs. 180" CLEAN AG ENT CALCULATION AREA/ZONE PROTECTED SPACE CUBIC FEET 1645.73 FLOODING FACTOR .0341 ® 70' FM-200 REQUIRED 571bs. USE 1 — 601b. CAPACITY CYLINDERS © 571bs. TOTAL CLEAN AGENT SUPPLIED = 57 Ibs. n 0'-6", 3/4" El -I /4" NOTE: 1 THE LENGTHS SHOWN ON THE J ISOMETRIC INCLUDE THE REQUIRED FITTINGS AND TANK ADAPTERS. VERIFY FINAL PIPE LENGTHS. TANK PORT SIZE: 1" TANK ISOMETRIC N.T.S. EQUIPMENT SCHEDULE AND LEGEND SYMBOL CITY PART NUMBER DESCRIPTION MANUFACTURER SCP 1 10-051 -R-1 SHP CONTROL SYSTEM FIKE 1 10-2176 SRM4, RELAY MODULE FIKE 1 10-2190-1, BATTERY ASSEMBLY FIKE Q 1 -- JUNCTION BOX FIKE Q 1 63-1024 PHOTOELECTRIC DETECTOR FIKE 1 67-1033 IONIZATION DETECTOR FIKE 2 67-1034 DETECTOR BASE FIKE 1 10-1639 SYSTEM ABORT FIKE ❑ 1 10-1638 MANUAL RELEASE FIKE 1 20-098 HORN/STROBE (15/75cd) FIKE s 1 20-091-SA STROBE (75cd) FIKE 1 20-1 10 6" BELL FIKE XX 1 70-022 601b. FM-200 CYLINDER FIKE 57 - POUNDS FM-200 AGENT FIKE 1 VARIES CEILING -MOUNTED NOZZLE FIKE - VARIES CEILING -MOUNTED DISCHARGE PIPE INPUT/OUTPUT MATRIX - SEQUENCE IS TYPICAL PER HAZARD SYSTEM INPUTS SMOKE DETECTOR (INITIAL) • e • SMOKE DETECTOR (SECONDARY) e e e MANUAL RELEASE STATION • • • • • • • DISCHARGE COUNTDOWN COMPLETE e ® e ABORT STATION • • TROUBLE INPUT • SUPERVISORY INPUT COUNTDOWN: 0 30 60 OHO �O� OOJ P�O� 5z:GF' -� * SECOND ALARM TONEo� P P� NON-SILENCABLE 60-PULSE-PER-MINUTE TONE �<)o�P� �\ pGZP� �P ��o I,�� ** DISCHARGE TONE SILENCABLE CONTINUOUS TONE PG P SYSTEM OUTPUTS NOTE: AIR HANDLER SHUTDOWN AND DAMPER CLOSURE BY BUILDING FIRE ALARM jk EL: 9'-4" EL: 0'-0" LOCATION OF INFORMATION FROM N FPA 2001 3-1 .2. 2 A) TITLE BLOCK B) TITLE BLOCK C) COMPASS / LEGEND D) FLOOR PLAN E) FLOOR PLAN F) CROSS SECTION DETAIL G) CLEAN AGENT CALCULATION H) CLEAN AGENT CALCULATION 1) PROTECTION AREA = SERVER ROOM NORMALLY OCCUPIED J) SURROUNDING AREA = OFFICE SPACE K) SUBMITTAL SHEET / CLEAN AGENT CALCULATION L) SUBMITTAL SHEET (NOZZLES) M) GENERAL PIPING REQUIREMENTS N) COLOR CODE 0) DETECTOR MOUNTING DETAIL P) CLEAN AGENT TANK DETAIL / SUBMITTAL PACK Q) ALL AIR TO BE SHUT DOWN BY BUILDING ALARM SYSTEM. DAMPERS ARE SHOWN ON FLOORPLAN AND WILL BE SHUT DOWN ON 2nd ALARM. R) ISOMETRIC DIAGRAM S) N/A T) PIPE SUPPORT DETAILS U) CLEAN AGENT TANK DETAILS V) SEQUENCE OF OPERATION W) PANEL DETAIL X) N/A Y) BATTERY CALCULATION Z) . N/A 9'— 4" PROTECTED SPACE SERVER ROOM ELEVATION N.T.S. PIPE AND NOZZLE BELOW DRYWALL CEILING 5URFACE MOUNT 57 DO NOT PENETRATE GREEN BOARD 4 € / 75cd (I H B si -- --; F 19 —4"CHI • SCP P-1 I NO SFj1 S3 A SEE PENETRATION 15/75cd DETAIL (TYPICAL) FLOOR PLAN SCALE: 1 /S° = V-❑° DECK DROP CEILING FINISHED FLOOR ly- O r- IN m r- v Z Q" m F_ U1 11 I— Q W 0 W LL 2.7K EOL IIIIIIIL + - R 8 Y G - + 1 2 3 4 5 6 7 8 ARM III D2 QP4.3K EOL D1 4.3K �S EOL S3 2.OK 15/75cd S PS-1 EOL 4.3K EOL Abt-1 S2 4.3K 2.0K 75cd �H a EOL EOL a Q m m n n S1 g 2.OK O B EOL w w CD 0 U U a - z CD z 0 POWE LIMIT D POWER UMI D > 6 7 8 , 1 , , , , 6 ,7 18 CIRCUITS RELEASE W P 2, 2 2 24 1 Fe • • 1 1 1� • • Q •••� A ••• N ® RES+ + - + - + - + - + - + - SW4 - ^' E1 + - + - + - + - AUXILIARY OUTPUT AUDIBLE #1 AUDIBLE #2 AUDIBLE #3 ADENT RELEASE SOLENOID ■ K5 ■ K, • INPUT #1 INPUT #2 INPUT #3 INPUT #4 MODULE Z7 Z8 Z11 Z9 Z10 Z72 Z18 ■ • ® Z, Z2 Z3 Z4 Z17 Z5 6<• • C15 to-),Z •7• 8 ® C13• • • • 4 • 5 cNn • n Z13 • ■K2 K3 K4 • � • C14• D11 • Do • •• O 9PS6 E10 E6 R Qi PS7 0 E3 0 • • 0 0 • • �• E2 • • • • J ® D15 ® N o •� • • • • =)• • • • • • D1 P6 00 . ; O • • R7 R10 75; R9 ■ • U9 ■ • + ■ • ■ • D9 • • Q C11 • • • • ■ • • • • D2 • • • U11 SW2 • s • • O • • • • ® • • ■ • (n • • cn • • • • Z21 e • • o ■ • �-, Q • • • O • • • C12 U8 • • R2 C2 • • ®R6 R21 • ■ • • C,9 + Z120•Z22 C9 D13 D4 • • •Am • ■ + D5 • • ■ • C3IQ • N ■ • ■• no I • cs • D7 • • Tl • • ••■ D8 • _ D12 • N ■ • • : ■ CUT LEAD FOR 0 OHM BASES 0 ; "P 4 • ON INPUT #16 • • C20 • • CUT LEAD FOR•. O �N�_ �u O OHM BASESU1 N ON INPUT y2 C Z14 C25 R28Swl • U7 U4X1 = R18TRANSFORMER + z + ■ =® • • • • • °' " • • PS, • PS2 • U2 K7 • • w • N N N ■ • • Ir • cn �w • • • • �z ••• e e e .. • • • • • 0 i • ®� • • • Z16 Z • • • • t7C2-4' • • v •SW3 • • • ■ W K6 • • w • ® w0 • ciz • n • U6 • • • • Z15 �3 • • • •+ • • C23 4 • • I R4 ■ C10 : C17 +: +. C18 m S� 02 ■ • ■ . 0 u5 ® SRM4 + ■ + SR1 ® F1 • • • • C16 • • • CB7 ••• T3 12A • w; e D14 ® ; ; ; ; • ; ; ABORT DISCHARGE PRE -DISCHARGE ALARM WHITE P ®®m R15 D10 • RI Z79 ® 0 ■ • ■=• I• •�■ R19 iq� Q2 R14 SILKSCREEN 03-0628 TIE INTO BUILDING STEEL OR GROUND PER MANUFACTURERS INSTRUCTIONS. SURGE SUPRESSOR Y a GROUNDING DTK-120 HW m SCREW - Z w Y w Q = w = o m Z CD 3#12, 1/2"C TO DEDICATED (B) 120VAC CIRCUIT W/BREAKER LOCK PANEL E1-CKT #10 Z I Y z Q m z J Q z z Q Z J Q z 1J :n m 0 D Q J z z :n / \I "N4111 ITT; r�...� SHP RELEASE PANEL (P-1) AND ALARM RISER DIAGRAM N.T.S. 1 J FIRE ALARM TIE IN (A) P-1 INPUT CIRCUIT DEVICE POWER CALCULATIONS INPUT #1 INPUT #i 2 INPUT #3 INPUT #4 TOTAL TOTAL TOTAL TOTAL DEVICE DEVICE DRAW DRAW DEVICE DRAW DRAW DEVICE DRAW DRAW DEVICE DRAW DRAW QUANTITY (AMPS) (AMPS) COUNT (AMPS) (AMPS) COUNT (AMPS) (AMPS) COUNT (AMPS) (AMPS) PHOTO DETECTORS 1 .000045 .000045 - - - - - - - - - ION DETECTORS - - - 1 .00004 .00004 - - - - - - MANUAL PULL STATION - - - - - - 1 0.000 0.000 - - - ABORT STATION - - - - - - - - - 1 0.000 0.000 TOTAL DRAW (AMPS) 000045 TOTAL DRAW (AMPS) 00004 TOTAL DRAW (AMPS) 0.000 TOTAL DRAW (AMPS) 0.000 FOR INPUT #1 FOR INPUT #2 FOR INPUT #3 FOR INPUT #4 08/04/03 W (AMPS1 TOFOR LALL ACIRCUITS) 000085 NOTE: UP TO TWO STYLE B INITIATING DEVICE CIRCUITS WITH AN OVERALL SYSTEM CAPACITY OF 50 DETECTORS MAXIMUM P-1 OUTPUT CIRCUIT DEVICE POWER CALCULATIONS AUDIBLE #1 AUDIBLE #2 AUDIBLE #3 AGENT RELEASE TOTAL TOTAL TOTAL TOTAL DEVICE DEVICE DRAW DRAW DEVICE DRAW DRAW DEVICE DRAW DRAW DEVICE DRAW DRAW QUANTITY (AMPS) (AMPS) COUNT (AMPS) (AMPS) COUNT (AMPS) (AMPS) COUNT (AMPS) (AMPS) BELL (6" GONG) 1 0.030 .030 - - - - - - - - - HORN/STROBE (75cd) - - - 1 .200 .200 - - -- - - - STROBE (15/75cd) - - - - - - 1 0.210 .210 - - - ARM - - - - - - - - - 1 0.01 .01 TOTAL DRAW (AMPS) O3O TOTAL DRAW (AMPS) 200 TOTAL DRAW (AMPS) 210 TOTAL DRAW (AMPS) FOR AUDIBLE #1 FOR AUDIBLE #2 FOR AUDIBLE #3 FOR AGENT RELEASE .01 03 04 08 / / TOTAL DRAW (AMPS) FOR ALL CIRCUITS 0.45 NOTE: THREE STYLE Y NOTIFICATION APPLIANCE CIRCUITS RATED AT 2.0 AMPS EACH ONE AGENT RELEASE CIRCUIT WITH MAXIMUM OF 6 ARM III'S COLOR CODE CONVENTIONAL SYSTEMS DET A=RED(+) & WHITE(-) DET B=ORANGE(+) & GREY(-) PULLSTATION=PURPLE (+) & YELLOW(-) ABORT=BLUE(+) & GREEN(-) TANK CKT=PINK(+) & BROWN(-) AUDIBLES ALL SYSTEMS BELLS=RED(+) & BLACK(-) HORN/STROBES=WHITE(+) & BLUE(-) DISCHARGE STROBES=PINK(+) & GREEN(-) ADDRESSABLE SYSTEMS COMMUNCATION=18/2 TWISTED SHIELDED 24VDC POWER=ORANGE(+) & GRAY(-) AUXILLARY FUCTIONS PINK PURPLE YELLOW GREEN CONDUCTOR & RACEWAY SCHEDULE A = (CONVENTIONAL) 2 #14 STRANDED THHN IN 1/2" CONDUIT A = (INTELLIGENT) 2 #14 TWISTED SHIELDED IN 1/2" CONDUIT B = 3 #12 SOLID THHN IN 1/2" CONDUIT GENERAL ELECTRICAL NOTES 1. CONDUCTOR TYPE: - CONVENTIONAL CIRCUITS: THHN - STRANDED. - INTELLIGENT CIRCUITS: TWISTED SHIELDED 2. CONDUCTOR SIZE: #14 MINIMUM. 3. RACEWAY AND SIZES: EMT, 1/2" MINIMUM. 4. IDENTIFICATION OF EQUIPMENT AND CATALOG NUMBERS OF ALL SYSTEM COMPONENTS: SEE SHEET BILL OF MATERIALS. 5. ALL COMPONENTS SHALL REFLECT U.L. LISTING FOR FIRE SERVICE AND SHALL BE COMPATIBLE, SEE ATTACHED SUBMITTAL DATA. 6. POWER LIMITED - 24 VDC. 7. SYSTEM SHALL CONFORM TO ALL REQUIREMENTS OF NFPA 2001, NFPA 72, NEC CHAPTER 7 ARTICLE 760, CHAPTER 9 TABLE 3B, STANDARD BUILDING CODE, UNIFORM RULE 4A-4B AND RULES AND REGULATIONS OF THE STATE FIRE MARSHALS OFFICE, F.S. 633.01 AND 633.701, AND ALL STATE AND LOCAL CODES. SHP (P-1) BATTERY CALCULATIONS STAN D-BY DEVICE DEVICE DRAW TOTAL DRAW QUANTITY (AMPS) (AMPS) MAIN BOARD 1 .09 .09 INPUT CIRCUIT PWR CALC. TOTAL DRAW (AMPS) .000085 TOTAL DRAW (AMPS) 091 IN STAND-BY HOURS IN STAND-BY 24 08/04/03 X - AMPS/HOURS 219 REQUIRED ALARM DEVICE DEVICE DRAW TOTAL DRAW QUANTITY (AMPS) (AMPS) MAIN BOARD 1 .09 .09 SRM4 1 0.10 .10 OUTPUT CIRCUIT PWR CALC. TOTAL DRAW (AMPS) 0.45 TOTAL DRAW (AMPS) 0.64 IN ALARM 08/04/03 X 5 MIN. ALARM (.084) .084 - REQUIRED (AMPS) 054 FOR ALARM + STAND-BY 2.19 = COMBINED AMP/HOURS 2.244 X DERATING FACTOR 1.2 TOTAL AMP/HOURS 2.693 REQUIRED NO-f ES; (1) ALL WIRING IS SUPERVISED EXCEPT RELAY AND AUX +24V OUT. (2) AGENT RELEASE MODULE "+" CONNECTS TO ARMIII (3) DETECTOR CIRCUITS HAVE COUNTING ZONE CAPABILITY. CIRCUITS ARE POWER LIMITED, EXCEPT P1 CIRCUITS. .5IF USING 0 OHM BASES OR CONTACT CLOSURE �4� DEVICES ON INPUT #1 OR #2, CLIP THE APPROPRIATE 0 OHM JUMPER. TWO 7-AH BATTERIES SUPPLIED RISER NOTES: 01 ALL CONVENTIONAL DETECTOR CIRCUITS SHALL BE WIRED USING #14 THHN STRANDED (19 STRAND). O2 ALL INTELLIGENT DETECTOR CIRCUITS SHALL BE WIRED USING #18 TWISTED CABLE. O3 ALL SIGNAL, 24V CIRCUITS, AND WIRING CIRCUITS SHALL BE WIRED USING #14 THHN STRANDED (19 STRAND). 0 1/2" MINIMUM CONDUIT OR 3/8" MC FOR RACEWAYS, TO NEXT DEVICE OR EOL (+ FACTORY INSTALLED JUMPERS 4° O ., TRUE CEILING -) FROM: (_r) FACP, MODULE OR PREVIOUS DEVICE HORN/STROBE COMBO WIRING DIAGRAM FROM (-} CONTROL PANEL N.T.S. BELL WIRING DIAGRAM N.T.S. FROM PANEL OR PREVIOUS DEVICE SYSTEM ABORT WIRING DIAGRAM N.T.S. CEILING DETECTOR MOUNTING DETAIL _CTOR (-) TO NEXT BELL OR END OF LINE (+) RESISTOR FROM CONTRC PREVIOUS AGENT NORMALLY OPEN CONTACTS N.T.S. TO NEXT STROBE OR EOL I N D E P E N DANT STROBE WIRING DIAGRAM N.T.S. FROM: FACP, MODULE OR PREVIOUS DEVICE INSTALLATION NOTE: THE INFORMATION SHOWN ON THIS DRAWING IS FOR REFERENCE PURPOSES ONLY. ITS INTENT IS TO PROVIDE THE SYSTEM INSTALLER WITH THE NECESSARY INFORMATION AS HOW TO WIRE FIELD DEVICES. ACTUAL CONDUIT ROUTING, CIRCUIT DIVISION, AND FIELD DEVICE LOCATIONS SHALL BE DETERMINED BY THE SYSTEM INSTALLER IN THE FIELD. CE MANUAL PULL STATION WIRING DIAGRAM N.T.S. It cl r- m a Z Q m I- ul It I- J Q W 0 W LL CONCRETE OR MASONRY BLOCK WALL ° d' • • ° d 1/4" X 1 1/4" TAPCON MINIMUM UNISTRUT CHANNEL CROSS-SECTION -4 TAPCON HEAD WASHER 1/4" X 1 1/4" FENDER AGENT STRAP MOUNTING DETAIL FOR CONCRETE OR BLOCK WALL ALLTHREAD TO BUILDING STRUCTURE PIPE CLAMP UNISTRUT DISCHARGE DISCHARGE PIPE NUT WASHER (TYP.) (TYP.) TRAPEZE -STYLE PIPE SUPPORT DETAIL N.T.S. DISCHARGE PIPE CLAMP PIPE LOW -PROFILE + UNISTRUT a 0 a SLAB D .o o SUBFLOOR-MOUNTED PIPE SUPPORT DETAIL (LOW) N.T.S. WALL STUD �- DRYWALL 1/4" X 3" BOLT --� MINIMUM TOGGLE BOLT WI UNISTRUT CHANNEL CROSS-SECTION 4" FENDER AGENT STRAP MOUNTING DETAIL FOR DRYWALL TOP VI EW I A 4" DIA. (OR SMALLER) STEEL PIPE, COPPER PIPE, EMT OR CONDUIT MIN. 1/2" DEPTH HILTI ITS 601 FIRESTOP SEALANT d > a LA MIN. 4-1/2" THICK CONCRETE FLOOR/WALL'OR ANY U.L. CLASSIFIED CONCRETE BLOCK WALL SECTION A —A 1/2" BEAD HILTI FS 601 L— MIN. 3" THICK MINERAL WOOL NOTES: (MIN. 4 PCF) TIGHTLY PACKED 1. MAXIMUM DIAMETER OF OPENING = 6". 2. ANNULAR SPACE = MIN. 0" (POINT CONTACT), MAX. 2". 3. WALLS REQUIRED 1/2" OF SEALANT FLUSH WITH BOTH SIDES. F RATING = 2-HR. T RATING = 0-HR. INSTALLATION INSTRUCTIONS FOR UL NO. -CAJJ1149 STEP 1 - PREPARATION: ALL SURFACES MUST BE CLEAN, SOUND, DRY AND FROST -FREE PRIOR TO APPLICATION OF MATERIALS. STEP 2 - BACKING MATERIAL: PACK MINERAL WOOL TIGHTLY AROUND THE PENETRATION ITEM TO THE DEPTH SHOWN IN THE DRAWINGS, AND RECESS IT BELOW THE TOP SURFACE OF THE FLOOR (OR BOTH SURFACES OF A WALL) TO ALLOW PROPER SPACE FOR THE FIRESTOP MATERIAL. STEP 3 - FIRESTOP SEALANT: APPLY THE FIRESTOP SEALANT OVER THE BACKING MATERIAL TO THE DEPTH SHOWN. IF THE PIPE IS OFFSET TO ONE SIDE, APPLY A 1/2" BEAD OF FIRESTOP SEALANT AROUND ITS CIRCUMFERENCE WHERE IT CONTACTS THE WALL OR FLOOR. WALL PENETRATIONS REQUIRE FIRESTOP SEALANT ON BOTH SIDES. LEAVE COMPLETED SEAL UNDISTURBED FOR 48 HOURS. METAL PIPE THROUGH CONCRETE FLOOR/WALL N.T.S. GENERAL PIPING REQUIREMENTS - CLEAN AGENT 1.) ALL PIPE SHALL BE BLACK OR GALVANIZED STEEL ASTM A-53 SEAMLESS OR ERW, GRADE A OR B, OR ASTM A-53 FURNACE WELD CLASS F OR ASTM A-106, GRADE A,B,C. 2.) A120 PIPE SHALL NOT BE USED. 3.) ALL FITTINGS DOWNSTREAM FROM THE PRESSURE REDUCER SHALL BE 300 LB. CLASS CONFORMING TO ASTM A-197. FLANGED FITTING SHALL BE 300 L.B. CLASS. 4.) CLASS 300 MALLEABLE IRON UNIONS OR STREET ELBOWS SHALL NOT BE USED. 5.) CONCENTRIC REDUCERS ARE THE ONLY MEANS FOR REDUCING PIPE EXCEPT AT THE NOZZLES AND MANIFOLD EL -CHECKS WHERE REDUCERS BUSHINGS MAY BE USED. 6.) GASKETS FOR FLANGED FITTINGS SHALL BE FLAT GRAY ASBESTOS, NEOPRENE IMPREGNATED. 7.) REAM, CLEAN, AND BLOW ALL PIPE BEFORE INSTALLING. 8.) ALL DISTRIBUTION PIPE AND FITTINGS MUST BE ASSEMBLIED USING PIPE OR PIPE DOPE. UNISTRUT PIPE CLAMP DISCHARGE PIPE BUILDING STRUCTURE WALL -MOUNTED PIPE SUPPORT DETAIL N.T.S, 180° SIDE WALL 180° SIDE WALL CLEAN AGENT NOZZLE PORT CONFIGURATION N.T.S. 28" APPROX. FRONT VIEW SECTION A —A �A 0- 1 3 2 4 A 1. GYPSUM WALL ASSEMBLY (U.L. CLASSIFIED U300 OR U400 SERIES) 1-HR OR 2-HR FIRE -RATING) (2-HR SHOWN). 2. PENETRATING ITEM TO BE ONE OF THE FOLLOWING: A. MAXIMUM 30" NOMINAL DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER). B. MAXIMUM 30" NOMINAL DIAMETER CAST IRON PIPE. C. MAXIMUM 6" NOMINAL DIAMETER COPPER PIPE. D. MAXIMUM 6". NOMINAL DIAMETER STEEL CONDUIT. E. MAXIMUM 4" NOMINAL DIAMETER EMT. 3. HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT: A. MINIMUM 5/8" DEPTH, FOR A 1-HR FIRE -RATING. B. MINIMUM 1-1/4" DEPTH, FOR A 2-HR FIRE -RATING. 4. MINIMUM 1/2" BEAD HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT AT POINT OF CONTACT. NOTES: 1. MAXIMUM DIAMETER OF OPENING: A. 32-1/4" FOR STEEL STUD WALLS. B. 14-1/2" FOR WOOD STUD WALLS. 2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 2-1/4". F RATING = 1-HR OR 2-HR. T RATING = 0-HR. L RATING AT AMBIENT = LESS THAN 1 CFM/SQ. FT. L RATING AT 4007 = LESS THAN 4 CFM/SQ. FT. INSTALLATION INSTRUCTIONS FOR UL NO. WL1054 STEP 1 - PREPARATION: ALL SURFACES MUST BE CLEAN, SOUND, DRY AND FROST FREE PRIOR TO APPLICATION OF FIRESTOPPING MATERIALS. STEP 2 - FIRESTOP SEALANT: APPLY THE REQUIRED DEPTH OF FIRESTOP SEALANT WITHIN THE ANNULUS ON BOTH SIDES OF WALL. TOOL WITH A PUTTY KNIFE UNTIL FLUSH WITH BOTH SURFACES, LEAVE COMPLETED SEAL UNDISTURBED FOR 48 HOURS. METAL PIPE THROUGH 1-HR.-OR 2-HR. GYPSUM WALL ASSEMBLY N.T.S. I" SCH. 40 PIPING, SEE NOTES. 1" UNION MOUNTING SURFACE 9" 7/16 D A. _++_ f 13 5/8" 1 18 1/2 f�- 3 1/2 10 3/4" TYPICAL MOUNTING DETAIL FOR 70-0227 60L8. CONTAINER I� 0 X uI i i 1.4 ki. 312 W ST FIRST STR T i,-,jANFORD, FLORIDA ARCHITECT Q"anteGroup, Inc. 804 N . BELCH ER ROAD CLEARWATER. FLORIDA 33765 727-443-1061 FAX 727-442-0609 GENERAL NOTES Y MECHANICAL ENGINEER HEATH ENGINEERING INC. 2607 AZEELE STREET TAMPA FLORIDA 33609 813-8 7 9-63 49 FAX 813-870-1 788 ELECTRICAL ENGINEER HAROLD HEART & ASSOCIATES, INC. 4201 WEST GRAY STREET TAMPA, FLORIDA 33609 813-287-2719 FAX 318-28 7-5 7 04 I. ALL WORK SHALL CONFORM WITH THE LATEST ADOPTED EDI- 4. CONTRACTOR TO OVERSEE CLEANING AND ENSURE THAT THE TION OF THE "STANDARD BUILDING CODE," THE "NATIONAL PREMISES ARE MAINTAINED FREE OF RUBBISH DURING CON - ELECTRIC CODE" AND ALL OTHER APPLICABLE LOCAL, STRUCTION. FINAL CLEANUP IS THE RESPONSIBILITY OF THE STATE AND FEDERAL CODES AND ORDINANCES, AND LOCAL CONTRACTOR. REPAIR, PATCH, TOUCH-UP AND MAINTAIN AUTHORITIES HAVING JURISDICTION. CLEANING UNTIL OCCUPIED BY OWNER. 2. ANY EXISTING CONDITIONS WHICH DIFFER SUBSTANTIALLY -1• AT THE TERMINATION OF THE WORK, SUBMIT TO OWNER MAIN - FROM THAT INDICATED ON THE ATTACHED PLANS, SHALL BE TENANCE MANUALS PRESENTING FULL DETAILS FOR CARE AND BROUGHT TO THE ATTENTION OF THE ARCHITECT, BEFORE MAINTENANCE OF ALL SURFACES AND EQUIPMENT OF EVERY PROCEEDING WITH OR CONTINUING ANY FURTHER CONSTRUCTION. NATURE. CONTENTS SHALL INCLUDE MANUFACTURER'S AND IN- STALLERS NAMES, ADDRESS AND PHONE NUMBER AND INSTRUC- TIONS FOR INSTALLATION, START-UP OPERATION. MAINTENANCE 3. THESE CONSTRUCTION DOCUMENTS HAVE BEEN PREPARED PARTS LIST AND DATA SHEETS, FROM THE MOST COMPLETE FIELD INFORMATION AVAILABLE TO THE ARCHITECT. ALL THE DATA ON EXISTING CON- S. WHEN "APPROVED EQUALS", "EQUAL TO" OR OTHER QUALIFYING STRUCTION CONDITIONS IS APPROXIMATE AND SHALL BE TERMS ARE USED, IT SHALL BE BASED UPON THE REVIEW AND VERIFIED PRIOR TO COMMENCING APPROVAL BY ARCHITECT, ANY WORK. ANY CONDITIONS WHICH DIFFER SUBSTAN- TIALLY FROM THAT INDICATED ON THESE CONSTRUCTION DOCUMENTS SHALL BE BROUGHT TO THE ATTENTION OF THE q. AL.L WORK IS TO CONFORM WITH DRAWINGS AND SPECIFICATIONS. ARCHITECT, BEFORE PROCEEDING WITH, OR CON- DRAWINGS ARE NOT TO BE SCALED FOR INFORMATION, TINUING ANY FURTHER CONSTRUCTION AS THE SITUATION WARRANTS. 10. CONTRACTOR SHALL PROVIDE WOOD BLOCKING. CONCEALED IN WALL FOR ALL WALL HUNG MILLWORK UNITS, DOOR JAMBS. SHELVES, SIGNS, 9, THE CONTRACTOR SHALL PERFORM ALL WORK IN ACCOR- ETC., AS REQUIRED. DANCE WITH THE "GENERAL CONDITION OF THE CONTRACT" AIA DOCUMENT A201. AND SHALL COMPLY WITH THE REQUIREMENTS 11. CONTRACTOR IS RESPONSIBLE FOR VERIFYING LEVEL OF FLOOR FOR OF THE CONSTRUCTION CONTRACT. WINDOWS, DOORS AND DOOR FRAMES. TOPS OF WINDOWS AND DOOR FRAMES SHALL REMAIN LEVEL AT CONTROLLED ELEVATION. S. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND JOB CON- DITIONS AND SHALL REPORT TO THE ARCHITECT ANY 12. THE GENERAL CONTRACTOR SHALL VISIT THE SITE AND EXAMINE DISCREPANCIES OR OMISSIONS WHICH WOULD INTERFERE WITH THE AREAS TO BE ALTERED AND ADJOINING AREAS TO DETERMINE SATISFACTORY COMPLETION CONTRACTOR IS THE EXTENT THAT HIS BID MAY- BE AFFECTED BY EXISTING CONDI- RESPONSIBLE FOR VER IO :OF A. LON OF ALL FIELD MEASUREMENT. TIONS. HE SHALL THOROUGHLY EXAMINE THE AREAS TO BE ALTERED IN FIELD CONSTRUCTION AND .INSTALLATION CRITERIA. COORDINATION AND FOR ACCESSIBILITY THERETO AND FOR OBSTRUCTIONS THEREON, !FOR OF ALL TRADES AND TENANT SUPPLIED ITEMS. AND THE MEANS AVAILABILITY OF STORAGE SPACE AND FOR ANY OTHER CONDITION AND METHODS OF CONSTRUCTION. CONTRACTOR IS RESPONSIBLE WHICH MAY AFFECT THE PERFORMANCE OF THE WORK. FOR ARRANGING FOR ELEVATORS, HOISTING FACILITIES, PARKING ETC., FOR THE COMPLETION OF WORK. CONTRACTOR IS RESPON- SIBLE FOR HANDLING OF MATERIALS. i/ti /r AL WA/MU A IL ■ IS Y Y OWL INDEX OF DRAWINGS T1 TITLE SHEET ARCHITECTURAL A-1 KEY PLAN, DEMOLITION PLAN, FLOOR PLAN, AND REFLECTED CEIUNG PLAN A-2 INTERIOR ELEVATIONS, ENLARGED PLAN, AND WALL SECTIONS PLUMBING & MECHANICAL MP-1 PLUMBING & MECHANICAL FLOOR PLAN ELECTRICAL 24 E-1 POWER AND. UGHTING PLANS & SPECIFICATIONS IMPROVEMENT AREA 331 SQ. FT. (CONDITIONED) ON FIRST FLOOR CONSTRUCTION TYPE TYPE V FIRE PROTECTION UNSPRINKLED TENANT SINGLE OCCUPANT/BUSINESS W >- p m W v Q 3 w UT11.ITY IMPACT FEES .'�_2s 10u ' : ,f r , 777 - a a: y,. t: a r r; : , I NEW V BATT INSUL ABOVE .CEILING AT ALL SOUND INS UL WALLS L - NFUI SAT In'-n" A F F TYP Muw RnTU coma - aGc 01 Au cno I FOR EXIST. REF:- III I CJ V W II I! WOM N 5 RESTRQO FioT 1 �fvvi [ OR F;rl -I PU z \ FIRST FLOOR PLUMBING PLAN mp-1 SCALE: „e _ .-o PLUMBING NOTES: Ol CONNECT NEW SANITARY PIPING TO EXISTING BUILDING DRAIN. O2 CONNECT NEW VENT PIPING TO EXISTING VENT STACK IN PLUMBING CHASE. O CONNECT NEW ;WATER PIPING TO EXISTING DOMESTIC WATER RISER IN PLUMBING CHASE. OTERMINATE P & T RELIEF AND SAFETY PAN DRAIN 6" ABOVE GRADE. O INSTALL SANITARY & WATER PIPING REQUIRED FOR DISHWASHER. O6 INSTALL TRAP PRIMER FOR FLOOR DRAIN, EQUAL TO "PRIME RITE" PRECISION PLUMBING PRODUCTS. O7 WATER PIPING WITHIN BLDG. TO BE TYPE "L" COPPER WITH "NO -LEAD" SOLDER CONNECTIONS, OR CPVC WITH SOLVENT FITTINGS. INSULATE H.W. LINE WITHIN BLDG. WITH 1 /2" THICK ARMAFLEX AND AS REQUIRED BY ENERGY CODE. O8 PROVIDE CHROME -PLATED ESCUTCHEONS WHERE PIPES PENETRATE FLOORS, WALLS OR CEILINGS. O PROVIDE WATER HAMMER ABSORBERS IN WATER LINES AS REQUIRED BY CODE. EQUAL TO J.R. SMITH "HYDROTROL". 10 PROVIDE STOP VALVES IN WATER SUPPLY PIPING AT ALL PLUMBING FIXTURES. 11 WATER PIPING SYSTEMS SHALL BE PRESSURE -TESTED ® 125 P.S.I.G. FOR 24 HOURS BEFORE STERILIZATION. 12 SANITARY LINE TO BE SCHEDULE 40 PVC PIPE WITH SOLVENT FITTINGS. (ASTM D-2665) 13 ALL FIXTURE _MOUNTING HEIGHTS & INSTALLATION DETAILS SHALL CONFORM TO A.D.A. AND STATE HANDICAP REQUIREMENTS. INSTALL INSULATION ON PIPING BENEATH LAV. EQUAL TO TRUEBRO, INC. HANDI-LAV-GUARD. PLUMBING FIXTURE SCHEDULE FIXTURE N0. DESCRIPTION PIPE SIZES MAKE & MODEL C.W. H.W. SOIL P-1 WATER CLOSET (H/C) 3/8" - 3" AMERICAN STANDARD 2998.012 / CENTOCO 50OCC P-2 WATER CLOSET 3/8" - 3" AMERICAN STANDARD 2399.012 / CENTOCO # 600 P-3 LAVATORY (H/C) 3/811 3/8" 1 1 /4" AMERICAN STANDARD 0124.024 / SYMMONS S-20-2 P-4 LAVATORY 3/8" 3/8" 1 1 /4" AMERICAN STANDARD 0476.028 / SYMMONS S-20-2 P-5 URINAL 3/4" - 2" AMERICAN STANDARD 6501.010 / SLOAN ROYAL 186-1 P-6 SINK 1 /211 1 /2" 1 1 /2" JUST SL-ADA-2017-A-GR / AMER. STD. 4205.241 P-7 ELEC. WATER HEATER 3/4" 3/4" 3/4" RUUD PEP 10-1 (10 GAL., 2.0 kw, 120V.) C1� W �w rI N `2 �. O Q 0 L . CD Q LL! !Y <P ILL Q 00r� LL CL cq 00 o �- - .- N � I n u(o) U O C v cp E O o t- ti It o : L 4 N .}., V jE Z 3 ti � c' U p U d v u x 3 Q L 0 W p Q 3 J cyQ 0007 LL. 3 Li O W 0 1 FIRST FLOOR MECHANICAL PLAN SCALE: 1 /4" = V-0" — — NORTH NORTH m o c H.V.A.C. NOTES Q 0 W �ooW i F1 DUCT SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS. ALLOW FOR 1 " DUCTBOARD THICKNESS 2 ROUND DUCTS .OF FLEXIBLE FIBERGLASS TO BE EQUAL TO FLEXMASTER TYPE "9". TAKE OFF i /- 2 FITTINGS TO BE EQUAL TO FLEXMASTER DBE-45' OR DBDE-45' WHERE ACCESSIBLE. � I �- 2 I ❑3 ALL DUCTWORK SHALL BE IN ACCORDANCE WITH SMACNA AND GOVERNING CODES. 2"--2st ® COORDINATE LOCATION OF AIR DISTRIBUTION WITH CEILING GRID AND LIGHTS. i l \ -el 2 i 2,. R5 EXHAUST DUCT THRU JOIST SPACE TO WALL CAP. 3" FD P6 I Q I P1 © TOILET FAN TO BE EQUAL TO GREENHECK MODEL CSP-150, 300 CFM ® 0.1" S.P., 1.5 SONES, 1.5 AMPS, 1 /60/1 15. =� - 2» P5 ALL TAPES AND MASTIC SHALL BE U.L. - 181 LISTED. 2"1117 ;P4 2" U 311 FD © P4 3„ Z Zr,_ 3» : Q AIR DISTRIBUTION SCHEDULE NO. SIZE C.F.M. "TYPE MODEL NO. * NOTES O 6 x 6' 80 CEIL. DIFF. 7000-6D7-4W 24 x 24 LAY -IN O2 8 x 8 150 CEIL. DIFF. 7000-6D7-4W 24 x 24 LAY -IN C�3 16 x 12 - DOOR GRILLE DGDF - I U � W 0 � O aT ti LLJ L0 ru 0 C) Lc-) (U 0 0 w rn 0 FI FCfRICAL SPECIFI 'At TIt)NS 1. MATERIALS MID INSiALLAII(-41, AS A MINPIUM, ARE TO CONFORM WITI1 THE LAIESF EDITION OF THE: NAFION�L ELECTRIC CODE, THE LATEST EDITION OF N.F.P.A„ 4D THE LATEST EDITION OF THI: LO(:AL .OULS AND ORDIIIANCLS, INCLUDING ALL AMENDMEIITS 10 THE N.E.C. EQUIPMENT, 7y'HERE APF•.ICI LIL.E, WILL BL LISIED Y111H THE UNDERYrRIJERS L.ABORAIORIES, INC. QUALITY AND 'NORKHANS111P I;STABLISIIED BY DRAWINGS AND SPECIFICATIONS ARE NDT 'TO BE REDUCED BY !HE ABOVI_ METfIONED CODES. 2. BIDDERS ARE 10 VI3IT 1' IE SJ 1E AND FAMILIARIZE TH£MSELVL.3 WITH EXISTING CONDI11 !NS ND SATISFY 1HEMSLI.VES AS 10 IdE NATURE AND SCOPE OF WORK. IIiE SUBMISSION OF A L 1) Y'IL.L BE EVIDENCE THAT SUCH AN EXAMINATION HAS BEEN MATE. LATER CUIMS FOR LABOR, N) ITEM OR MATERIALS RE°MIRED, OR FOR DIFFICULTIES [NCCUNll:RED WHICH COULD HAVE UEEr SEEN HAD AN EXAMINA 1ION BEEN MADE, WILL NOT BE ALL0'�iED. 3. ALL WORK SHALL BE P•=RFORMED BY A LICENSED LLEC]RICAL CONTRACTOR IN A FIRSi.-i WORKMANLIKE MANNER TIIE COMPLETED SYSTEM [S I) UE FULLY OPERABLE %ND AC:CEF OF THIS SYSTEM BY THE I NGINEER/ARCHITECT MUSF BE I. CONDITION OF [HE SUB CON IRA' 4. ALL WORK TO DE COORDINATED WITH OTHER iRA TES 10 AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUCTION. 5. CONTRACTOR TO GUARATI TEE ALL h1ATERtALS AND WORKMANSHIP FREE i ROM DEFECTS FOR PERIOD OF NOT LES`; THAT Offl- (1) YEAR FROM DATE OF ACCEPTANCE. ! 6. CORRECTION OF , NY D1_FEC IS 10 BE WJPL.E1FD `?fa 111 )U T ADD i TIONAL CHARC I: AND TO INCLUDE REPLACEMEN F OR REPAIR OF ANY OTHER PHASE CF 11 E I1'•STA LATION WHICH MAY HAVE BEEN DAMAGLD THEREB Y. 7. ALL REQUIFEI) lr, ;SURAHCI: TO BE PROVIDED FOR PROTECiI IN \GAINS f PUBLIC LIABILITY OF PROPERTY DAMA.E FOR THE DURATION OF THE: WORK. 8. CONTRACTOR TO PAY FOR ALL PERMIiS, FEES INSPECi101 AVO TESTINGS. 9. ELECTRICAL IN FAU.ATI011 TO MEET All STANDARD REQUI 'JJE31TS OF LOCAL POWER AND TELEPHONE COI.IPANIES. ELECTRICAL CONTRACTOR SITALL CCNTACT LOCAL POWER AND TELEPHONE COMPANIES PRIOR TO START OF C011STRUCTION 10, ALL WIRING SHALL EVE. IN CONDUIT Uf 1LESS OTHL R 11SE MOVED, MINIMUM WIRE SIZE SHALL BE #12 AWG, FNCLUDING CONTROL_ WIRING. ALL !:OPUUCit'R'; SkIALL BE COPPER WITH THiV1N/TTIHN INSUTA11011. C(AIDUCTOitS #10 ANL- 5,MALLER itAY BE SOLID; ALL THOSE #8 AND LARGER TO FE SiRANDED. 11. ALL UNDERGROUND RA,EWA'(S SIiALL 13E MINIMUM 3/4'. GALVANIZED RIGID STEEL CONDUIT OR SCHEDULE 40 PVC. ALL OTHER FACEYIAYS TO COMPLY Till uOVERNING CODE`_. WERE RIGID SU _:L IS USED, IT SHALL BE COMIILETI LY C)ATED WI111 AN KA'.I AND RUST RESISFANT BITUMASFIC PAINT, KOPPER NO. 50, AND '11-1"FADS SHALL BE COAT ) i ITtl ZINC (HROMAIE. RIGID STEEL SHALL ALSO 12E U`.ED VAIEN CONDUIT IS EXPOSED TO E:'IEINIOR ENVIROtlMENT SUCH AS EXIERIOR OF BUILDITiG OR V+iER' IT IS EXPOSLD AND SUUEC1 TO UAMACE, INSIDE Of BUILDING. I 12. OUTLET BOXES SHALL I E PRESSER STE1:L IN DRY LOCATIONS, CAST ALLOY WI III THREADED HU0:3 IN WET OR DAMP LOCATIONS, AND BE ()F SPECIAL CONNSTRUCTION FOR OTHER CLASSIFIED AREAS. ALL BOXES Si'AL "E RI�CESSED (FLUSH) IN WALLS OR CEILINGS WHENEVER POSSIBLE. i 13. DISCONNECT SWIIG'IIES SHALL. BE H.P. RATED, GEiIERAL IIUTY, QUICK -MAKE, QUICK -BREAK TYPE. ENCLOSURES SHALL 13C AS REQUIRED B`( N.E.C. AND U iTION (WEATHERPROOF, EXPLOSION PROOF, ETC). L1NGR ~,VED LAMINAiED PLASTIC IDENTIFI 1.410N PLATES SILALL BE FURNISHED AND INSTALLED (1N ALL DISCONNECT SWITCHES, CONTACTOR.; /ND '_TARiERS.. 13.1. ALL FUSES FOR SAFETY SWITCHES SHALL. BE DUAL ELERIFNF, CARTRIDGE TYPE. FUSES SHALL BE THOSE: MANUFACiURED BY EITHER BUSSMAN OR L.ITTLEFUSE. TIIE CCNTRACTOR SHALL FURNISH TO THE OWNER ONE SPARE FUSE FOR EACH SIZE AND FYPI OF FUS{_ INSTALI-ED. FUSES 600 AMPS OR LESS SHALL 13E CLASS RK1, TYPICAL UNLESS OTHERWISF NOTED. FUSES OVER 600 AMPS SHALL BE CLASS L. 14. ALL GENERAL- FlJRPO5E SWITCHES AND RECEPTACLES fHALL LIE THE PRODUCT OF A SINGLE MANUFACTURER. CAii'1-00 NUMBERS LISTED ARE LEVIi!AI: 10vEVER, COMPARABLE DEVICES BY PASS & SEYidOtfR, BIiYANF, OR ARROW HART WILL BE ACCEI ' D. COLOR OF DEVICES AND PLATES SHALL LIE DICTATED BY ARCHITECT/OWtIER. A. SWITCHES: LEVITON IGSDI-20I B. RECEPTACLES: LE11 TON JUR20-I C. COVER PLATES: S1+001[11 PLASTIC NOTE: ALL 011-JER REQUIRED DEVICES SHALL MAfCII IN COLOR AND STYLE. 15. ALL RACEWAYS AND PIPES, SPACED IN OR THROUGH ANY CONCREiI: SLAB, SHALL BE SPACED A MINIMUM OF THREE TIMES THE DIAMETER OF THE LARGEST RACEWAY. 16. IT IS NOT THE INiENT OF THESE PLANS TO SHOW F:VE.!'( PRIOR DETAIL OF CONSTRUCTION. 'THE COSI fRACTOR IS EXPECTED 'TO FURNISH AND P ISfA L 1 ; 1. I fEMS FOR A COMPLETE ELECTRICAL SYSTEM, AND PROVIDE AH NECESSARY DEVICES AT 1) I !jV,1'OIIEN IS FOR EQUIPMENT BE PLACED IN PROPER WORKING ORDER. 17. A SEPARATE, GREEN TYPE 'IIFN C013PER GROUND C(TIDUCTOR SH1\LL BE RUN FROM GROUND LUG OF EACH GROUNDED ftECEfyTACLE '10 AN APPROVEI) CONti CTION IN ADE IIIE ENCLOSING STEEL OUILEI BUX. DEVICE MOUNTING SCREWS SHALL NOT BE CO"ISI.OEKED AN APPROVED GROUND. A SEPARATE GROUND CONDUCTOR SHALL BE INSTA LEI IN 'EVER)' CONDUIT AND RACEWAY AND SECURELY BONDED .IN AN APPROVED GROUNDING TLRhIINAL AT BOiTI ENDS OF THE RUN. THE GROUNDING CONDUCTOR 5I11:LL BE SIZED IN ACCORDANCE Y'1.TH TABLE 250-95 OF THE N.E.C. CONTRACTOR SHALL SIZE CONIDUIT TO ACCOMMODAIE i'%DDII ONAL CONDUCTOR. 18. LOAD DATA IS BASED ON INFOR.MAiION GIVEN ENGUILER AT THE TIME OF DESIGN. VERIFY ALL EQUIPMENT NAMEPLAiE RATINGS BEFORE ORDERING. 19. CIRGLIITS SHOWN (FI PLANS ARE 1-0 DETERMINE LOAD DAIA 111) PANEL. SIZES. THE CONTRACTOR IS 10 PROVIDE CIRCUITS AND ROUTING OF CONDUITS TO SI' i JOB COONDITIONS. 20. FURNISH AND INST/siL DISCONNECT SWITCHES, WIRING, f W .:OAT IECTICIIS ON AIR CONDITIONING SYSTEM AS SHOWN (il PLANS. ELECTRICAL COtIIR1',CTOR SI 1LL `i+ERIFY AND COORDINATE WITH MECHANICAL CONTRACTOR REGARDIIIG SUPPLY VID INSD U 1TION OF ALL REQUIRED CONTROLS, 21. ALL FLUORESCE14F ATID F.I.D. LIGHTING FIXTURI S S'ALL IJE FUSED, AS REQUIRED BY LOCAL CODE ONLY. 22. TANDEM AND HALF -SPACE CIRCUIT BREAY.ERS SHALL tNOI BE USED. 23. TYPEWRITTEN CIRCUIT INDEX SHALL BE AFFIXED 'TO INSIDE SURFACE (X- EACH PANELa3OARD DOOR, CLEARLY INUICAIING AREA AtiD TYPE OF LOAD SERVED BY FACH BRANCH CIRCUIT PROfECiIVE DEVICE, INCLUDLNG SPARES. HAND PRINTED WILL NOT BE ACCEPTED. 24, ENGRAVED, LA),+INAiF_1) PLASTIC IDENTIFICATION PLATES SHALL BE FURNISHED AND INSFALJED ON AI L PANELS AND SWI FCIMAR. PLATES SHALL BE AFFIXED 10 F RONY OF PANELS, 1FID.ICATING PANEL NAME, VOLTAGE AND AMPERAGE. 25. ALL ELECTRICAL CNiDUCTORS SHALL BE INSTALLED IN AN A'PPRO� :D RACEWAY, EMT, RIGID GALVANIZED COt1DUI f OF SCHEDULE 40 P.V.C. TYPE 1IM', 'MC', ELECTRICAL MON-METAL! IC TUBING, & FLEXIBLE METAL CONDUIT MAY BE tJSLD FOR RE`,;IDLt1T1AL TYPE BRANCH CIRCUITING. MAXIMUM NUMBER OF 120 VOLT CIRCUITS ALLOWED IN A COMMON CO'IDUIT SHALT. BE SIX (6). 111E CONTRACTOR SHALL STRICTLY CONFORM TO THE N.E.C. REQUIREMP ITS OF DEBATING FOR CONDUCTOR AMPAC1fY AND CONDUIT FILL ELECTRICAj.. CONfRAC1CR SHALL VERIFY W/ LOCAL AUIHORIfIES PRIOR TO SUBMITTING BID. 25.1. CONDUCTORS SIIALI. BE COLOR CODED AS FOLLOWS: 208`J SYS LL A, 480V SYSTEM A2u EQUE.:N NEUIRA- - WHIiE NEUTRAL - YdIITE ABC, TOP TO BIJTTOM PHASE A - BLACK PHASE A - BROWN LEFT TO RIGHT, FRONT PHASL-: B - RED PHASE B - ORANGE '10 BACK PHASE C - BLUE PHASE C - YELLOW (M.CON - GREEN GRD.CON - GREEN 26. COtT[RAGFOR SHALL BE RESPONSIBLE FOR SEALING \LL CONDUIT PIJIETRATIO NS MADE THROUGH FIRE RATED WALL:, CEILINGS, SLABS, ETC. PENE'lkATION SEALS SHALL BE PER U.L ASSEMBLY STANDARDS, 27. CONTRACTOR SHALL. PROVIUI- SHOP DRAWING SUBMI TTALS FUR 1_191T FIXTURES, SYIITCHGEAR, WIRING DEVICES, L.:MER(XNCY GENERATOR/TRANSFER EQUIPMENT, AND ALL SYSTEMS (FIRE ALARM, SECURITY, ETC.) PROVIDE iWO (2) COPIES, TEN (10) DAYS PRIOR TO BID DATE FOR ENGINEER'S APPROVAL TO SUB3;IIT. ENGINEER'S APPROVAL OF THE PRIOR APPROVAL PACKAGE WILL BE C014SIDERED PREI_JHINARY. FINAL APPROVAL WILL DE Ct ' 1 FITN^ TENT UPON REVIEW OF FINAL SHOP DRAWINGS. ALL PROPOSED ALTERNATES MUST BE INDUS" OY S ANDARD EQUALS TO THE ITEMS SPECIFIED AS IFIE BASIS OF DESIGN; HOWEVER, IF THE ITEM.) ARE NOT CONSIDERED EQUAL BY THE ENGINEER, (T' STALL BE DISAPPROVED FOR FINA'_ V BMIFIAL. IF ELECTRICAL C(H'NfRACTUR/ GENERAL CONTRACTC'N DOES NOF SUBMIT SHOT' DRA'i IN( : TO FLECTRICAL ENGINEER FOR ITEMS LISTED ABOVE, I L.ECIRIGPL ENGINEER WIL.. NOT BE ESI A4SIB;_E FOR ANY, AND OR (MISSIONS OR ERRORS DUE TO 1-.41(41 DRAWINGS NOT SUU+lITTE' . S! OP DRAWINGS WILL ONLY BE REVIEWED TWICE AS PART OF THIS CONIRACf. ADDITIONAL S! 'rP LIRAWBIG REVIEWS SHALL BE I14VOICED AT $85.00 PER HOUR, BILLABLE TO THE SUB-(:ONI `,010R, C.O.U. 28. CONTRACTOR SHALL MAINTAIN A COMPLETE SE F Of C(;tiIRACT DRAWINGS AT JO13 SITE Vil ITT COLORED MARKINGS INDICATItIG PROGRESS OF WORK. THIS S! f OF CONTRACT DRAWINGS IS 10 BE SEPARATE FROM AND IN ADDITION TO CONIRACTCNI'S C')NNt TRUCTIOI'N SET. EVERY UNIF Oi EQUIPMENT, DEVICE, CONDUCT AND WIRE IS TO MARKED W)"_N INSTALLED. USE GREEN 10 INDICATE INS FALLAT.IOM AS S} lOYIN ON DRAWINGS AND `RT D TO INDICAiE FIELD CHANGES. UPON COMPLETION OF WOTM, THIS SET OF CONlRA':T I A, 141 S IS TO BF TURNED OVER TO, AND BECOME PROPERTY OF THE ARCHITECT. 29. 111E OWNER RESERVES THE RIGHT TO REVISE THE DRATON (I; )M TIME I0 TIME TO INDICATE CHANGES IN THE WORK. 1141EM REVISED DRAWING ARE IS'; 'El , THE (:ON IRACTOR SHALL EVALUATE THE CHANGES PROMPTLY. BEFORE INSTAL.L.ATIOT' 0' ANY ITEM OR PERFORMANCE OF THE WORK. INDICATED BY THE REVISED DRAWINGS, '11IF COt IT? ;CTOR SHALL NOTIFY ]TIE OV?TIER IN WRITING THAT THE REVISED DRAWINGS INVOL'tE All AD[ 1.110N OR DEDUCTION OF A SPECIFIC AMOUNT OF MONEY 10 THE CONTRACT PRICE. THE COP IRE': TOR SHALL NOT PROCEED WITH THE REVISED WORK WIiHOUT PRIOR MUTTEN APPROVAL B't IFIE-_ OWNER OF THE COST OF IFIE REVISED WORK. 30. IF ELECTRICAL CON IRACTOR HAS QUESTIONS, OR IN link Ill OPII,II01`1 FINDS OMISSIONS OR ERRORS ON ELECTRICAL DOCUMEf I IS, IT IS THEIR RESP(-NS''.JIL11Y 10 B KING THIS TO THE AiTENT(ON OF TITU ELECTRICAL IMMEDIATELY. IF EI_ECIRICAL CONTRACTOR PROCEEDS WI111 Art( CHANGES TO TLIE C(''1IVACI DOCUMEIITS YA111OUT'ARITiEN PRIOR APPROVAL FROM THE EL_EECIRICAL ENGINEERN/ARCIl11I:CT/OYttLER VIELL NOT BE COMPENSATED. ELECTRICAL LEGE1N1ffu"_1 ( L A i t-i FLUORESCENT LIGHT FIXTURE, LETTER INDICATES TYPE OB INCANDESCENT OR HID LIGHT FIXTURE, LETTER INDICATES TiPE I c WALL BRACKET LIGHT FIXTURE, LETTER INDICATES TYPE Am EXIT LIGHT (ARROW INDICATES DIRECIiON) Vj BATTERY POWERED EMERGENCY LIGHT S, SINGLE POLE SWITCH, LOWER CASE LETTER INDICATES LIGHT CONTROLLED, MOUNT 48" A.F.F. U.O.N. S2 DOUBLE POLE SWITCH, MOUNT 48" A.F.F. U.O.N. S� THREE-WAY SWITCH, MOUNT 48" A.F.F. U.O.N. [� DIMMER SWITCH, WATTS AS NOTED, MOUNT 48" A.F.F. U.O.N. SA( MOTOR RATED SWITCH DUPLEX RECEPTACLE, MOUNT 18" A.F.F. U.O.N. DUPLEX RECEPTACLE, MOUNT ABOVE COUNTER HEICIIT U.O.N. ( QUADRAPL.EX RECEPTACLE, MOUNT 18" A.F.F. U.O.N. MA 10, 250V. RECEPTACLE, AMPS AS NOTED, MOUNT 18" A.F.F. U.O.N. (. FLOOR MOUNTED DUPLEX RECEPTACLE I V JUNCTION BOX (FLUSH MOUNT IN FINISHED AREAS U.O.N.) 91 DEVICE AS NOTED LIGHTING OR POWER PANELBOARD CONDUIT CONCEALED IN WALL OR ABOVE CEILING WITH 2 112, 1 #12 E.G. CCNNDUCIORS IN 1/2" CONDUIT MIN. U.O.N. v COMBINATI(Al TELEPHONE/DAiA OUTLET. PROVIDE 3/4" C. WITH PULL -CORD STUBBED INTO CEILING SPACE WITH INSULATED BUSHING. MOUNT 18" A.F.F. U.O.N. ABOREVIATIONS EG EQUIPMENT CROUND NIL NIGHT LIGNF 101 ISOLATED GROUND C/T CURRENT IRANSFOBMEIZ WP WEAiHERPROIF EX EXISTING DEVICE EMT ELECTRIC WATER THEATER AFF ABOVE FINIS11 FLOOR EWC ELECTRIC WATER COOLER AFG ABOVE FINIS1 GRADE E/F-EF EXHAUST FAN U.U.M. UNLESS OTHERWISE NOTED A/H-AHU AIR HANDLING UNIT N.I.S. NOT TO SCALE ACC-CU CONDENSING UNIT EC EMPTY CONDUIT RTU ROOF TOP UNIT NOTE: MOUNTING HEIGHTS NOTiD ARE TO CENTERLINE OF DEVICE SHOrfft U.O.N. (NOT ALL SYMBOLS MAY BE USED FOR A PARTICULAR PROJECT) !0 fl) s ,) EXISTING; 2500 AMP MAIN SWITCHBOARD r---------- ----------- r---------- a I I 1 I I I i I I I I I 1 I f I I I I I I 1 i I I I I I I I I I I 1 1 I I I I I 1 I I L_J I I I I I 1 I I 1 I I I I i I I I I I I I L_J I I i I I 1 I I 1 I I I I i I I I I I I 1 I I I t I I I I I I I I I I I I I I I I I T--L---------------------1---------- L-------------------------� I I------- `---------� C�------------ EXISTING 200 AMP FEEDERS I PANEL I "P" (EX.) PARTIANL POWE111 RISER DIAGRAM. N. T. S. TOTAL CONNECTED LOAD NE`rV): 1.0 KW ® 120/208V-30, 4W = 3 AMPS DEMOLIT ON NOTES: 1. BIDDERS ARE 'TO VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND SATISFY THEMSELVES AS TO THE NATURE AND SCOPE OF WORK. THE SUBMISSION OF A BID WILL BE EVIDENCE THAT SUCH AN EXAiv!INATION HAS BEEN MADE. LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED, OR FOR DIFFICULTIES ENCOUNTERED WHICH COULD HAVE BEEN FORESEEN HAD AN EXAMINATION BEEN MADE, WILL NOT BE ALLOWED. 2. ALL EXISTING CIRCUITS TO REMAIN SHALL BE RECONNECTED 'WHETHER INDICATED OR NOT 014 PROJECT DOCUMENTS. 3. NEW AND EXISTING CIRCUIT DESIGNATIONS MAY NOT REPRESENT ACTUAL FIELD CONDITIONS. "THEY ARE INTENDED FOR REFERENCE ONLY. 4. COORDINATE WI1H OTHER TRADES FOR ITEMS IN THEIR SCOPE OF WORK WHICH WOULii REQUIRE ELECTRICAL WORK (DISCONNECTION/RECONNECTION, ETC.) AND ARE NOT INDICATED ON THE ELECTRICAL PLANS. EY,ISTIN( PANEL "I PO , SCALE: 1/T=1'-O" y V PCI 1'I_AN NOTES: 1. RE--+E "1EAREST EXISTING 120A/1P POWER CIRCUIT. I �ITI I P LAN SCALE: 1 /8"�-1.'.-0' 0 LIGFITING PLAN NOTES: 1. RE -USE NEAREST EXISTING 120A/1P LIGHTING CIRCUIT. 2. MATCH EXISTING FIXTURES. II Tel 11 LT�C�i�sCY EE SE'a, (ITC. 1/f��Street : Tampa, Florida 33609 , �) 2 7-2719 Fax: (813) 287--5704 CO 00 oC'4 (D Ua Cr) _ CD E00>6 ri ! QD O 01 4- L7i Q J ,��++, I MR e<� LLk �LLij T LLI Z LLJ 7 / 1 t s CIZ �tMEMM" E� Jm,- Wj?`�fl 11 _ 0Qap�u,°trJ 71 0 \..J' c,. �• `� 'l ��` � i 4^ {� 1. ('-- :\ vu L 4 w C7, 7,zi trrr mma �[ `� c ` _ LL v r c 4 < LU Z ZuQQ to 0p C.� -,L� p w ZL L L ..,,sto���a_ II L}-it! ` Z +JrUat_�"